This document contains design drawings and specifications for the replacement of the well system serving the Peck Residence in Olympic National Park. The key details are:

The project involves construction and testing of a new potable water well, as well as installation of a new pump/treatment building. Key components include a new 60 sq. ft. pump house, a 1000-gallon septic tank and 450 sq. ft. drainfield, and electrical upgrades to the existing 200-amp service panel at the Peck Residence. The drawings provide specifications for the well, pump, water treatment equipment, and building construction. The project is solicited under Solicitation Number 140P8324Q0064 by the National Park Service's Pacific West Region. No specific award date or pricing terms are provided in the document.

View the file

Other files for this federal contract opportunity

Other files attached to Replace Well System, Peck Residence, Olympic NP, newest first.
File Type Posted
Sol_140P8324Q0064_Amd_0001.pdf PDF
Attachment_E_Site_Visit_Clarifications_0001.pdf PDF
Attachment_D_Forms_to_Return_with_Quote.docx DOCX document
Attachment_A_Specifications.pdf PDF
Attachment_C__DOL_Wage_Determination.pdf PDF
Sol_140P8324Q0064.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SHEET SUB SHEET TITLE OF SHEET

1 G0 COVER SHEET

2 G1 GENERAL NOTES

3 G2 PROPERTY BOUNDARY MAP

4 G3 SITE PLAN

5 C1 DEMOLITION & SALVAGE

6 C2 PUMP HOUSE PLAN

7 C3 PROCESS FLOW DIAGRAM

8 C4 WELL SCHEMATIC

9 A1 FOUNDATION PLAN & SECTION

10 A2 PUMP HOUSE SECTION DETAIL

11 E1 ELECTRICAL SERVICE DETAILS

UNITED STATES

DEPARTMENT OF THE INTERIOR

TITLE OF PROJECT

REPLACE PECK RESIDENCE

WELL SYSTEM

DRAWING NO.

_149_

193,378

NATIONAL PARK SERVICE

OLYMPIC NATIONAL PARK

LOCATION WITHIN PARK

QUINAULT

PMIS/PKG NO.

338781

REGION COUNTY STATE

PACIFIC WEST GRAYS HARBOR WASHINGTON

SHEET

_1_ OF _11_

GENERAL NOTES

1. ALL CONSTRUCTION SHALL BE IN CONFORMANCE WITH NPS STANDARDS AND

THE REQUIREMENTS OF CHAPTER 173-160 WASHINGTON ADMINISTRATIVE

CODE (IN ADDITION TO OTHER STATE AND LOCAL STANDARDS).

2. CONTRACTOR SHALL CONTACT DIG ALERT AND FIELD VERIFY ALL UTILITIES

PRIOR TO EXCAVATION. DIAL 811 BEFORE YOU DIG.

3. DIMENSIONS SHOWN ON PLANS ARE TO BE USED BY CONTRACTOR TO

DETERMINE APPROXIMATE FIELD CONDITIONS. PRIOR TO CONSTRUCTION,

CONTRACTOR SHALL FIELD VERIFY EXISTING LOCATIONS, ELEVATIONS,

MATERIAL TYPES, DIAMETER OF PIPES, ETC. OF ALL UTILITIES AND FEATURES

WHERE PROPOSED IMPROVEMENTS CONNECT. NOTIFY CONTRACTING

OFFICER OF ANY DISCREPANCIES IN WRITING.

4. EXISTING FACILITIES, INCLUDING BUT NOT LIMITED TO ROADS, SIDEWALKS,

STRUCTURES AND UTILITIES, DAMAGED BY CONTRACTOR’S OPERATIONS

SHALL BE RESTORED TO MATCH ORIGINAL PRE-CONSTRUCTION CONDITION

AND TO THE SATISFACTION OF THE CONTRACTING OFFICER WITHOUT

ADDITIONAL COST TO THE GOVERNMENT.

5. ALL DISTURBED ASPHALT, GRASS, DRAINAGE PATTERNS, ROADSIDE DITCHES,

TRAILS AND GRADE SHALL BE RESTORED TO ITS ORIGINAL CONDITION OR AS

CALLED FOR IN THE CONTRACT DOCUMENTS, WHICHEVER IS MORE

STRINGENT.

6. CONTRACTOR SHALL FURNISH AND INSTALL EVERYTHING REQUIRED TO

PROVIDE COMPLETE AND OPERABLE FACILITIES AS SHOWN HEREIN. IF THERE

IS AN OMISSION ON THE CONSTRUCTION DOCUMENTS, SUCH OMISSION

SHALL NOT BE CONSTRUED TO MEAN THAT THE CONTRACTOR IS NOT

REQUIRED TO FURNISH OR PROVIDE EVERYTHING THAT IS NECESSARY TO

PROVIDE COMPLETE AND OPERABLE FACILITIES.

7. ALL CONTRACTORS WORKING WITH THE PROJECT BOUNDARIES ARE

RESPONSIBLE FOR COMPLIANCE WITH ALL APPLICABLE SAFETY LAWS.

CONTRACTOR IS RESPONSIBLE FOR PROVIDING ALL EMPLOYEES AND/OR

SUBCONTRACTORS WITH PERSONAL PROTECTIVE EQUIPMENT AND

FOLLOWING ALL SAFETY PROTOCOLS.

8. CONTRACTOR SHALL PROVIDE DETECTABLE LOCATOR TAPE FOR ALL BURIED

PIPE AND CONDUITS. BURY DEPTH SHALL BE 24” MINIMUM, UNLESS STATED

OTHERWISE.

9. ALL COSTS INCURRED IN CORRECTION OF DEFICIENT WORK SHALL BE THE

RESPONSIBILITY OF THE CONTRACTOR.

10. CONSTRUCTION FENCING OR BARRIERS SHALL BE PROVIDED WHERE

NECESSARY, INCLUDING AROUND OPEN EXCAVATIONS WHEN WORK IS NOT

ACTIVELY IN PROGRESS, TO PREVENT UNAUTHORIZED ACCESS.

11. UNLESS OTHERWISE INDICATED, DEMOLISHED MATERIALS BECOME THE

PROPERTY OF THE CONTRACTOR. COMPLY WITH EPA REGULATIONS AND

DISPOSAL REGULATIONS OF AUTHORITIES HAVING JURISDICTION.

12. MINIMIZE CONSTRUCTION IMPACTS TO SOILS, WATER, PLANTS, AND

ANIMALS, AND OTHER NATURAL RESOURCES DURING CONSTRUCTION.

CONFINE CONSTRUCTION OPERATIONS TO MINIMUM PRACTICAL AREA. IN NO

CASE SHALL CONSTRUCTION OPERATIONS EXTEND BEYOND LIMITS OF

CONSTRUCTION INDICATED WITHOUT PRIOR APPROVAL BY THE

CONTRACTING OFFICER.

DESIGNED:

K. COOK

SUB SHEET NO. TITLE OF SHEET

GENERAL NOTES

DRAWING NO.

_149_

193,378

TECH REVIEW:

G1

PECK RESIDENCE WELL SYSTEM PMIS/PKG NO.

338781

DATE:

5/2024

QUINAULT, WA

OLYMPIC NATIONAL PARK

SHEET

_2_ OF _11_

DESIGNED:

K. COOK

SUB SHEET NO. TITLE OF SHEET

PROPERTY BOUNDARY MAP

DRAWING NO.

_149_

193,378

TECH REVIEW:

G2

PECK RESIDENCE WELL SYSTEM PMIS/PKG NO.

338781

DATE:

5/2024

QUINAULT, WA

OLYMPIC NATIONAL PARK

SHEET

_3_ OF _11_

NOTES:

1. PARCEL NUMBER: 230903230030

2. SITE ADDRESS: 1031 NORTH SHORE

RD., AMANDA PARK, WA 98562

SCALE 1:3,049

NORTH SHORE ROAD

SUB SHEET NO. TITLE OF SHEET

SITE PLAN

DRAWING NO.

_149_

193,378

TECH REVIEW:

G3

PECK RESIDENCE WELL SYSTEM PMIS/PKG NO.

338781

DATE:

5/2024

QUINAULT, WA

OLYMPIC NATIONAL PARK

SHEET

_4_ OF _11_

NOTES:

1. REMOVE 6 ALDER TREES (APPROXIMATELY

10-14” DBH) OVERHANGING NEW WELL

AND PUMP HOUSE SITE.

2. RETAIN RESIDENTIAL ACCESS AT ALL TIMES,

OR COORDINATE TEMPORARY ACCESS

LIMITATIONS WITH CONTRACTING OFFICER.

EXISTING WELL INSIDE 53 FT2

PUMP HOUSE (6’-5” X 8’-3”)

NEW 60 FT2

PUMP HOUSE

1200 FT2

PECK RESIDENCE

(25’ X 48’)

KESTNER CREEK

ASSUMED

CHLORINE CONTACT

PIPING

ASSUMED

WATER & DIRECT

BURY ELECTRICAL

CORRIDOR

PROTECT & RE-USE

WATER LINE; INSTALL

NEW ELECTRICAL

CONDUIT & WIRE

NEW WELL

DEMOLISH &

DECOMMISSION

CONSTRUCT

1000-GALLON SEPTIC

TANK & 450 FT2

DRAINFIELD

DRIVEWAY /

ACCESS ROAD

LIMITS OF

CONSTRUCTION

& CONTRACTOR

STAGING AREA WOODSHED &

STORAGE SHED

INSTALL NEW

ELECTRICAL CONDUIT

& CONDUCTOR WIRE,

REPLACE 30 AMP

BREAKER IN 200 AMP

PANEL FOR NEW

PUMP HOUSE

SUB SHEET NO. TITLE OF SHEET

DEMOLITION & SALVAGE

DRAWING NO.

_149_

193,378

TECH REVIEW:

C1

PECK RESIDENCE WELL SYSTEM PMIS/PKG NO.

338781

DATE:

5/2024

QUINAULT, WA

OLYMPIC NATIONAL PARK

SHEET

_5_ OF _11_

NOTES:

1. PROTECT & CONNECT TO CHLORINE CONTACT PIPING (LOCATED NEAR BACK LEFT CORNER OF BUILDING) FOR EXTENSION TO NEW PUMP HOUSE

BUILDING SITE. INSTALL NEW ELECTRICAL CONDUIT BETWEEN NEW PUMP HOUSE AND RESIDENCE. REPLACE 30 AMP “BARN” CIRCUIT BREAKER ON 200 AMP SERVICE PANEL WITH NEW 30 AMP BREAKER & CONDUCTOR WIRE TO NEW 100 AMP PUMP HOUSE SUBPANEL.

2. SALVAGE AND TRANSFER TO GOVERNMENT EXISTING DOOR HARDWARE, CHEMICAL FEED PUMP, SODIUM HYPOCHLORITE, AND TERMINATOR IRON FILTER WITH FLECK 2510 CONTROL VALVE WATER TREATMENT COMPONENTS PRIOR TO BUILDING DEMOLITION.

3. DEMOLISH & DISPOSE OF EXISTING PUMP HOUSE, CONCRETE PADS, AND REMAINING COMPONENTS. DECOMMISSION WELL.

EXISTING 53 FT2 PUMP HOUSE (6’-5” X 8’-3”) PECK RESIDENCE 200 AMP SERVICE PANELEXISTING WELL & TREATMENT COMPONENTS

SUB SHEET NO. TITLE OF SHEET

PUMP HOUSE PLAN

DRAWING NO.

_149_

193,378

TECH REVIEW:

C2

PECK RESIDENCE WELL SYSTEM PMIS/PKG NO.

338781

DATE:

5/2024

QUINAULT, WA

OLYMPIC NATIONAL PARK

SHEET

_6_ OF _11_

BYPASS VALVE

& AIR INJECTOR

WITH UNIONS

PRESSURE

RELIEF VALVE

PRESSURE

TANK

PRESSURE

SWITCH &

TANK DRAIN

AIR CONTACT

TANK WITH

AIR VENT

¾” BACKWASH

LINE TO EXTERIOR

DRAIN POINT

HOSE BIB

SAMPLE TAP

& PRESSURE

GAUGE

CHECK

VALVE

BALL

VALVE

IRON FILTER

WITH BACKWASH

CONTROL VALVE

CHEMICAL

METERING

PUMP (ON

SHELF) &

INJECTION

QUILL

SCALE OF FEET

4 0 4 8

FROM

NEW WELL

3’

10’

6’

TO EXISTING

CHLORINE

CONTACT PIPING

WELL PUMP

CONTROLLER

110V

GFCI

LIGHT

SWITCH

110V

GFCI

NOTES:

1. PUMP HOUSE PLAN IS SCHEMATIC; PROVIDE

ALL COMPONENTS NECESSARY FOR A FULLY

FUNCTIONING SYSTEM.

2. ALL COMPONENTS IN CONTACT WITH

DRINKING WATER SHALL BE NSF 61

CERTIFIED.

3. ALL PLUMBING SHALL BE 1” PEX, PVC, OR

BRASS UNLESS OTHERWISE NOTED.

4. WELL PUMP & CONTROLLER SHALL BE

FRANKLIN ELECTRIC, OR APPROVED EQUAL.

5. PRESSURE TANK SHALL BE AMTROL WELL-X-

TROL 200 SERIES, OR APPROVED EQUAL.

6. IRON FILTER SHALL BE TERMINATOR WITH

FLECK CONTROL VALVE AND AIR TANK WITH

HONEYWELL AIR VENT, OR APPROVED

EQUAL.

7. SODIUM HYPOCHLORITE CHEMICAL

METERING PUMP SHALL BE WALCHEM E-

CLASS BY IWAKI, OR APPROVED EQUAL.

8. FLUSH ENTRANCE DOOR SHALL BE FACTORY

PRIMED FIBERGLASS WITH INSULATED CORE

& STAINLESS HARDWARE. INCLUDE LEVER

AND SFIC 6 OR 7 PIN CORE/LOCKSET

COMPATIBLE WITH BEST ACCESS KEY

SYSTEM, BEST 9K37AB15D53626, OR

APPROVED EQUAL.

9. FURNISH AND INSTALL PLYWOOD SHELF FOR

CHEMICAL METERING PUMP.

10. ENSURE WATER TREATMENT COMPONENTS

ARE POWERED BY A RECEPTACLE THAT IS

ONLY ENERGIZED WHEN WELL PUMP IS

RUNNING.

LED OVERHEAD LIGHT

BALL

VALVE

100 AMP

LOAD CENTER

FIBERGLASS

DOOR

5’ X 5’ CONCRETE PAD

(2% SLOPE TO DRAIN)

HOSE BIB

SAMPLE TAP

& PRESSURE

GAUGE

SUB SHEET NO. TITLE OF SHEET

PROCESS FLOW DIAGRAM

DRAWING NO.

_149_

193,378

TECH REVIEW:

C3

PECK RESIDENCE WELL SYSTEM PMIS/PKG NO.

338781

DATE:

5/2024

QUINAULT, WA

OLYMPIC NATIONAL PARK

SHEET

_7_ OF _11_

¾”

SODIUM

HYPOCHLORITE

SODIUM

HYPOCHLORITE

SUB SHEET NO. TITLE OF SHEET

WELL SCHEMATIC

DRAWING NO.

_149_

193,378

TECH REVIEW:

C4

PECK RESIDENCE WELL SYSTEM PMIS/PKG NO.

338781

DATE:

5/2024

QUINAULT, WA

OLYMPIC NATIONAL PARK

SHEET

_8_ OF _11_

NOTES:

1. WELL CAP SHALL BE WATER-TIGHT

REMOVABLE CAST-IRON BLANK WELL

SEAL SIZED FOR WELL CASING,

CAMPBELL MANUFACTURING OR

APPROVED EQUAL.

2. WELL PUMP SHALL BE FRANKLIN

ELECTRIC SUBMERSIBLE WELL PUMP,

OR APPROVED EQUAL.

3. PITLESS ADAPTOR AND WATER SHALL

BE 18” MINIMUM BELOW GRADE.

4. WIRE IN CONDUIT SHALL BE 18”

MINIMUM BELOW GRADE FROM

WELL TO PUMP HOUSE.

5. TORQUE ARREST SHALL BE INSTALLED

WITHIN 2 FEET OF PUMP DISCHARGE.

6. CHECK VALVE SHALL BE INSTALLED 20

FEET ABOVE PUMP DISCHARGE.

SUB SHEET NO. TITLE OF SHEET

FOUNDATION PLAN & SECTION

DRAWING NO.

_149_

193,378

TECH REVIEW:

A1

PECK RESIDENCE WELL SYSTEM PMIS/PKG NO.

338781

DATE:

5/2024

QUINAULT, WA

OLYMPIC NATIONAL PARK

SHEET

_9_ OF _11_

10’-0”

9’-5”

3½” STEM WALL

3’-6”

4” CONCRETE SLAB

W/ 6X6 W2.1 X

W2.1 WELDED

WIRE MESH

4” CONCRETE SLAB

W/ 6X6 W2.1 X

W2.1 WELDED

WIRE MESH

NOTE: INSTALL

UFER GROUNDING

AT LOCATION OF

ELECTRICAL PANEL

SLEEVES &

STUB-UPS

FOR WATER &

ELECTRICAL

OPENING FOR

DOOR FRAME

5’-0”

6’-0”

5’-0”

#4 VERT. TYP.

SCALE OF FEET

4 0 4 8

FOUNDATION PLAN

NOTES:

1. CONCRETE AT 3,000 PSI.

SUB SHEET NO. TITLE OF SHEET

PUMP HOUSE SECTION DETAIL

DRAWING NO.

_149_

193,378

TECH REVIEW:

A1

PECK RESIDENCE WELL SYSTEM PMIS/PKG NO.

338781

DATE:

5/2024

QUINAULT, WA

OLYMPIC NATIONAL PARK

SHEET

_10_ OF _11_

NOTES:

1. STANDING SEAM PANEL METAL

ROOFING W/ HIGH TEMP SELF-

ADHERED ICE & WATER PROTECTION

UNDERLAYMENT; 26-GA CONCEALED

FASTENER STANDING SEAM

(CHAMPION METAL “SNAP-LOC” OR

EQUAL) STYLE ROOFING PANELS AND

ASSOCIATED FLASHING/TRIM/RIDGE

CAP IN “WEATHERED COPPER”

COLOR. ALL FASTENERS TO BE 304

STAINLESS, MINIMUM. VENT VIA

SCREENED BLOCKING AND RIDGE

VENTS.

2. INSTALL ONE ANSI 359.1 D-RING

RIDGE ANCHOR AT CENTER OF RIDGE.

3. ½” CDX PLYWOOD AT WALLS AND

CEILING.

4. PAINT EXTERIOR WITH ACRYLIC

EXTERIOR PAINT, COLOR

BEECHWOOD. PAINT FASCIA AND

DOOR TRIM GREEN GOLD TO MATCH

EXISTING PUMP HOUSE AND PECK

RESIDENCE COLOR SCHEME.

5. INCLUDE TWO SCREENED WALL

VENTS ON SOUTH OR WEST WALL,

SIMILAR TO EXISTING PUMP HOUSE.

FIBER CEMENT

PANEL W/ REVERSE

BATTEN

3-½” MINERAL INSULATION

2 X 4 CONSTRUCTION

2 X 4 PRESSURE TREATED PLATE

SILL PLATE GASKET

BROWN PAINTED

ALUMINUM FLASHING

HOUSE WRAP

2 LAYERS 3-½” MINERAL INSULATION

½” CDX PLYWOOD. PAINT ONE COAT PRIMER THEN 2 TOP COATS

OF WHITE IN SATIN/EGGSHELL

BASIS OF DESIGN: RODDA UNIQUE II ACRYLIC LATEX PAINT, OR

APPROVED EQUAL (INTERIOR & EXTERIOR)

HOLDOWN AT LOCATIONS PER CODE

ANCHOR BOLT MIN. 7” IN CONCRETE

#4 HORIZONTAL

SUB SHEET NO. TITLE OF SHEET

ELECTRICAL SERVICE DETAILS

DRAWING NO.

_149_

193,378

TECH REVIEW:

E1

PECK RESIDENCE WELL SYSTEM PMIS/PKG NO.

338781

DATE:

5/2024

QUINAULT, WA

OLYMPIC NATIONAL PARK

SHEET

_11_ OF _11_

PECK RESIDENCE 200 AMP SERVICE PANEL

NOTES:

1. REPLACE EXISTING 30 AMP BREAKER

INSIDE PECK RESIDENCE 200 AMP

SERVICE PANEL.

2. REPLACE EXISTING DIRECT BURY WIRE

WITH NEW CONDUIT AND

CONDUCTOR WIRE TO FEED NEW 100

AMP SUBPANEL IN NEW PUMP

HOUSE.

PECK RESIDENCE ELECTRICAL SERVICE METER

Slide Number 1
GENERAL NOTES
Slide Number 3
Slide Number 4
Slide Number 5
Slide Number 6
Slide Number 7
Slide Number 8
Slide Number 9
Slide Number 10
Slide Number 11