The key requirements include furnishing a 480-volt secondary unit substation, motor control centers, metal-clad unit and station service breakers, and 125-volt DC distribution panelboards. The specifications provide details on the components to be furnished, such as voltage, amperage, and transformer sizes. The solicitation also includes information on a site visit scheduled for August 14, 2024, and instructions for submitting technical questions. Any responses to technical questions that affect the Components of Work requirement will result in a follow-on amendment to the solicitation.

View the file

Other files

Show all 24

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Solicitation No. 140R2024Q0080

SECTION C - Components of Work

A. Furnish secondary unit substation including station service transformers, 480-volt station service lineup, associated protective relay systems, and associated instrumentation transformers:

1. D1A: 480-volt, 600 ampere bus lineup with motor control buckets, draw out breakers, and panelboards.

2. K1B and K1C: 300 kVA, 4.16 kilovolt-480 volt dry-type transformers.

3. 52C: 4.16 kilovolt, 2,000 ampere vacuum circuit breaker.

B. Furnish motor control centers (MCCs), associated protective relay systems, and associated instrumentation transformers:

1. N2A: 480-volt, 600 ampere heating and ventilating MCC.

2. MSA: 480-volt, 600 ampere miscellaneous power MCC.

C. Furnish metal-clad unit and station service breakers and associated instrument transformers:

1. U1A2 and U2A2: 4.16 kilovolt, 2,000 ampere unit breakers.

2. U1A3 and U2A3: 4.16 kilovolt, 2,000 ampere station service breakers.

D. Furnish 125-volt DC, 250 ampere distribution panelboards.

E. Drawings and Data:

1. Furnish required drawings and data.

F. Site Visit: The Government will hold a site visit at Sacramento State Aquatic Center - 1901 Hazel Ave., Gold River, CA 95670. Main Parking Lot on 14 August 2024 between 12:00 pm to 4:00 pm PST. All interested may attend with a limit of three (3) attendees per firm. The names of all attendees and all questions regarding this solicitation should be directed via e-mail to Contract Specialist Charlesetta Seibure at cseibure@usbr.gov two days prior to the scheduled site visit.

Point of Contact – Alex Sanchez Technical questions will not be addressed during the site visit. Technical questions must be submitted via e-mail to Contract Specialist, Charlesetta Seibure at cseibure@usbr.gov at 3:00 pm PST no later than two business days after the scheduled site visit. If Government responses to technical questions affect the Components of Work requirement, a follow-on Amendment to the Solicitation will be issued.

END OF SECTION