Emergency_Lighting_Inverter_CLINs Salient Characteristics.docx

DOCX document 37 KB Posted

Attached to
USP Canaan IPS Supply and Startup
Solicitation number
15B21527Q00000002
Issued by

About this file

This document specifies the salient characteristics for emergency lighting inverter systems required under solicitation 15B21527Q00000002 for the Federal Bureau of Prisons, USP Canaan.

Three contract line items (CLINs) detail Myers Power Systems inverter units with the following specifications: CLIN 0001 requires a approximately 10,000 VA/W capacity unit with 277/480 VAC three-phase input/output, 90-minute minimum battery runtime using VRLA batteries, two-cabinet configuration, ten output breakers (five 20A normally ON and five 20A normally OFF), dry contacts for remote monitoring, and fast-transfer design suitable for emergency lighting. CLIN 0002 specifies a Myers unit with approximately 4,800 VA/W capacity, identical electrical specifications to CLIN 0001, the same battery and transfer requirements, but with four total output breakers (two 20A normally ON and two 20A normally OFF). CLIN 0003 requires a Myers 6-IE-6-BD2005-M unit with approximately 6,000 VA/W capacity, 277 VAC single-phase input/output, VRLA batteries, five 20A single-pole output breakers, internal maintenance bypass, and standard-transfer design. All three units must be UL-listed for emergency lighting service and furnished as new equipment. The procurement is on a Brand Name or Equal basis, requiring offerors proposing alternative products to submit complete technical documentation, exact make and model information, and cross-referenced compliance evidence for each salient characteristic.

View the file

Other files

File Type Posted
USP_Canaan_PWS_Emergency_Lighting_Inverters.docx DOCX document
15B21527Q00000002-SF1449.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Emergency Lighting Inverter Systems - CLIN Salient Characteristics

CLIN 0001

Basis of Design: Myers 2-D-4-S-BD2005-ND2005-S

Characteristic
Requirement
Capacity
Approximately 10,000 VA/W
Input
277/480 VAC, 3-phase, 60 Hz, 4-wire plus ground
Output
277/480 VAC, 3-phase, 60 Hz, 4-wire plus ground
Minimum battery runtime
90 minutes
Battery type
VRLA (Valve Regulated Lead Acid)
Configuration
Two-cabinet system
Output breakers
Five (5) 20A, single-pole, normally ON output breakers; Five (5) 20A, single-pole, normally OFF output breakers
Includes
Summary dry contacts for remote monitoring and alarm notification
Transfer design
Fast-transfer design suitable for emergency lighting applications
Listing
UL listed for emergency lighting service
Condition
Furnished as new equipment

CLIN 0002

Basis of Design: Myers 2-D-1-S-BD2002-ND2002-S

Characteristic
Requirement
Capacity
Approximately 4,800 VA/W
Input
277/480 VAC, 3-phase, 60 Hz, 4-wire plus ground
Output
277/480 VAC, 3-phase, 60 Hz, 4-wire plus ground
Minimum battery runtime
90 minutes
Battery type
VRLA (Valve Regulated Lead Acid)
Configuration
Two-cabinet system
Output breakers
Two (2) 20A, single-pole, normally ON output breakers; Two (2) 20A, single-pole, normally OFF output breakers
Includes
Summary dry contacts for remote monitoring and alarm notification
Transfer design
Fast-transfer design suitable for emergency lighting applications
Listing
UL listed for emergency lighting service
Condition
Furnished as new equipment

CLIN 0003

Basis of Design: Myers 6-IE-6-BD2005-M

Characteristic
Requirement
Capacity
Approximately 6,000 VA/W
Input
277 VAC, single-phase, 60 Hz
Output
277 VAC, single-phase, 60 Hz
Battery type
VRLA (Valve Regulated Lead Acid)
Output breakers
Five (5) 20A, single-pole output breakers
Includes
Internal maintenance bypass
Transfer design
Standard-transfer design suitable for emergency lighting applications
Listing
UL listed for emergency lighting service
Condition
Furnished as new equipment