This is a Statement of Work Supplement that establishes fire prevention and hot work safety requirements for the Shade Structure Demolition project at Cabrillo National Monument. The supplement clarifies mandatory safety protocols applicable to all demolition and construction activities involving hot work operations, including welding, torch cutting, grinding, soldering, and any activity producing sparks, flame, or heat capable of igniting combustible materials.

The contractor must maintain a minimum of one fully charged and operable portable fire extinguisher rated not less than 2A:20BC in the active work area during all hot work operations. A dedicated fire watch is required during all hot work activities and for a minimum of three hours following completion of each day's operations. The fire watch personnel must have no other assigned duties, be trained in portable fire extinguisher use, continuously monitor the work area and adjacent combustible exposures for signs of smoke, heat, or fire, and possess authority to stop work and initiate emergency response actions if unsafe conditions develop. The contractor must immediately notify the Contracting Officer Representative or designated Government representative of any fire, smoke event, or unsafe condition. All work must comply with applicable OSHA standards, NFPA 51B (Standard for Fire Prevention During Welding, Cutting, and Other Hot Work), and all applicable federal, state, and local fire safety requirements.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

“This document is a supplement to Attachment 2 SOW and is issued to clarify additional fire prevention and hot work safety requirements applicable to the Shade Structure Demolition project.”

Fire Prevention / Hot Work Requirements The contractor shall be responsible for implementing appropriate fire prevention measures during all demolition and construction activities involving hot work, including but not limited to welding, torch cutting, grinding, soldering, or any activity capable of producing sparks, flame, or heat sufficient to ignite combustible materials.

At a minimum, the contractor shall comply with the following requirements:

1. A minimum of one fully charged and operable portable fire extinguisher rated not less than 2A:20BC shall be immediately available within the active work area during all hot work operations.

2. The contractor shall maintain a dedicated fire watch during all hot work activities and for a minimum period of three (3) hours following completion of the hot work operation each day.

3. The fire watch shall:

· Have no other assigned duties during fire watch operations;

· Be trained in the use of portable fire extinguishers;

· Continuously monitor the work area and adjacent combustible exposures for signs of smoke, heat, or fire; and

· Have the authority to stop work and initiate emergency response actions if unsafe conditions develop.

4. The contractor shall immediately notify the Contracting Officer Representative (COR) or designated Government representative of any fire, smoke event, or unsafe condition.

5. All work shall be performed in accordance with applicable OSHA standards, NFPA 51B (Standard for Fire Prevention During Welding, Cutting, and Other Hot Work), and all applicable federal, state, and local fire safety requirements.