Asbestos report - Federal Bureau of Prison.pdf
PDF 2 MB Posted
- Attached to
- FEDERAL PRISON CAMP ASBESTOS REMOVAL HVAC OFFICE; VACANT FARM BUILDING; BARN STORAGE AREA
- Solicitation number
- 15B41824Q00000016
About this file
This document is a limited asbestos survey report for a vacant farm building at 4700 South Bureau Road in Terre Haute, Indiana, which is owned by the Federal Bureau of Prisons. The inspection identified asbestos-containing materials (ACMs) in the pipe wrap insulation, joint compound, and duct wrap, which are all friable regulated asbestos-containing materials (RACMs). The estimated quantities of the ACMs are 228 linear feet of pipe wrap insulation, 81 pipe insulation joints, and 20 square feet of duct wrap insulation. The report recommends that the ACMs be abated and disposed of by an Indiana Licensed Asbestos Abatement Contractor prior to any renovations or demolition activities.
The related federal contract opportunity is for a firm-fixed-price construction contract to remove the asbestos-containing materials at the Federal Prison Camp HVAC, Plumb and Communication Shop at the Federal Correctional Complex in Terre Haute, Indiana. The estimated magnitude of the project is between $25,000 and $100,000, and it is a 100% Small Business Set-Aside with a NAICS code of 562910. The solicitation is anticipated to be issued on or about May 1, 2024 and will be distributed solely through the SAM.gov website.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| IMG_0369.JPG | JPG image | |
| IMG_0392.JPG | JPG image | |
| IMG_0397.JPG | JPG image | |
| site meeting minutes.pdf | ||
| INSTRUCTIONS TO OFFERERS TEMPLATE.doc | DOC document | |
| IMG_0387.JPG | JPG image | |
| IMG_0370.JPG | JPG image | |
| WAGE DETERMINATION.pdf | ||
| IMG_0388.JPG | JPG image | |
| SITE VISIT PRE BID .docx | DOCX document | |
| IMG_0395.JPG | JPG image | |
| Contractor Whistleblower Rights - EACI.pdf | ||
| IMG_0371.JPG | JPG image | |
| IMG_0375.JPG | JPG image | |
| IMG_0384.JPG | JPG image | |
| IMG_0394.JPG | JPG image | |
| IMG_0372.JPG | JPG image | |
| IMG_0393.JPG | JPG image | |
| IMG_0399.JPG | JPG image | |
| IMG_0391.JPG | JPG image | |
| RFQ.pdf | ||
| IMG_0398.JPG | JPG image | |
| IMG_0386.JPG | JPG image | |
| SOW UPDATED.pdf | ||
| IMG_0396.JPG | JPG image | |
| IMG_0373.JPG | JPG image | |
| Questions.docx | DOCX document | |
| IMG_0390.JPG | JPG image | |
| IMG_0374.JPG | JPG image | |
| IMG_0385.JPG | JPG image | |
| IMG_0389.JPG | JPG image |
Show all 31
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
May 4, 2023
Federal Bureau of Prison 4700 South Bureau Road Terre Haute, Indiana 47802 Attention: Bryan Dunn
RE: Limited Asbestos Survey Vacant Farm Building 4700 South Bureau Road Terre Haute, Indiana 47802 Aegis Project #23-083
Dear Mr. Dunn, Aegis Environmental, Inc. (Aegis) is pleased to present the findings of the Limited Asbestos Survey performed on the vacant farm building located at 4700 South Bureau Road in Terre Haute, Indiana (Site). In accordance with the United States Environmental Protection Agency (USEPA) National Emission Standards for Hazardous Air Pollutants (NESHAP) regulation for asbestos, the purpose of the inspection was to determine the presence of asbestos-containing materials (ACMs) which must be identified and removed (if friable or potentially friable) prior to the renovations planned at the Site. The inspection and testing for asbestos were limited to the roofing materials, damaged ceilings, and HVAC components throughout the building.
Site Background
Improvements at the Site consist of a 30,000-square-foot, one-story former farm building.
The construction date is unknown. The building is constructed with a concrete block exterior, a wood roof deck, and metal and asphalt shingle roofs. Interior walls and ceilings consist of plaster.
The building layout is illustrated in Figure 1.
The building was inspected on April 18, 2023. The inspection was performed by Indiana-licensed Asbestos Building Inspectors Mya Smith (license #19A013071, expires 08/15/2023). A copy of Ms. Smith’s license is provided in Appendix A.
Asbestos-Containing Material (ACM)
According to the USEPA, an ACM is defined as any material containing greater than one percent (1%) asbestos. Asbestos-containing materials fall into three categories: friable ACM, category I non-friable ACM, and category II non-friable ACM. Friable ACM is any material that can be crushed, crumbled, pulverized, or reduced to powder by hand pressure or mechanical forces reasonably expected to act upon the material. All friable ACM is regulated. Category I non-friable
Vacant Farm Building – Terre Haute, Indiana 2 materials are packings, gaskets, resilient floor coverings, and asphalt roofing materials. Category I materials become regulated when subjected to sanding, grinding, cutting, abrading, or burning, which will crush, crumble, pulverize or reduce the materials to a powder. Category II non-friable materials are any materials, excluding Category I, which cannot be crushed, crumbled, pulverized, or reduced to powder by hand pressure or mechanical forces reasonably expected to act upon the material. Category II non-friable materials become friable if the material will become crushed, crumbled, pulverized, or reduced to powder by the forces expected to act upon them during renovation or demolition activities. Regulated asbestos-containing materials (RACM) must be removed before any renovation or demolition activity that may disturb them. Removal of regulated ACM must be performed by an Indiana Licensed Asbestos Abatement contractor.
Discussion
Field information was organized per the USEPA Asbestos Hazard Emergency Response Act (AHERA) concept of the Homogeneous Area (HA). An HA is defined as a suspect material of similar age, appearance, function, and texture. Each material represents a specific HA, sampled and then assessed for condition. Eleven (11) HAs were identified during the limited inspection.
A summary of inspected suspect ACMs identified and sampled is provided in Appendix B.
Samples of suspect building materials were collected, logged on chain of custody forms, and submitted for analysis to SanAir Technologies Laboratory (SanAir) in North Chesterfield, Virginia, for analysis by Polarized Light Microscopy (PLM), EPA 600/R-93-116. SanAir is a National Voluntary Laboratory Accreditation Program (NVLAP) accredited laboratory. Table 1 provides a summary of the ACMs identified during the inspection.
Table 1. Summary of Inspected Asbestos-containing Materials 4700 South Bureau Road
Terre Haute, Indiana Material Sample ID(s) Asbestos Friable? Regulated
ACM?
Estimated Quantity
Pipe wrap insulation, paper, brown, white cloth
TSI1-A, B, C 5% Chrysotile Yes Yes 228 linear feet
Pipe wrap insulation joint compound, white, white cloth
TSI3-A, B, C 15% Chrysotile Yes Yes 81 joints
Pipe wrap insulation, white, white cloth TSI4-A, B, C 10% Chrysotile Yes Yes 581 linear feet
Duct wrap insulation, papery, white TSI5-A, B, C 70% Chrysotile Yes Yes 20 ft²
Asbestos was detected in pipe wrap insulation (TSI1 and TSI4) at 5% and 10%. Asbestos was detected in pipe insulation joint compound (TSI3) at 15%. Asbestos was detected in duct wrap at 70% (TSI 5). Photos taken during the inspection are included in Appendix C. A copy of the SanAir analytical report is included in Appendix D.
As summarized in Table 1, the pipe wrap, joint compound, and duct wrap are friable RACMs. The estimated quantities of the ACMs are listed in Table 1. The asbestos-containing pipe insulation and joint compound are located throughout the attic and building plenums and along walls. The asbestos-containing duct wrap is located in the attic. Sample locations are illustrated in Figure 1.
Vacant Farm Building – Terre Haute, Indiana 3
Asbestos Survey Limitations
Some building structures may have been constructed after the application of ACM materials and, therefore, may have obscured these materials from visual examination during this inspection. Typical scenarios include thermal system insulation inside hardened mechanical chases, floor tile, and mastic under walls and sprayed-on texturing or fireproofing behind structural supports or architectural features. Suspect materials that were hidden or inaccessible may not have been characterized by this inspection. Therefore, any material not identified in this report as having been tested should be treated as a suspect ACM until it has been sampled and analyzed.
Summary
The pipe insulation, joint compound, and duct wrap are friable RACMs. The pipe insulation, joint compound, and duct wrap should be abated and disposed of by an Indiana Licensed Asbestos Abatement Contractor before repairs and renovation. During renovation or demolition activities, all OSHA regulations should be followed.
Since the total amount of friable RACM to be abated exceeds 260 linear feet (pipe insulation and joint compound), 160 square feet and/or 35 cubic feet, the Owner/Operator must file a 10-working day notification with the IDEM. Furthermore, since the total amount of debris to be collected will be greater than 0.75 cubic feet, the workers, supervisor, and contractor must be licensed by the State of Indiana.
The term “suspect ACM” would include materials discovered in the course of renovation and demolition, which only become visible during these activities, or material in areas inaccessible during the inspection. If such materials are discovered during renovation or demolition, work in the area should be halted immediately, and Aegis should be contacted so that we may sample the suspect ACM in question. Only after laboratory analysis has been conducted on these samples and reported to you should regulatory-appropriate demolition or renovation continue.
A comprehensive asbestos survey of the entire structure was not conducted by Aegis. The inspection and testing for asbestos were limited to the roofing materials, damaged ceilings, and HVAC components throughout the building. As such, other asbestos-containing building materials may or may not be present. If an EPA NESHAP-compliant asbestos survey of the entire structure is desired, please contact our office.
Vacant Farm Building – Terre Haute, Indiana 4
We appreciate the opportunity to provide our asbestos services and look forward to assisting you in the future. If you have any questions or require additional information, please contact us at (317) 833-9000.
Sincerely, Aegis Environmental, Inc.
Mya Smith Project Manager License #19A013071 Expiration: 08/15/2023
Bruce Bultman, LPG Senior Principal Geologist
STORAGE
PRIVATE
OFFICE
MAIN
OFFICE
EQUIPMENT
ROOM
24 HR
ROOM
ATTIC
ACCESS
ATTIC
ACCESS
FORMER CATTLE
BARN/STORAGE
PLBC1-F,G
PLFC1-F,G
PLBC1-D,E
PLFC1-D,E
PLBC1-B,C
PLFC1-B,C
TP1-A,B,C
AR1-A,B,C
AR2-A,B,CPLBC1-A
PLFC1-A
TSI4-C
TSI5-A,B,C
TSI4-B
TSI3-A
TSI2-A,B,C
TSI1-C
CT1-A,B,C
TSI1-A,B
TSI3-B,C
TSI4-A
PROJECT NO.: 23-083 CLIENT: SITE:
FIGURE 1
ASBESTOS SAMPLING MAP
1013 NORTH BLUFF ROAD
GREENWOOD, IN 46142
Tel: 317-833-9000 Fax: 317-833-9001
VACANT BUILDING
4700 S BUREAU ROAD
TERRE HAUTE, IN 47802FEDERAL BUREAU OF PRISONS
4700 S BUREAU ROAD
TERRE HAUTE, INDIANA 47802
LEGEND
ASBESTOS SAMPLING LOCATION
(NO ASBESTOS DETECTED)
ASBESTOS SAMPLING LOCATION
(ASBESTOS CONTAINING MATERIAL)
AutoCAD SHX Text
BEARING
Appendix A
Inspector License
Appendix B
Summary of Suspect Asbestos-containing Building Materials
Table 2. Summary of Suspect Asbestos-containing Materials Federal Bureau of Prison 4700 South Bureau Road
Terre Haute, Indiana Material Sample ID(s) Asbestos
Ceiling tile, 2"x2", gray CT1-A, B, C ND Asphalt roof shingle, green, black AR1-A, B, C ND Tar paper, black TP1-A, B, C ND Asphalt roof shingle, black AR2-A, B, C ND Pipe wrap insulation, paper, brown, white cloth TSI1-A, B, C 5% Chrysotile Pipe wrap insulation, brown foam, white cloth TSI2-A, B, C ND Pipe wrap insulation joint compound, white, white cloth
TSI3-A, B, C 15% Chrysotile
Pipe wrap insulation, white, white cloth TSI4-A, B, C 10% Chrysotile Duct wrap insulation, papery, white TSI5-A, B, C 70% Chrysotile Plaster base coat, gray PLBC1-A, B, C, D, E, F, G
ND
Plaster finish coat, white PLFC1-A, B, C, D, E, F, G
ND
An asbestos-containing material (ACM) is defined as any material with greater than 1% asbestos by volume.
Bold = ACM
* = Analyzed by Point Count ND = Non-detect
Appendix C
Photographs
Photo 1. Exterior view of the building
Photo 2. Asbestos-containing pipe wrap (TSI1)
Photo 3. Location of TSI1
Photo 4: Asbestos-containing pipe wrap insulation joint compound (TSI3)
Photo 5. Non-asbestos pipe wrap (TSI2)
Photo 6. Asbestos-containing pipe wrap (TSI4)
Photo 7. Asbestos-containing duct wrap insulation (TSI5)
Photo 8. Floor below attic with TSI4 and TSI5
Appendix D
Laboratory Certificates of Analysis
SanAir ID#: 23022459
Project #: 23-083 Project Name: Federal Bureau Of Prison Report Date: 5/3/2023
Analysis Report prepared for Aegis Environmental Inc.
Dear Mya Smith, We at SanAir would like to thank you for the work you recently submitted. The 41 sample(s) were received on Monday, April 24, 2023 via UPS. The final report(s) is enclosed for the following sample(s): CT1-A, CT1-B, CT1-C, AR1-A, AR1-B, AR1-C, TP1-A, TP1-B, TP1-C, AR2-A, AR2-B, AR2-C, TSI1-A, TSI1-B, TSI1-C, TSI2-A, TSI2-B, TSI2-C, TSI3-A, TSI3-B, TSI3-C, TSI4-A, TSI4-B, TSI4-C, TSI5-A, TSI5-B, TSI5-C, PLBC1-A, PLBC1-B, PLBC1-C, PLBC1-D, PLBC1-E, PLBC1-F, PLBC1-G, PLFC1-A, PLFC1-B, PLFC1-C, PLFC1-D, PLFC1-E, PLFC1-F, PLFC1-G.
These results only pertain to this job and should not be used in the interpretation of any other job. This report is only complete in its entirety. Refer to the listing below of the pages included in a complete final report.
Sincerely, Sandra Sobrino Asbestos & Materials Laboratory Manager SanAir Technologies Laboratory
Final Report Includes:
- Cover Letter
- Analysis Pages
- Disclaimers and Additional Information
Sample conditions:
- 41 samples in Good condition.
10501 Trade Ct., N. Chesterfield, VA 23236 | 804.897.1177 | Fax: 804.897.0070 | www.SanAir.com | IAQ@SanAir.com
23-083Project Number:
P.O. Number:
Project Name: Federal Bureau Of Prison
4/18/2023Collected Date:
4/24/2023 10:10:00 AMReceived Date:
5/3/2023 9:50:14 AM
23022459 SanAir ID Number
FINAL REPORT
Aegis Environmental Inc.Name:
Address: 1013 N. Bluff Road
Greenwood, IN 46142
317-833-9000Phone:
Analyst: Moore, Brandi
Asbestos Bulk PLM EPA 600/R-93/116 Stereoscopic Components
SanAir ID / Description Appearance % Fibrous % Non-fibrous Asbestos Fibers
CT1-A / 23022459-001
Ceiling Tile, 2'x2'
Gray Fibrous
Homogeneous
75% Glass 25% Other None Detected
CT1-B / 23022459-002
Ceiling Tile, 2'x2'
Gray Fibrous
Homogeneous
75% Glass 25% Other None Detected
CT1-C / 23022459-003
Ceiling Tile, 2'x2'
Gray Fibrous
Homogeneous
75% Glass 25% Other None Detected
AR1-A / 23022459-004
Asphalt Roof Shingle
Green Non-Fibrous
Heterogeneous
10% Cellulose 90% Other None Detected
AR1-B / 23022459-005
Asphalt Roof Shingle
Green Non-Fibrous
Heterogeneous
10% Cellulose 90% Other None Detected
AR1-C / 23022459-006
Asphalt Roof Shingle
Green Non-Fibrous
Heterogeneous
10% Cellulose 90% Other None Detected
TP1-A / 23022459-007
Tar Paper
Black Fibrous
Heterogeneous
60% Cellulose 40% Other None Detected
TP1-B / 23022459-008
Tar Paper
Black Fibrous
Heterogeneous
60% Cellulose 40% Other None Detected
TP1-C / 23022459-009
Tar Paper
Black Fibrous
Heterogeneous
60% Cellulose 40% Other None Detected
AR2-A / 23022459-010
Asphalt Roof Shingle
Black Non-Fibrous
Heterogeneous
5% Glass 95% Other None Detected
Analyst:
Analysis Date: 5/3/2023 Date: 5/3/2023
Approved Signatory:
23-083Project Number:
P.O. Number:
Project Name: Federal Bureau Of Prison
4/18/2023Collected Date:
4/24/2023 10:10:00 AMReceived Date:
5/3/2023 9:50:14 AM
23022459 SanAir ID Number
FINAL REPORT
Aegis Environmental Inc.Name:
Address: 1013 N. Bluff Road
Greenwood, IN 46142
Stereoscopic Components
SanAir ID / Description Appearance % Fibrous % Non-fibrous Asbestos Fibers
AR2-B / 23022459-011
Asphalt Roof Shingle
Black Non-Fibrous
Heterogeneous
5% Glass 95% Other None Detected
AR2-C / 23022459-012
Asphalt Roof Shingle
Black Non-Fibrous
Heterogeneous
5% Glass 95% Other None Detected
TSI1-A / 23022459-013
Pipe Wrap, Papery, Cloth, Pipe Wrap
Brown Fibrous
Heterogeneous
60% Cellulose 35% Other 5% Chrysotile
TSI1-A / 23022459-013
Pipe Wrap, Papery, Cloth, Cloth
White Fibrous
Heterogeneous
90% Glass 10% Other None Detected
TSI1-B / 23022459-014
Pipe Wrap, Papery, Cloth, Pipe Wrap
Not Analyzed
TSI1-B / 23022459-014
Pipe Wrap, Papery, Cloth, Cloth
White Fibrous
Heterogeneous
90% Glass 10% Other None Detected
TSI1-C / 23022459-015
Pipe Wrap, Papery, Cloth, Pipe Wrap
Not Analyzed
TSI1-C / 23022459-015
Pipe Wrap, Papery, Cloth, Cloth
White Fibrous
Homogeneous
95% Cellulose 5% Other None Detected
TSI2-A / 23022459-016
Pipe Wrap, Foam, Cloth, Foam
Brown Non-Fibrous
Homogeneous
100% Other None Detected
TSI2-A / 23022459-016
Pipe Wrap, Foam, Cloth, Cloth
White Fibrous
Heterogeneous
90% Cellulose 10% Other None Detected
Analyst:
Analysis Date: 5/3/2023 Date: 5/3/2023
Approved Signatory:
10501 Trade Ct., N. Chesterfield, VA 23236 | 804.897.1177 | Fax: 804.897.0070 | www.SanAir.com | IAQ@SanAir.com
23-083Project Number:
P.O. Number:
Project Name: Federal Bureau Of Prison
4/18/2023Collected Date:
4/24/2023 10:10:00 AMReceived Date:
5/3/2023 9:50:14 AM
23022459 SanAir ID Number
FINAL REPORT
Aegis Environmental Inc.Name:
Address: 1013 N. Bluff Road
Greenwood, IN 46142
Stereoscopic Components
SanAir ID / Description Appearance % Fibrous % Non-fibrous Asbestos Fibers
TSI2-B / 23022459-017
Pipe Wrap, Foam, Cloth, Foam
Brown Non-Fibrous
Homogeneous
100% Other None Detected
TSI2-B / 23022459-017
Pipe Wrap, Foam, Cloth, Cloth
White Fibrous
Heterogeneous
90% Cellulose 10% Other None Detected
TSI2-C / 23022459-018
Pipe Wrap, Foam, Cloth, Foam
Brown Non-Fibrous
Homogeneous
100% Other None Detected
TSI2-C / 23022459-018
Pipe Wrap, Foam, Cloth, Cloth
White Fibrous
Heterogeneous
90% Cellulose 10% Other None Detected
TSI3-A / 23022459-019
Pipe Wrap Joint Compound, Cloth, Compound
White Non-Fibrous
Homogeneous
85% Other 15% Chrysotile
TSI3-A / 23022459-019
Pipe Wrap Joint Compound, Cloth, Cloth
White Fibrous
Heterogeneous
90% Glass 10% Other None Detected
TSI3-B / 23022459-020
Pipe Wrap Joint Compound, Cloth, Compound
Not Analyzed
TSI3-B / 23022459-020
Pipe Wrap Joint Compound, Cloth, Cloth
White Fibrous
Heterogeneous
90% Cellulose 10% Other None Detected
TSI3-C / 23022459-021
Pipe Wrap Joint Compound, Cloth, Compound
Not Analyzed
TSI3-C / 23022459-021
Pipe Wrap Joint Compound, Cloth, Cloth
White Fibrous
Heterogeneous
90% Cellulose 10% Other None Detected
Analyst:
Analysis Date: 5/3/2023 Date: 5/3/2023
Approved Signatory:
10501 Trade Ct., N. Chesterfield, VA 23236 | 804.897.1177 | Fax: 804.897.0070 | www.SanAir.com | IAQ@SanAir.com
23-083Project Number:
P.O. Number:
Project Name: Federal Bureau Of Prison
4/18/2023Collected Date:
4/24/2023 10:10:00 AMReceived Date:
5/3/2023 9:50:14 AM
23022459 SanAir ID Number
FINAL REPORT
Aegis Environmental Inc.Name:
Address: 1013 N. Bluff Road
Greenwood, IN 46142
Stereoscopic Components
SanAir ID / Description Appearance % Fibrous % Non-fibrous Asbestos Fibers
TSI4-A / 23022459-022
Pipe Wrap, Cloth, Compound
White Non-Fibrous
Homogeneous
90% Other 10% Chrysotile
TSI4-A / 23022459-022
Pipe Wrap, Cloth, Cloth
White Fibrous
Heterogeneous
90% Cellulose 10% Other None Detected
TSI4-B / 23022459-023
Pipe Wrap, Cloth, Compound
Not Analyzed
TSI4-B / 23022459-023
Pipe Wrap, Cloth, Cloth
White Non-Fibrous
Heterogeneous
100% Other None Detected
TSI4-C / 23022459-024
Pipe Wrap, Cloth, Compound
Not Analyzed
TSI4-C / 23022459-024
Pipe Wrap, Cloth, Cloth
White Fibrous
Heterogeneous
90% Cellulose 10% Other None Detected
TSI5-A / 23022459-025
Duct Wrap, Papery
White Fibrous
Homogeneous
15% Cellulose 15% Other 70% Chrysotile
TSI5-B / 23022459-026
Duct Wrap, Papery
Not Analyzed
TSI5-C / 23022459-027
Duct Wrap, Papery
Not Analyzed
PLBC1-A / 23022459-028
Plaster Base Coat
Gray Non-Fibrous
Homogeneous
100% Other None Detected
Analyst:
Analysis Date: 5/3/2023 Date: 5/3/2023
Approved Signatory:
10501 Trade Ct., N. Chesterfield, VA 23236 | 804.897.1177 | Fax: 804.897.0070 | www.SanAir.com | IAQ@SanAir.com
23-083Project Number:
P.O. Number:
Project Name: Federal Bureau Of Prison
4/18/2023Collected Date:
4/24/2023 10:10:00 AMReceived Date:
5/3/2023 9:50:14 AM
23022459 SanAir ID Number
FINAL REPORT
Aegis Environmental Inc.Name:
Address: 1013 N. Bluff Road
Greenwood, IN 46142
Stereoscopic Components
SanAir ID / Description Appearance % Fibrous % Non-fibrous Asbestos Fibers
PLBC1-B / 23022459-029
Plaster Base Coat
Gray Non-Fibrous
Homogeneous
100% Other None Detected
PLBC1-C / 23022459-030
Plaster Base Coat
Gray Non-Fibrous
Homogeneous
100% Other None Detected
PLBC1-D / 23022459-031
Plaster Base Coat
Gray Non-Fibrous
Homogeneous
100% Other None Detected
PLBC1-E / 23022459-032
Plaster Base Coat
Gray Non-Fibrous
Homogeneous
100% Other None Detected
PLBC1-F / 23022459-033
Plaster Base Coat
Gray Non-Fibrous
Homogeneous
100% Other None Detected
PLBC1-G / 23022459-034
Plaster Base Coat
Gray Non-Fibrous
Homogeneous
100% Other None Detected
PLFC1-A / 23022459-035
Plaster Finish Coat
White Non-Fibrous
Homogeneous
100% Other None Detected
PLFC1-B / 23022459-036
Plaster Finish Coat
White Non-Fibrous
Homogeneous
100% Other None Detected
PLFC1-C / 23022459-037
Plaster Finish Coat
White Non-Fibrous
Homogeneous
100% Other None Detected
PLFC1-D / 23022459-038
Plaster Finish Coat
White Non-Fibrous
Homogeneous
100% Other None Detected
Analyst:
Analysis Date: 5/3/2023 Date: 5/3/2023
Approved Signatory:
10501 Trade Ct., N. Chesterfield, VA 23236 | 804.897.1177 | Fax: 804.897.0070 | www.SanAir.com | IAQ@SanAir.com
23-083Project Number:
P.O. Number:
Project Name: Federal Bureau Of Prison
4/18/2023Collected Date:
4/24/2023 10:10:00 AMReceived Date:
5/3/2023 9:50:14 AM
23022459 SanAir ID Number
FINAL REPORT
Aegis Environmental Inc.Name:
Address: 1013 N. Bluff Road
Greenwood, IN 46142
Stereoscopic Components
SanAir ID / Description Appearance % Fibrous % Non-fibrous Asbestos Fibers
PLFC1-E / 23022459-039
Plaster Finish Coat
White Non-Fibrous
Homogeneous
100% Other None Detected
PLFC1-F / 23022459-040
Plaster Finish Coat
White Non-Fibrous
Homogeneous
100% Other None Detected
PLFC1-G / 23022459-041
Plaster Finish Coat
White Non-Fibrous
Homogeneous
100% Other None Detected
Analyst:
Analysis Date: 5/3/2023 Date: 5/3/2023
Approved Signatory:
10501 Trade Ct., N. Chesterfield, VA 23236 | 804.897.1177 | Fax: 804.897.0070 | www.SanAir.com | IAQ@SanAir.com
23-083Project Number:
P.O. Number:
Project Name: Federal Bureau Of Prison
4/18/2023Collected Date:
4/24/2023 10:10:00 AMReceived Date:
5/3/2023 9:50:14 AM
23022459 SanAir ID Number
FINAL REPORT
Aegis Environmental Inc.Name:
Address: 1013 N. Bluff Road
Greenwood, IN 46142
Disclaimer
This report is the sole property of the client named on the SanAir Technologies Laboratory chain-of-custody (COC). Results in the report are confidential information intended only for the use by the customer listed on the COC. Neither results nor reports will be discussed with or released to any third party without our client's written permission. The final report shall not be reproduced except in full without written approval of the laboratory to assure that parts of the report are not taken out of context. The information provided in this report applies only to the samples submitted and is relevant only for the date, time, and location of sampling. The accuracy of the results is dependent upon the client’s sampling procedure and information provided to the laboratory by the client. SanAir assumes no responsibility for the sampling procedure and will provide evaluation reports based solely on the sample(s) in the condition in which they arrived at the laboratory and information provided by the client on the COC, such as: project number, project name, collection dates, po number, special instructions, samples collected by, sample numbers, sample identifications, sample type, selected analysis type, flow rate, total volume or area, and start stop times that may affect the validity of the results in this report. Samples were received in good condition unless otherwise noted on the report. SanAir assumes no responsibility or liability for the manner in which the results are used or interpreted. This report does not constitute and shall not be used to claim product certification, approval, or endorsement by NVLAP, NIST, or any other U.S. governmental agencies and may not be certified by every local, state, and federal regulatory agencies.
Samples are held for a period of 60 days. Fibers smaller than 5 microns cannot be seen with this method due to scope limitations.
For NY state samples, method EPA 600/M4-82-020 is performed.
NYELAP Disclaimer:
Polarized- light microscopy is not consistently reliable in detecting asbestos in floor covering and similar non-friable organically bound materials. Quantitative transmission electron microscopy is currently the only method that can be used to determine if this material can be considered or treated as non-asbestos containing.
Asbestos Certifications NVLAP lab code 200870-0 City of Philadelphia: ALL-460 PA Department of Environmental Protection Number: 68-05397 California License Number: 2915 Colorado License Number: AL-23143 Connecticut License Number: PH-0105 Massachusetts License Number: AA000222 Maine License Number: LB-0075, LA-0084 New York ELAP lab ID: 11983 Rhode Island License Number: PCM00126, PLM00126, TEM00126 Texas Department of State Health Services License Number: 300440 Commonwealth of Virginia 3333000323 Washington State License Number: C989 West Virginia License Number: LT000616 Vermont License: AL166318 Louisiana Department of Environmental Quality: 212253, Cert 05088
Revision Date: 8/14/2020
Page 1 of 1Page 9 of 11