This is a Questions and Answers document for federal contract opportunity 140P8326Q0041 regarding the replacement of a Fire Alarm Control Panel (FACP) at the John Day Fossil Beds National Monument (JODA) Maintenance Shop.
The Government has amended the Statement of Work to require installation of a currently manufacturer-supported, UL-listed addressable or hybrid-addressable fire alarm control panel. For monitoring communications, the Government will provide and activate two analog telephone/POTS (Plain Old Telephone Service) lines using existing copper telephone infrastructure. The Contractor must supply all required listed communicators, dialer modules, RJ31X jacks or equivalent line-seizure connections, surge protection, cabling, terminations, programming, coordination, testing, and monitoring-provider signal verification to connect the system to the Government-provided telephone lines. The Government assumes responsibility for line activation, provisioning, and recurring telephone service charges. The Contractor shall coordinate with the Contracting Officer Representative (COR), the Government-designated telephone/service provider, and the Government-designated central station monitoring provider. If the analog telephone/POTS lines become unavailable or non-functional, alternate communication methods may be utilized only with prior Government approval. The document also includes interior photographs of the existing panel and architectural/mechanical drawings (floor plan, electrical plans for lighting and power/signal, and plumbing plan) to assist quoters in determining specifications and pricing.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Attachment_8_REVISED_SOW_JODA_Maint_Shop_FACP_0001.pdf | ||
| Sol_140P8326Q0041_Amd_0001.pdf | ||
| Attachment_5_Forms_to_Return_with_Quote_P8326Q0041.docx | DOCX document | |
| Attachment_6_Project_Photo.pdf | ||
| Sol_140P8326Q0041.pdf | ||
| Attachment_2_Terms_Provisions_Clauses_JODA_FACP_Replacement.pdf | ||
| Attachment_3_DOL_Wage_Determination_Grant_County_OR.pdf | ||
| Attachment_4_SOW_JODA_Maint_Shop_FACP.pdf | ||
| Attachment_1_READ_ME_FIRST_-_FAQs.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Attachment 7 Q&A 140P8326Q0041 Replacement Maintenance Shop Fire Alarm Control Panel 140P8326Q0041 John Day Fossil Beds National Monument (JODA)
The following are questions/answers that were brought up that supplement the Request for Quotes, and in some cases may provide some different information than what is stated in the Request for Quotes. Where there are differences, quoters shall make pen and ink changes in those sections of the Request for Quotes, with the information provided in this Question and Answer round.
1. Q: Can we use addressable fire alarm panel?
A: Yes the government amended the SOW to require a currently manufacturer-supported, UL-listed addressable or hybrid-addressable fire alarm control panel. See Attachment 8 REVISED SOW JODA Maint Shop FACP
2. Q: What method is available at this location for monitoring? IP Internet? Standard Phone Lines?
A: The Government will provide and activate two analog telephone/POTS communication lines using existing copper telephone/backbone infrastructure serving the JODA Maintenance Shop. Contractor shall include all required listed communicators, dialer modules, RJ31X jacks or equivalent listed line-seizure connections, surge protection, cabling, terminations, programming, coordination, testing, and monitoring-provider signal verification required to connect the installed system to the Government-provided telephone lines. The Government will be responsible for line activation/provisioning and recurring telephone service charges.
Contractor shall coordinate with the COR, the Government-designated telephone/service provider, and the Government-designated central station monitoring provider. If the Government-provided analog telephone/POTS lines are not available or cannot be made functional, alternate communication methods are available but will require prior Government approval before installation or connection.
3. Q: Could you please provide interior photos of the panel so we can accurately determine the required specs and pricing? Any available drawings would also be greatly appreciated.
A: See following photos and drawings:
Attachm ent 7 Q
A 140P8326Q
Replacem ent M aintenance Shop Fire Alarm
C ontrol Panel
140P8326Q
John D ay Fossil Beds N ational M onum ent (JO
D A) aintenance Shop Fire Alarm
C ontrol Panel ational M onum ent (JO aintenance Shop Fire Alarm
C ontrol Panel ational M onum ent (JO aintenance Shop Fire Alarm
C ontrol Panel ational M onum ent (JO aintenance Shop Fire Alarm
C ontrol Panel ational M onum ent (JO aintenance Shop Fire Alarm
C ontrol Panel ational M onum ent (JO
Approved for the NPS By:
Ibzan O. Ortiz, CFO Regional Fire Marshal
File details come from the government source that posted it. Updated .