ATTACHMENT_07_-_140P8624Q0034_-_SEA_SCOUT_BASE_-_2023_INSPECTION_REPORT_0001.pdf

PDF 184 KB Posted

Attached to
ANNUAL INSPECTION, TESTING, MAINTENANCE AND ALARM
Solicitation number
140P8624Q0034
Issued by

About this file

This document is an Inspection and Testing Certificate for the Sea Scout Base located in San Francisco, California. The inspection was conducted by Battalion One Fire Protection on October 26, 2023 and covered the fire alarm control panel, initiating devices, and power supplies. All equipment passed the inspection, including the Bosch 5520 fire alarm control panel, 12 smoke detectors, 2 heat detectors, and a sealed lead acid backup battery. The inspection was performed in compliance with NFPA 72 standards and accepted by the National Park Service, which manages the property.

The related federal contract opportunity is for annual inspection, testing, maintenance, and alarm services for fire and intrusion alarm systems at facilities managed by the National Park Service Pacific West Region. The solicitation number is 140P8624Q0034, and the opportunity type is a solicitation. The contract is for services at the Sea Scout Base and other National Park Service properties in the Pacific West Region.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Inspection and Testing Certificate Presented To

National Park Service - NPS

For

Sea Scout Base

3500 Van Ness Ave

San Francisco, California 94109

United States

This site has been inspected and tested in compliance with applicable standards.

Completed Thursday, October 26, 2023

Test Session :26 Oct 2023 09:07

Test Plans : Fire Alarm Annual Inspection

ACCEPTED BY TESTED BY

National Park Service - NPS

2 Marina Blvd Building E SAN FRANCISCO, California 94123 United States

Julian Rodriguez

Battalion One Fire Protection

14755 Catalina Street San Leandro, CA 94577 United States

Battalion One Fire Protection

Inspection Summary

Building Information

PROPERTY Sea Scout Base CONTACT

ADDRESS 3500 Van Ness Ave PHONE

CITY/STATE/ZIP San Francisco, California 94109 MOBILE

COUNTRY United States EMAIL

Inspector Information

COMPANY Battalion One Fire Protection CONTACT Julian Rodriguez

ADDRESS

14755 Catalina Street San Leandro, CA 94577

LICENSE NUMBER

PHONE +1 510-736-7755

COUNTRY United States EMAIL jrodriguez@battaliononefire.com

Testing Summary

EQUIPMENT TYPE TOTAL TESTED PASSED FAILED

1 1(100%) 1(100%) 0(0%)

12 12(100%) 12(100%) 0(0%)

1 1(100%) 1(100%) 0(0%)

Certification The equipment specified herein was inspected and tested according to the NFPA 72 standard for fire alarm and signaling systems, with the inspection completed on Thursday, October 26, 2023

ACCEPTED BY 10/26/2023 TESTED BY 10/26/2023

Julian Rodriguez

Building Representative Technician

Fire Control Panel

Initiating Device

Power Supplies

Page 2 of 6Page 2 of 6Battalion One Fire Protection

System Details

Control Units

DESCRIPTION FACP Bosch 5520ADDRESS / SCAN ADDRESS

S/W VERSIONMANUFACTURER

LAST UPDATEMODEL

S/W LOCATIONSERIAL NUMBER

INSTALL DATE 09/26/2019

Secondary Power TYPE Battery - Sealed Lead Acid DESCRIPTION Facp Back up Batt. (1) 12 volt 7 amp

ADDRESS / SCAN ADDRESS NOMINAL VOLTAGE

LOAD VOLTAGE AMP HOURS

STANDBY HOURS ALARM MINUTES

BATTERY LOCATION CHARGER VOLTAGE

Page 3 of 6Page 3 of 6Battalion One Fire Protection

Testing Details

Fire Control Panel

Passed

EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME

Fire Alarm Control Panel FACP Bosch 5520 Manual 10/26/2023 9:12:19 AM

FACP Passed Visual Inspection Passed (Manual)

Functional Inspection Passed

Alarm Verification Timer (s) 30_seconds

Initiating Device

Passed

EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME

Smoke Detector Zone 12 Lockers / changing area Manual 10/26/2023 9:08:38 AM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Smoke Detector Zone 17 Store Room 2 Manual 10/26/2023 9:08:43 AM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Smoke Detector Zone 14 Front Meeting Room Manual 10/26/2023 9:08:47 AM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Smoke Detector Zone 16 Store Room 1 Manual 10/26/2023 9:12:10 AM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Smoke Detector Zone 18 Store Room 3 Manual 10/26/2023 9:12:14 AM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Smoke Detector Zone 19 Store Room 4 Manual 10/26/2023 9:12:50 AM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Smoke Detector Zone 20 Store Room 5 Manual 10/26/2023 9:13:29 AM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Smoke Detector Zone 21 Store Room 6 Manual 10/26/2023 9:14:13 AM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Smoke Detector Zone 15 Rear Meeting Room Manual 10/26/2023 9:17:07 AM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Heat Detector Zone 11 Restroom Heat Manual 10/26/2023 9:17:11 AM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Heat Detector Zone 13 Shop Heat Manual 10/26/2023 9:17:16 AM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Smoke Detector Zone 10 Front doorway entry Manual 10/26/2023 9:17:19 AM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Power Supplies

Passed

EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME

Page 4 of 6Page 4 of 6Battalion One Fire Protection

EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME

Battery - Sealed Lead Acid Facp Back up Batt. (1) 12 volt 7 amp Manual 10/26/2023 9:08:28 AM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Page 5 of 6Page 5 of 6Battalion One Fire Protection

Device/Equipment Details

Fire Control Panel

ADDRESS DESCRIPTION MANUFACTURER MODEL SERIAL INSTALL DATE

Fire Alarm Control Panel

FACP Bosch 5520 09/27/2019

Initiating Device

ADDRESS DESCRIPTION MANUFACTURER MODEL SERIAL INSTALL DATE

Smoke Detector

Zone 10 Front doorway entry 09/27/2019

Zone 12 Lockers / changing area 09/27/2019

Zone 14 Front Meeting Room 09/27/2019

Zone 15 Rear Meeting Room 09/27/2019

Zone 16 Store Room 1 09/27/2019

Zone 17 Store Room 2 09/27/2019

Zone 18 Store Room 3 09/27/2019

Zone 19 Store Room 4 09/27/2019

Zone 20 Store Room 5 09/27/2019

Zone 21 Store Room 6 09/27/2019

Heat Detector

Zone 13 Shop Heat 09/27/2019

Zone 11 Restroom Heat 09/27/2019

Power Supplies

ADDRESS DESCRIPTION MANUFACTURER MODEL SERIAL INSTALL DATE

Battery - Sealed Lead Acid

Facp Back up Batt. (1) 12 volt 7 amp

09/27/2019

Page 6 of 6Page 6 of 6Battalion One Fire Protection