Att 09 - Site Visit Q and A_0002.pdf

PDF 68 KB Posted

Attached to
Underground Propane Piping and Tank Installation Federal contract opportunity
Solicitation number
140P8420R0007
Issued by
Department of the Interior National Park Service Pacific West Region

About this file

This document includes a solicitation for underground propane piping and tank installation at Lassen Volcanic National Park in California. The National Park Service requires the removal of existing above-ground 500-gallon propane tanks serving park buildings and installation of two new underground 6500-gallon propane storage tanks at a central tank farm. The contractor shall distribute propane gas from the tank farm to all park buildings via an underground main piping system. Additional requirements include installation of a direct-fired vaporizer and truck-fill station. The contractor must provide all labor, equipment, testing and supplies for the installation and related services outlined in project specifications. The acquisition is set aside for total HUBZone small businesses. The estimated value is between $500,000 to $1,000,000.

View the file

Other files for this federal contract opportunity

Other files attached to Underground Propane Piping and Tank Installation, newest first.
File Type Posted
Sol_140P8420R0007_Amd_0004.pdf PDF
Sol_140P8420R0007_Amd_0003.pdf PDF
Sol_140P8420R0007_Amd_0002.pdf PDF
Sol_140P8420R0007_Amd_0001.pdf PDF
Att 03- Drawings.pdf PDF
Att 01- Bid Schedule.pdf PDF
Sol_140P8420R0007.pdf PDF
Att 06- Key Personnel Form.pdf PDF
Att 07- PP Questionnaire.pdf PDF
Att 04- Construction Wage Rates.pdf PDF
Att 08- Standard Form-24 Bid Bond.pdf PDF
Att 02- Specifications.pdf PDF
Att 05- Technical Information Form.pdf PDF
Show all 13

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Attachment 09 Solicitation: 140P8420R0007

Site Visit Attendees and Questions

Attendees:

White Bear Construction

Site Work Solutions

Questions & Answers:

Q1) What is acceptable for driving surfaces after trenching occurs?

A1) Cold mix asphalt is acceptable as the entire roads network in the housing area is slated for re-paving in 2021.

Q2) The 6500 gallon tanks requested may require a longer time to fabricate and deliver than the stated period of performance

A2) Market research indicates that any tank over 2,000 gallons will have to be custom-constructed. It is suggested that if the offeror can suggest alternate sizes with a delivery schedule, and that information will be considered during the evaluation process.