This document is an Inspection and Testing Certificate for the Sea Scout Base located in San Francisco, California. The inspection was conducted by Battalion One Fire Protection on October 26, 2023 and covered the fire alarm control panel, initiating devices, and power supplies. All equipment passed the inspection, including the Bosch 5520 fire alarm control panel, 12 smoke detectors, 2 heat detectors, and a sealed lead acid backup battery. The inspection was performed in compliance with NFPA 72 standards and accepted by the National Park Service, which manages the property.
The related federal contract opportunity is for annual inspection, testing, maintenance, and alarm services for fire and intrusion alarm systems at facilities managed by the National Park Service Pacific West Region. The solicitation number is 140P8624Q0034, and the opportunity type is a solicitation. The contract is for services at the Sea Scout Base and other National Park Service properties in the Pacific West Region.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Inspection and Testing Certificate Presented To
National Park Service - NPS
For
Sea Scout Base
3500 Van Ness Ave
San Francisco, California 94109
United States
This site has been inspected and tested in compliance with applicable standards.
Completed Thursday, October 26, 2023
Test Session :26 Oct 2023 09:07
Test Plans : Fire Alarm Annual Inspection
ACCEPTED BY TESTED BY
National Park Service - NPS
2 Marina Blvd Building E SAN FRANCISCO, California 94123 United States
Julian Rodriguez
Battalion One Fire Protection
14755 Catalina Street San Leandro, CA 94577 United States
Battalion One Fire Protection
Inspection Summary
Building Information
PROPERTY Sea Scout Base CONTACT
ADDRESS 3500 Van Ness Ave PHONE
CITY/STATE/ZIP San Francisco, California 94109 MOBILE
COUNTRY United States EMAIL
Inspector Information
COMPANY Battalion One Fire Protection CONTACT Julian Rodriguez
ADDRESS
14755 Catalina Street San Leandro, CA 94577
LICENSE NUMBER
PHONE +1 510-736-7755
COUNTRY United States EMAIL jrodriguez@battaliononefire.com
Testing Summary
EQUIPMENT TYPE TOTAL TESTED PASSED FAILED
1 1(100%) 1(100%) 0(0%)
12 12(100%) 12(100%) 0(0%)
1 1(100%) 1(100%) 0(0%)
Certification The equipment specified herein was inspected and tested according to the NFPA 72 standard for fire alarm and signaling systems, with the inspection completed on Thursday, October 26, 2023
ACCEPTED BY 10/26/2023 TESTED BY 10/26/2023
Julian Rodriguez
Building Representative Technician
Fire Control Panel
Initiating Device
Power Supplies
Page 2 of 6Page 2 of 6Battalion One Fire Protection
System Details
Control Units
DESCRIPTION FACP Bosch 5520ADDRESS / SCAN ADDRESS
S/W VERSIONMANUFACTURER
LAST UPDATEMODEL
S/W LOCATIONSERIAL NUMBER
INSTALL DATE 09/26/2019
Secondary Power TYPE Battery - Sealed Lead Acid DESCRIPTION Facp Back up Batt. (1) 12 volt 7 amp
ADDRESS / SCAN ADDRESS NOMINAL VOLTAGE
LOAD VOLTAGE AMP HOURS
STANDBY HOURS ALARM MINUTES
BATTERY LOCATION CHARGER VOLTAGE
Page 3 of 6Page 3 of 6Battalion One Fire Protection
Testing Details
Fire Control Panel
Passed
EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME
Fire Alarm Control Panel FACP Bosch 5520 Manual 10/26/2023 9:12:19 AM
FACP Passed Visual Inspection Passed (Manual)
Functional Inspection Passed
Alarm Verification Timer (s) 30_seconds
Initiating Device
Passed
EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME
Smoke Detector Zone 12 Lockers / changing area Manual 10/26/2023 9:08:38 AM
Visual Inspection Passed (Manual)
Functional Inspection Passed
Smoke Detector Zone 17 Store Room 2 Manual 10/26/2023 9:08:43 AM
Visual Inspection Passed (Manual)
Functional Inspection Passed
Smoke Detector Zone 14 Front Meeting Room Manual 10/26/2023 9:08:47 AM
Visual Inspection Passed (Manual)
Functional Inspection Passed
Smoke Detector Zone 16 Store Room 1 Manual 10/26/2023 9:12:10 AM
Visual Inspection Passed (Manual)
Functional Inspection Passed
Smoke Detector Zone 18 Store Room 3 Manual 10/26/2023 9:12:14 AM
Visual Inspection Passed (Manual)
Functional Inspection Passed
Smoke Detector Zone 19 Store Room 4 Manual 10/26/2023 9:12:50 AM
Visual Inspection Passed (Manual)
Functional Inspection Passed
Smoke Detector Zone 20 Store Room 5 Manual 10/26/2023 9:13:29 AM
Visual Inspection Passed (Manual)
Functional Inspection Passed
Smoke Detector Zone 21 Store Room 6 Manual 10/26/2023 9:14:13 AM
Visual Inspection Passed (Manual)
Functional Inspection Passed
Smoke Detector Zone 15 Rear Meeting Room Manual 10/26/2023 9:17:07 AM
Visual Inspection Passed (Manual)
Functional Inspection Passed
Heat Detector Zone 11 Restroom Heat Manual 10/26/2023 9:17:11 AM
Visual Inspection Passed (Manual)
Functional Inspection Passed
Heat Detector Zone 13 Shop Heat Manual 10/26/2023 9:17:16 AM
Visual Inspection Passed (Manual)
Functional Inspection Passed
Smoke Detector Zone 10 Front doorway entry Manual 10/26/2023 9:17:19 AM
Visual Inspection Passed (Manual)
Functional Inspection Passed
Power Supplies
Passed
EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME
Page 4 of 6Page 4 of 6Battalion One Fire Protection
EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME
Battery - Sealed Lead Acid Facp Back up Batt. (1) 12 volt 7 amp Manual 10/26/2023 9:08:28 AM
Visual Inspection Passed (Manual)
Functional Inspection Passed
Page 5 of 6Page 5 of 6Battalion One Fire Protection
Device/Equipment Details
Fire Control Panel
ADDRESS DESCRIPTION MANUFACTURER MODEL SERIAL INSTALL DATE
Fire Alarm Control Panel
FACP Bosch 5520 09/27/2019
Initiating Device
ADDRESS DESCRIPTION MANUFACTURER MODEL SERIAL INSTALL DATE
Smoke Detector
Zone 10 Front doorway entry 09/27/2019
Zone 12 Lockers / changing area 09/27/2019
Zone 14 Front Meeting Room 09/27/2019
Zone 15 Rear Meeting Room 09/27/2019
Zone 16 Store Room 1 09/27/2019
Zone 17 Store Room 2 09/27/2019
Zone 18 Store Room 3 09/27/2019
Zone 19 Store Room 4 09/27/2019
Zone 20 Store Room 5 09/27/2019
Zone 21 Store Room 6 09/27/2019
Heat Detector
Zone 13 Shop Heat 09/27/2019
Zone 11 Restroom Heat 09/27/2019
Power Supplies
ADDRESS DESCRIPTION MANUFACTURER MODEL SERIAL INSTALL DATE
Battery - Sealed Lead Acid
Facp Back up Batt. (1) 12 volt 7 amp
09/27/2019
Page 6 of 6Page 6 of 6Battalion One Fire Protection