WHITE SHIELD, INC. Page i Phone: (888) 882-1142 | info@whiteshieldinc.com Hazards Materials Survey - Headquarters Sand Truck Shed-05032023
May 10, 2023
National Park Service, Olympic National Park 600 E Park Avenue Port Angeles, WA 98362
Attention: Jeffrey Dorland
Re: Headquarters Sand Truck Storage Building
Hazardous Materials Survey 600 E Park Ave Port Angeles, WA 98362
Mr. Doryland, White Shield, Inc., per your request, completed a hazardous materials survey on the Headquarters Sand Truck Storage Building. The structure consisted of a Two-story wood framed sand shed that houses the facilities snowplow.
White Shield Environmental Professional and Licensed AHERA Building Inspector and Lead Paint Risk Assessor Kyle Spencer completed the site reconnaissance and sampling on April 26th, 2023. Asbestos was confirmed Not to be present and lead-based paint was confirmed Not to be present. Light fixtures with potentially PCB containing ballasts and mercury containing bulbs and switches were observed and should be removed prior to demolition. The following report documents the work completed, provides analytical findings and recommendations.
We appreciate the opportunity to provide environmental services for you on this project.
Best Regards, Kyle A. Spencer Environmental Scientist
AAI Qualified Environmental Professional Licensed AHERA Building Inspector & Risk Assessor
Headquarters Sand Truck Storage Building Hazardous Materials Survey 600 E Park Ave, Port Angeles, WA 98362 May 10, 2023
WHITE SHIELD, INC. Page ii
Hazards Materials Survey-Headquarters Sand Truck Shed-05032023
TABLE OF CONTENTS
1.0 INTRODUCTION
1.1 Purpose and Scope
1.2 Hazardous Materials
1.2.1 Asbestos
1.2.2 Lead-based Paint (LBP)
1.2.3 Additional Hazardous Materials / Universal Wastes
2.0 HAZARDOUS MATERIALS SURVEY
2.1 Methodology
2.1.1 Visual Inspection
2.1.2 Asbestos
2.1.3 Lead-based Paint – XRF Testing Protocol
2.1.4 Additional Hazardous Materials
3.0 SURVEY RESULTS
3.1 Asbestos
3.2 Lead-Based Paint
3.3 Additional Hazardous Materials
4.0 CONCLUSIONS
4.1 Asbestos
4.2 Lead-based Paint
4.3 Additional Hazardous Materials
5.0 LIMITATIONS
List of Tables:
Table 1: List of Additional Potential Hazardous Materials
List of Appendices:
Appendix A: Project Figures
• Figure 1 – Project Location Map
• Figure 2 – Sample Location Map
Appendix B: Project Tables
• Asbestos Sample Survey Log
• XRF Results
Appendix C: Project Analytical Results
• Laboratory Report - Bulk Asbestos PLM Analysis
• Chain of Custody
Appendix D: Project Documentation
• Sample Collection Requirements
• EPA / AHERA Certification
WHITE SHIELD, INC. Page 1
Hazards Materials Survey-Headquarters Sand Truck Shed-05032023
1.0 INTRODUCTION
On April 26, 2023, White Shield environmental professional Kyle Spencer completed a Hazardous Materials Survey on the Headquarters Sand Truck Storage Building (the Subject Property). The site consisted of a Two-story sand shed. The property overall was in poor condition.
1.1 Purpose and Scope
The purpose of this hazardous materials survey (survey) was to assess, sample and analyze suspect hazardous materials including asbestos-containing materials (ACM), suspect lead-based paint (LBP) and complete a visual inspection to identify mercury-containing equipment, fluorescent lights and ballasts, Polychlorinated Biphenyl (PCB) - containing equipment, chlorofluorocarbons (CFCs) - containing equipment as well as any other potentially hazardous materials that may be present in the building which could present an exposure risk during demolition activities.
1.2 Hazardous Materials
1.2.1 Asbestos
Asbestos refers to a group of six types of naturally occurring minerals. Asbestos minerals are made up of fine, durable fibers and are resistant to heat, fire, and many chemicals. These minerals are commonly found in building materials for fireproofing and added durability. Building materials such as vinyl flooring, drywall/ texturing, and wall insulations/ Thermal System Insulation (TSI) among others. Asbestos was ultimately banned in 1989 from general use due to its lung cancer-causing side-effects and lung related diseases such as asbestoses when it becomes air-born. This ban on use has not prevented new building materials imported from other countries from containing asbestos. It remains a potential hazard even in new construction.
The ACM most likely to release asbestos fibers are those which are in a friable state. Friability describes the condition of asbestos. The definition of friable is any material, when dry, that is capable of being crumbled, pulverized, or reduced to powder by hand pressure (40 CFR 763).
Non-friable sources of asbestos are materials containing a cement or asphalt binder which may become friable and release fibers if the sources are exposed to actions such as abrasion, drilling, cutting, fracturing, or hammering. Non-friable sources of asbestos do not typically pose a significant exposure risk if they remain in good condition and are not disturbed. During renovation or demolition activities, non-friable sources may become friable and thus may pose an exposure risk.
The PLM method is the most commonly used method to analyze building materials for the presence of asbestos. This method utilizes the optical properties of minerals to identify the selected constituent. The use of this method enables identification of the type and the percentage of asbestos in a given sample.
The detection limit of the PLM method for asbestos identification is typically one percent (1%) asbestos.
WHITE SHIELD, INC. Page 2
Hazards Materials Survey- Headquarters Sand Truck Shed-05032023
1.2.2 Lead-based Paint (LBP)
Lead was used as an additive in paint until 1978 when it was banned for use in homes and schools because it caused lead-poisoning and other diseases when there was exposure to the paint and paint dust.
Although production was banned in 1978, existing stocks of paint could still be used up. As a result, lead-based paint may be present in many structures. A lead-based paint inspection is a surface-by-surface investigation to determine the presence of lead-based paint and provide a report explaining the results of the investigation.
In general, there are many other building materials which can contain lead in the average building.
Therefore, when conducting construction or demolition activities which disturb lead in any amount or create the potential for exposure to workers, the employer is required to provide worker protection and conduct exposure assessments. Employers should consult Federal Occupational Safety and Health Administration (OSHA) Regulations at 29 CFR 1926.62, “Lead in Construction” standards for complete requirements prior to construction or demolition activities.
Notification must be given to all other contractors at the work site prior to the start of activities that may create a lead hazard. Characterization and disposal of lead-containing waste materials (LCWMs) must comply with federal, state, and local authorities.
Contractors must maintain current licenses as required by applicable state or local jurisdictions for the removal, transport, disposal of LCWMs, or other regulated lead-based paint activities.
1.2.3 Additional Hazardous Materials / Universal Wastes
Mercury-containing Equipment
The Environmental Protection Agency (EPA) regulates the management of hazardous waste through the Resource Conservation and Recovery Act (RCRA) Subtitle C (40 CFR Part 260 through 270). The RCRA hazardous waste program regulates commercial businesses and government facilities that generate, transport, treat, store, or dispose of hazardous waste. Mercury-containing equipment, fluorescent lights are considered hazardous waste when disposed of by commercial businesses and government facilities and are regulated under RCRA.
Polychlorinated Biphenyl (PCB)-containing Equipment
Historically PCBs were used in electrical equipment and various types of oils. The production and use of PCBs was banned in 1978, however the equipment was not required to be replaced and may remain present in some equipment. Commercial disposal of PCB-containing material such as fluorescent light ballasts, PCB-containing hydraulic oils, and PCB-containing electrical transformer and capacitor oils are regulated under the Toxic Substances Control Act (TSCA) (40 CFR Parts 700 through 799).
Chlorofluorocarbons (CFCs)-containing Equipment
CFCs were and are still used as a refrigerant in heating and cooling systems and as propellants in aerosol containers. In 1978, the use of CFCs such as Freon in aerosol cans was banned. However, it is still used in heating and cooling systems and as refrigerants. The manufacture, use, and disposal of refrigerants and
WHITE SHIELD, INC. Page 3
Hazards Materials Survey- Headquarters Sand Truck Shed-05032023 other CFC- containing materials is regulated under the Clean Air Act regulations (40 CFR Part 82.1 through Part 82.306).
Tritium-containing Signage
Radioactive sources such as tritium-containing signage cannot be disposed of as normal trash. They are regulated by the Untied State Nuclear Regulatory Commission under 10 CFR Part 31.5.
A visual survey was conducted to evaluate the following hazardous materials in terms of presence, number, and configuration. An inventory was compiled for the various materials encountered.
• Mercury light ballasts, fluorescent lights, mercury light switches, and thermostat bulbs.
• Radioactive sources such as tritium-containing signage.
• PCB-containing equipment including elevator hoists, switching equipment and panels, electrical transformers, hydraulic lifts.
• CFC-containing equipment such as HVAC pumps and compressors.
Paints, Solvents & Cleaning Materials
Commercial facilities commonly have various paints and solvents along with cleaning materials used in the operation and maintenance of the facility. These materials can pose a potential threat if not stored and maintained correctly.
WHITE SHIELD, INC. Page 4
Hazards Materials Survey- Headquarters Sand Truck Shed-05032023
2.0 HAZARDOUS MATERIALS SURVEY
2.1 Methodology
Sampling or sample collection is the process of selecting representative samples from the materials/ media being surveyed. This is done through observation and select sample collection by properly trained and certified environmental professionals.
2.1.1 Visual Inspection
White Shield environmental professionals completed an inspection of accessible areas of the Subject Property for the presence of hazardous materials. The purpose of this assessment is for Renovation.
Regardless of the thoroughness of a survey, the possibility exists that some areas containing hazardous materials such as ACM and/or LBP may be present but inaccessible.
2.1.2 Asbestos
Suspect asbestos-containing materials observed at the time of the inspection were sampled and analyzed for asbestos content. Suspect ACMs were sampled according to the guidelines set forth in 40 CFR Part 763, and later analyzed using the Polarized Light Microscopy (PLM) method in accordance with the United States Environmental Protection Agency (EPA) Method for Determination of Asbestos in Bulk Building Materials (EPA 600/R-93/116).
The regulations (40 CFR 763), require that a minimum number of representative samples be collected from each homogeneous area. If asbestos is identified in any of the samples from a homogeneous area, the entire homogeneous area is considered to contain asbestos. Homogeneous areas, as defined by 40 CFR 763 are “an area of surfacing material, thermal system insulation material, or miscellaneous material that is uniform in color and texture.”
The aforementioned testing and analytical constraints can affect the findings and recommendations of this survey. Specifically, no assurance is given regarding the asbestos content of the samples beyond these parameters. Further investigation is not recommended unless the client can determine it is cost-effective to do so.
The survey also established whether any of the substrates sampled could be considered friable and/or significantly damaged and capable of immediate worker exposure.
2.1.3 Lead-based Paint – XRF Testing Protocol
During the course of the property visit, Kyle Spencer performed a review of accessible areas of the buildings on the Subject Property for the presence of suspect LBP. The purpose of this assessment is for renovation. The painted/finished surfaces containing suspect LBP were analyzed and the data was recorded using an x-ray fluorescence instrument (XRF).
The XRF uses a Cadmium 109 (Cd) isotope radioactive source to ‘excite’ the atomic structure of painted surfaces. Once lead (Pb) atoms are “excited”, they emit unique x-ray fluorescence radiation energy. The
WHITE SHIELD, INC. Page 5
Hazards Materials Survey- Headquarters Sand Truck Shed-05032023 radiation detector within the XRF then translates these x-rays into a quantitative measure of lead concentration. If present, the XRF will determine the amount of lead in paint with a 95% confidence level.
The lead concentrations are reported in milligrams per square centimeter (mg/cm2). XRF analysis yields the total lead content of a painted surface, thereby not distinguishing between individual concentrations of painted layers. The XRF was calibrated with a National Institute of Standards and Testing (NIST) calibration surface prior to and post analysis of painted surfaces.
Measurements were taken at locations representative of all painted or varnished surfaces for each different testing combination in the areas inspected. In order to obtain a reading, the XRF analyzer is placed with the face of the instrument flush against the surface to be tested. It is then held in place for the duration of the sample, approximately 4 to 16 source seconds, or until the measurement has reached the acceptable range of accuracy. The sampling time is dependent on the age of the radioactive source inside the XRF.
The building’s orientation was described using the United States Department of Housing and Urban Development’s (HUD’s) recommended guidelines, assigning the letters A, B, C and D to each side of a structure. Side A corresponds to the main entrance of each building. The remaining side identifications are assigned in a clockwise manner. Each tested component location is identified using the building’s assigned letter as a reference point.
The HUD Guidelines for lead-containing paint require a lead hazard abatement activity in cases where lead content is above one half of one percent (0.5%) by weight or equal to or in excess of one milligram per square centimeter (1.0 mg/cm2). This requirement for lead hazard abatement only applies to housing that is administrated or funded by HUD.
Section 1017 of the HUD Guidelines, Residential LBP Reduction Act of 1992, otherwise known as “Title X”, defines a lead-based paint hazard as:
“…any condition that causes exposure to lead that would result in adverse human health effects resulting from lead-contaminated dust, bare lead-contaminated soil, and/or lead-contaminated paint that is deteriorated or present on accessible, friction, or impact surfaces.”
Therefore, under Title X, intact LBP on most walls and ceilings would not be considered a “hazard” However, the paint should be maintained, and its condition monitored to ensure that it does not deteriorate and become a hazard.
2.1.4 Additional Hazardous Materials
A visual inspection was conducted to review and identify current and/or past evidence of hydraulic lifts, mercury-containing equipment, fluorescent lights and ballasts, PCB- and CFC-containing equipment, and any other regulated materials that may be present in the building. Further confirmation involving disassembly and/or testing may be required to confirm the existence of hazardous materials.
WHITE SHIELD, INC. Page 6
Hazards Materials Survey- Headquarters Sand Truck Shed-05032023
3.0 SURVEY RESULTS
3.1 Asbestos
A total of thirteen (13) bulk samples of presumed ACM were collected for analysis. The samples were assigned individual sample numbers, sealed in plastic bags, and transported/shipped under proper chain-of-custody documentation to EMSL Analytical, Inc in Seattle, WA for analysis. EMSL is an American Industrial Hygiene Association (AIHA)-accredited laboratory that participates in the National Volunteer Laboratory Accreditation Program (NVLAP) quality assurance/quality control program.
3.2 Lead-Based Paint
A representative number of interior and exterior painted surfaces/components were tested for LBP on the building(s) at the Subject Property.
A total of 17 XRF readings (including 6 calibration readings) were collected throughout the building at the Subject Property. None of the 12 actual readings contained lead at levels greater than 1.0 milligrams per cementer squared (mg/cm). Please see Appendix B, XRF Results for Lead-Based Paint Inspection Results.
Documentation of the results should be retained as a reference for future renovation/ demolition activities.
3.3 Additional Hazardous Materials
The following hazardous materials were observed at the site:
Table 1: List of Additional Potential Hazardous Materials
Location Type of Material Quantity Container
Interior Fluorescent Light Bulbs & Ballast ~24 Bulbs 12 Fixtures Light Fixture
4.0 CONCLUSIONS
4.1 Asbestos
No Asbestos was found within the structure located at 600 E Park Ave Port Angeles, WA 98362.
During demolition and/or renovation activities, the potential exists for additional suspect ACM to be exposed. Such materials should be sampled and analyzed for asbestos content prior to any renovation and/or demolition activities that could impact these materials.
4.2 Lead-based Paint
No LBP was identified in the interior or exterior of the building.
WHITE SHIELD, INC. Page 7
Hazards Materials Survey- Headquarters Sand Truck Shed-05032023
4.3 Additional Hazardous Materials
The visually identified hazardous materials should be confirmed where necessary, and properly removed and segregated prior to renovation/demolition activities. Proper packaging and disposal should be conducted in compliance with federal, state, and local regulations. Certain restrictions regarding packaging methods (lab packs), transportation (hazmat certification & manifesting) and disposal (landfill regulations) of hazardous materials could apply.
It is possible that other / additional hazardous materials are present within the buildings at locations out of sight and not readily accessible. As with all demolition / remodeling projects, caution should be taken, and the work area inspected prior to any invasive work.
5.0 LIMITATIONS
White Shield subcontracted with EMSL Laboratories to perform the asbestos analysis. No warranties expressed or implied, are made by White Shield or its subcontractor EMSL Laboratories, or their employees as to the use of any information, apparatus, product or process disclosed in this report. Every reasonable effort has been made to assure correctness. If an asbestos contractor or other demolition/construction contractor is employed, such contractor should bring any discrepancies found in this report as it relates to current site conditions or newly discovered site conditions to the immediate attention of White Shield.
This report should not be used solely for asbestos abatement bidding purposes. Any quantities of ACM listed are estimates only and not meant to be used to solicit abatement quotations. These quantities should be confirmed by abatement contractors prior to submitting bids for abatement.
State-of-the-art practices have been employed to perform this hazardous materials survey. The scope of this evaluation was limited to areas that were considered reasonably accessible (i.e., less than 15 feet from the floor), or within range of a visual inspection through reasonable means. No demolition or product research was performed in attempts to reveal material compositions. The services consist of professional opinions and recommendations made in accordance with generally accepted engineering principles/practices. These services are designed to provide an analytical tool to assist the client. WHITE SHIELD and its subcontractor EMSL and their employees/representatives bear no responsibility for the actual condition of the structure or safety of this site pertaining to asbestos and/or lead contamination regardless of the actions taken by the survey team or the client.
Appendix A: Project Figures Figure 1 – Project Location Map Figure 2 – Sample Location Map
Figure 3 – Site Photographs
Appendix B: Project Tables Asbestos Sample Survey Log
XRF Results Log
Appendix C: Project Analytical Results Laboratory Report - Bulk Asbestos PLM Analysis
Chain of Custody
Appendix D: Project Documentation Sample Collection Requirements
EPA / AHERA Certification
List of Appendices
Li st o f
A p p e n d ic e s
Appendix A
Appendix A: Project Figures
Figure 1 – Project Location Map
Figure 2 – Sample Location Map Figure 3 – Site Photographs A p p e n d ix
A P ro je ct F ig u re s
N Not To ScaleNot To Scale
Site Loca�on 600 E Park Ave
Port Angeles, WA 98362
Sample Loca�ons Hazards Materials Survey
600 E Park Ave Port Angeles, WA 98362
Figure No.:
Date:
Completed By:
Reviewed By.:
Version:
Project No.:
May 4th, 2023
K. Spencer
S. Spencer
WSI-001
0506-31-03 Sheet 01 of 03
Explanation Sample Location <1%
Sample Location >1%
Room Numbers
Figure No.:
Date:
Completed By:
Reviewed By.:
Version:
Project No.:
May 4th, 2023
K. Spencer
S. Spencer
WSI-001
0506-31-03 Sheet 02 of 03
Sample Loca�ons Hazards Materials Survey
600 E Park Ave Port Angeles, WA 98362
16 17
S17
S28
S27
S26
S20
S21
S22
S7 S19
S18
S15
S19
S11
S12
S16
S13 S18
S9
S8
S4
S5S6
S10
A
B
C
D
Wall Containing Lead Based Paint
Sample Location >0% <1%
Sealed Vault ~Inaccessible~
S1-FP
S2-FP
S4-DW
S5-DW
S6-DW
S9-DW
S10-DW
S13-I
S11-I
S12-I
S7-DW
S8-DW
S3-FP
A
B
C
D1
Figure No.:
Date:
Completed By:
Reviewed By.:
Version:
Project No.:
May 4th, 2023
K. Spencer
S. Spencer
WSI-001
0506-31-03 Sheet 03 of 03
Sample Loca�ons Hazards Materials Survey
600 E Park Ave Port Angeles, WA 98362
Photograph One: Example of Exterior
Photograph Three: Example of Interior
Photograph Five:Example of Interior
Photograph Two: Example of Exterior
Photograph Four: Example of Interior
Photograph Six: Example of Interior
Appendix B: Project Tables
Asbestos Sample Survey Log XRF Results Log
A p p e n d ix B
P ro je ct
T ab le sAppendix B
Project:
Project Information:
Client: AHERA Inspector:
Contact: Certification No.:
Phone: Date: May 3rd 2023
Site Address: 600 E Park Ave Port Angeles, WA 98362 ECI Project No 0506-31-03
Sample ID Description PLM Analytical Results Discrete Friable Condition Photograph
S1-FP Felt Paper None Detected Yes Fair NA
S2-FP Felt Paper None Detected Yes Fair NA
S3-FP Felt Paper None Detected Yes Fair NA
S4-DW Drywall None Detected Yes Fair NA
S5-Texture Drywall None Detected Yes Fair NA
S5-Tape Drywall None Detected Yes Fair NA
S5-Drywall Drywall None Detected Yes Fair NA
158623
Headquarters Sand Truck Shed
Kyle Spencer
Table 1: Asbestos Survey Log
600 E Park Ave Port Angeles, WA 98362
*ACM= Asbestos Containing Material, L = LayerND = None detected Page 1 of 2
Project:
Project Information:
Client: AHERA Inspector:
Contact: Certification No.:
Phone: Date: May 3rd 2023
Site Address: 600 E Park Ave Port Angeles, WA 98362 ECI Project No 0506-31-03
Sample ID Description PLM Analytical Results Discrete Friable Condition Photograph
158623
Headquarters Sand Truck Shed
Kyle Spencer
Table 1: Asbestos Survey Log
600 E Park Ave Port Angeles, WA 98362
S7-DW Drywall None Detected Yes Fair NA
S8-DW Drywall None Detected Yes Fair NA
S9-DW Drywall None Detected Yes Fair NA
S10-DW Drywall None Detected Yes Fair NA
S11-I-Insulation Insulation None Detected Yes Fair NA
S11-I-Paper Insulation None Detected Yes Fair NA
S12-I Insulation None Detected Yes Fair NA
S13-I Insulation None Detected Yes Fair NA
RED: Sample Reported Exceedin 1% Asbestos, Blue: Sample Reported Greater Than Detection, Less than 1% Asbeston
*ACM= Asbestos Containing Material, L = LayerND = None detected Page 2 of 2
Index Type Units Sequence Component Substrate Side Condition Color Inspector Room Results PbC PbC Error PbL PbL Error PbK PbK Error Depth
Index
1 Paint mg / cm ^2 Final Calibration Calibration Calibration Calibration Calibration Calibration Calibration 2.68 0 0.47 0 0.01 0
2 Paint mg / cm ^2 Final Calibration Calibration Calibration Calibration Calibration Calibration Calibration Null 1 0.1 1 0.1 < LOD 0.75 1.12
3 Paint mg / cm ^2 Final Calibration Calibration Calibration Calibration Calibration Calibration Calibration Positive 1.1 0.1 1.1 0.1 < LOD 0.9 1.17
4 Paint mg / cm ^2 Final Calibration Calibration Calibration Calibration Calibration Calibration Calibration Positive 1.1 0.1 1.1 0.1 < LOD 1.05 1.1
5 Paint mg / cm ^2 Final WALL WOOD A FAIR BEIGE Kyle S. Exteror Negative < LOD 0.03 < LOD 0.03 < LOD 3.48 1
6 Paint mg / cm ^2 Final DOOR METAL A FAIR BEIGE Kyle S. Exteror Negative < LOD 0.03 < LOD 0.03 < LOD 3.69 1
7 Paint mg / cm ^2 Final DOOR TRIM METAL A FAIR YELLOW Kyle S. Exteror Negative < LOD 0.03 < LOD 0.03 < LOD 3.72 1
8 Paint mg / cm ^2 Final WALL WOOD B FAIR BEIGE Kyle S. Exteror Negative < LOD 0.03 < LOD 0.03 < LOD 3.04 1
9 Paint mg / cm ^2 Final WALL WOOD C FAIR BEIGE Kyle S. Exteror Negative < LOD 0.03 < LOD 0.03 < LOD 3.62 1
10 Paint mg / cm ^2 Final WALL WOOD D FAIR BEIGE Kyle S. Exteror Negative < LOD 0.03 < LOD 0.03 < LOD 3.36 1
11 Paint mg / cm ^2 Final WALL DRYWALL D FAIR WHITE Kyle S. 1 Negative < LOD 0.03 < LOD 0.03 < LOD 2.56 1
12 Paint mg / cm ^2 Final WALL DRYWALL C FAIR WHITE Kyle S. 1 Negative < LOD 0.03 < LOD 0.03 < LOD 2.34 1
13 Paint mg / cm ^2 Final WALL DRYWALL B FAIR WHITE Kyle S. 1 Negative < LOD 0.03 < LOD 0.03 < LOD 2.52 1
14 Paint mg / cm ^2 Final WALL DRYWALL B FAIR BLUE Kyle S. 1 Negative < LOD 0.03 < LOD 0.03 < LOD 2.67 1
15 Paint mg / cm ^2 Final CEILING DRYWALL B FAIR BLUE Kyle S. 1 Negative < LOD 0.03 < LOD 0.03 < LOD 2.62 1
16 Paint mg / cm ^2 Final Calibration Calibration Calibration Calibration Calibration Calibration Calibration Positive 1 0.1 1 0.1 < LOD 0.6 1.11
17 Paint mg / cm ^2 Final Calibration Calibration Calibration Calibration Calibration Calibration Calibration Positive 1.1 0.1 1.1 0.1 1 0.4 1.03
Old Agency Courts Building
Calibration
Calibration
Table 2: XRF Analysis Results 600 E Park Ave
Port Angeles, WA 98362 May 3, 2023
Inspected by: Kyle A. Spencer - Certified Lead
Inspector No. 6713 XRF: Niton XLp 300A - Certification 26518
Explanation Red Highlight - Lead Based Paint Blue Highlight - Lead Cantaing Paint Gray Highlight - Reading was Interupted
Appendix C: Project Analytical Results Laboratory Report - Bulk Asbestos PLM Analysis
Chain of Custody
A p p e n d ix C
P ro je ct
A n al yt ic al
R es u lt sAppendix C
EMSL Analytical, Inc.
5009 Pacific Highway East, Unit 19 Fife, WA 98424
Tel/Fax: (253) 319-5658 / http://www.emsl.com / tacomalab@EMSL.com
742300168EMSL Order:
Customer ID: ECIE42
Customer PO:
Project ID:
Attention: Phone:Kyle Spencer (253) 921-7059
Fax:ECI Environmental
Received Date:PO Box 153 04/28/2023 12:00 PM
Analysis Date:Fox Island, WA 98333 05/02/2023
Collected Date: 04/26/2023
Project: Headquarters
Test Report: Asbestos Analysis of Bulk Materials via AHERA Method 40CFR 763 Subpart E
Appendix E supplemented with EPA 600/R-93/116 using Polarized Light Microscopy
Sample Description Appearance % Fibrous % Non-Fibrous
Non-Asbestos Asbestos
% Type
S1-FP
742300168-0001
None DetectedNon-fibrous (Other)5%Cellulose95%Black
Fibrous
Homogeneous
Felt Paper
S2-FP
742300168-0002
None DetectedNon-fibrous (Other)5%Cellulose95%Black
Fibrous
Homogeneous
Felt Paper
S3-FP
742300168-0003
None DetectedNon-fibrous (Other)5%Cellulose95%Black
Fibrous
Homogeneous
Felt Paper
S4-DW
742300168-0004
None DetectedGypsum
Non-fibrous (Other)
65%
5%
Cellulose30%Brown/White
Fibrous
Heterogeneous
Drywall
S5-Texture
742300168-0005
None DetectedNon-fibrous (Other)100%White
Non-Fibrous
Homogeneous
Drywall
S5-Tape
742300168-0005A
None DetectedNon-fibrous (Other)5%Glass95%White
Fibrous
Homogeneous
Drywall
S5-Drywall
742300168-0005B
None DetectedGypsum
Non-fibrous (Other)
55%
5%
Cellulose40%Brown/White
Fibrous
Heterogeneous
Drywall
S7-DW
742300168-0006
None DetectedGypsum
Non-fibrous (Other)
65%
5%
Cellulose30%Brown/White
Fibrous
Heterogeneous
Drywall
S8-DW
742300168-0007
None DetectedGypsum
Non-fibrous (Other)
65%
5%
Cellulose30%Brown/White
Fibrous
Heterogeneous
Drywall
S9-DW
742300168-0008
None DetectedGypsum
Non-fibrous (Other)
65%
5%
Cellulose30%Brown/White
Fibrous
Heterogeneous
Drywall
S10-DW
742300168-0009
None DetectedGypsum
Non-fibrous (Other)
65%
3%
Cellulose
Glass
30%
2%
Brown/White
Fibrous
Heterogeneous
Drywall
S11-I-Insulation
742300168-0010
None DetectedNon-fibrous (Other)5%Glass95%Pink
Fibrous
Homogeneous
Insulation
S11-I-Paper
742300168-0010A
None DetectedNon-fibrous (Other)5%Cellulose95%Brown
Fibrous
Homogeneous
Insulation
S12-I
742300168-0011
None DetectedNon-fibrous (Other)5%Glass95%Pink
Fibrous
Homogeneous
Insulation
S13-I
742300168-0012
None DetectedNon-fibrous (Other)5%Glass95%Pink
Fibrous
Homogeneous
Insulation
Initial report from: 05/02/2023 19:07:50
Page 1 of 2ASB_PLM_0008_0001 - 1.78 Printed: 5/2/2023 4:07 PM
EMSL Analytical, Inc.
5009 Pacific Highway East, Unit 19 Fife, WA 98424
Tel/Fax: (253) 319-5658 / http://www.emsl.com / tacomalab@EMSL.com
742300168EMSL Order:
Customer ID: ECIE42
Customer PO:
Project ID:
Analyst(s)
Claire Byers (15)
EMSL maintains liability limited to cost of analysis . Interpretation and use of test results are the responsibility of the client. This report relates only to the samples reported above, and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations . The report reflects the samples as received.
Results are generated from the field sampling data (sampling volumes and areas, locations, etc.) provided by the client on the Chain of Custody. Samples are within quality control criteria and met method specifications unless otherwise noted. The above analyses were performed in general compliance with Appendix E to Subpart E of 40 CFR (previously EPA 600/M4-82-020 “Interim Method”) but augmented with procedures outlined in the 1993 (”final”) version of the method. This report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST or any agency of the federal government. Non- friable organically bound materials present a problem matrix and therefore EMSL recommends gravimetric reduction prior to analysis . Unless requested by the client, building materials manufactured with multiple layers (i.e. linoleum, wallboard, etc.) are reported as a single sample. Estimation of uncertainty is available on request.
Samples analyzed by EMSL Analytical, Inc. Fife, WA NVLAP Lab Code 600324-0, WA C1075
Initial report from: 05/02/2023 19:07:50
Page 2 of 2ASB_PLM_0008_0001 - 1.78 Printed: 5/2/2023 4:07 PM
OrderID: 742300168
Appendix D: Project Documentation Sample Collection Requirements
EPA / AHERA Certification
Appendix D
A p p e n d ix D
P ro je ct
D o cu m en ta ti o n
State of Oregon
Oregon Health Authority
Kyle A. Spencer is certified by the Oregon Health Authority to conduct Lead-Based Paint Activities
Risk Assessor
Certification Number: 2693--Indv--R Issuance Date: 1/22/2021 Expiration Date: 1/22/2024
Building Inspector
Kyle Spencer This certificate is awarded to:
In recognition of satisfactory completion of the EPA-approved annual asbestos refresher training provided in accordance with the Model Accreditation Plan (MAP) (40 CFR Part 763, Subpart E, Appendix C) and AHERA of the Toxic Substances Control Act (TSCA) entitled:
Course Completion:
Examination Date:
Expiration Date:
Course Hours:
59666237 R22-1035-AI-O
October 5, 2022
October 5, 2023 4.0
Danaya N. WilsonDanaya N. Wilson Aaron HixAaron Hix
Credential License ID: CHC Training Certificate No.
October 5, 2022
InstructorCEO & Training Program Manager
Certificate of Achievement www.chctraining.com 303.412.6360
855.60.CERTIFY
CHC Training Environmental Compliance Certification Experts
1775 W. 55th Avenue Denver, Colorado 80221
United States of America
Verify this Certificate Renew this Certificate
| 1.0 introduction |
| 1.1 Purpose and Scope |
| 1.2 Hazardous Materials |
| 1.2.1 Asbestos |
| 1.2.2 Lead-based Paint (LBP) |
| 1.2.3 Additional Hazardous Materials / Universal Wastes |
| 2.0 HAZARDOUS MATERIALS SURVEY |
| 2.1 Methodology |
| 2.1.1 Visual Inspection |
| 2.1.2 Asbestos |
| 2.1.3 Lead-based Paint – XRF Testing Protocol |
| 2.1.4 Additional Hazardous Materials |
| 3.0 SURVEY RESULTS |
| 3.1 Asbestos |
| 3.2 Lead-Based Paint |
| 3.3 Additional Hazardous Materials |
| 4.0 CONCLUSIONS |
| 4.1 Asbestos |
| 4.2 Lead-based Paint |
| 4.3 Additional Hazardous Materials |
| 5.0 LIMITATIONS |
| Hazards Materials Survey-Headquarters Sand Truck Shed.pdf |
| 1: List of Appen |
| 2: Appen A |
| 3: Appen B |
| 4: Appen C |
| 5: Appen D |
| Figures.pdf |
| Page 1 |
| Page 2 |
| Page 3 |
| Page 4 |
| Page 5 |
| Appendix A Figures1.pdf |
| Page 1 |
| Page 2 |
| Page 3 |
| Page 4 |
| Page 5 |
| Appendix A Figures1.pdf |
| Page 1 |
| Page 2 |
| Page 3 |
| Page 4 |
| Page 5 |
| Appendix A Figures1.pdf |
| Page 1 |
| Page 2 |
| Page 3 |
| Page 4 |
| Page 5 |
| Appendix A Figures.pdf |
| Page 1 |
| Page 2 |
| Page 3 |
| Page 4 |
| Page 5 |
| Page 6 |
| Appendix A Figures.pdf |
| Page 1 |
| Page 2 |
| Page 3 |
| Page 4 |
| Page 5 |
| Page 6 |
| Page 7 |
| Appendix A Figures.pdf |
| Page 1 |
| Page 2 |
| Page 3 |
| Page 4 |
| Page 5 |
| Page 6 |
| Page 7 |
| Appendix A Figures.pdf |
| Page 1 |
| Page 2 |
| Page 3 |
File details come from the government source that posted it. Updated .