This document is a detailed utility service specification for electrical power requirements at multiple locations for the Klamath Basin Area Office (KBAO). The file lists 10 line items specifying electric service details for various pumping stations, dams, and facilities across California and Oregon, including No. 1, 2, and 3 Drainage Pumps, Lower Lake Road Merrill pumps, KBAO & Boat Barn/O&M Office, Wilson Dam, Pumping Plants E, EE, F, FF, A Canal, Keno Dam, Link River Dam, and Station 48. Each location has specific requirements for power type, including underground or overhead service, single or three-phase power, voltage specifications (primarily 240/480 or 2400 volts), and connection types, with most sites requiring underground, 60 cycle/hertz, alternating current electrical service.

View the file

Other files for this federal contract opportunity

Other files attached to Electrical Services for Klamath Basin Area Office, newest first.
File Type Posted
Sol_140R2025Q0043.pdf PDF
C5_5_Attach_3_Meter_Locations_Maps_C-J.pdf PDF
C5_5_Attach_1_Site_Map_A.pdf PDF
C5_5_Attach_2_Site_Map_B.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

KBAO Pacific Power Utility Service – Updated 4/04/2025

Line Item

Description Account # Address Map Number

The type of electric service required by the Government is:

The normal delivery voltage shall be:

00010 Pumping Power to No.

1,2 and 3- Drainage Pumps, Sump

40470641-005-1, No. 2 Pump, 1.4 Mile S. Township Road, Worden, CA (AREA K)

12-201-5283 Attach 1 Site Map A

[] overhead [X] underground, 60 cycle/hertz, [] single-phase [] 3- phase, [] 2-wire [] 3-wire [] 4-wire, [] Delta-connected [] Wye-connected, alternating current. [Enter requirement for dual-feeder service, if justified.]

[] 120/240 [] 120/208 [X] 240/480 [] 277/480 [] [Enter other secondary and/or primary voltages, as appropriate], with an allowable variation of percent above or below normal. [Enter, if applicable, information on the maximum acceptable frequency and maximum duration of outages.]

40470641-006-9, No. 3 Pump, 1.4 Mile S. Township Road, Warden, CA (AREA K)

12-201-5283 Attach 1 Site Map A

[] overhead [X] underground, 60 cycle/hertz, [] single-phase [] 3- phase, [] 2-wire [] 3-wire [] 4-wire, [] Delta-connected [] Wye-connected, alternating current. [Enter requirement for dual-feeder service, if justified.]

[] 120/240 [] 120/208 [X] 240/480 [] 277/480 [] [Enter other secondary and/or primary voltages, as appropriate], with an allowable variation of percent above or below normal. [Enter, if applicable, information on the maximum acceptable frequency and maximum duration of outages.]

40470641-007-7, No. 1 Pump, 1 Mile S.

Township Road, Worden, CA (AREA K)

12-201-5283 Attach 1 Site Map A

[] overhead [X] underground, 60 cycle/hertz, [] single-phase [] 3- phase, [] 2-wire [] 3-wire [] 4-wire, [] Delta-connected [] Wye-connected, alternating current. [Enter requirement for dual-feeder service, if justified.]

[] 120/240 [] 120/208 [X] 240/480 [] 277/480 [] [Enter other secondary and/or primary voltages, as appropriate], with an allowable variation of percent above or below normal. [Enter, if applicable, information on the maximum acceptable frequency and maximum duration of outages.]

40470641-015-0 Sump 3, Lot 8327 Washrack # 3, County Road 103, Tulelake, CA

12-201-5386 Attach2 Site Map B

[X] overhead [] underground, 60 cycle/hertz, [] single-phase [] 3- phase, [] 2-wire [] 3-wire [] 4-wire, [] Delta-connected [] Wye-connected, alternating current. [Enter requirement for dual-feeder service, if justified.]

[] 120/240 [] 120/208 [X] 240/480 [] 277/480 [] [Enter other secondary and/or primary voltages, as appropriate], with an allowable variation of percent above or below normal. [Enter, if applicable, information on the maximum acceptable frequency and maximum duration of outages.]

00020 Power to Lower Lake Rd Merrill

40470641-002-8 No. 4 Pump & C-1-1 pump, AREA K, OR

12-201-5283 Attach 1 Site Map A

[] overhead [X] underground, 60 cycle/hertz, [] single-phase [X] 3- phase, [] 2-wire [] 3-wire [] 4-wire, [] Delta-connected [] Wye-connected, alternating current. [Enter requirement for dual-feeder service, if justified.]

[] 120/240 [] 120/208 [X] 240/480 [] 277/480 [] [Enter other secondary and/or primary voltages, as appropriate], with an allowable variation of percent above or below normal. [Enter, if applicable, information on the maximum acceptable frequency and maximum duration of outages.]

00030 Power to

KBAO &

Boat Barn/O&M Office

40470641-011-9, 6600 Washburn Way, Klamath Falls OR, 97603

Attach 3 - Map C (pg 1)

[X- historical meter # 237657730] overhead [X-historical meter # 16488548] underground, 60 cycle/hertz, [X] single-phase [] 3- phase, [] 2-wire [] 3-wire [] 4-wire, [] Delta-connected [] Wye-connected, alternating current. [Enter requirement for dual-feeder service, if justified.]

[X] 120/240 [] 120/208 [] 240/480 [] 277/480 [] [Enter other secondary and/or primary voltages, as appropriate], with an allowable variation of percent above or below normal. [Enter, if applicable, information on the maximum acceptable frequency and maximum duration of outages.]

40470641-001-0 6600 Washburn Way, Klamath Falls OR, 97603

Attach 3 - Map C (pg 1)

[] overhead [X] underground, 60 cycle/hertz, [X] single-phase [] 3- phase, [] 2-wire [] 3-wire [] 4-wire, [] Delta-connected [] Wye-connected, alternating current. [Enter requirement for dual-feeder service, if justified.]

[X] 120/240 [] 120/208 [] 240/480 [] 277/480 [] [Enter other secondary and/or primary voltages, as appropriate], with an allowable variation of percent above or below normal. [Enter, if applicable, information on the maximum acceptable frequency and maximum duration of outages.]

0040 Wilson Dam 40470641-013-5 Wilson Dam at Hill Road, Lost River

Attach 3 - Map H (pg 6)

[] overhead [X] underground, 60 cycle/hertz, [X] single-phase [] 3- phase, [] 2-wire [] 3-wire [] 4-wire, [] Delta-connected [] Wye-connected, alternating current. [Enter requirement for dual-feeder service, if justified.]

[X] 120/240 [] 120/208 [] 240/480 [] 277/480 [] [Enter other secondary and/or primary voltages, as appropriate], with an allowable variation of percent above or below normal. [Enter, if applicable, information on the maximum acceptable frequency and maximum duration of outages.]

00050 Power to Plant E & EE

40470641-004-4, Pumping Plant E, Klamath Falls, OR Attach 3 -

Map E (pg 3)

[] overhead [X] underground, 60 cycle/hertz, [] single-phase [X] 3- phase, [] 2-wire [] 3-wire [] 4-wire, [] Delta-connected [] Wye-connected, alternating current. [Enter requirement for dual-feeder service, if justified.]

[] 120/240 [] 120/208 [] 240/480 [] 277/480 [X] 2400 [Enter other secondary and/or primary voltages, as appropriate], with an allowable variation of percent above or below normal. [Enter, if applicable, information on the maximum acceptable frequency and maximum duration of outages.]

40470641-008-5 Pumping Plant EE, Hwy 97, Klamath Falls, OR

Attach 3 - Map E (pg 3)

[] overhead [X] underground, 60 cycle/hertz, [] single-phase [X] 3- phase, [] 2-wire [] 3-wire [] 4-wire, [] Delta-connected [] Wye-connected, alternating current. [Enter requirement for dual-feeder service, if justified.]

[] 120/240 [] 120/208 [] 240/480 [] 277/480 [X] 2400 [Enter other secondary and/or primary voltages, as appropriate], with an allowable variation of percent above or below normal. [Enter, if applicable, information on the maximum acceptable frequency and maximum duration of outages.]

00060 Power to Plant F & FF

40470641-009-3, Pumping Plant FF, Ashland Star Rt Attach 3 -

Map F (pg 4)

[] overhead [X] underground, 60 cycle/hertz, [] single-phase [X] 3- phase, [] 2-wire [] 3-wire [] 4-wire, [] Delta-connected [] Wye-connected, alternating current. [Enter requirement for dual-feeder service, if justified.]

[] 120/240 [] 120/208 [] 240/480 [] 277/480 [X] 2400 [Enter other secondary and/or primary voltages, as appropriate], with an allowable variation of percent above or below normal. [Enter, if applicable, information on the maximum acceptable frequency and maximum duration of outages.]

40470641-010-1 Pumping Plant F, Klamath Falls, OR

Attach 3 - Map F (pg 4)

[] overhead [X] underground, 60 cycle/hertz, [] single-phase [X] 3- phase, [] 2-wire [] 3-wire [] 4-wire, [] Delta-connected [] Wye-connected, alternating current. [Enter requirement for dual-feeder service, if justified.]

[] 120/240 [] 120/208 [] 240/480 [] 277/480 [X] 2400 [Enter other secondary and/or primary voltages, as appropriate], with an allowable variation of percent above or below normal. [Enter, if applicable, information on the maximum acceptable frequency and maximum duration of outages.]

00070 A Canal 40470641-004-4 A Canal Structures at 400 Nevada Street, Klamath Falls, OR

Attach 3 - Map D (pg 2)

[] overhead [X] underground, 60 cycle/hertz, [] single-phase [X] 3- phase, [] 2-wire [] 3-wire [] 4-wire, [] Delta-connected [] Wye-connected, alternating current. [Enter requirement for dual-feeder service, if justified.]

[] 120/240 [] 120/208 [X] 240/480 [] 277/480 [] [Enter other secondary and/or primary voltages, as appropriate], with an allowable variation of percent above or below normal. [Enter, if applicable, information on the maximum acceptable frequency and maximum duration of outages.]

00080 Keno Dam 40470641-027-5 Keno Dam on Green Springs Hwy 66, Keno, OR

Attach 3 – Map I (pg 7)

[X] overhead [] underground, 60 cycle/hertz, [] single-phase [X] 3- phase, [] 2-wire [] 3-wire [] 4-wire, [] Delta connected [] Wye-connected, alternating current. [Enter requirement for dual-feeder service, if justified.]

[] 120/240 [] 120/208 [] 240/480 [X] 277/480 [] [Enter other secondary and/or primary voltages, as appropriate], with an allowable variation of percent above or below normal. [Enter, if applicable, information on the maximum acceptable frequency and maximum duration of outages.]

00090 Link River Dam

40470641-028-3 Link River Dam structure along the Link River Trail on Lakeshore Drive, Klamath Falls, OR

Attach 3 – Map J (pg 8)

[] overhead [X] underground, 60 cycle/hertz, [] single-phase [X] 3- phase, [] 2-wire [] 3-wire [] 4-wire, [] Delta connected [] Wye-connected, alternating current. [Enter requirement for dual-feeder service, if justified.]

[X] 120/240 [] 120/208 [] 240/480 [] 277/480 [] [Enter other secondary and/or primary voltages, as appropriate], with an allowable variation of percent above or below normal. [Enter, if applicable, information on the maximum acceptable frequency and maximum duration of outages.]

00100 Power to Station 48

40470641-012-7 Station 48 at Henley Road, Lost River Attach 3 -

Map C (pg 1)

[X- historical meter # 237657730] overhead [X-historical meter # 16488548] underground, 60 cycle/hertz, [X] single-phase [] 3- phase, [] 2-wire [] 3-wire [] 4-wire, [] Delta-connected [] Wye- connected, alternating current. [Enter requirement for dual-feeder service, if justified.]

[] 120/240 [] 120/208 [X] 240/480 [] 277/480 [] [Enter other secondary and/or primary voltages, as appropriate], with an allowable variation of percent above or below normal. [Enter, if applicable, information on the maximum acceptable frequency and maximum duration of outages.]