Emergency Lighting Inverter Systems - CLIN Salient Characteristics
CLIN 0001
Basis of Design: Myers 2-D-4-S-BD2005-ND2005-S
| Characteristic |
| Requirement |
| Capacity |
| Approximately 10,000 VA/W |
| Input |
| 277/480 VAC, 3-phase, 60 Hz, 4-wire plus ground |
| Output |
| 277/480 VAC, 3-phase, 60 Hz, 4-wire plus ground |
| Minimum battery runtime |
| 90 minutes |
| Battery type |
| VRLA (Valve Regulated Lead Acid) |
| Configuration |
| Two-cabinet system |
| Output breakers |
| Five (5) 20A, single-pole, normally ON output breakers; Five (5) 20A, single-pole, normally OFF output breakers |
| Includes |
| Summary dry contacts for remote monitoring and alarm notification |
| Transfer design |
| Fast-transfer design suitable for emergency lighting applications |
| Listing |
| UL listed for emergency lighting service |
| Condition |
| Furnished as new equipment |
CLIN 0002
Basis of Design: Myers 2-D-1-S-BD2002-ND2002-S
| Characteristic |
| Requirement |
| Capacity |
| Approximately 4,800 VA/W |
| Input |
| 277/480 VAC, 3-phase, 60 Hz, 4-wire plus ground |
| Output |
| 277/480 VAC, 3-phase, 60 Hz, 4-wire plus ground |
| Minimum battery runtime |
| 90 minutes |
| Battery type |
| VRLA (Valve Regulated Lead Acid) |
| Configuration |
| Two-cabinet system |
| Output breakers |
| Two (2) 20A, single-pole, normally ON output breakers; Two (2) 20A, single-pole, normally OFF output breakers |
| Includes |
| Summary dry contacts for remote monitoring and alarm notification |
| Transfer design |
| Fast-transfer design suitable for emergency lighting applications |
| Listing |
| UL listed for emergency lighting service |
| Condition |
| Furnished as new equipment |
CLIN 0003
Basis of Design: Myers 6-IE-6-BD2005-M
| Characteristic |
| Requirement |
| Capacity |
| Approximately 6,000 VA/W |
| Input |
| 277 VAC, single-phase, 60 Hz |
| Output |
| 277 VAC, single-phase, 60 Hz |
| Battery type |
| VRLA (Valve Regulated Lead Acid) |
| Output breakers |
| Five (5) 20A, single-pole output breakers |
| Includes |
| Internal maintenance bypass |
| Transfer design |
| Standard-transfer design suitable for emergency lighting applications |
| Listing |
| UL listed for emergency lighting service |
| Condition |
| Furnished as new equipment |