Att_03_140P8419R0013_Construction_Drawings.pdf
PDF 3 MB Posted
- Solicitation number
- 140P8419R0013
About this file
This document package includes construction drawings and specifications for repairing raw water intake infrastructure and installing a water main at Oregon Caves National Monument and Preserve. The project involves repairing the existing raw water intake structure screens and manifold piping, and installing approximately 6,290 linear feet of 4-inch HDPE water main along an existing trail. Key details include specifications for trenching, bedding, backfill and restoration; notes on pipe material and fittings; and drawings showing the proposed water main alignment and details for connections, valves, air release assemblies and blow-off hydrants. The solicitation is for the National Park Service Pacific West Region under opportunity number 140P8419R0013.
Att 03_140P8419R0013_Construction Drawings
View the file
Other files
Show all 21
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
87977
ROBERT L. BE NN
IO
N
ENGI EERN
Robert L Bennion, PE
2019.04.29 17:49:01 -07'00'
0+
2+50
5+00
7+50
+0
+5
+0
+5
+0
+5
+0
+5
+00
+5
+0
+5
40+00
42+50
45+00 47 +5
50+00
52+50
55+00
57+50
+0
+5
+0
+5
+0
+5
+0
+5
80+00
+1
KEY MAP
SCALE: 1" = 250'
HEADQUARTERS AREA
87977
9797Robert L Bennion, PE
2019.04.29 17:49:17
879879879
W W W
W W W
87977
7979Robert L Bennion, PE
2019.04.29 17:49:32
878787
SCALE IN FEET
1005002550
S C
A
LE
IN
F
E E
T
.5
1. THE HORIZONTAL LAYOUT OF THE PIPE IS
SCHEMATIC AND SHOULD BE REFERENCED FOR
GENERAL BEARING ON ORIENTATION OF THE
PROPOSED POTABLE WATER LINE. PIPE JOINTS,
FITTINGS, AND DEFLECTIONS ARE SUBJECT TO
CHANGE BY THE CONTRACTOR TO ACCOUNT FOR
SITE CONSTRAINTS ALONG THE PROPOSED
LAYOUT.
2. CONSTRUCTION LIMITS ARE 10-FEET EITHER SIDE
OF THE EXISTING WATER LINE. CONTRACTOR IS TO
RESTORE SLOPES AND COVERAGE TO EXISTING
CONDITION FOLLOWING INSTALLATION EXCEPT
FOR A 6-FOOT WIDE PATH FOR FUTURE
MAINTENANCE ACCESS.
3. CONTRACTOR TO SCARIFY AND STOCKPILE THE
TOPSOILS, AND CHIP/MULCH ANY BRUSH DURING
CLEARING FOR USE IN RESTORATION OF FINISHED
SURFACE FOLLOWING CONSTRUCTION.
4. THE PROPOSED PIPE INSTALLATION SHALL
MAINTAIN A MINIMUM COVERAGE OF 3-FEET OVER
THE CROWN OF THE INSTALLED PIPE.
5. PIPE SHALL BE INSTALLED VERTICALLY TO
MAINTAIN A POSITIVE SLOPE FROM THE EAST TO
THE CONNECTION POINT NEAR THE STORAGE
TANKS TO AVOID LOW POINTS WITHIN THE SYSTEM.
IF ANY LOW-POINTS ARE REQUIRED THE
CONTRACTOR SHALL INSTALL A BLOW-OFF VALVE.
GENERAL NOTES:
977977Robert L Bennion, PE
2019.04.29 17:49:47
+0
+5
+0
+5
+0
+5
247 LF 4" HDPE DR 9
(42 LF THIS SHEET)
103 LF 4" HDPE DR 9
(55 LF THIS SHEET)
103 LF 4" HDP
(55 LF TH
INTERSECTION OF
BIG TREE TRAIL
EXISTING
WATERLINE
ROCK FACE
9+00 9+50 10+00 10+50 11+00 11+50 12+00 12+50 13+00 13+50 14+00 14+50 15+00 15+50 16+00 16+50 17+00 17+50 18+00 18+50 19+00 19+50 20+00 20+50 21+00 21+50 22+00
9+00 9+50 10+00 10+50 11+00 11+50 12+00 12+50 13+00 13+50 14+00 14+50 15+00 15+50 16+00 16+50 17+00 17+50 18+00 18+50 19+00 19+50 20+00 20+50 21+00 21+50 22+00
1 EA - 4" 22.50° BEND (MJ)
FUSED OR MECHANICALLY
RESTRAINED
1 EA - 4" 22.50° BEND (MJ)
FUSED OR MECHANICALLY
RESTRAINED
1 EA - 4" 22.50° BEND (MJ)
FUSED OR MECHANICALLY
RESTRAINED
1 EA - 4" 11.25° BEND (MJ)
FUSED OR MECHANICALLY
RESTRAINED
1 EA - 4" 11.25° BEND (MJ)
FUSED OR MECHANICALLY
RESTRAINED
1 EA - 4" 11.25° BEND (MJ)
FUSED OR MECHANICALLY
RESTRAINED
1 EA - 4" 11.25° BEND (MJ)
FUSED OR MECHANICALLY
RESTRAINED
629 LF 4" HDPE DR 9
225 LF 4" HDPE DR 9
62 LF 4" HDPE DR 9
94 LF 4" HDPE DR 9 95 LF 4" HDPE DR 9
97 LF 4" HDPE DR 9
247 LF 4" HDPE DR 9
(42 LF THIS SHEET)
103 LF 4" HDPE DR 9
(55 LF THIS SHEET)
EXISTING GRADE AT
EXISTING WATERLINE
87977
S C
A
LE
IN
F
E E
T
.5
1. THE HORIZONTAL LAYOUT OF THE PIPE IS
SCHEMATIC AND SHOULD BE REFERENCED FOR
GENERAL BEARING ON ORIENTATION OF THE
PROPOSED POTABLE WATER LINE. PIPE JOINTS,
FITTINGS, AND DEFLECTIONS ARE SUBJECT TO
CHANGE BY THE CONTRACTOR TO ACCOUNT FOR
SITE CONSTRAINTS ALONG THE PROPOSED
LAYOUT.
2. CONSTRUCTION LIMITS ARE 10-FEET EITHER SIDE
OF THE EXISTING WATER LINE. CONTRACTOR IS TO
RESTORE SLOPES AND COVERAGE TO EXISTING
CONDITION FOLLOWING INSTALLATION EXCEPT
FOR A 6-FOOT WIDE PATH FOR FUTURE
MAINTENANCE ACCESS.
3. CONTRACTOR TO SCARIFY AND STOCKPILE THE
TOPSOILS, AND CHIP/MULCH ANY BRUSH DURING
CLEARING FOR USE IN RESTORATION OF FINISHED
SURFACE FOLLOWING CONSTRUCTION.
4. THE PROPOSED PIPE INSTALLATION SHALL
MAINTAIN A MINIMUM COVERAGE OF 3-FEET OVER
THE CROWN OF THE INSTALLED PIPE.
5. PIPE SHALL BE INSTALLED VERTICALLY TO
MAINTAIN A POSITIVE SLOPE FROM THE EAST TO
THE CONNECTION POINT NEAR THE STORAGE
TANKS TO AVOID LOW POINTS WITHIN THE SYSTEM.
IF ANY LOW-POINTS ARE REQUIRED THE
CONTRACTOR SHALL INSTALL A BLOW-OFF VALVE.
GENERAL NOTES:
9797Robert L Bennion, PE
2019.04.29 17:50:01
22+00 22+50 23+00 23+50 24+00 24+50 25+00 25+50 26+00 26+50 27+00 27+50 28+00 28+50 29+00 29+50 30+00 30+50 31+00 31+50 32+00 32+50 33+00 33+50 34+00 34+50 35+00
22+00 22+50 23+00 23+50 24+00 24+50 25+00 25+50 26+00 26+50 27+00 27+50 28+00 28+50 29+00 29+50 30+00 30+50 31+00 31+50 32+00 32+50 33+00 33+50 34+00 34+50 35+00
1 EA - 4" 22.50° BEND (MJ)
FUSED OR MECHANICALLY
RESTRAINED
1 EA - 4" 22.50° BEND (MJ)
FUSED OR MECHANICALLY
RESTRAINED
1 EA - 4" 11.25° BEND (MJ)
FUSED OR MECHANICALLY
RESTRAINED
1 EA - 4" 11.25° BEND (MJ)
FUSED OR MECHANICALLY
RESTRAINED
1 EA - 4" 11.25° BEND (MJ)
FUSED OR MECHANICALLY
RESTRAINED
1 EA - 4" 11.25° BEND (MJ)
FUSED OR MECHANICALLY
RESTRAINED
428 LF 4" HDPE DR 9
(374 LF THIS SHEET)
73 LF 4" HDPE DR 9
144 LF 4" HDPE DR 9
91 LF 4" HDPE DR 9
AIR RELEASE VALVE
264 LF 4" HDPE DR 9300 LF 4" HDPE DR 9
103 LF 4" HDPE DR 9
(55 LF THIS SHEET)
EXISTING GRADE AT
EXISTING WATERLINE
87977
S C
A
LE
IN
F
E E
T
.5
1. THE HORIZONTAL LAYOUT OF THE PIPE IS
SCHEMATIC AND SHOULD BE REFERENCED FOR
GENERAL BEARING ON ORIENTATION OF THE
PROPOSED POTABLE WATER LINE. PIPE JOINTS,
FITTINGS, AND DEFLECTIONS ARE SUBJECT TO
CHANGE BY THE CONTRACTOR TO ACCOUNT FOR
SITE CONSTRAINTS ALONG THE PROPOSED
LAYOUT.
2. CONSTRUCTION LIMITS ARE 10-FEET EITHER SIDE
OF THE EXISTING WATER LINE. CONTRACTOR IS TO
RESTORE SLOPES AND COVERAGE TO EXISTING
CONDITION FOLLOWING INSTALLATION EXCEPT
FOR A 6-FOOT WIDE PATH FOR FUTURE
MAINTENANCE ACCESS.
3. CONTRACTOR TO SCARIFY AND STOCKPILE THE
TOPSOILS, AND CHIP/MULCH ANY BRUSH DURING
CLEARING FOR USE IN RESTORATION OF FINISHED
SURFACE FOLLOWING CONSTRUCTION.
4. THE PROPOSED PIPE INSTALLATION SHALL
MAINTAIN A MINIMUM COVERAGE OF 3-FEET OVER
THE CROWN OF THE INSTALLED PIPE.
5. PIPE SHALL BE INSTALLED VERTICALLY TO
MAINTAIN A POSITIVE SLOPE FROM THE EAST TO
THE CONNECTION POINT NEAR THE STORAGE
TANKS TO AVOID LOW POINTS WITHIN THE SYSTEM.
IF ANY LOW-POINTS ARE REQUIRED THE
CONTRACTOR SHALL INSTALL A BLOW-OFF VALVE.
GENERAL NOTES:
9797Robert L Bennion, PE
2019.04.29 17:50:18
35+00 35+50 36+00 36+50 37+00 37+50 38+00 38+50 39+00 39+50 40+00 40+50 41+00 41+50 42+00 42+50 43+00 43+50 44+00 44+50 45+00 45+50 46+00 46+50 47+00 47+50 48+00
35+00 35+50 36+00 36+50 37+00 37+50 38+00 38+50 39+00 39+50 40+00 40+50 41+00 41+50 42+00 42+50 43+00 43+50 44+00 44+50 45+00 45+50 46+00 46+50 47+00 47+50 48+00
1 EA - 4" 22.50° BEND (MJ)
FUSED OR MECHANICALLY
RESTRAINED
1 EA - 4" 22.50° BEND (MJ)
FUSED OR MECHANICALLY
RESTRAINED
1 EA - 4" 22.50° BEND (MJ)
FUSED OR MECHANICALLY
RESTRAINED
1 EA - 4" 22.50° BEND (MJ)
FUSED OR MECHANICALLY
RESTRAINED
1 EA - 4" 22.50° BEND (MJ)
FUSED OR MECHANICALLY
RESTRAINED 1 EA - 4" 22.50° BEND (MJ)
FUSED OR MECHANICALLY
RESTRAINED
1 EA - 4" 45° BEND (MJ)
FUSED OR MECHANICALLY
RESTRAINED
1 EA - 4" 45° BEND (MJ)
FUSED OR MECHANICALLY
RESTRAINED
1 EA - 4" 11.25° BEND (MJ)
FUSED OR MECHANICALLY
RESTRAINED
1 EA - 4" 11.25° BEND (MJ)
FUSED OR MECHANICALLY
RESTRAINED
1 EA - 4" 11.25° BEND (MJ)
FUSED OR MECHANICALLY
RESTRAINED
1 EA - 4" 11.25° BEND (MJ)
FUSED OR MECHANICALLY
RESTRAINED
1 EA - 4" 11.25° BEND (MJ)
FUSED OR MECHANICALLY
RESTRAINED
428 LF 4" HDPE DR 9
(54 LF THIS SHEET)
278 LF 4" HDPE DR 9
(202 LF THIS SHEET)
170 LF 4" HDPE DR 9
55 LF 4" HDPE DR 9
15 LF 4" HDPE DR 9
25 LF 4" HDPE DR 9
43 LF 4" HDPE DR 9
53 LF 4" HDPE DR 9
38 LF 4" HDPE DR 9
26 LF 4" HDPE DR 9
53 LF 4" HDPE DR 9
46 LF 4" HDPE DR 9
360 LF 4" HDPE DR 9
130 LF 4" HDPE DR 9
EXISTING GRADE AT
EXISTING WATERLINE
87977
S C
A
LE
IN
F
E E
T
.5
1. THE HORIZONTAL LAYOUT OF THE PIPE IS
SCHEMATIC AND SHOULD BE REFERENCED FOR
GENERAL BEARING ON ORIENTATION OF THE
PROPOSED POTABLE WATER LINE. PIPE JOINTS,
FITTINGS, AND DEFLECTIONS ARE SUBJECT TO
CHANGE BY THE CONTRACTOR TO ACCOUNT FOR
SITE CONSTRAINTS ALONG THE PROPOSED
LAYOUT.
2. CONSTRUCTION LIMITS ARE 10-FEET EITHER SIDE
OF THE EXISTING WATER LINE. CONTRACTOR IS TO
RESTORE SLOPES AND COVERAGE TO EXISTING
CONDITION FOLLOWING INSTALLATION EXCEPT
FOR A 6-FOOT WIDE PATH FOR FUTURE
MAINTENANCE ACCESS.
3. CONTRACTOR TO SCARIFY AND STOCKPILE THE
TOPSOILS, AND CHIP/MULCH ANY BRUSH DURING
CLEARING FOR USE IN RESTORATION OF FINISHED
SURFACE FOLLOWING CONSTRUCTION.
4. THE PROPOSED PIPE INSTALLATION SHALL
MAINTAIN A MINIMUM COVERAGE OF 3-FEET OVER
THE CROWN OF THE INSTALLED PIPE.
5. PIPE SHALL BE INSTALLED VERTICALLY TO
MAINTAIN A POSITIVE SLOPE FROM THE EAST TO
THE CONNECTION POINT NEAR THE STORAGE
TANKS TO AVOID LOW POINTS WITHIN THE SYSTEM.
IF ANY LOW-POINTS ARE REQUIRED THE
CONTRACTOR SHALL INSTALL A BLOW-OFF VALVE.
GENERAL NOTES:
7979Robert L Bennion, PE
2019.04.29 17:50:33
48+00 48+50 49+00 49+50 50+00 50+50 51+00 51+50 52+00 52+50 53+00 53+50 54+00 54+50 55+00 55+50 56+00 56+50 57+00 57+50 58+00
48+00 48+50 49+00 49+50 50+00 50+50 51+00 51+50 52+00 52+50 53+00 53+50 54+00 54+50 55+00 55+50 56+00 56+50 57+00 57+50 58+00
1 EA - 4" 22.50° BEND (MJ)
FUSED OR MECHANICALLY
RESTRAINED
1 EA - 4" 22.50° BEND (MJ)
FUSED OR MECHANICALLY
RESTRAINED
1 EA - 4" 22.50° BEND (MJ)
FUSED OR MECHANICALLY
RESTRAINED
1 EA - 4" 45° BEND (MJ)
FUSED OR MECHANICALLY
RESTRAINED
1 EA - 4" 11.25° BEND (MJ)
FUSED OR MECHANICALLY
RESTRAINED
278 LF 4" HDPE DR 9
(76 LF THIS SHEET)
120 LF 4" HDPE DR 9
(52 LF THIS SHEET)
417 LF 4" HDPE DR 9
22 LF 4" HDPE DR 9
21 LF 4" HDPE DR 9
85 LF 4" HDPE DR 9
233 LF 4" HDPE DR 9
93 LF 4" HDPE DR 9
EXISTING GRADE AT
EXISTING WATERLINE
AIR RELEASE VALVE
87977
S C
A
LE
IN
F
E E
T
.5
1. THE HORIZONTAL LAYOUT OF THE PIPE IS
SCHEMATIC AND SHOULD BE REFERENCED FOR
GENERAL BEARING ON ORIENTATION OF THE
PROPOSED POTABLE WATER LINE. PIPE JOINTS,
FITTINGS, AND DEFLECTIONS ARE SUBJECT TO
CHANGE BY THE CONTRACTOR TO ACCOUNT FOR
SITE CONSTRAINTS ALONG THE PROPOSED
LAYOUT.
2. CONSTRUCTION LIMITS ARE 10-FEET EITHER SIDE
OF THE EXISTING WATER LINE. CONTRACTOR IS TO
RESTORE SLOPES AND COVERAGE TO EXISTING
CONDITION FOLLOWING INSTALLATION EXCEPT
FOR A 6-FOOT WIDE PATH FOR FUTURE
MAINTENANCE ACCESS.
3. CONTRACTOR TO SCARIFY AND STOCKPILE THE
TOPSOILS, AND CHIP/MULCH ANY BRUSH DURING
CLEARING FOR USE IN RESTORATION OF FINISHED
SURFACE FOLLOWING CONSTRUCTION.
4. THE PROPOSED PIPE INSTALLATION SHALL
MAINTAIN A MINIMUM COVERAGE OF 3-FEET OVER
THE CROWN OF THE INSTALLED PIPE.
5. PIPE SHALL BE INSTALLED VERTICALLY TO
MAINTAIN A POSITIVE SLOPE FROM THE EAST TO
THE CONNECTION POINT NEAR THE STORAGE
TANKS TO AVOID LOW POINTS WITHIN THE SYSTEM.
IF ANY LOW-POINTS ARE REQUIRED THE
CONTRACTOR SHALL INSTALL A BLOW-OFF VALVE.
GENERAL NOTES:
9797Robert L Bennion, PE
2019.04.29 17:50:50
58+00 58+50 59+00 59+50 60+00 60+50 61+00 61+50 62+00 62+50 63+00 63+50 64+00 64+50 65+00 65+50 66+00 66+50 67+00 67+50 68+00 68+50 69+00
58+00 58+50 59+00 59+50 60+00 60+50 61+00 61+50 62+00 62+50 63+00 63+50 64+00 64+50 65+00 65+50 66+00 66+50 67+00 67+50 68+00 68+50 69+00
1 EA - 4" 22.50° BEND (MJ)
FUSED OR MECHANICALLY
RESTRAINED
1 EA - 4" 22.50° BEND (MJ)
FUSED OR MECHANICALLY
RESTRAINED
1 EA - 4" 11.25° BEND (MJ)
FUSED OR MECHANICALLY
RESTRAINED
1 EA - 4" 11.25° BEND (MJ)
FUSED OR MECHANICALLY
RESTRAINED
1 EA - 4" 11.25° BEND (MJ)
FUSED OR MECHANICALLY
RESTRAINED
1 EA - 4" 11.25° BEND (MJ)
FUSED OR MECHANICALLY
RESTRAINED
1 EA - 4" 11.25° BEND (MJ)
FUSED OR MECHANICALLY
RESTRAINED
1 EA - 4" 11.25° BEND (MJ)
FUSED OR MECHANICALLY
RESTRAINED
1 EA - 4" 11.25° BEND (MJ)
FUSED OR MECHANICALLY
RESTRAINED
1 EA - 4" 11.25° BEND (MJ)
FUSED OR MECHANICALLY
RESTRAINED
1 EA - 4" 11.25° BEND (MJ)
FUSED OR MECHANICALLY
RESTRAINED
120 LF 4" HDPE DR 9
(68 LF THIS SHEET)
224 LF 4" HDPE DR 9
194 LF 4" HDPE DR 9
(82 LF THIS SHEET)
176 LF 4" HDPE DR 9
80 LF 4" HDPE DR 9
38 LF 4" HDPE DR 9
117 LF 4" HDPE DR 9
44 LF 4" HDPE DR 9
25 LF 4" HDPE DR 9
35 LF 4" HDPE DR 9
130 LF 4" HDPE DR 9
72 LF 4" HDPE DR 9
EXISTING GRADE AT
EXISTING WATERLINE
87977
S C
A
LE
IN
F
E E
T
.5
1. THE HORIZONTAL LAYOUT OF THE PIPE IS
SCHEMATIC AND SHOULD BE REFERENCED FOR
GENERAL BEARING ON ORIENTATION OF THE
PROPOSED POTABLE WATER LINE. PIPE JOINTS,
FITTINGS, AND DEFLECTIONS ARE SUBJECT TO
CHANGE BY THE CONTRACTOR TO ACCOUNT FOR
SITE CONSTRAINTS ALONG THE PROPOSED
LAYOUT.
2. CONSTRUCTION LIMITS ARE 10-FEET EITHER SIDE
OF THE EXISTING WATER LINE. CONTRACTOR IS TO
RESTORE SLOPES AND COVERAGE TO EXISTING
CONDITION FOLLOWING INSTALLATION EXCEPT
FOR A 6-FOOT WIDE PATH FOR FUTURE
MAINTENANCE ACCESS.
3. CONTRACTOR TO SCARIFY AND STOCKPILE THE
TOPSOILS, AND CHIP/MULCH ANY BRUSH DURING
CLEARING FOR USE IN RESTORATION OF FINISHED
SURFACE FOLLOWING CONSTRUCTION.
4. THE PROPOSED PIPE INSTALLATION SHALL
MAINTAIN A MINIMUM COVERAGE OF 3-FEET OVER
THE CROWN OF THE INSTALLED PIPE.
5. PIPE SHALL BE INSTALLED VERTICALLY TO
MAINTAIN A POSITIVE SLOPE FROM THE EAST TO
THE CONNECTION POINT NEAR THE STORAGE
TANKS TO AVOID LOW POINTS WITHIN THE SYSTEM.
IF ANY LOW-POINTS ARE REQUIRED THE
CONTRACTOR SHALL INSTALL A BLOW-OFF VALVE.
GENERAL NOTES:
99Robert L Bennion, PE
2019.04.29 17:51:02
69+00 69+50 70+00 70+50 71+00 71+50 72+00 72+50 73+00 73+50 74+00 74+50 75+00 75+50 76+00 76+50 77+00 77+50 78+00 78+50 79+00 79+50 80+00 80+50
69+00 69+50 70+00 70+50 71+00 71+50 72+00 72+50 73+00 73+50 74+00 74+50 75+00 75+50 76+00 76+50 77+00 77+50 78+00 78+50 79+00 79+50 80+00 80+50
1 EA - 4" 22.50° BEND (MJ)
FUSED OR MECHANICALLY
RESTRAINED
1 EA - 4" 45° BEND (MJ)
FUSED OR MECHANICALLY
RESTRAINED
1 EA - 4" 11.25° BEND (MJ)
FUSED OR MECHANICALLY
RESTRAINED
1 EA - 4" 11.25° BEND (MJ)
FUSED OR MECHANICALLY
RESTRAINED
1 EA - 4" 11.25° BEND (MJ)
FUSED OR MECHANICALLY
RESTRAINED
1 EA - 4" 11.25° BEND (MJ)
FUSED OR MECHANICALLY
RESTRAINED
1 EA - 4" 22.50° BEND (MJ)
FUSED OR MECHANICALLY
RESTRAINED
1 EA - 4" 11.25° BEND (MJ)
FUSED OR MECHANICALLY
RESTRAINED
1 EA - 4" 11.25° BEND (MJ)
FUSED OR MECHANICALLY
RESTRAINED
1 EA - 4" 45° BEND (MJ)
FUSED OR MECHANICALLY
RESTRAINED
194 LF 4" HDPE DR 9
(102 LF THIS SHEET)
218 LF 4" HDPE DR 9
286 LF 4" HDPE DR 9
44 LF 4" HDPE DR 9
22 LF 4" HDPE DR 9
7 LF 4" HDPE DR 9
73 LF 4" HDPE DR 9
65 LF 4" HDPE DR 9
54 LF 4" HDPE DR 9
101 LF 4" HDPE DR 9
CONNECT TO
EXISTING WM
EXISTING GRADE AT
EXISTING WATERLINE
87977
S C
A
LE
IN
F
E E
T
.5
DAYLIGHT
PIPE END
INSTALL 4"
FLAP VALVE
(1) 4" GATE
VALVE (MJ)
PROVIDE AT LEAST A
10' LENGTH OF PIPE
WITH 5% OR GREATER
SLOPE TO ACT AS A
SEDIMENT TRAP IN LINE
WITH THE EXISTING
PIPE DIRECTION
(1) 4" TEE (MJ)
CONNECT TO EXISTING
WATER LINE. COUPLERS
AND REDUCERS AS
NEEDED
(1) 4" GATE
VALVE (MJ)
(1) 4" 45°
BEND (MJ)
NTS
CONNECT TO EXISTING WM
1. THE HORIZONTAL LAYOUT OF THE PIPE IS
SCHEMATIC AND SHOULD BE REFERENCED FOR
GENERAL BEARING ON ORIENTATION OF THE
PROPOSED POTABLE WATER LINE. PIPE JOINTS,
FITTINGS, AND DEFLECTIONS ARE SUBJECT TO
CHANGE BY THE CONTRACTOR TO ACCOUNT FOR
SITE CONSTRAINTS ALONG THE PROPOSED
LAYOUT.
2. CONSTRUCTION LIMITS ARE 10-FEET EITHER SIDE
OF THE EXISTING WATER LINE. CONTRACTOR IS TO
RESTORE SLOPES AND COVERAGE TO EXISTING
CONDITION FOLLOWING INSTALLATION EXCEPT
FOR A 6-FOOT WIDE PATH FOR FUTURE
MAINTENANCE ACCESS.
3. CONTRACTOR TO SCARIFY AND STOCKPILE THE
TOPSOILS, AND CHIP/MULCH ANY BRUSH DURING
CLEARING FOR USE IN RESTORATION OF FINISHED
SURFACE FOLLOWING CONSTRUCTION.
4. THE PROPOSED PIPE INSTALLATION SHALL
MAINTAIN A MINIMUM COVERAGE OF 3-FEET OVER
THE CROWN OF THE INSTALLED PIPE.
5. PIPE SHALL BE INSTALLED VERTICALLY TO
MAINTAIN A POSITIVE SLOPE FROM THE EAST TO
THE CONNECTION POINT NEAR THE STORAGE
TANKS TO AVOID LOW POINTS WITHIN THE SYSTEM.
IF ANY LOW-POINTS ARE REQUIRED THE
CONTRACTOR SHALL INSTALL A BLOW-OFF VALVE.
GENERAL NOTES:
INSTALL NEW SCREENS AND MANIFOLD
PIPING IN EXISTING INTAKE STRUCTURE.
9797Robert L Bennion, PE
2019.04.29 17:51:15
NTS
TYPICAL TRENCH SECTION
NTS
WATER VALVE EXTENSION
1. ALL ROAD CUTS MUST MEET COUNTY OR
NPS REQUIREMENTS.
2. ALL TRENCH BACKFILL CAN BE NATIVE
MATERIAL EXCEPT AS DIRECTED BY THE
COR. NATIVE MATERIAL UNSUITABLE FOR
BACKFILL CAN BE REPLACED WITH
TRENCH BANK RUN GRAVEL.
3. LOCATER WIRES SHALL BE BLUE COATED
14 GAGE COPPER WIRE CONTINUOUS TO
ABOVE GROUND ACCESS POINTS (AIR
RELEASE VALVES) SPLICES IN WIRE, IF
NEEDED, SHALL BE MADE WITH
WATERPROOF SPLICE KITS.
PIPE BEDDING
3" UNDER AND
3" OVER PIPE
NATIVE
BACKFILL
3' MIN
WATER LINE
MARKER /
DETECTOR TAPE
& LOCATER WIRE
CROWN FOR
SETTLEMENT
N E
A T
LI
N
E
12"
1' TYP
4" HDPE
PIPE
RESTORE TRAIL
AS REQUIRED BY
COR
N E
A T
LI
N
E
NOTES:
NOTES:
A. AIR RELEASE UNIT AND BOX
SHALL BE INSTALLED IN A
NON-TRAFFIC AREA.
B. SADDLE FOR AIR RELEASE
UNIT SHALL BE INSTALLED AT
THE HIGH POINT OF THE LINE.
IF HIGH POINT FALLS IN
LOCATION WHERE
ASSEMBLY CANNOT BE
INSTALLED, INSTALL WATER
MAIN TO CREATE A HIGH
POINT WHERE AIR RELEASE
CAN BE LOCATED.
C. ALL PIPE AND FITTINGS
SHALL BE MINIMUM
PRESSURE CLASS 200 PSI,
IPS SIZE. ALL FITTINGS
BETWEEN MAIN AND AIR
RELEASE SHALL BE BRASS
AND ALL FITTINGS ON THE
AIR RELEASE DISCHARGE
SHALL BE GALVANIZED.
D. CONCRETE METER BOX
PENETRATIONS SHALL BE
GROUTED.
E. AIR RELEASE RISER SHALL
BE PAINTED AS DIRECTED BY
THE COR.
8"X8"X6" CONC. BLOCK
1" BRASS UNION
1" BRASS NIPPLE
1" BRASS 90° ELL
12" MIN.
1" BRASS
UNION
BACKFILL WITH STYROFOAM
PEANUTS TO TOP OF BONNET
6" PVC PIPE NOTCHED AT THE BOTTOM
TO PROVIDE CLEARANCE OVER PIPE
LARGE CONCRETE METER BOX
WITH RISERS AS NEEDED
BROOKS SERIES 65T,
CARSON SERIES 1730,
OR FOGTITE NO. 2.
1" HIGH DENSITY
POLYETHYLENE IPS1" 90° ANGLE
COUPLING
BRONZE
CORPORATION
STOP
MUELLER
WATER MAIN
SADDLE
ROMAC OR
ROCKWELL
1" COMPRESSION
COUPLING
1" CURB STOP
MUELLER
1" BRASS
NIPPLE
(TYPICAL) 1" BRASS
NIPPLE
3"
3" MIN.
EXIST. GRADE
12" MIN. DEPTH
1-1/2" MINUS
WASHED DRAIN ROCK
EXIST. GRADE
STAINLESS
STEEL
METAL STRAP
1" GALV. STREET ELL (HORIZ.)
1" GALV. 90° ELL (VERT.)
4"X4" PRESSURE
TREATED POST
1" GALV.
PIPE
1" BRASS 90° ELL
1" BRASS
NIPPLE
AIR RELEASE
VALVE
1" GALV. RETURN BEND
1" GALV.
BEEHIVE
STRAINER
24" MIN.
1" HIGH DENSITY
POLYETHYLENE IPS
TEST TAP W/
HOSE BIB
LOCATOR
WIRE
NTS
AIR RELEASE VALVE
Robert L Bennion, PE
2019.04.29 17:51:30
18"
UNDISTURBED SOIL
WATER MAIN
MARKER/
DETECTOR TAPE
AND LOCATER
WIRE
2" BRASS NIPPLE
6" LONG
2" - 90°
LOCATER WIRE
2" FIP VERTICAL INLET
FINISHED GRADE
MAINGUARD 2" BLOW-OFF HYDRANT
CAP (MJ) SURROUND
WITH PLASTIC PRIOR
TO POURING CONCRETE
2" SADDLE AND
CORP STOP OFF
LOWER 13 OF PIPE
2-1/2" NST NOZZLE
GEOSYTHETIC FABRIC
SOLID CONCRETE BEARING
BLOCK 4"x8"x16" OR AS DIRECTED
BY THE ASSOCIATION
3/4"-0" CRUSHED ROCK
NOTES:
1. LOCATER WIRES SHALL BE BLUE COATED 14 GAGE COPPER WIRE CONTINUOUS TO ABOVE
GROUND ACCESS POINTS (METERS & HYDRANTS) SPLICES IN WIRE, IF NEEDED, SHALL BE MADE
WITH WATERPROOF SPLICE KITS.
2. BLOW-OFF HYDRANTS SHALL BE NON-FREEZING, SELF DRAINING TYPE WITH A MIN. DEPTH OF
BURY OF 3 FEET. SET UNDERGROUND IN A CONCRETE METER BOX. THESE HYDRANTS SHALL BE
FURNISHED WITH A 2" FIP INLET, A NON-TURNING OPERATING ROD, AND SHALL OPEN TO THE
LEFT. ALL OF THE WORKING PARKS SHALL BE OF BRONZE-TO-BRONZE DESIGN WITH AN
ALUMINUM PLUNGER AND SERVICEABLE FROM ABOVE GRADE WITH NO DIGGING. THE OUTLET
SHALL BE BRONZE AND BE 2-1/2" NST. HYDRANTS SHALL BE LOCKABLE TO PREVENT
UNAUTHORIZED USE.
SPLICE SERVICE
LOCATER WIRE
INTO MAIN
LOCATER WIRE
CONCRETE BLOCK
2" GALV. PIPE
CONCRETE METER BOX
WITH METAL COVER
FOGTITE TYPE 1D
87977
NTS
MAIN FILLING
NTS
BLOWOFF ASSEMBLY
7979Robert L Bennion, PE
2019.04.29 17:51:46