B08_Attachment_2_Drawings_Amendment_2_0002.pdf
PDF 4 MB Posted
- Attached to
- Rehabilitate Wolf Creek Water System, NPS-REDW
- Solicitation number
- 140P8424R0005
About this file
This document contains drawings and plans for the rehabilitation of the Wolf Creek Water System in Redwood National and State Parks, Del Norte County, California. The project involves replacing the existing 4-inch water main from the campground to Station 13+13, as well as modifying the existing water treatment plant under the base bid. Bid Option 1 includes replacing the remaining water distribution system from Station 13+13 through the rest of the Wolf Creek area, including new service connections.
Key details include:
- The project requires horizontal directional drilling (HDD) from Station 0+00 to 13+13
- Staging areas and potential drilling pit locations are identified
- Drawings provide details on the water main alignment, stream crossing, water treatment plant modifications, and water system details such as thrust blocks and valve boxes
- The solicitation number is 140P8424R0005, issued by the Department of the Interior National Park Service Pacific West Region
View the file
Other files
Show all 15
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SUBSHEET
SHEET
DRAWN BY:
PMIS NO.
D
ES
C R
IP
TI
O N
D
AT
E N
O
R
EV
IS
IO
N S
309710
NWA
G-001
D
EL
N O
R
TE
C O
U N
TY
C
AL
IF
O R
N
IA
W O
LF
C
R
EE
K W
AT
ER
S
YS
TE
M
R
EH
AB
IL
IT
AT
IO
N
TIC NO.
167-192197
TI
TL
E
SH
EE
T
SHEET INDEX
DESCRIPTIONSHEET
G-001 G-002
TITLE SHEET
GENERAL PROJECT INFORMATION
STATE PARKS
PARK HEADQUARTERS
TRAIL
UNPAVED ROAD
VISITOR CENTER
MAJOR RIVER OR CREEK
PAVED ROAD
PARK BOUNDARY
LEGEND
U.S DEPARTMENT OF THE INTERIOR
NATIONAL PARK SERVICE
PACIFIC WEST REGION
DEL NORTE COUNTY, CALIFORNIA
C-001 PROJECT OVERVIEW
C-002 WATER MAIN PLAN
C-003 STREAM CROSSING DETAILS
C-004 WATER PLANT PLAN
C-005 WATER SYSTEM DETAILS
C-006 DETAILS
C-007-010 BID OPTION 1 PLAN & DETAILS
/1
7/
A M
E N
D M
E N
T
HUMBOLDT COUNTY, CALIFORNIA
DRAWN BY:
PMIS NO.
D
ES
C R
IP
TI
O N
D
AT
E N
O
R
EV
IS
IO
N S
309710
NWA
G-002
D
EL
N O
R
TE
C O
U N
TY
C
AL
IF
O R
N
IA
W O
LF
C
R
EE
K W
AT
ER
S
YS
TE
M
R
EH
AB
IL
IT
AT
IO
N
TIC NO.
167-192197
G
EN
ER
AL
P R
O
JE
C T
IN
FO
R M
AT
IO
N
1. IN GENERAL, EXISTING STRUCTURES, EQUIPMENT, AND FACILITIES ARE SHOWN
AS LIGHT LINE WEIGHTS OR SCREENED BACKGROUND. NEW STRUCTURES,
EQUIPMENT, AND FACILITIES ARE SHOWN IN HEAVY LINE WEIGHTS. OTHER
DISCIPLINES MAY SCREEN NEW STRUCTURES TO SHOW THEIR INFORMATION.
2. ALL EXISTING TREES TO REMAIN UNLESS OTHERWISE SPECIFIED.
3. ALL DISTURBED ASPHALT, GRASS, DRAINAGE PATTERNS, ROADSIDE DITCHES,
TRAILS AND GRADE SHALL BE RESTORED TO ITS ORIGINAL CONDITION OR AS
CALLED FOR ON THE CONTRACT DOCUMENTS, WHICHEVER IS MORE STRINGENT.
4. SCHEDULE ALL EXISTING UTILITY LINE SHUTDOWNS WITH THE CONTRACTING
OFFICER.
5. ALL CONNECTIONS TO EXISTING MAINS SHALL BE MADE BY THE CONTRACTOR
ONLY AFTER THE PROPOSED CONNECTION PROCEDURE AND WORK SCHEDULE
HAS BEEN REVIEWED AND APPROVED BY THE CONTRACTING OFFICER. THE
CONTRACTOR SHALL SUBMIT A WRITTEN REQUEST TO THE CONTRACTING
OFFICER A MINIMUM OF FIVE (5) WORKING DAYS PRIOR TO SCHEDULING ANY
CONNECTIONS. THE REQUEST SHALL OUTLINE THE FOLLOWING:
A. POINTS OF CONNECTION, FITTINGS TO BE USED, AND METHOD OF FLUSHING
AND DISINFECTION,
B. ESTIMATED CONSTRUCTION TIME FOR THE CONNECTION, AND DISINFECTION.
AFTER RECEIPT OF THE WRITTEN REQUEST THE CONTRACTING OFFICER SHALL
REVIEW THE SUBMITTAL AND GIVE AN APPROVAL OR REJECTION OF THE
REQUEST WITHIN THREE (3) WORKING DAYS. IF THE REQUEST IS REJECTED, THE
CONTRACTOR SHALL RESUBMIT THE REQUEST, MAKING MODIFICATIONS IN A
MANNER ACCEPTABLE TO THE CONTRACTING OFFICER. ALL CONNECTIONS SHALL
ONLY BE MADE ON AGREED UPON DATE AND TIME. IF THE CONTRACTOR DOES
NOT INITIATE AND COMPLETE THE CONNECTION WORK IN THE AGREED UPON
MANNER, THE CONTRACTOR SHALL BE REQUIRED TO RESCHEDULE THE
CONNECTION BY FOLLOWING THE PROCEDURE OUTLINED ABOVE. MAINS SHALL
NOT BE PLACED IN SERVICE UNTIL CLEARANCE IS GRANTED BY THE
CONTRACTING OFFICER.
6. PIPE AND JOINT DEFLECTIONS PERMITTED WITHIN RANGE OF MANUFACTURER'S
ALLOWANCES.
7. ALL COSTS ASSOCIATED WITH REPAIR AND/OR REPLACEMENT OF EXISTING
UTILITIES, DUE TO CONTRACTOR'S ACTIVITIES, SHALL BE THE RESPONSIBILITY OF
THE CONTRACTOR.
8. ANY KNOWN SEWERS, WATER MAINS, CONDUITS, ELECTRIC CABLES, AND OTHER
UNDERGROUND/OVERHEAD ITEMS ARE SHOWN ON THE DRAWINGS ONLY TO THE
EXTENT SUCH INFORMATION HAS BEEN MADE AVAILABLE OR DISCOVERED BY
THE ENGINEER. IT IS EXPECTED THAT THERE MAY BE DISCREPANCIES AND
OMISSIONS IN THE LOCATION AND QUANTITIES OF EXISTING UTILITIES AND
STRUCTURES SHOWN. THIS INFORMATION IS SHOWN FOR THE CONVENIENCE OF
THE CONTRACTOR BUT IS NOT GUARANTEED TO BE EITHER CORRECT OR
COMPLETE AND ALL RESPONSIBILITY FOR THE ACCURACY AND COMPLETENESS
THEREOF IS EXPRESSLY DISCLAIMED. THE CONTRACTOR SHALL MAKE SUCH
INVESTIGATION AS NECESSARY TO VERIFY ITS CORRECTNESS AND
COMPLETENESS.
9. FIELD LOCATE ALL EXISTING UTILITIES, BURIED PIPING, INCLUDING WATER
SERVICE CONNECTIONS, AND ALL OTHER SURFACE AND SUB-SURFACE
FEATURES PRIOR TO CONSTRUCTION. ANY FEATURES DAMAGED BY
CONTRACTOR'S ACTIVITIES SHALL BE REPLACED TO PRE-CONSTRUCTION
CONDITION AT NO ADDITIONAL EXPENSE TO THE GOVERNMENT. ANY FIELD
LOCATED EXISTING CONDITIONS IMPACTING NEW WORK SHALL BE IMMEDIATELY
BROUGHT TO THE CONTRACTING OFFICER'S ATTENTION.
10. ALL EXISTING VALVES AND EQUIPMENT SHALL ONLY BE OPERATED BY THE THE
NATIONAL PARK SERVICE.
LEGEND AND ABBREVIATIONS
FIRE HYDRANT
EXISTING SANITARY SEWER (GRAVITY)
ABANDONED LINE (VARIOUS TYPES)
EXISTING WATER
PROPOSED WATER (SIZE)
IRRIGATION LINES
UNDERGROUND ELECTRIC
EXISTING SANITARY FARCE MAIN
OVERHEAD ELECTRIC
FENCE
POWER POLE
SANITARY MANHOLE
DRAINAGE INTAKES
LIGHT POLE
EXISTING GAS
STORM SEWER
NEW WATER MAIN
1. CONTRACTOR SHALL PROVIDE A FRAC-OUT CONTINGENCY PLAN, INCLUDING MINIMUM
REQUIREMENTS PER PROJECT SPECIFICATIONS, PRIOR TO CONSTRUCTION.
2. CONTRACTOR SHALL PROVIDE MONITORING FULL TIME DURING HORIZONTAL DIRECTION
DRILLING (HDD) OPERATIONS.
1. THE BASE BID FOR THIS PROJECT INCLUDES REPLACING THE WATER MAIN FROM
CAMPGROUND TO STA. 13+13, AND MODIFYING THE EXISTING WATER PLANT.
2. BID OPTION 1 INCLUDES REPLACING THE REMAINING WATER DISTRIBUTION SYSTEM
FROM STA. 13+13 THROUGH THE REST OF THE WOLF CREEK AREA, INCLUDING NEW
SERVICE CONNECTIONS.
3. THE EXISTING SYSTEM FEEDS THE DISTRIBUTION SYSTEM BY SENDING FLOW THROUGH
THE BOOSTER STATION. FLOW THEN FLOWS BACKWARDS TO SUPPLY THE SYSTEM.
4. THE BID OPTION WOULD ELIMINATE THE REVERSE FLOW SCENARIO AND FEED THE
WOLF CREEK BUILDINGS DIRECTLY, THEREBY ELIMINATING THE UNNECESSARY LENGTH
OF PIPE.
95 10
110105
0+00
1+00
2+00
3+00
4+00
5+00
6+00
7+00
8+00
9+00
10+00
+0
+0
+0
+1
SUBSHEET
SHEET
DRAWN BY:
PMIS NO.
D
ES
C R
IP
TI
O N
D
AT
E N
O
R
EV
IS
IO
N S
309710
NWA
C-001
D
EL
N O
R
TE
C O
U N
TY
C
AL
IF
O R
N
IA
W O
LF
C
R
EE
K W
AT
ER
S
YS
TE
M
R
EH
AB
IL
IT
AT
IO
N
TIC NO.
167-192197
PR
O
JE
C
T O
VE
R
VI
EW
2525 0 50
HORIZ.
BASE BID
CONSTRUCT NEW 4" WATER MAIN
SEE SHEET C-002
MODIFY EXISTING WATER (BOOSTER) PLANT.
BASE BID SEE SHEET C-004.
BID OPTION 1 SEE SHEET C-009.
PRAIRIE CREEK
NPS FIRE CACHE BUILDING
WOLF CREEK EDUCATION CENTER
ACCESS ROAD
NPS STAFF HOUSING
ACCESS. (CAMPGROUND LOOP ROAD)
BEGIN BID OPTION 1
REPLACE WATER MAIN &
SERVICE CONNECTIONS
(WEST OF THIS POINT)
BID OPTION 1
SEE SHEETS C-007
THROUGH C-010
105110
0+
1+
2+
3+
4+
5+
6+
7+
8+
9+
+0
11+00
12+00
13+00
13+13
SUBSHEET
SHEET
DRAWN BY:
PMIS NO.
D
ES
C R
IP
TI
O N
D
AT
E N
O
R
EV
IS
IO
N S
309710
NWA
C-002
D
EL
N O
R
TE
C O
U N
TY
C
AL
IF
O R
N
IA
W O
LF
C
R
EE
K W
AT
ER
S
YS
TE
M
R
EH
AB
IL
IT
AT
IO
N
TIC NO.
167-192197
4040 0 80
HORIZ.
LOCATE AND CONNECT TO EXISTING
4" WATER MAIN NEAR END OF
CAMPGROUND LOOP
REMOVE EXISTING 1" OVERHEAD
WATER MAIN CROSSING. CAP ENDS
BOTH SIDES
SEE SHEET C-003
PRAIRIE CREEK
WATER MAIN ALIGNMENT GENERALLY
FOLLOWS EXISTING TRAIL
CONNECT TO EXISTING 4" WATER MAIN
EXISTING 4" WATER MAIN
TO BE ABANDONED IN PLACE.
W
AT
ER
M
AI
N
P
LA
N
LOCATE BEND ALONG
EXISTING TRAIL
POTENTIAL DRILLING PIT
(4'X4'X4')
NOTES
1. HDD IS REQUIRED FROM STA. 0+00 TO STA. 13+13
2. VEGETATION MAY BE TRIMMED ALONG ALIGNMENT AND IN STAGING AREAS
TO IMPROVE ACCESS AND AID MONITORING. HOWEVER, ALL TREES SHALL
BE PROTECTED.
3. SEE G-002 FOR FRAC-OUT CONTINGENCY PLAN NOTES.
4. CONTRACTOR PROVIDED FIELD SOIL SAMPLING INVESTIGATION CAN
INCLUDE HAND OR HANDTOOL AUGER SAMPLE COLLECTION AT STAGING
LOCATIONS INDICATED.
WATER MAIN ALIGNMENT GENERALLY
FOLLOWS EXISTING TRAIL
POTENTIAL DRILLING PIT
(4'X4'X4')
POTENTIAL DRILLING PIT
(4'X4'X4')
POTENTIAL STAGING AREA
25'X25'
POTENTIAL STAGING AREA
(25'X50')
REFERENCE FRAC-OUT CONTINGENCY
PLAN FOR ADDITIONAL MEASURES
REQUIRED AT WATER BODIES (PRAIRIE CREEK)
POTENTIAL STAGING AREA
(40'X40')
POTENTIAL STAGING AREA
(40'X40')
POTENTIAL STAGING AREA
(40'X40')
/1
7/
A M
E N
D M
E N
T
DRAWN BY:
PMIS NO.
D
ES
C R
IP
TI
O N
D
AT
E N
O
R
EV
IS
IO
N S
309710
NWA
C-003
D
EL
N O
R
TE
C O
U N
TY
C
AL
IF
O R
N
IA
W O
LF
C
R
EE
K W
AT
ER
S
YS
TE
M
R
EH
AB
IL
IT
AT
IO
N
TIC NO.
167-192197
PROPOSED 4" WATER MAIN
GENERAL WATER MAIN PROFILE
NTS
PROPOSED 4" GATE VALVE
(BOTH SIDES) - REF SHEET C-002
FOR LOCATIONS
' M
IN
TOP OF BANK
4' M
IN
EXISTING GRADE
MARK VALVE LOCATION
W/ PERMANENT MARKER
EXISTING GRADE
4" WATER MAIN BELIEVED
TO BE PVC
4" WATER MAIN BELIEVED
TO BE PVC
TRANSITIONS TO 1"
HDPE AT CROSSING
TRANSITIONS BACK TO 4"
DOWNSTREAM OF CROSSING
1" HDPE AT ATTACHED TO CABLE
WOODEN POST
EXISTING STREAM CROSSING
NTS
UPSTREAM WOOD POST
1" HDPE PIPE ATTACHED TO CABLE
ST
R
EA
M
C R
O
SS
IN
G
D
ET
AI
LS
NOTES
1. CONTRACTOR SHALL PERFORM DEMOLITION WORK WITH MEANS AND METHODS THAT
PREVENT MATERIAL AND CREW FROM ENTERING THE STREAM.
2. FULLY DRAIN WATER LINE PRIOR TO DEMOLITION.
3. CUT EXISTING 4" LINE AT GROUND TRANSITION TO RISER.
4. CAP AND ABANDON IN PLACE EXISTING IN-GROUND LINE.
5. REMOVE OVERHEAD 1" HDPE LINE AND CABLE.
6. CUT OFF WOOD POSTS AT GROUND LEVEL.
* CONSTRUCT 12' DEEP UNDER STREAM TO
PREVENT FRAC-OUT INTO WATER BODY. ALL
OTHER SEGMENTS ONLY NEED TO BE 4' DEEP.
/1
7/
A M
E N
D M
E N
DRAWN BY:
PMIS NO.
D
ES
C R
IP
TI
O N
D
AT
E N
O
R
EV
IS
IO
N S
309710
NWA
C-004
D
EL
N O
R
TE
C O
U N
TY
C
AL
IF
O R
N
IA
W O
LF
C
R
EE
K W
AT
ER
S
YS
TE
M
R
EH
AB
IL
IT
AT
IO
N
TIC NO.
167-192197
TREATMENT PLAN PLAN
NTS
F&I 6" TEE
F&I HYDRANT ASSEMBLY
(PAINT PURPLE)
DISCONNECT OUTLET AND
CAP TEE END
F&I 4" TEE
F&I STATE APPROVED (HIGH HAZARD FIRE CONNECTION)
REDUCED PRESSURE BACKFLOW
ASSEMBLY. BASIS OF DESIGN AMES LMF500 (MAXIUM 500)
REMOVE 2" PIPE AND ACCESSORIES BETWEEN
GATE VALVES AND RECONNECT WITH 4" LINE.
F&I 4"x6" INCREASER
CONNECT TO EXISTING PIPE
F&I 6" 90° BEND
F&I 4" GATE VALVE
PATCH HOLE IN BUILDINGREMOVE GATE VALVE AFTER TEST
NOTES
1. WORK TO THE PLANT WILL ONLY BE ALLOWED AFTER THE WATER MAIN CONSTRUCTION.
2. PRIOR TO WORKING ON THE PLANT, THE CONTRACTOR SHALL VERIFY STATIC
PRESSURE , AND CONDUCT A FLOW TEST. THE PURPOSE OF THE FLOW TEST WILL BE
TO VERIFY THAT THE MODIFIED WATER MAIN CAN DELIVER THE AMOUNT OF FLOW
REQUIRED BASED ON A 4-INCH LINE SIZE. THE FLOW TEST WILL CONFIRM THAT THERE
ARE NO OTHER RESTRICTIONS ALONG THE LINE THAT THE NPS IS NOT AWARE OF.
3. IF THE FLOW TEST FAILS, NOTIFY THE NPS IMMEDIATELY.
4. THERE IS AN EXISTING HYDRANT ASSEMBLY NEAR THE TREATMENT BUILDING THAT
WAS DAMAGED AND IS BADLY CORRODED. REPLACE THE FULL ASSEMBLY INCLUDING
THE TEE FITTING. FULLY EXCAVATE AND REMOVE SOIL WITHIN 3' OF ALL ASSEMBLY
COMPONENTS. BACKFILL WITH COMPACTED APPROVED SOIL BROUGHT IN FROM
OUTSIDE SOURCE. THE SOIL THAT WAS USED TO BACKFILL THE EXISTING ASSEMBLY
WAS FOUND TO BE BEACH SAND WHICH LED TO THE FAILURE OF THE FITTINGS DUE TO
CORROSION.
CONDUCT FLOW TEST BY DISSEMBLING
PIPE DOWNSTREAM OF 4" GATE VALVE.
REMOVE GATE VALVE AFTER TEST
W
AT
ER
P
LA
N
T
PL
AN
REPLACE HYDRANT ASSEMBLY.
SEE NOTE 4
F&I 4" GATE VALVE
F&I 4" DI PIPE
F&I 6" DI PIP
BID OPTION VARIATION
1. IF BID OPTION 1 IS EXECUTED THE CONFIGURATION
NEAR THE EXISTING PLANT WILL VARY. IF BID
OPTION 1 IS AWARDED, CONSTRUCT AS SHOWN ON
SHEET C-009
DRAWN BY:
PMIS NO.
D
ES
C R
IP
TI
O N
D
AT
E N
O
R
EV
IS
IO
N S
309710
NWA
C-005
D
EL
N O
R
TE
C O
U N
TY
C
AL
IF
O R
N
IA
W O
LF
C
R
EE
K W
AT
ER
S
YS
TE
M
R
EH
AB
IL
IT
AT
IO
N
TIC NO.
167-192197
TEST PRESSURES AND SOIL BEARING PRESSURES, USE THE FOLLOWING EQUATION:
PRESSURE OF 2,000 psf AND A SAFETY FACTOR OF 1.5, TO COMPUTE BEARING AREAS FOR DIFFERENT
1. BEARING AREAS (TABLE 1) BASED ON TEST PRESSURE OF 150 psi, AN ALLOWABLE SOIL BEARING
BEARING AREA = (TEST PRESSURE / 150 psi) x (2,000 / SOIL BEARING PRESSURE psf) x (TABLE 1 VALUE)
3. BEARING AREA OF THRUST BLOCK SHALL NOT BE LESS THAN 1.0 SQUARE FOOT.
(HORIZONTAL BENDS & VERTICAL UPWARD BENDS)
TABLE 1 - BEARING AREA OF THRUST BLOCKS IN SQUARE FEET
HORIZONTAL BENDS AND VERTICAL UPWARD BENDS:
TEE PLUGGED ON RUN
4. IF THE DEPTH REQUIREMENT (SEE TYPICAL CROSS SECTION) CAN NOT BE ACHIEVED,
UNDISTURBEDBEDDING
1/2 TO 1 TIMES ITS WIDTH.
BLOCK HEIGHT (h) SHALL BE
LESS THAN THE PIPE DIAMETER
OF THE BLOCK (H), BUT NOT
THE TOTAL DEPTH TO THE BOTTOM
EQUAL TO OR LESS THAN 1/2
BLOCK HEIGHT (h) SHALL BE
TYPICAL CROSS SECTION
MATERIAL
DEPTH REQUIREMENT:
A
BEND
A1
A1
PLUGGED CROSS
SOIL
1A
1A
PLUGGED CROSS
A1
3. CONCRETE THRUST BLOCKING TO BE POURED AGAINST UNDISTURBED EARTH OR STRUCTURAL BACKFILL.
UNLESS OTHERWISE NOTED.
1. ALL MECHANICAL FITTINGS SHALL BE PROVIDED WITH THRUST BLOCKS AT ALL DIRECTION CHANGES
4. KEEP CONCRETE CLEAR OF JOINT, BOLTS, NUTS, CLAMPS, AND OTHER ACCESSORIES.
6. A BOND BREAKER SHALL BE PLACED BETWEEN THE PIPE AND THRUST BLOCK.
5. THRUST BLOCKS SHALL NOT BE LOCATED OR SIZED TO ENCASE ADJACENT PIPES OR FITTINGS.
2/
O .D
PI
PE
BEARING
SURFACE
BREAKER
BOND
45° (TYP)
GENERAL:
10 8.8 12.5
THE ENGINEER SHALL BE NOTIFIED.
h
H
50.9 35.3
72.0 50.0
17.3 22.6 28.6
12.7 24.5 32.0 40.5
18.0
FITTING
SIZE
(IN)
3.2 5.7
1.4
(SF)
4.5 8.0
2.0
(SF)
PLUG OR
TEE, WYE
CAP
A1
BEND
O
VERTICAL DOWNWARD BEND
IN CONCRETE (SEE TABLE
WYE
A1
1/4" PLYWOOD OVER
PLUG OR CAP
TEE
A1
FACE OF BOLTS
V1
USED FOR 11 1/4 BENDS.
A1
2 FOR SIZES)
FITTING AND EMBEDDED
COATED RODS OVER
VALVE
FITTING AND EMBEDDED
COATED RODS OVER
IN CONCRETE
(SEE NOTE 3)
1. VERTICAL BENDS THAT REQUIRE A THRUST BLOCK VOLUME EXCEEDING 5 CUBIC YARDS REQUIRE
4050 LBS/CUBIC YARD, AND A SAFETY FACTOR OF 1.5. TO COMPUTE VOLUMES FOR DIFFERENT
THRUSTS ARE BASED ON TEST PRESSURE OF 150 PSI, THE WEIGHT OF CONCRETE =
SPECIAL BLOCKING DETAILS. SEE DRAWINGS FOR VOLUMES SHOWN TO LEFT OF HEAVY, BOLD
2. THRUST BLOCK VOLUMES (TABLE 2) FOR VERTICAL DOWNWARD BENDS HAVING UPWARD RESULTANT
3. VOLUME OF THRUST BLOCK IN CUBIC YARDS FOR VALVES SHALL BE THE SAME VOLUME
(VERTICAL DOWNWARD BENDS)
TABLE 2 - VOLUME OF THRUST BLOCK IN CUBIC YARDS
VERTICAL DOWNWARD BENDS:
TEST PRESSURES AND CONCRETE WEIGHTS, USE THE FOLLOWING EQUATION:
1.73.46.8
39.0 27.1
19.9 13.8
13.3 17.3 21.9
9.7 6.8 8.8
11.2
5.0
10.0 6.9
3.4 4.4 5.6
2.5
LINE IN TABLE 2.
17.8 12.3
7.9 10.0
4.4 6.1
O
2.4 4.3
1.1
(SF)
1.2 2.2
1.0
(SF)
BEND
O
BEND
22 1/2
A2
1.0 1.1
(SF)
1.0
BEND
11 1/4 O
(CY)(IN)
3.1 2.0
0.5 1.1
SIZE
FITTING
BEND
45O
#6
9.6 6.7
4.9 3.4
5.4 4.3 3.3 2.4
2.8 2.2 1.7 1.2
#8 #8
3.0 3.0
#8 #8
#6 #8
3.0 3.0 3.0 2.5
(CY) (CY)
1.7 1.1
0.3 0.6
0.9 0.5
0.1 0.3
22 1/2
BEND
O V1
11 1/4
BEND
O
(FT)
#6 #6
#6
2.5 2.5
2.5 2.5
EMBEDMENT
SIZE
ROD
2. UNLESS OTHERWISE NOTED ON THE GENERAL DRAWINGS IN THE GENERAL NOTES OR SPECIFICATIONS, USE SOIL BEARING PRESSURE = 2000 psf FOR THIS PROJECT.
GALVANIZED OR EPOXY GALVANIZED OR EPOXY
VOLUME = (TEST PRESSURE / 150) x (4,050 / CONCRETE WEIGHT) x (TABLE 2 VALUE)
ALL PIPE JOINTS SHALL BE MECHANICALLY RESTRAINED FOR A MINIMUM OF 40 FEET IN ALL DIRECTIONS
2. FUSED HDPE PIPE & FITTINGS DO NOT REQUIRE THRUST RESTRAINTS.
FROM MECHANICAL FITTINGS.
WATER
VALVE BOX PAD
VALVE BOX COVER
ETCH FLOW DIRECTIONAL
ARROWS, PIPE DIAMETER AND
PIPE MATERIAL INTO
CONCRETE PRIOR TO CURING
AS DIRECTED BY THE
CONTRACTING OFFICER.
2'-0" SQ.x6" THICK CAST
IN PLACE CONC. PAD W/
#4 BARS E.W., SET
FLUSH IN PAVED AREAS
A
1/4"
1/4"
SECTION A
VALVE BOX PAD
VALVE BOX
VALVE BOX TOP
SECTION W/ COVER
CENTER SECTION
(LENGTH AS REQ'D)
GATE VALVE
CONCRETE
VALVE SUPPORT
ADJUSTABLE
VALVE BOX
FINISH GRADE
SET 3" ABOVE GRADE IN YARD
AREAS
VALVE BOX PAD
12" MAX
PROVIDE VALVE STEM EXTENSION
(SEE DETAIL BELOW)
VALVE BOX WITH
WIDE OVAL BASE
GATE VALVE
INSTALLATION
CONC VALVE SUPPORT,
SEE
1/8" FLAT PL CENTERING
GUIDE (SEE SECTION A)
3/4" (TYP)
NOTE:
1. PROVIDE PROTECTIVE COATING TO
EXTERIOR SURFACES OF VALVE BODY
VALVE BOX, EXTENSION STEM AN
APPURTENANCES.
ADAPTER TO FIT AWWA
SQUARE NUT
1/8"
1-1/4" DIA STEEL
EXTENSION MACHINE TO
MATCH NUT
2" AWWA SQUARE OPERATING
NUT
BUTTERFLY VALVE OR PLUG
VALVE FOR DIRECT BURIAL
REDWOOD BLOCKS 2-2"x2"x12"
LONG
CRUSHED ROCK
ADJUSTABLE VALVE BOX
FINISH GRADE
SLOPE CONC 2" AND PROVIDE
3/4" CHAMFER ALL AROUND. 2'-0"
SQ.x6" THICK CONC. PAD W/ #4
BARS E.W.
A
NOTE:
CONCRETE PAD SHALL BE
INSTALLED IN UNPAVED
AREAS. PAVED AREAS DO NOT
REQUIRE A CONCRETE PAD.
THRUST RESTRAINTS
GATE VALVE
NTSC-005
C-005 NTS
C-005
VA
R
IE
S
W
AT
ER
S
YS
TE
M D
ET
AI
LS
DRAWN BY:
PMIS NO.
D
ES
C R
IP
TI
O N
D
AT
E N
O
R
EV
IS
IO
N S
309710
NWA
C-006
D
EL
N O
R
TE
C O
U N
TY
C
AL
IF
O R
N
IA
W O
LF
C
R
EE
K W
AT
ER
S
YS
TE
M
R
EH
AB
IL
IT
AT
IO
N
TIC NO.
167-192197
6" MIN.
TRACER WIRE
5' MAX 5' MAX
2 TRACE WIRE BOX
5' MAX
PIPE
1 TIE IN AT FITTING
TW
2TW
TRACER WIRES SHALL HAVE
A MINIMUM 24" OF SLACK
LOOSELY COILED IN THE
BOX
TEST BOX
VALVE BOX PAD, SEE DET.
2/C11
CONCRETE
ENCASEMENT (TYP)
VALVE BOX TOP
2" DUCT TAPE @ 6' MAX.
MINIMUM 3 PER LENGTH OF
PIPE
TRACER WIRE 14 GAGE SOLID
COPPER WIRE
OUT OF ASPHALT
BACKFILL
COMPACTED
MIN. WIDTH
W -3
6" M
IN
TRENCH STABILIZATION
WHERE REQD.
UNDISTURBED
EARTH (TYP)
NOTE:
8" TO 10" DEEP
DETECTABLE UTILITY
MARKING TAPE
VA
R
IE
S
BEDDING MATERIAL
1'-0"
6" MIN.
DIA.
EXISTING ASPHALT
WITH TACK COAT
UNIFORM SAW CUT LINE
EXISTING AGGREGATE BASE
NEW AGGREGATE BASE
IN ASPHALT
1'-0"
MIN.
SURFACE
1'-0"+PIPE O.D.
1. TRENCH SHALL CONFORM TO OSHA STANDARDS.
TRACER WIRE
4" ASPHALT PAVEMENT
6" AGGREGATE BASE COURSE
6" COMPACTED SUBGRADE
GRAVEL SURFACE
6" COMPACTED AGGREGATE
BASE COURSE
6" COMPACTED SUBGRADE
ASPHALT PAVING (SEE NOTE 2)
REMOVE PAVING AND
REPLACE SURFACE
COURSE (NOTE 3)
2. TRACER WIRE DETAIL 3
C-006
S-
" M
IN
COLOR PER APWA
COLOR & LABEL PER
PER APWA
5'-0"
TYP
CROSSED
UTILITY
VERTICAL THRUST
BLOCKS,
SEE DETAIL (TYP)
2 - 45° MJ BENDS
W/ RESTRAINED
JOINT GLANDS
SUITABLE FOR
PVC PIPE (TYP
BOTH SIDES)
THRUST BLOCK SEE
HORIZONTAL THRUST
BLOCK DETAIL (TYP)
WATER LINE
C-005
M
IN
6"
6"
NOTE 3
NOTE 2
TRACER WIRE
UTILITY CROSSING
TYPICAL PIPE TRENCH
PAVEMENT & GRAVEL SURFACING
NTSC-006
NTSC-006
NTSC-006
NTSC-006
D
ET
AI
LS
DRAWN BY:
PMIS NO.
D
ES
C R
IP
TI
O N
D
AT
E N
O
R
EV
IS
IO
N S
309710
NWA
C-007
D
EL
N O
R
TE
C O
U N
TY
C
AL
IF
O R
N
IA
W O
LF
C
R
EE
K W
AT
ER
S
YS
TE
M
R
EH
AB
IL
IT
AT
IO
N
TIC NO.
167-192197
BI
D
O
PT
IO
N
2525 0 50
HORIZ.
CONSTRUCT NEW 4" HDPE WATER
MAIN
CONNECT TO EXISTING 6" FIRE
SERVICE LATERAL. USE 4" TEE
AND 4"X6" INCREASER
CONNECT TO BUILDING
SEE SHEET C-009
NEW 4" TEE AND GATE VALE
AT SUPPLY SIDE OF TEE
NOTES
1. WATER MAIN CONSTRUCTED UNDER THE BID OPTION MAY BE CONSTRUCTED USING A
VARIETY OF TECHNIQUES, INCLUDING TRENCHED AND TRENCHLESS.
2. TRENCHLESS TECHNIQUES MAY INCLUDE HDD, OR PIPE BURSTING.
3. IT MAY BE FEASIBLE TO UTILIZE THE EXISTING 6" WATER MAIN BY SLIP LINING WITH 4"
HDPE PIPE. SLIGHT ADJUSTMENTS TO THE PLAN WILL BE REQUIRED FROM WHAT IS
SHOWN.
NEW 4"X6" INCREASER
CONNECT (E) 6" SUPPLY TO
(N) 4" HDPE WATER MAIN AT TEE
(E) SERVICE TO REMAIN AS-IS
NOT IN PROJECT SCOPE
TRENCH & EXCAVATION EXCESS SPOILS
CAN BE PILED IN DESIGNATED SPACE
FINAL SPACE LOCATION TO BE
COORDINATED W/ NPS
PRIOR TO CONSTRUCTION
/1
7/
A M
E N
D M
E N
+0
+1
SUBSHEET
SHEET
DRAWN BY:
PMIS NO.
D
ES
C R
IP
TI
O N
D
AT
E N
O
R
EV
IS
IO
N S
309710
NWA
C-008
D
EL
N O
R
TE
C O
U N
TY
C
AL
IF
O R
N
IA
W O
LF
C
R
EE
K W
AT
ER
S
YS
TE
M
R
EH
AB
IL
IT
AT
IO
N
TIC NO.
167-192197
BI
D
O
PT
IO
N
2525 0 50
HORIZ.
LOCATE AND CONNECT NEW 4"
SUPPLY TO EXISTING HYDRANT
BEGIN BID OPTION AT ENDING OF BASE BID
WATER MAIN. RATHER THAN CONNECT TO EXISTING
CONSTRUCT NEW 4" HDPE WATER MAIN.
LOCATE & CONNECT TO EXISTING
LOCATE & CONNECT TO EXISTINGEXISTING SERVICES
TO BE ABANDONED IN PLACE
LOCATE AND
CONNECT NEW 4"
SUPPLY TO
EXISTING HYDRANT
/1
7/
A M
E N
D M
E N
DRAWN BY:
PMIS NO.
D
ES
C R
IP
TI
O N
D
AT
E N
O
R
EV
IS
IO
N S
309710
NWA
C-009
D
EL
N O
R
TE
C O
U N
TY
C
AL
IF
O R
N
IA
W O
LF
C
R
EE
K W
AT
ER
S
YS
TE
M
R
EH
AB
IL
IT
AT
IO
N
TIC NO.
167-192197
TREATMENT PLAN PLAN
NTS
F&I 6" TEE
F&I HYDRANT ASSEMBLY
(PAINT PURPLE)
DISCONNECT OUTLET AND
CAP TEE END
F&I 4" TEE
F&I STATE APPROVED (HIGH HAZARD FIRE CONNECTION)
REDUCED PRESSURE BACKFLOW
ASSEMBLY. BASIS OF DESIGN AMES LMF500 (MAXIUM 500)
REMOVE 2" PIPE AND ACCESSORIES BETWEEN
GATE VALVES AND RECONNECT WITH 4" LINE.
PATCH HOLE IN BUILDINGREMOVE GATE VALVE AFTER TEST
NOTES
1. WORK TO THE PLANT WILL ONLY BE ALLOWED AFTER THE WATER MAIN CONSTRUCTION.
2. PRIOR TO WORKING ON THE PLANT, THE CONTRACTOR SHALL VERIFY STATIC
PRESSURE , AND CONDUCT A FLOW TEST. THE PURPOSE OF THE FLOW TEST WILL BE
TO VERIFY THAT THE MODIFIED WATER MAIN CAN DELIVER THE AMOUNT OF FLOW
REQUIRED BASED ON A 4-INCH LINE SIZE. THE FLOW TEST WILL CONFIRM THAT THERE
ARE NO OTHER RESTRICTIONS ALONG THE LINE THAT THE NPS IS NOT AWARE OF.
3. IF THE FLOW TEST FAILS, NOTIFY THE NPS IMMEDIATELY.
4. THERE IS AN EXISTING HYDRANT ASSEMBLY NEAR THE TREATMENT BUILDING THAT
WAS DAMAGED AND IS BADLY CORRODED. REPLACE THE FULL ASSEMBLY INCLUDING
THE TEE FITTING. FULLY EXCAVATE AND REMOVE SOIL WITHIN 3' OF ALL ASSEMBLY
COMPONENTS. BACKFILL WITH COMPACTED APPROVED SOIL BROUGHT IN FROM
OUTSIDE SOURCE. THE SOIL THAT WAS USED TO BACKFILL THE EXISTING ASSEMBLY
WAS FOUND TO BE BEACH SAND WHICH LED TO THE FAILURE OF THE FITTINGS DUE TO
CORROSION. IF BID OPTION 1 IS EXECUTED, THE FIRE ASSEMBLY WILL CONNECT
DIRECTLY TO THE NEW 4" MAIN.
CONDUCT FLOW TEST BY DISSEMBLING
PIPE DOWNSTREAM OF 4" GATE VALVE.
REMOVE GATE VALVE AFTER TEST
BI
D
O
PT
IO
N
REPLACE HYDRANT ASSEMBLY.
SEE NOTE 4
F&I 4" GATE VALVE
DRAWN BY:
PMIS NO.
D
ES
C R
IP
TI
O N
D
AT
E N
O
R
EV
IS
IO
N S
309710
NWA
C-010
D
EL
N O
R
TE
C O
U N
TY
C
AL
IF
O R
N
IA
W O
LF
C
R
EE
K W
AT
ER
S
YS
TE
M
R
EH
AB
IL
IT
AT
IO
N
TIC NO.
167-192197
BI
D
O
PT
IO
N
| REDW 309710 DESIGN_BID OPTION-G-001 |
| Sheets and Views |
| REDW 309710 DESIGN_BID OPTION-G-001 |
| REDW 309710 DESIGN_BID OPTION-G-002 |
| Sheets and Views |
| REDW 309710 DESIGN_BID OPTION-G-002 |
| REDW 309710 DESIGN_BID OPTION-C-001 |
| Sheets and Views |
| REDW 309710 DESIGN_BID OPTION-C-001 |
| REDW 309710 DESIGN_BID OPTION-C-002 |
| Sheets and Views |
| REDW 309710 DESIGN_BID OPTION-C-002 |
| REDW 309710 DESIGN_BID OPTION-C-003 |
| Sheets and Views |
| REDW 309710 DESIGN_BID OPTION-C-003 |
| REDW 309710 DESIGN_BID OPTION-C-004 |
| Sheets and Views |
| REDW 309710 DESIGN_BID OPTION-C-004 |
| REDW 309710 DESIGN_BID OPTION-C-005 |
| Sheets and Views |
| REDW 309710 DESIGN_BID OPTION-C-005 |
| REDW 309710 DESIGN_BID OPTION-C-006 |
| Sheets and Views |
| REDW 309710 DESIGN_BID OPTION-C-006 |
| REDW 309710 DESIGN_BID OPTION-C-007 |
| Sheets and Views |
| REDW 309710 DESIGN_BID OPTION-C-007 |
| REDW 309710 DESIGN_BID OPTION-C-008 |
| Sheets and Views |
| C-008 |
| REDW 309710 DESIGN_BID OPTION-C-009 |
| Sheets and Views |
| REDW 309710 DESIGN_BID OPTION-C-009 |
| REDW 309710 DESIGN_BID OPTION-C-010 |
| Sheets and Views |
| REDW 309710 DESIGN_BID OPTION-C-010 |
File details come from the government source that posted it. Updated .