Site_Visit_Synopsis_with_QAs_0001.docx
DOCX document 27 KB Posted
- Attached to
- BGNDRF REPLACE AHU-01, ACCU-01 Federal contract opportunity
- Solicitation number
- 140R4026Q0097
About this file
This is a Site Visit Synopsis with Questions and Answers document for a federal contract opportunity to replace HVAC equipment at a Bureau of Reclamation facility. The project, identified as Solicitation Number 140R4026Q0097, involves replacing AHU-01 and ACCU-01 units at 500 La Velle Rd, Alamosordo, NM 88310. Site visits were conducted on June 25 and July 1, 2026, with multiple mechanical contractors and construction inspectors in attendance, including representatives from Gray Heating & Cooling, Dynamic Heating & Cooling, Mechanical Technologies, Rio West Mechanical Solutions, Axis Air LLC, 3R Texas Mechanical, and Bering Straits Global Innovation. The COR for the Bureau of Reclamation provided a walking tour of the existing equipment, including controls, workshop access, electrical and server rooms, mezzanine evaporator coil location, and outside condenser unit.
Key contractual clarifications addressed in the Q&A include that any qualified small business with active SAM.gov registration may bid; contractors must provide technical justification for replacing refrigerant lines, copper lines, and insulation based on warranty and operational requirements; the condensate drain line replacement requires justification, with copper preferred due to location; electrical breaker sizing may be upgraded to 30-amp if operationally necessary; and coordination with Trane is required to ensure new controls integrate with the existing 2020 Trane Tracer Synchrony system (v5.40.1469 release) that was previously installed by Trane's El Paso office. The technical proposal format allows flexibility in design approach provided adequate justification is supplied for all modifications to existing systems.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Sol_140R4026Q0097_Amd_0001.pdf | ||
| Additional_Questions_and_Answers_0001.docx | DOCX document | |
| E4(200_1_0001.PDF | ||
| Sol_140R4026Q0097.pdf | ||
| Attachment_3_-_Wage_Rates_NM20260025.pdf | ||
| Attachment_2_-_Price_Schedule.docx | DOCX document | |
| Attachment_1_-_SOW_Replace_AHU01__ACCU-01.docx | DOCX document |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
140R4026Q0097 – BGNDRF Replace AHU-01, ACCU-01 Page 2 of 2
Site Visit Synopsis with Questions and Answers
| Location: | 500 La Velle Rd, Alamogordo, NM, 88310 | |
| Date & Time: | June 25, 9 a.m. and July 1, 2026, 9:00 a.m. and 10:30 a.m. |
Attendees:
Jose Huela and Raul Guerrero, Gray Heating & Cooling Robert Vigil, Dynamic Heating & Cooling Jaime Zubiate, Mechanical Technologies Ruben Hernandez, Rio West Mechanical Solutions Justin Horan, Axis Air, LLC Richard Osiecki, 3R Texas Mechanical (Derek Gonzalez)/Texas Plumbing (Eddie Gonzalez)/Texas Electric (Javier Garcia) Andy Bizzell and Cody Lee, Bering Straits Global Innovation (Construction Inspectors) Malynda Cappelle, COR for Bureau of Reclamation (Reclamation)
Site Visit Overview:
Malynda provided a walking tour showing the locations of the existing controls, workshop (to access evaporator coil), electrical room, server room (location of Trane BCU), mezzanine (evaporator coil), and outside (condenser unit).
The scope of work was summarized, and companies were able to ask questions, take measurements, and take pictures. A summary is provided below.
Questions asked:
1. If a company was present for the tour as a representative of another company, are they able to also bid on the job.
Government Response:
Any qualified small business with an active SAM.gov registration can provide a quote.
2. Does the SOW include replacing copper refrigerant and other lines connecting the condenser and evaporator units?
Government Response:
All companies should provide a technical approach with justification for new versus new lines and insulation. If the warranty or proper operation require replacement, include that as part of the technical proposal.
3. Does the condensate drain line need to be replaced and if so does the government prefer PVC?
Government Response:
The condensate line appears to be in good condition, however, if there is a reason to replace it, include a justification in the technical proposal. Copper is preferred because of the location.
4. The ACCU-1 breaker seems to be undersized. The wire and fuses suggest 30-amp service and label says 22 amps. Does the breaker need to be replaced with a higher capacity?
Government Response:
If the new unit requires the same or higher amperage and operation is better with 30-amp breaker, it is acceptable. The BS-1 (building supply) electrical one-line drawing is provided for reference. Note that the original 40-amp breaker for ACU-1 was replaced with a 50-amp breaker (noted in 3216B680 E4 drawing). The two breakers for ACCU-1 and AHU-1 are circled in the drawing.
5. What is the current model of the Trane Tracer program?
Government Response:
We believe it is 2020 Trane Tracer® Synchrony – v5.40.1469 release based on the program screen. The original BAS was removed and new system installed in 2020 by Trane (El Paso office). Coordination or subcontracting Trane will ensure the correct controls are included and integrated with the existing system.
image1.png