Emergency_Lighting_Inverter_CLINs Salient Characteristics.docx
DOCX document 37 KB Posted
- Attached to
- USP Canaan IPS Supply and Startup
- Solicitation number
- 15B21527Q00000002
About this file
This document specifies the salient characteristics for emergency lighting inverter systems required under solicitation 15B21527Q00000002 for the Federal Bureau of Prisons, USP Canaan.
Three contract line items (CLINs) detail Myers Power Systems inverter units with the following specifications: CLIN 0001 requires a approximately 10,000 VA/W capacity unit with 277/480 VAC three-phase input/output, 90-minute minimum battery runtime using VRLA batteries, two-cabinet configuration, ten output breakers (five 20A normally ON and five 20A normally OFF), dry contacts for remote monitoring, and fast-transfer design suitable for emergency lighting. CLIN 0002 specifies a Myers unit with approximately 4,800 VA/W capacity, identical electrical specifications to CLIN 0001, the same battery and transfer requirements, but with four total output breakers (two 20A normally ON and two 20A normally OFF). CLIN 0003 requires a Myers 6-IE-6-BD2005-M unit with approximately 6,000 VA/W capacity, 277 VAC single-phase input/output, VRLA batteries, five 20A single-pole output breakers, internal maintenance bypass, and standard-transfer design. All three units must be UL-listed for emergency lighting service and furnished as new equipment. The procurement is on a Brand Name or Equal basis, requiring offerors proposing alternative products to submit complete technical documentation, exact make and model information, and cross-referenced compliance evidence for each salient characteristic.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 15B21527Q00000002 SF-1449 (Rev).pdf | ||
| USP_Canaan_PWS_Emergency_Lighting_Inverters.docx | DOCX document | |
| 15B21527Q00000002-SF1449.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Emergency Lighting Inverter Systems - CLIN Salient Characteristics
CLIN 0001
Basis of Design: Myers 2-D-4-S-BD2005-ND2005-S
| Characteristic |
| Requirement |
| Capacity |
| Approximately 10,000 VA/W |
| Input |
| 277/480 VAC, 3-phase, 60 Hz, 4-wire plus ground |
| Output |
| 277/480 VAC, 3-phase, 60 Hz, 4-wire plus ground |
| Minimum battery runtime |
| 90 minutes |
| Battery type |
| VRLA (Valve Regulated Lead Acid) |
| Configuration |
| Two-cabinet system |
| Output breakers |
| Five (5) 20A, single-pole, normally ON output breakers; Five (5) 20A, single-pole, normally OFF output breakers |
| Includes |
| Summary dry contacts for remote monitoring and alarm notification |
| Transfer design |
| Fast-transfer design suitable for emergency lighting applications |
| Listing |
| UL listed for emergency lighting service |
| Condition |
| Furnished as new equipment |
CLIN 0002
Basis of Design: Myers 2-D-1-S-BD2002-ND2002-S
| Characteristic |
| Requirement |
| Capacity |
| Approximately 4,800 VA/W |
| Input |
| 277/480 VAC, 3-phase, 60 Hz, 4-wire plus ground |
| Output |
| 277/480 VAC, 3-phase, 60 Hz, 4-wire plus ground |
| Minimum battery runtime |
| 90 minutes |
| Battery type |
| VRLA (Valve Regulated Lead Acid) |
| Configuration |
| Two-cabinet system |
| Output breakers |
| Two (2) 20A, single-pole, normally ON output breakers; Two (2) 20A, single-pole, normally OFF output breakers |
| Includes |
| Summary dry contacts for remote monitoring and alarm notification |
| Transfer design |
| Fast-transfer design suitable for emergency lighting applications |
| Listing |
| UL listed for emergency lighting service |
| Condition |
| Furnished as new equipment |
CLIN 0003
Basis of Design: Myers 6-IE-6-BD2005-M
| Characteristic |
| Requirement |
| Capacity |
| Approximately 6,000 VA/W |
| Input |
| 277 VAC, single-phase, 60 Hz |
| Output |
| 277 VAC, single-phase, 60 Hz |
| Battery type |
| VRLA (Valve Regulated Lead Acid) |
| Output breakers |
| Five (5) 20A, single-pole output breakers |
| Includes |
| Internal maintenance bypass |
| Transfer design |
| Standard-transfer design suitable for emergency lighting applications |
| Listing |
| UL listed for emergency lighting service |
| Condition |
| Furnished as new equipment |