Generator_Maint_Monthly_Checklist_Baldor_1250KW(ST._LOUIS _MO).pdf
PDF 21 KB Posted
- Attached to
- Notice of Intent to Award - Limited Sources Basis - Cummins and Baldor Generator Maintenance
- Solicitation number
- 14IAS-CUMMINS-BALDOR-GENERATOR-MAINTENANCE
About this file
Baldor Generator Maintenance Monthly Maintenance Log
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
1250 KW BALDOR GENERATORS MONTHLY GENERATOR MAINTENANCE LOG PAGE 1 OF 3
WORK TO BE PERFORMED OCT NOV DEC JAN FEB MAR APR MAY JUN JUL AUG SEP
MONTHLY
RECORD HOURS OF OPERATION
BEFORE GENERATOR START-UP:
CONDUCT EXTERNAL INSPECTION (CHECK FOR LEAKAGE OF FUEL, OIL, COOLANT)
CHECK FUEL LEVEL AND RECORD READINGS IN LOG. NOTIFY COR IF 1/2 TANK
OR BELOW.
CHECK ENGINE OIL LEVEL (CHECK FOR MIXING OF OIL AND WATER)
CHECK AIR COOLER FOR LEAKS
CHECK ALL BATTERY CONNECTIONS AND ELECTROLYTE LEVELS
RECORD ANTI-FREEZE STRENGTH (CHECK FOR OIL IN COOLANT)
INSPECT FUEL CONTROL LINKAGES AND BALL JOINTS
CLEAN FUEL FILTER (WIRE ELEMENT TYPE) TURN HANDLE ONE OR TWO TIMES
CHECK BELTS FOR WEAR AND REPLACE AS NEEDED
CLEAN INTERIOR OF GENERATOR ENCLOSURE
BLOW OUT GENERATOR WINDINGS
CHECK ALL FUEL LINES FOR LEAKS
CHECK FUEL PUMPS FOR LEAKS AND TEST RUN FOR PROPER OPERATION
CHECK FOR WATER IN ALL FUEL TANKS
WHILE GENERATOR IS RUNNING FOR 1/2 HOUR UNDER LOAD
CHECK FOR EASE OF STARTING, COLOR OF EXHAUST SMOKE, ABNORMAL
VIBRATION, NOISE, SMELL, ETC., AND GAUGE INDICATION OF A PROBLEM
RECORD EXHAUST TEMPERATURE GAUGE, IF PRESENT
RECORD TACHOMETER
RECORD OIL PRESSURE (psi) RECORD FUEL PRESSURE (psi) RECORD FREQUENCY (rpm)
RECORD GENERATED VOLTAGE
RECORD CHARGING AMPERAGE
CHECK GOVERNOR OPERATION
RECORD OUTPUT POWER (KW)
CHECK FUEL INJECTION PUMP AND HYDRAULIC AND ELECTRONIC GOVERNOR
RACK MOVEMENT
INSPECT PARALELLING GEAR FOR PROPER OPERATION; ADJUST AS NEEDED
MANUALLY STICK ABOVEGROUND FUEL TANK AND RECORD READINGS IN LOG
TANK AND RECORD READINGS ON LOG
JADAMS
Typewritten Text
1250 KW BALDOR GENERATORS MONTHLY MAINTENANCE LOG
JADAMS
Typewritten Text
JADAMS
Typewritten Text
JADAMS
Typewritten Text
JADAMS
Typewritten Text
1250 KW BALDOR GENERATORS SEMI-ANNUAL & ANNUAL GENERATOR MAINTENANCE LOG PAGE 2 OF 3
WORK TO BE PERFORMED OCT NOV DEC JAN FEB MAR APR MAY JUN JUL AUG SEP
SEMI-ANNUALLY (OCT, APR)
PERFORM MONTHLY MAINTENANCE
REPLACE AIR FILTERS IF NEEDED
CHECK CONTROL PANEL FOR LOOSE WIRING
CHECK INTAKE/EXHAUST AREAS
CHECK HOLD DOWN BOLTS
CHECK LLC CONCENTRATION IN THE COOLANT
CLEAN THE INSIDE OF THE COOLANT TANK
ANNUALLY (OCT)
PERFORM MONTHLY & SEMI-ANNUAL MAINTENANCE
INSPECT V BELT. ADJUST TENSION AS NEEDED. REPLACE BELTS
AS NEEDED.
INSPECT AND TIGHTEN EXTERNAL NUTS, BOLTS.
INSPECT AND ADJUST VALVE CLEARANCE AND RELATED PARTS
INSPECT VIBRATION ISOLATING RUBBER COMPONENTS
INSPECT FOUNDATION ANCHOR NUTS, BOLTS
INSPECT COUPLINGS. REPLACE COUPLINGS AS NEEDED
DRAIN WATER AND SEDIMENT FROM ALL FUEL TANKS
DRAIN WATER FROM WIRE ELEMENT-TYPE FUEL FILTERS
INSPECT AND ADJUST FUEL INJECTION NOZZLE SPRAY CONDITION
AND SPRAY PRESSURE
INSPECT AND ADJUST FUEL INJECTION TIMING
PERFORM ENGINE OIL SAMPLING AND ANALYSIS
INSPECT AND ADJUST ENGINE OIL PRESSURE
INSPECT WATER PUMP
INSPECT AND CLEAN STRAINER FOR COOLANT
ANALYZE COOLANT PROPERTIES AND REPLACE AS NEEDED
INSPECT AIR FILTER. REPLACE AIR FILTER AS NEEDED.
INSPECT STARTER(S)
INSPECT ALTERNATOR
CHECK SPECIFIC GRAVITY OF BATTERY ELECTROLYTE
INSPECT AIR HEATER
CHECK FOR ANY LOOSE WIRES OR LOOSE CONNECTIONS
CHECK DEVICES FOR PROPER OPERATION: HIGH TEMP, LOW OIL
PRESSURE, OVERSPEED, START FAILURE, WATER SUPPLY FAILURE,
UNDERVOLTAGE, OVERVOLTAGE, OVERCURRENT, LOW COOLANT
LEVEL, LOW FUEL LEVEL, ETC.
CHECK AUXILIARY DEVICES FOR PROPER OPERATION: FUEL
CONTROL SOLENOIDS, FUEL SUPPLY PUMPS, UNIT HEATERS,
WATER JACKET HEATERS, BATTERY CHARGERS, ETC.
AFTER GENERATORS RUN:
CHECK OIL LEVEL
CHECK FOR LEAKS-WATER, FUEL, OIL
CHECK TO INSURE STATUS IN AUTO-START MODE & BREAKERS SET
RECORD SERVICE METER
MAKE ANY REPAIRS OR ADJUSTMENTS AS
NEEDED
TAKE FUEL SAMPLES OF ALL TANKS
IN NOVEMBER AND MAY
JADAMS
Typewritten Text
JADAMS
Typewritten Text
JADAMS
Typewritten Text
1250 KW BALDOR GENERATOR MONTHLY MAINTENACNE LOG
JADAMS
1250 KW BALDOR GENERATORS TWO-YEAR AND FOUR-YEAR GENERATOR MAINTENANCE LOG
WORK TO BE PERFORMED DURING TWO-YEAR MAINTENANCE: 2012 2014 2016 2018 2020 2022
PERFORM MONTHLY, SEMI-ANNUAL, AND ANNUAL
MAINTENANCE (OCT)
CHANGE ENGINE OIL, OIL FILTERS, AND BYPASS OIL
SAMPLE AND ANALYZE ENGINE OIL PROPERTIES
CLEAN WIRE ELEMENT FUEL FILTERS
CHANGE NON-WIRE ELEMENT FUEL FILTERS
DRAIN & CLEAN COOLING SYSTEM
REPLACE THERMOSTATS, GASKETS, AND SEALS
REFILL COOLING SYSTEM
REPLACE RUBBER BELTS & HOSES
REPLACE BATTERIES
CHECK/INSPECT TURBOCHARGERS
WORK TO BE PERFORMED DURING FOUR-YEAR MAINTENANCE: 2012 2016 2020
PERFORM MONTHLY, SEMI-ANNUAL, ANNUAL, AND TWO-YEAR
MAINTENANCE (OCT)
CHECK OIL COOLER FOR SOILING, CLOGGING, AND LEAKAGE
CHECK OIL PUMP FOR DISCOLORATION AND OTHER EXTERNAL
DEFECTS
INSPECT AND TEST GOVERNOR. REPAIR AS NEEDED.
INSPECT AND CLEAN FUEL TANK
INSPECT AND TEST FUEL INJECTION PUMP. REPAIR AS NEEDED.
REPLACE RUBBER HOSES.
INSPECT AND CLEAN AIR CLEANER ELEMENT
INSPECT AND CLEAN PRE-CLEANER
INSPECT ALL GAUGES. REPAIR AS NEEDED.
JADAMS
Typewritten Text
JADAMS
Typewritten Text
JADAMS
1250 KW BALDOR GENERATOR MONTHLY MAINTENACNE LOG
File details come from the government source that posted it. Updated .