Attach_2_-_Drawings_HVAC_and_Roof.pdf
PDF 8 MB Posted
- Attached to
- Replace Alan Bible Visitor Center HVAC and Roof
- Solicitation number
- 140P8124B0002
About this file
This document contains construction drawings related to the replacement of the HVAC system and roof at the Alan Bible Visitor Center at Lake Mead National Recreation Area in Boulder City, Nevada. The drawings include a roof demolition plan, roof plan, and various roof details. The key scope of work includes:
- Replace rooftop HVAC units AC-2, AC-3, and AC-4
- Replace exhaust fans EF-1 and RF-2
- Replace split system fan coil/condensing units FC/CU-4, 5, 6, and 7
- Replace ductwork and diffusers serving office and basement spaces
- Reconfigure lobby supply and return ductwork
- Provide supply air to restrooms from AC-2
- Remove and replace the entire roof system including membrane, insulation, and flashing
The drawings also include structural details for patching existing roof openings and framing new openings. This appears to be part of a larger federal solicitation to replace the HVAC and roof at the Alan Bible Visitor Center.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SHEET INDEX
04/26/2023 04/26/202304/28/2023
ENGINEER RESPONSIBLE FOR
MECHANICAL DRAWINGS:
ENGINEER RESPONSIBLE FOR
ELECTRICAL DRAWINGS:
ENGINEER RESPONSIBLE FOR
STRUCTURAL DRAWINGS:
SHEET INDEX
PAGE NO. SHEET NO. SHEET TITLE
ARCHITECTURAL
25 A0.0 LEGEND & ABBREVIATIONS
26 A0.1 GENERAL NOTES
27 A1.0 ROOF DEMOLITION PLAN
28 A1.1 ROOF PLAN
29 A5.0 ROOF DETAILS
30 A5.1 ROOF DETAILS
31 A5.2 ROOF DETAILS
32 A5.3 ROOF DETAILS
PMIS#228968 (ABVC HVAC)
PMIS#334958 (ABVC ROOF)
REPLACE ABVC HVAC AND ROOF
AutoCAD SHX Text
INDIAN
AutoCAD SHX Text
CALIFORNIA
AutoCAD SHX Text
NEVADA
AutoCAD SHX Text
AutoCAD SHX Text
COVE
AutoCAD SHX Text
SEARCHLIGHT
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
COTTONWOOD
AutoCAD SHX Text
NELSON
AutoCAD SHX Text
AutoCAD SHX Text
NEVADA
AutoCAD SHX Text
LANDING
AutoCAD SHX Text
BULLHEAD CITY
AutoCAD SHX Text
LAUGHLIN
AutoCAD SHX Text
DAVIS
AutoCAD SHX Text
DAM
AutoCAD SHX Text
AutoCAD SHX Text
KATHERINE
AutoCAD SHX Text
MOHAVE
AutoCAD SHX Text
LAKE
AutoCAD SHX Text
AutoCAD SHX Text
CANYON
AutoCAD SHX Text
ELDORADO
AutoCAD SHX Text
ARIZONA
AutoCAD SHX Text
SPRINGS
AutoCAD SHX Text
DOLAN
AutoCAD SHX Text
HUALAPAI
AutoCAD SHX Text
TO ST. GEORGE, UTAH
AutoCAD SHX Text
PARK
AutoCAD SHX Text
DAM
AutoCAD SHX Text
HOOVER
AutoCAD SHX Text
FIRE STATE
AutoCAD SHX Text
VALLEY OF
AutoCAD SHX Text
BLUE POINT SPRING
AutoCAD SHX Text
ROGERS SPRING
AutoCAD SHX Text
BEACH
AutoCAD SHX Text
BOULDER
AutoCAD SHX Text
AutoCAD SHX Text
TO
AutoCAD SHX Text
CALIFORNIA
AutoCAD SHX Text
LAS VEGAS
AutoCAD SHX Text
ANGELES,
AutoCAD SHX Text
LOS
AutoCAD SHX Text
TO
AutoCAD SHX Text
AutoCAD SHX Text
NEVADA
AutoCAD SHX Text
RENO,
AutoCAD SHX Text
HENDERSON
AutoCAD SHX Text
BOULDER CITY
AutoCAD SHX Text
AutoCAD SHX Text
HQ.
AutoCAD SHX Text V.C.
AutoCAD SHX Text
LAS VEGAS
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
WASH
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
LAKE
AutoCAD SHX Text
BAY
AutoCAD SHX Text
CALLVILLE
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
ECHO
AutoCAD SHX Text
BAR
AutoCAD SHX Text
BEACH
AutoCAD SHX Text
WILLOW
AutoCAD SHX Text
GREGGS
AutoCAD SHX Text
HIDEOUT
AutoCAD SHX Text
MEAD
AutoCAD SHX Text
LANDING
AutoCAD SHX Text
BONELLI
AutoCAD SHX Text
REDSTONE
AutoCAD SHX Text
AutoCAD SHX Text
TEMPLE
AutoCAD SHX Text
BAY
AutoCAD SHX Text
COVE
AutoCAD SHX Text
MEADVIEW
AutoCAD SHX Text
GRAND
AutoCAD SHX Text
FERRY
AutoCAD SHX Text
PEARCE
AutoCAD SHX Text
SOUTH
AutoCAD SHX Text
OVERTON
AutoCAD SHX Text
AutoCAD SHX Text
OVERTON
AutoCAD SHX Text
BEACH
AutoCAD SHX Text
ARIZONA
AutoCAD SHX Text
NEVADA
AutoCAD SHX Text
COLORADO
AutoCAD SHX Text
CREEK
AutoCAD SHX Text
PARK
AutoCAD SHX Text
RESERVATION
AutoCAD SHX Text
DIAMOND
AutoCAD SHX Text
RIVER
AutoCAD SHX Text
TO
AutoCAD SHX Text
WHITMORE
AutoCAD SHX Text
CANYON
AutoCAD SHX Text
NATIONAL
AutoCAD SHX Text
CANYON
AutoCAD SHX Text
PLATEAU
AutoCAD SHX Text
SHIVWITS
AutoCAD SHX Text
AutoCAD SHX Text
CITY
AutoCAD SHX Text
BULLHEAD
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
NATIONAL
AutoCAD SHX Text
NATIONAL
AutoCAD SHX Text
PARK
AutoCAD SHX Text
AutoCAD SHX Text
PRESCOTT
AutoCAD SHX Text
CITY
AutoCAD SHX Text
HAVASU
AutoCAD SHX Text
LAKE
AutoCAD SHX Text
AutoCAD SHX Text
KINGMAN
AutoCAD SHX Text
RECREATION
AutoCAD SHX Text
AutoCAD SHX Text
AREA
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
FLAGSTAFF
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
WINSLOW
AutoCAD SHX Text
CANYON
AutoCAD SHX Text
GRAND
AutoCAD SHX Text
PAGE
AutoCAD SHX Text
AutoCAD SHX Text
CANYON
AutoCAD SHX Text
UTAH
AutoCAD SHX Text
NEVADA
AutoCAD SHX Text
AutoCAD SHX Text
LAKE MEAD
AutoCAD SHX Text
AutoCAD SHX Text
ARIZONA
AutoCAD SHX Text
UTAH
AutoCAD SHX Text
LAKE
AutoCAD SHX Text
JACOB
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text N.R.A.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
GLEN
AutoCAD SHX Text
AutoCAD SHX Text
LAKE MEAD
AutoCAD SHX Text
NATIONAL RECREATION AREA
AutoCAD SHX Text
PARK HEADQUARTERS
AutoCAD SHX Text
PAVED ROAD
AutoCAD SHX Text
HQ.
AutoCAD SHX Text
STATE LINE
AutoCAD SHX Text
COUNTY LINE
AutoCAD SHX Text
PARK BOUNDARY
AutoCAD SHX Text
LEGEND
AutoCAD SHX Text
LOCATION OF SITE
AutoCAD SHX Text
NEVADA
AutoCAD SHX Text
LOCATION WITHIN STATE
AutoCAD SHX Text
STATE
AutoCAD SHX Text
NATIONAL PARK SERVICE
AutoCAD SHX Text
DENVER SERVICE CENTER
AutoCAD SHX Text
REGION
AutoCAD SHX Text
COUNTY
AutoCAD SHX Text
DEPARTMENT OF THE INTERIOR
AutoCAD SHX Text
NAME OF PARK
AutoCAD SHX Text
UNITED STATES
AutoCAD SHX Text
LOCATION WITHIN PARK
AutoCAD SHX Text
TITLE OF PROJECT
AutoCAD SHX Text
PKG.
AutoCAD SHX Text
OF
AutoCAD SHX Text
NO.
AutoCAD SHX Text
SHEET
AutoCAD SHX Text
DRAWING NO.
AutoCAD SHX Text 22/01/2019 11:16 JENNIFER CHEEK G:\CLIENTS\NPS\LAKE\228968\DRAWINGS\GEN\1 COVER SHEET.DWG
AutoCAD SHX Text
PMIS#228968
AutoCAD SHX Text
CONSTRUCTION DRAWINGS
AutoCAD SHX Text
REPLACE ALAN BIBLE VISITOR CENTER HVAC
AutoCAD SHX Text
ALAN BIBLE VISITOR CENTER
AutoCAD SHX Text
LAKE MEAD
AutoCAD SHX Text
PACIFIC WEST
AutoCAD SHX Text
CLARK
AutoCAD SHX Text
NEVADA
AutoCAD SHX Text
AutoCAD SHX Text 25005A
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
PROJECT LOCATION
AutoCAD SHX Text
PAGE NO.
AutoCAD SHX Text
SHEET TITLE
AutoCAD SHX Text
SHEET NO.
AutoCAD SHX Text
GENERAL
AutoCAD SHX Text
AutoCAD SHX Text
COVER SHEET
AutoCAD SHX Text G0.0
AutoCAD SHX Text
MECHANICAL
AutoCAD SHX Text
AutoCAD SHX Text
MECHANICAL GENERAL NOTES AND LEGEND
AutoCAD SHX Text M0.0
AutoCAD SHX Text
AutoCAD SHX Text
MECHANICAL BASEMENT DEMOLITION PLAN
AutoCAD SHX Text M1.0
AutoCAD SHX Text
AutoCAD SHX Text
MECHANICAL FIRST FLOOR DEMOLITION PLAN
AutoCAD SHX Text M1.1
AutoCAD SHX Text
AutoCAD SHX Text
MECHANICAL ROOF DEMOLITION PLAN
AutoCAD SHX Text M1.2
AutoCAD SHX Text
AutoCAD SHX Text
MECHANICAL BASEMENT FLOOR PLAN
AutoCAD SHX Text M2.0
AutoCAD SHX Text
AutoCAD SHX Text
MECHANICAL FIRST FLOOR PLAN
AutoCAD SHX Text M2.1
AutoCAD SHX Text
AutoCAD SHX Text
MECHANICAL ROOF PLAN
AutoCAD SHX Text M2.2
AutoCAD SHX Text
AutoCAD SHX Text
MECHANICAL DETAILS
AutoCAD SHX Text M5.0
AutoCAD SHX Text
AutoCAD SHX Text
MECHANICAL DETAILS
AutoCAD SHX Text M5.1
AutoCAD SHX Text
AutoCAD SHX Text
MECHANICAL SCHEDULES
AutoCAD SHX Text M6.0
AutoCAD SHX Text
AutoCAD SHX Text
MECHANICAL CONTROLS
AutoCAD SHX Text M7.0
AutoCAD SHX Text
AutoCAD SHX Text
MECHANICAL CONTROLS
AutoCAD SHX Text M7.1
AutoCAD SHX Text
ELECTRICAL
AutoCAD SHX Text
AutoCAD SHX Text
ELECTRICAL COVER SHEET
AutoCAD SHX Text E0.0
AutoCAD SHX Text
AutoCAD SHX Text
BASEMENT ELECTRICAL DEMOLITION PLAN
AutoCAD SHX Text E1.0
AutoCAD SHX Text
AutoCAD SHX Text
FIRST FLOOR ELECTRICAL DEMOLITION PLAN
AutoCAD SHX Text E1.1
AutoCAD SHX Text
AutoCAD SHX Text
ROOF ELECTRICAL DEMOLITION PLAN
AutoCAD SHX Text E1.2
AutoCAD SHX Text
AutoCAD SHX Text
BASEMENT ELECTRICAL PLAN
AutoCAD SHX Text E2.0
AutoCAD SHX Text
AutoCAD SHX Text
FIRST FLOOR ELECTRICAL PLAN
AutoCAD SHX Text E2.1
AutoCAD SHX Text
AutoCAD SHX Text
ROOF ELECTRICAL PLAN
AutoCAD SHX Text E2.2
AutoCAD SHX Text
AutoCAD SHX Text
ELECTRICAL SINGLE LINE DIAGRAM
AutoCAD SHX Text E3.0
AutoCAD SHX Text
AutoCAD SHX Text
SCHEDULES
AutoCAD SHX Text E3.1
AutoCAD SHX Text
STRUCTURAL
AutoCAD SHX Text
AutoCAD SHX Text
STRUCTURAL NOTES
AutoCAD SHX Text S0.0
AutoCAD SHX Text
AutoCAD SHX Text
STRUCTURAL DETAILS
AutoCAD SHX Text S1.0
FIN
AL D
RAFT
PIPE SIZE
CONDENSATE DRAIN
REFRIGERANT LIQUID
REFRIGERANT SUCTION
REFRIGERANT VENT
PIPING SYSTEMS (HVAC)
2 1/2"
CWR
REF(L)
REF(S)
REF(V)
FCU
NEW WORK
EXISTING (E)
DEMO EXISTING (X)
KEY NOTE
EQUIPMENT IDENTIFICATION
WORK DEFINITION
UP
DN
BDD
M
UC
T
AIR FLOW ARROW
RECTANGULAR DUCT AND SIZE*
ROUND DUCT AND SIZE*
FLAT OVAL DUCT AND SIZE*
EXTERIOR DUCT TREATMENT*
RECTANGULAR DUCT WITH ACOUSTIC LINING*
DUCT SECTION, SUPPLY AIR. APPLIES TO RECT., ROUND AND OVAL
DUCT SECTION, OUTSIDE AIR. APPLIES TO RECT., ROUND AND OVAL
DUCT SECTION, RETURN AIR. APPLIES TO RECT., ROUND AND OVAL
DUCT SECTION, EXHAUST AIR. APPLIES TO RECT., ROUND AND OVAL
FLEXIBLE DUCT
ELBOW TURN, SUPPLY DOWN. APPLIES TO RECT., ROUND AND OVAL
DUCT SECTION, OUTSIDE AIR. APPLIES TO RECT., ROUND AND OVAL
DUCT SECTION, OUTSIDE AIR. APPLIES TO RECT., ROUND AND OVAL
DUCT SECTION, OUTSIDE AIR. APPLIES TO RECT., ROUND AND OVAL
CHANGE IN DUCT ELEVATION RISING IN DIRECTION INDICATED
CHANGE IN DUCT ELEVATION DROPPING IN DIRECTION INDICATED
END CAP
ELBOW, RECTANGULAR, SMOOTH RADIUS WITH SPLITTER VANES
(0.25 R/W DEFAULT)
ELBOW, RECTANGULAR, SMOOTH RADIUS WITHOUT VANES
(1.5 R/W DEFAULT)
ELBOW, ROUND, SMOOTH RADIUS
(1.5 R/W DEFAULT)
MITERED ELBOW, RECTANGULAR, WITH TURNING VANES
RECTANGULAR TO ROUND TRANSITION
DUCT ACCESS DOOR(TOP,SIDE,BOTTOM)
FLEXIBLE CONNECTION
BACKDRAFT DAMPER
MANUAL DAMPER
MOTORIZED DAMPER
FIRE DAMPER
SMOKE DAMPER
SMOKE AND FIRE DAMPER
DUCT SILENCER
CONTROL DEVICE (REFER TO CONTROLS LEGEND)
AIR FLOW MEASURING STATION (REFER TO CONTROLS LEGEND)
QUANTITY
TYPE
AIR OUTLET OR INLET TAG (REFER TO SCHEDULE)SIZE (IN.)
VOLUME (CFM)
RECTANGULAR DIFFUSER, SUPPLY.
OPTIONAL ARROWS SHOW THE FLOW DIRECTION.
RECTANGULAR REGISTER OR GRILLE RETURN
RECTANGULAR REGISTER OR GRILLE, EXHAUST
ROUND DIFFUSER, SUPPLY
LINEAR DIFFUSER
SIDEWALL REGISTER OR GRILLE, SUPPLY
SIDEWALL GRILLE, RETURN OR EXHAUST
UNDERCUT DOOR
DOOR GRILLE OR LOUVER
TRANSFER GRILLE OR LOUVER
COIL (REFER TO CONTROLS LEGEND)
QUANTITY
TYPE
LENGTH (FT.)
RADIATION HEATING TAG (REFER TO SCHEDULE)
CAPACITY (MBH)
18"x12" 18"x12"
18"x12" 18"x12" 18"x12"
18"x12"ø 18"x12"ø 18"ø 18"ø
30"x12"
*NOTE: ALL DUCT SIZES ARE INTERIOR, FREE DIMENSIONS
ALWAYS WIDTH (HORIZONTAL DIM.) x HEIGHT (VERTICAL DIM.)
VENTILATION (HVAC)
PROJECT
NORTH
TRUE
NORTH
1. CONTRACTOR SHALL VISIT SITE TO REVIEW SCOPE OF WORK PRIOR
TO SUBMISSION OF BID
2. THE MECHANICAL PLANS ARE DIAGRAMMATIC IN NATURE AND ARE
BASED ON ONE MANUFACTURER'S EQUIPMENT. THEY ARE NOT
INTENDED TO SHOW EVERY ITEM IN ITS EXACT LOCATION, THE
EXACT DIMENSIONS, OR ALL OF THE DETAILS FOR THE EQUIPMENT.
THE HVAC CONTRACTOR SHALL VERIFY THE ACTUAL DIMENSIONS
OF THE EQUIPMENT AND ENSURE THAT IT WILL FIT IN THE AVAILABLE
SPACE AND THAT PROPER MAINTENANCE CLEARANCES ARE
ACHIEVED.
3. MECHANICAL CONTRACTOR RESPONSIBLE FOR INSTALLATION OF
COMPLETED AND OPERATIONAL SYSTEMS WITH DUE RESPECT TO
ALL APPLICABLE CODES AND AUTHORITIES HAVING JURISDICTION.
4. IT IS THE CONTRACTOR RESPONSIBILITY TO FIELD VERIFY ALL
CONNECTION POINTS PRIOR TO INSTALL. NOT ALL CONNECTION
SIZES ARE SHOWN, BUT THOSE THAT ARE APPROXIMATE AND TAKEN
FROM EXISTING AS-BUILTS AND FIELD OBSERVATIONS.
5. COORDINATE PIPE ROUTING WITH DUCTWORK, SPRINKLER PIPING
AND ELECTRICAL POWER/LIGHTING CIRCUITING AND STRUCTURAL
MEMBERS PRIOR TO INSTALLATION
6. ALL WORK SHALL COMPLY WITH APPLICABLE CODES AND
ORDINANCES INCLUDING NEVADA STATE RULES AND REGULATIONS.
7. CONTRACTORS TO VERIFY ALL GRADES, DIMENSIONS AND EXISTING
CONDITIONS AT THE SITE BEFORE PROCEEDING WITH WORK.
NOTIFY PRIME CONSULTANT OF ANY DISCREPANCIES BETWEEN
DRAWINGS AND ACTUAL CONDITIONS BEFORE INSTALLATION.
8. ALL MATERIALS AND INSTALLATION SHALL COMPLY WITH THE
NATIONAL PARK SERVICE CONSTRUCTION SPECIFICATIONS.
9. COORDINATE INSTALLATION OF PIPING AND DUCTWORK WITH
ELECTRICAL CONTRACTOR AND OTHER TRADES.
10. CONTRACTOR IS RESPONSIBLE FOR ALL PERMITS NEEDED TO
CONSTRUCT WORK IN THE CONSTRUCTION DOCUMENTS AND
ACCOMPANYING SPECIFICATIONS
11. IF THERE IS A CONFLICT BETWEEN THE CONSTRUCTION
DOCUMENTS AND SPECIFICATIONS, THE MOST STRINGENT WILL
APPLY.
12. ALL EQUIPMENT SHALL BE INSTALLED IN STRICT ACCORDANCE WITH
THE EQUIPMENT MANUFACTURERS. CONTRACTOR TO PROVIDE ALL
FITTINGS,TRANSITIONS, DAMPERS, VALVES, AND OTHER DEVICES
REQUIRED FOR A COMPLETE WORKABLE INSTALLATION.
13. PENETRATIONS OF DUCTS, PIPES, CONDUITS,ETC IN WALLS
REQUIRING PROTECTED OPENINGS SHALL BE FIRE STOPPED, FIRE
STOP MATERIAL, SHALL BE A UL-LISTED ASSEMBLY APPROPRIATE
FOR FIRE OR SMOKE PENETRATIONS AS APPLICABLE AND AS
APPROVED BY THE FIRE MARSHAL.
14. THE HVAC CONTRACTOR SHALL PROVIDE AND INSTALL APPROVED
FIRE DAMPERS AND ACCESS PANELS IN ALL DUCTWORK THAT
PENETRATES A HORIZONTAL OR VERTICAL FIRE PARTITION, OR AS
OTHERWISE SHOWN ON THE DRAWINGS.
15. ALL BRANCH DUCTS HAVE VOLUME DAMPERS.
16. WHERE FLOW EXCEEDS 150 CFM, THE CONTRACTOR SHALL USE
SMOOTH RADIUS ELBOWS OR TURNING VANES.
17. ALL DUCT JOINTS SHALL BE SEALED IN ACCORDANCE WITH SMACNA
STANDARDS AND ACCEPTED GOOD PRACTICE.
18. ALL DUCT DIMENSIONS ARE NET INSIDE VALUES. DIMENSIONS MAY
BE CHANGED PROVIDED THAT THE NET FREE AREA IS MAINTAINED.
19. ALL CONCEALED DUCTWORK SHALL BE INSULATED WITH 1"
FIBERGLASS INSULATING BLANKET WITH ALUMINUM FOIL FACING.
20. ALL DUCTWORK SHALL BE CONSTRUCTED, ERECTED AND TESTED IN
ACCORDANCE WITH THE LOCAL REGULATIONS AND PROCEDURES
DETAILED IN THE APPLICABLE STANDARDS ADOPTED BY THE SHEET
METAL AND AIR CONDITIONING CONTRACTORS NATIONAL
ASSOCIATION. (SMACNA).
21. ALL PIPE SHALL BE SUPPORTED FROM THE BUILDING STRUCTURE IN
A NEAT AND WORKMANLIKE MANNER. THE USE OF WIRE OR METAL
STRAPS TO SUPPORT PIPES WILL NOT BE PERMITTED. SPACING OF
PIPE SUPPORTS SHALL NOT EXCEED 8 FEET FOR ALL PIPING.
PLASTIC PIPING SHALL BE SUPPORTED EVERY 4 FEET.
22. THE HVAC SYSTEMS SHALL BE TESTED AND BALANCED BY AN
INDEPENDENT AGENCY, UNDER THE SUPERVISION OF A LICENSED
PROFESSIONAL ENGINEER. A SEALED TYPE WRITTEN REPORT SHALL
BE SUBMITTED TO THE ARCHITECT/ENGINEER.
23. ALL EQUIPMENT TO BE INSTALLED ON MIN 6" CURBS.
24. ALL EQUIPMENT, DUCTS PIPING, AND OTHER DEVICES AND
MATERIALS INSTALLED OUTSIDE OF THE BUILDING OR OTHERWISE
EXPOSED TO THE WEATHER SHALL BE COMPLETELY
WEATHERPROOFED.
1. THE CONTRACTOR SHALL VISIT THE SITE AND BE THOROUGHLY
FAMILIARIZED WITH THE EXISTING CONDITIONS PRIOR TO BIDDING.
INFORMATION GIVEN ON THESE DRAWINGS ABOUT THE EXISTING
INSTALLATION HAS BEEN OBTAINED FROM THE EXISTING AS-BUILT
DRAWINGS BUT CANNOT BE GUARANTEED ACCURATE IN ALL
RESPECTS. VERIFY ALL SUCH INFORMATION BEFORE PROCEEDING
WITH ANY NEW WORK THAT MAY BE AFFECTED. INCLUDE AS PART
OF THE CONTRACT ALL WORK REQUIRED TO PRODUCE THE
INDICATED RESULT.
2. UPON SUBMITTING A BID THE CONTRACTOR SHALL BE HELD TO
HAVE MADE SUCH EXAMINATIONS OF THE SITE AND NO ALLOWANCE
FOR EXTRAS WILL BE ALLOWED FOR ANY ERROR OR OVERSIGHT
RESULTING FORM THE CONTRACTOR'S UNFAMILIARITY WITH THE
SITE OR EXISTING CONDITIONS.
3. CONTRACTOR SHALL NOT SCALE DRAWINGS. DIMENSIONS MISSING
FROM PLANS OR NEEDED FOR EXECUTION OF WORK SHALL BE
CLARIFIED OR PROVIDED BY THE FACILITY REPRESENTATIVE
BEFORE WORK IS INSTALLED.
4. INTERRUPTION OF EXISTING SERVICES: THE CONTRACTOR'S
ATTENTION IS CALLED TO THE PRESENCE OF EXISTING, CONDUIT,
PIPING, ETC. THE CONTRACTOR WILL BE HELD RESPONSIBLE FOR
THE PROPER AND APPROVED REPAIR OF ANY AND ALL DAMAGE
CAUSED BY THEM OR THEIR WORK TO EXISTING BUILDING. THE
BUILDING IS A HISTORIC STRUCTURE AND ANY DAMAGE MUST BE
REPAIRED TO MATCH COLOR AND MATERIALS OF THE EXISTING
BUILDING. ANY INTERRUPTIONS REQUIRED SHALL BE SCHEDULED
TO MINIMIZE INCONVENIENCE TO THE FACILITY, AND AT TIMES AS
APPROVED IN ADVANCE BY THE FACILITY REPRESENTATIVE. NEW
WORK AND INSTALLATIONS SHALL NOT IMPAIR THE PROPER
FUNCTIONING OF THE EXISTING FACILITY. THE COMPLETED
PROJECT SHALL BE A PROPERLY FUNCTIONING ENTITY
THROUGHOUT. FURNISH ALL LABOR AND MATERIALS REQUIRED TO
RELOCATE, REMOVE, REINSTALL, RECONNECT, REPLACE, ANY
EXISTING PIPING TO ACCOMMODATE THE WORK. CONTRACTOR
SHOULD CONSIDER IN THEIR BID ANY EXTRA WORK REQUIRED TO
MINIMIZE SHUTDOWN TIME.
5. EQUIPMENT FIXTURE, PIPING ETC. THAT ARE TO BE
REMOVED/DEMOLISHED SHALL BE THE PROPERTY OF THIS
CONTRACTOR UNLESS NOTED FOR SALVAGE BY FACILITY AND
SHALL BE REMOVED IN ITS ENTIRELY FROM THE PREMISES.
6. BEFORE DEMOLITION COMMENCES ON SITE, ALL EXISTING
EQUIPMENT TO BE RETAINED AND REUSED WILL BE SURVEYED AND
VALIDATED TO ESTABLISH CONDITION AND CAPACITIES. ANY
EXISTING DAMAGE TO EQUIPMENT IS TO BE RECORDED AT THIS
STAGE BY THE CONTRACTOR AND A FULL WRITTEN REPORT
SUBMITTED TO THE FACILITY REPRESENTATIVE FOR REVIEW. THE
REPORT WILL INCLUDE PHOTOGRAPHIC EVIDENCE OF DAMAGE.
7. CONTRACTOR TO CROSS REFERENCE DEMOLITION & NEW
CONSTRUCTION DRAWINGS TO ENSURE CONSISTENCY IN DESIGN
INTENT BEFORE PROCEEDING WITH ANY DEMOLITION WORK. ANY
PIPE, VALVE, EQUIPMENT THAT IS MISTAKENLY DEMOLISHED SHALL
BE RESTORED AT CONTRACTOR'S COST.
8. ALL POWER SUPPLIES TO EXISTING EQUIPMENT TO BE REMOVED
SHALL BE ISOLATED AND MADE SAFE PER NEC PRIOR TO
DEMOLITION STARTS. THIS PROCESS SHALL BE COORDINATED WITH
FACILITY REPRESENTATIVES.
9. CONTRACTOR TO DO PRE-DEMOLITION SURVEY AND RED TAG
UTILITIES FOR DEMOLITION. COORDINATE WITH FACILITY
REPRESENTATIVE ALL PROPOSED UTILITY SHUT DOWN AND
ISOLATION PRIOR TO DEMOLITION.
1. SYSTEMS TO BE BALANCED TO AIR QUANTITIES SHOWN ON PLANS
AND AS BUILT DRAWINGS. PROVIDE AN INDEPENDENT AIR BALANCE
REPORT CERTIFIED BY AABC.
2. DUCT INSULATION SHALL BE APPROVED AND MEET CLASS 1
REQUIREMENTS NOT TO EXCEED A FLAME SPREAD OF 25 NOR
SMOKE DEVELOPED RATING OF 50.
3. ALL REQUIRED CEILING/WALL ACCESS PANELS ARE FURNISHED
UNDER THE MECHANICAL SECTION AND INSTALLED BY THE
GENERAL CONTRACTOR. SUBMIT SHOP DRAWINGS FOR REVIEW
PRIOR TO INSTALLATION.
4. UPON COMPLETION OF THE TEST AND BALANCE OF THE HVAC
SYSTEMS AND WITH THE SYSTEM OPERATING AT DESIGN CAPACITY,
AIR-BORNE SOUND LEVEL MEASUREMENTS SHALL BE MADE TO
FIELD VERIFY NOISE EMISSIONS IN ACCORDANCE WITH
SPECIFICATIONS AND LOCAL ORDINANCES.
5. DURING CONSTRUCTION, PROTECT OPENINGS AND MECHANICAL
EQUIPMENT FROM DUST AND POLLUTANTS; SEAL PERMANENT HVAC
DUCTS/EQUIPMENT STORED ON SITE.
CONSTRUCTION NOTES
DEMO NOTESGENERAL NOTES
M0.0 MECHANICAL GENERAL NOTES & LEGENDS
M1.0 MECHANICAL BASEMENT DEMOLITION PLAN
M1.1 MECHANICAL FIRST FLOOR DEMOLITION PLAN
M1.2 MECHANICAL ROOF DEMOLITION PLAN
M2.0 MECHANICAL BASEMENT FLOOR PLAN
M2.1 MECHANICAL FIRST FLOOR PLAN
M2.2 MECHANICAL ROOF PLAN
M5.0 MECHANICAL DETAILS
M5.1 MECHANICAL DETAILS
M6.0 MECHANICAL SCHEDULES
M7.0 MECHANICAL CONTROLS
M7.1 MECHANICAL CONTROLS
MECHANICAL SHEETS LIST
MECHANICAL SCOPE OF WORK
· REPLACE ROOFTOP UNITS AC-2, AC-3, AND AC-4
· REPLACE FANS, EF-1 AND RF-2
· REPLACE SPLIT SYSTEMS FC/CU-4, 5 AND 6
· REPLACE DUCTWORK AND DIFFUSERS SERVING THE
OFFICE AND BASEMENT SPACES
· RECONFIGURE LOBBY SUPPLY AND RETURN DUCTWORK
DISTRIBUTION
· PROVIDE SUPPLY AIR TO RESTROOMS FROM AC-2
· ADD FC/CU-7 TO SERVE STORAGE ROOM
AC AIR CONDITIONING UNIT
ADJ ADJUSTABLE
AFC ABOVE FINISHED CEILING
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AP ACCESS PANEL
APD AIR PRESSURE DROP
AVG AVERAGE
BDD BACKDRAFT DAMPER
BHP BRAKE HORSEPOWER
BMS BUILDING MANAGEMENT SYSTEM
BOD BOTTOM OF DUCT
BOP BOTTOM OF PIPE
BTU BRITISH THERMAL UNIT
BTUH BRITISH THERMAL UNIT PER HOUR
C/W COMPLETE WITH
CFM CUBIC FEET PER MINUTE
DB DRY BULB TEMPERATURE
dB DECIBEL(S)
DDC DIRECT DIGITAL CONTROL
DEG DEGREE
DIA./Ø DIAMETER
DIFF DIFFERENTIAL
DIV DIVISION
DN DOWN
DWG DRAWING
EA EXHAUST AIR
EAT ENTERING AIR TEMPERATURE
EER ENERGY EFFICIENCY RATIO
ER EXISTING RELOCATED (NEW
CONSTRUCTION PLANS)
ESP EXTERNAL STATIC PRESSURE
EWT ENTERING WATER TEMPERATURE
EXIST/E EXISTING (DEMOLITION AND NEW
CONSTRUCTION PLANS)
FLA FULL LOAD AMPERAGE
FP FIRE PROTECTION
FPM FEET PER MINUTE
FPS FEET PER SECOND
FT FOOT/FEET
GA GAUGE
GAL GALLON
GC GENERAL CONTRACTOR
GPM GALLONS PER MINUTE
HEPA HIGH EFFICIENCY PARTICULATE
AIR (FILTER)
HP HORSEPOWER
HR HOUR
HVAC HEATING / VENTILATION / AIR
CONDITIONING
HZ HERTZ
IE INVERT ELEVATION
IN INCHES
IN WG INCHES WATER GAUGE
IPLV INTEGRATED PART LOAD FAILURE
kW KILOWATT kW KILOWATT HOUR
LAT LEAVING AIR TEMPERATURE
LBS POUNDS
LF LINEAR FEET
LWT LEAVING WATER TEMPERATURE
M METER
MAX MAXIMUM
MBH THOUSAND OF BTUH
MCA MINIMUM CIRCUIT AMPS
MFR MANUFACTURER
MIN MINIMUM
MOP MAXIMUM OVERCURRENT
PROTECTION
MVD MANUAL VOLUME DAMPER
N/A NOT APPLICABLE
NC NOISE CRITERIA
NC NORMALLY CLOSED
NIC NOT IN CONTRACT
NO NORMALLY OPEN
NPS NOMINAL PIPE SIZE
NTS NOT TO SCALE
OA OUTSIDE AIR
OFCI OWNER FURNISHED, CONTRACTOR
INSTALLED
PG PROPYLENE GLYCOL
POE POINT OF ENTRANCE
POS POINT OF SERVICE
PPM PARTS PER MILLION
PSI POUNDS PER SQUARE INCH
PSIA POUNDS PER SQUARE INCH,
ABSOLUTE
PSIG POUNDS PER SQUARE INCH, GAGE
RA RETURN AIR
RELA RELIEF AIR
REQD REQUIRED
RH RELATIVE HUMIDITY
RPM REVOLUTIONS PER MINUTE
ABBREVIATIONS ABBREVIATIONS
SA SUPPLY AIR
SP STATIC PRESSURE
TA TRANSFER AIR
TEMP TEMPERATURE
TSP TOTAL STATIC PRESSURE
TSTAT THERMOSTAT
TYP TYPICAL
UG UNDERGROUND
UP UP
VAV VARIABLE AIR VOLUME
VFD VARIABLE FREQUENCY DRIVE
VIF VERIFY IN FIELD
VTR VENT-THRU-ROOF
W/ WITH
W/O WITHOUT
WB WET BULB TEMPERATURE
WG WATER GAUGE
X EXISTING TO BE DEMOLISHED
°C CELSIUS
°F FAHRENHEIT
AC-# AIR COMPRESSOR
ACU-# AIR CONDITIONING UNIT
AHU-# AIR HANDLING UNIT
CU-# CONDENSING UNIT
E-# EXHAUST GRILLE / REGISTER /
DIFFUSER
EF-# FAN EXHAUST
RF-# FAN RETURN
F-# FAN
FC-# FAN COIL UNIT
R-# RETURN AIR GRILLE / REGISTER /
DIFFUSER
S-# SUPPLY GRILLE / REGISTER /
DIFFUSER
EH-# ELECTRIC HEATER
EQUIPMENT IDENTIFICATION
OUTDOOR DESIGN CONDITIONS
LOCATION: BOULDER CITY, NEVADA
ELEVATION: 2458 FT
SUMMER DESIGN: 115 DEG F DB / 73 DEG F WB
WINTER DESIGN: 27 DEG F
APPLICABLE CODES
THE CONTRACTOR SHALL COMPLY WITH ALL
APPLICABLE LAWS AND CODES AND INCLUDE, BUT NOT
BE LIMITED TO, THE LATEST ADOPTED EDITIONS OF:
2018 INTERNATIONAL BUILDING CODE
2018 INTERNATIONAL EXISTING BUILDING CODE
2018 UNIFORM MECHANICAL CODE
2018 UNIFORM PLUMBING CODE
2017 NATIONAL ELECTRICAL CODE
2018 INTERNATIONAL ENERGY CONSERVATION CODE
SOUTHERN NEVADA AMENDMENTS
ASHRAE STANDARDS
WHERE LAWS AND CODES ARE FOUND TO BE IN
CONFLICT WITH EACH OTHER,THE MORE STRINGENT
REQUIREMENTS WILL PREVAIL.
MATCH LINE
DRAWING REVISION
NORTH ARROW
LEVEL CALLOUT
WALL SECTION CALLOUT
BUILDING SECTION CALLOUT
INTERIOR ELEVATION CALLOUT
EXTERIOR ELEVATION CALLOUT
DETAIL CALLOUT
SHEET NUMBER
DETAIL NUMBER
GENERAL SYMBOLS
POINT OF CONNECTION (POC)
POINT OF DISCONNECT (POD)
DAT
06/30/2024
04/26/2023
RAFT
DAT
06/30/2022
FIN
AL D
RAFT
DAT
RAFT
DAT
06/30/2022
FIN
AL D
RAFT
DAT
RAFT
DAT
06/30/2022
FIN
AL D
RAFT
DAT
RAFT
DAT
06/30/2022
FIN
AL D
RAFT
DAT
RAFT
DAT
06/30/2022
FIN
AL D
RAFT
DAT
RAFT
DAT
06/30/2022
FIN
AL D
RAFT
DAT
RAFT
WOOD NAILER
B
ROOF DECKING
ROOF INSULATION
ROOFING MATERIAL
ABS PLASTIC
CURB COVER
MULTIPLE PIPE
PORTAL
ROOF
ROOF RAIL
ROOF RAIL CAP
VIBRATION ISOLATION AND RAIL
MOUNTING PER SPECIFICATIONS
STAINLESS STEEL DISCHARGE DUCT. PROVIDE
BACK DRAFT DAMPER AND FRAMED BIRD SCREEN
OVER OPENING.
FLEX
DRAIN
WOOD NAILER
BLOCKING
NOTE: ALL DUCTWORK ABOVE ROOF TO BE STAINLESS
REFER TO ARCH DRAWINGS
FOR ROOFING DETAILS
EQUIPMENT MOUNTING
POINT
EQUIPMENT
CAP FLASHING
WOOD NAILER
EQUIPMENT ROOF
CURB / RAIL
ROOFING MATERIAL
ROOF DECKING / SLAB
NOTES:
1. COORDINATE THE LOCATION AND SIZE OF THE EQUIPMENT RAIL BASED
ON THE EQUIPMENT
2. THE PURPOSE OF THE EQUIPMENT RAIL IS TO SUPPORT THE WEIGHT
OF THE EQUIPMENT. IT SHALL BE RATED FOR THE OPERATING WEIGHT
OF THE EQUIPMENT. FOLLOW VIBRATION / SEISMIC REQUIREMENTS
PER THE CONTRACT DOCUMENTS.
3. THE RAIL IS TO BE MOUNTED A MINIMUM OF 18 INCHES / 46 CM ABOVE
THE TOP OF THE ROOF UNLESS NOTED OTHERWISE.
1" SPACE - PACK WITH FIBROUS PACKING
16 GAUGE TELESCOPING SHEET METAL SLEEVE
SET IN WALL
DUCT JOINTS
SEAL ALL AROUND
1" SPACE - PACK WITH FIBROUS PACKING
SEAL ALL AROUND
DUCT JOINTS
16 GAUGE TELESCOPING SHEET
METAL SLEEVE SET IN WALL
WOOD BLOCKING
ROOF DECKING
ROOF INSULATION
SECURE CAP TO CURB
COUNTERFLASHING INTEGRAL
TO DUCT
STAINLESS STEEL
CONSTRUCTION ABOVE ROOF
GASKET OR SEALANT
ROOF CURB
ROOFING MATERIAL
DUCT ROOF DECKING
ROOFING MATERIAL
WOOD BLOCKING
PIPING
ROOF INSULATION
SUPPORT TO FASTEN TO CURB
NAILER ON VERTICAL SIDE
SEE SPECIFICATION FOR
SPACING OF SUPPORTS
ROLLER
RAIL
SEAL ALL AROUND
SECURE SAFING TO PARTITION
PACK GLASS FIBER INSULATION AROUND DUCT
FULL DEPTH OF PARTITION
STUD PARTITION
SEAL ALL AROUND
SHEETMETAL SAFING ALL AROUND
DUCT
WOOD BLOCKING
ROOF DECKING
ROOF INSULATION
SUPPORT TO FASTEN TO CURB
NAILER ON VERTICAL SIDE
RAIL
ROOFING MATERIAL
SEE SPECIFICATION FOR
SPACING OF SUPPORTS
DUCT
DUCT MOUNTING PEDESTAL
AS SPECIFIED
STAINLESS STEEL DRAWBANDS
EDPM RUBBER CAP
CURB
WOOD BLOCKING
MITER (TYP)
HSS 4X4X1/4
HS
S
4X 4X
1/4
(TYP)
HSS 4X4X1/4
HS
S
4X 4X
1/4
(TYP)
4'-2" MAX.
4'-2"
3'-0"
7'-2" MAX.
1/4" STIFFENER PLATES
@ BEAM SIDES
BEAM
3/16
1/4
MAX. SPACING= 10'-0" O.C.
SEE DETAIL A
FINISHED ROOF
HSS COLUMN
3" SQUARE TUBE (TYP)
DETAIL A
DAT
06/30/2022
FIN
AL D
RAFT
DAT
RAFT
RECTANGULAR DUCT RECTANGULAR DUCT RECTANGULAR DUCT
ROUND
DUCT
ROUND DUCT
AIR FLOW AIR FLOW AIR FLOW
CONICAL TEE
FITTING WITH FLANGE
TYPICAL TAKEOFF FROM RECTANGULAR
TO ROUND DUCT - SHOE TAP
TYPICAL TAKEOFF FROM RECTANGULAR
TO ROUND DUCT - BELL MOUTH
TYPICAL TAKEOFF FROM RECTANGULAR
TO ROUND DUCT - SHOE TAP
NOTES:
1. HOLE IN RECTANGULAR DUCT SHALL BE CUT LARGE ENOUGH SO THAT ROUGH METAL EDGE SHALL NOT PROJECT INTO
AIR STREAM.
2" R
45°
45°
1-1/2"
1-1/2"
TURNING VANES
(SEE DETAIL THIS SHEET)
RECTANGULAR
DUCT ROUND DUCT
SLOPE NOT TO EXCEED 1" IN 3"SLOPE NOT TO EXCEED 1" IN 3"
DETAIL OF TURNING VANES
TYPICAL RECTANGULAR TO ROUND TRANSITIONTYPICAL RECTANGULAR TRANSITIONFULL RADIUS 45° ELBOWCONSTRUCTION OF 90° ELBOW
USE THIS DESIGN
WHERE 45° ROUND OR
RECTANGULAR RADIUS
ELS ARE SHOWN ON
PLANS
USE THIS DESIGN
WHERE SQUARE 90° ELS
ARE SHOWN ON PLANS
OR IF SPACE
CONDITIONS DO NOT
PERMIT INSTALLATION
OF RADIUS 90° ELS
SQUARE 90° ELBOWFULL RADIUS 90° ELBOW
USE THIS DESIGN
WHERE 90° ROUND
OR RECTANGULAR
RADIUS ELS ARE
SHOWN ON PLANS
1 1/2 W
1 1/2 WW W
W
WW
W
CL
CL
CL
CL
TRANSITION AS REQ'D.
(TYPICAL)
MAIN
TRANSITION AS REQ'D.
(TYPICAL)
EQUAL SIDE
(TYPICAL)
DUCT SPLIT RATIO
(SIZE FOR EQUAL
VELOCITIES)
OPPOSED ACTING BLADESCONNECTING LINKAGE
HINGE POINTOPERATING SHAFT
FOR QUADRANT LOCK
VANES
(TYPICAL)
TURN VANES
DUCT SPLIT RATIO
(SIZE FOR EQUAL
VELOCITIES)
R=W MIN. AIR
FLOW
TYPICAL VOLUME DAMPERSQUARE DIVERGING MAINSQUARE BRANCH TAKEOFFSPLIT MAIN
DISCHARGE AT NEAREST EQUIPMENT
DRAIN. REFER TO PLANS FOR
LOCATIONS. ROUTE THE PIPING SO
AS NOT TO OBSTRUCT WALKING
PATHWAYS. PROVIDE THE CODE
REQUIRED AIR GAP WHERE THE
PIPING TERMINATES AT THE
EQUIPMENT DRAIN.
CLEANOUT PLUG
DRAIN PAN
SLOPE PIPE AT 2%
H1 H2
H 1 : BLOW-THRU = 1 INCH (25MM)
H 1 : DRAW-THRU = FAN INLET PRESSURE (IN WC) + 1 INCH OR FAN INLET PRESSURE IN MM + 25MM H 2 : BLOW-THRU = FAN OUTLET PRESSURE (IN WC) + 1 INCH OR FAN OUTLET PRESSURE IN MM + 25MM H 2 : DRAW-THRU = 1/2 OF THE FAN INLET PRESSURE (IN WC) + 1/2 INCH OR 1/2 OF THE FAN INLET PRESSURE IN MM + 13MM
NOTES:
1. INCREASE UNIT PAD / STRUCTURE / CURB HEIGHT FOR FLOOR MOUNTED EQUIPMENT TO ACHIEVE THE HEIGHT
REQUIRED TO INSTALL THE TRAP DEPTH. THE PRESSURES SHALL BE BASED ON 1.25 TIMES THE SCHEDULED AHU
STATIC PRESSURE
2. IF THE TRAP IS LOCATED OUTDOOR OR IN AN UN-HEATED SPACE, PROVIDE A DRAIN W/ BALL VALVE IN THE LOW POINT
OF THE TRAP WITH A CAP. THIS WILL ALLOW THE TAP TO BE DRAINED IF REQUIRED.
3. REFER TO THE CONTRACT DOCUMENTS FOR PIPE MATERIAL AND INSULATION REQUIREMENTS.
4. THE TRAP PIPE SIZE SHALL BE A MINIMUM OF 1-1/2" / 40MM. REFER TO THE CHART ABOVE FOR THE CONDENSATE DRAIN
SIZE (UNLESS NOTED ELSEWHERE IN THE CONTRACT DOCUMENTS THAT THE PIPE SIZE SHOULD BE LARGER THAN NOTED IN THE CHART). THE DRAIN LINE SHALL NEVER BE SMALLER THAN THE DRAIN PAN CONNECTION.
DUCT SIZE AS SHOWN ON
DRAWING
VERTICAL DUCT EQUAL TO THE
GRILLE NECK SIZE (AS NOTED ON
THE GRILLE SCHEDULE) OWN AND
CONNECT DIRECTLY TO THE
GRILLE.
GRILLE FACE SIZE SHALL BE AS
NOTED IN THE CONTRACT
DOCUMENTS
SHOE TAP
NOTES:
1. APPLIES TO ALL DUCTED RETURN AND EXHAUST GRILLES EXCEPT FOR WHEN THE CONTRACTOR ELECTS TO USE
ANOTHER APPROVED DETAIL
WOOD NAILER VIBRATION ISOLATION
AND FAN BASE
ROOFING MATERIAL
REFER TO ARCH DRAWINGS
FOR ROOFING DETAILS
EQUIPMENT ROOF CURB/RAIL
CAP FLASHING
EQUIPMENT MOUNTING
POINT
FAN DISCHARGE
ATTACHMENT POINTS TO
STRUCTURAL SUPPORT
STEEL (TYP)
STACK
FLEX
STRAIGHT LENGTH
OF DUCTWORK AT
FAN INLET SIZE
DUCT SIZE
MOTORIZED
DAMPER
DRAIN
TRAP
FAN
'0"
/30 5C
M
MI
NI
MU
M
NOTES:
1. COORDINATE THE LOCATION AND SIZE OF THE EQUIPMENT RAIL
BASED ON THE EQUIPMENT
2. THE PURPOSE OF THE EQUIPMENT RAIL IS TO SUPPORT THE
WEIGHT OF THE EQUIPMENT. IT SHALL BE RATED FOR THE
OPERATING WEIGHT OF THE EQUIPMENT. FOLLOW VIBRATION /
SEISMIC REQUIREMENTS PER THE CONTRACT DOCUMENTS.
3. THE TOP OF THE RAIL/CURB IS TO BE MOUNTED A MINIMUM OF 18
INCHES / 46 CM ABOVE THE TOP OF THE ROOF UNLESS NOTED
OTHERWISE.
4. REFER TO THE CONTRACT DOCUMENTS FOR DUCT MATERIAL AND
INSULATION REQUIREMENTS.
5. THE STRAIGHT DUCT BEFORE THE FAN INLET SHALL BE A MINIMUM
OF 3 DUCT DIAMETERS.
6. FILL THE TRAP PRIOR TO START-UP. FOLLOW THE MFRS
REQUIREMENTS FOR DEPTH OF TRAP BASED ON THE FAN STATIC
PRESSURE. PROVIDE A CAP FOR THE TRAP IN A PLASTIC BAG THAT
IS FASTENED TO THE TRAP.
7. SET STACK FLANGE AND VIBRATION ISOLATION BASES IN SILICONE
CAULKING.
8. ENCAPSULATE ALL STACK AND FAN FASTENERS IN SILICONE
CALKING.
9. FLANGES AND GUSSETS ARE WELDED TO THE STACK.
10. EXIT CONE OUTLET SHALL BE CONSTRUCTED TO ACHIEVE A
MINIMUM EXIT VELOCITY OF 3000 FPM.
11. COORDINATE SCOPE OF WORK WITH ROOFING CONTRACTOR /
OWNER TO NOT VOID ANY WARRANTIES.
DAT
06/30/2022
FIN
AL D
RAFT
DAT
RAFT
ROOF TOP UNIT SCHEDULE - PART A
UNIT IDENTIFICATION AIRFLOW PHYSICAL CHARACTERISTICS COMPONENTS
MARK NUMBER LOCATION AREA SERVED
SUPPLY AIR
(CFM)
MIN
OUTSIDE
AIR
(CFM)
UNIT
OPERATING
WEIGHT
(LBS)
MAXIMUM UNIT DIMENSIONS FILTER HEATING SECTION DX COOLING COIL
HEIGHT
(IN)
WIDTH
(IN)
LENGTH
(IN) FILTER TYPE MERV
RATING
MAX APD
(IN-WG)
HEATING
AIRFLOW
(CFM)
EAT
(F)
LAT
(F)
OUTPUT
RATING
(MBH)
TOTAL
CAPACITY
(MBH)
SENSIBLE
CAPACITY
(MBH)
EDB
(F)
EWB
(F)
LDB
(F)
LWB
(F)
MAX APD
(IN-WG)
AC 2 EAST ROOF RESTROOM, OFFICE, BASEMENT 4,450 1,400 1,435 58 64 116 2 13 0.14 4,450 56 75.8 87.9 117.0 117.0 87.6 65.5 61.2 56.8 - AC 3 SOUTH ROOF AUDITORIUM 3,850 750 1,375 49 60 89 2 13 0.21 3,850 61 81.9 80.4 99.3 94.5 82.8 64.2 58.2 55.4 - AC 4 LOW ROOF LOBBY 1,600 250 850 34 47 75 2 13 0.17 1,600 61 83 38.1 38.1 34.9 80.0 67.0 57.9 54.9 -
ROOF TOP UNIT SCHEDULE - PART B
UNIT IDENTIFICATION CONDENSER SECTION FANS CAPACITY AND PERFORMANCE ELECTRICAL
MANUFACTURER MODEL
NUMBER NOTES
MARK NUMBER
COMPRESSORS EVAP FAN COND. FANS SUPPLY (2 SPEED 66% AND 100%)
NOMINAL
CAPACITY
(TONS)
EER IEER REFRIG
TYPE
REFRIG
CHARGE VOLTS PHASE MCA MOCP
NOTE 3
CONV
OUTLET
115 V/20a
NOTE 5
FUSED
DISCONNECTNO. OF
COMP.
NO. OF
STAGES
NO. OF
CIRCUIT
TYPE OF
COMP.
NO. OF FANS
ECM
NO. OF FANS
ECM
ESP
(IN-WG) BHP HP
SPEED
(RPM)
AC 2 2 2 1 VANE AXIAL 1 3 1.8 2.9 5 1,819 12.5 10.6 15.0 410 24 LBS 14 OZ 460 3 24.0 30 YES YES CARRIER 50FCQM14A ALL
AC 3 2 2 1 VANE AXIAL 1 1 1.3 2.3 3 1,913 10.0 11.0 15.0 410 21 LBS 5 OZ 460 3 28.0 30 YES YES CARRIER 50FCQM12A ALL
AC 4 1 1 1 VANE AXIAL 1 1 1.3 1.0 1.5 2,141 4.0 14.3 ARI SEER N/A 410 11 LB 13 OZ 460 3 11.0 15 YES YES CARRIER 50FCQA05A ALL
NOTES:
1. FILTERS ARE TO BE PROVIDED WITH PRE-FILTER. MAXIMUM PRESSURE DROP SHALL BE BASED ON TOTAL PRESSURE DROP ACROSS THE FILTER BANK WITH DIRTY FILTERS. EXTERNAL STATIC ALSO INCLUDES DUCT MOUNTED ELECTRIC HEATING COILS
2. PROVIDE UNIT WITH 14" CURB. REFER TO MECHANICAL DETAILS FOR CURB FILLING MATERIAL REQUIREMENTS.
3. PROVIDE WITH POWERED EXHAUST FANS WHICH REQUIRE FIELD SUPPLIED DISCONNECTS BY DIV. 26
4. PROVIDE UNIT WITH ECONOMIZER
5. FUSED DISCONNECT BY DIV 26
6. SUMMER OUTDOOR TEMP IS 115 AND WINTER IS 27 DEGREES F. PROVIDE WITH LOW AMBIENT KIT WITH HEAD PRESSURE CONTROL. UNIT SELECTED AT ELEVATION 2200
7. PROVIE WITH MANUFACTURER'S STANDALONE CONTROLS
GRILLE, REGISTER, DIFFUSER SCHEDULE
UNIT IDENTIFICATION DIFFUSER
FACE SIZE
(IN)
DIFFUSER
NECK SIZE
(IN)
MOUNTING
TYPE COLOR MATERIAL ACCESSORY MANUFACTURER MODEL NUMBER NOTES
MARK NUMBER
SG 1 SEE PLANS SEE PLANS WALL/DUCT NOTE 3 STEEL - TITUS 272FL ALL
SG 2 36x4 SEE PLANS FLOOR NOTE 3 STEEL AG-35 OBD TITUS CT--580 1,3
RG 1 24X24 SEE PLANS CEILING NOTE 3 STEEL - TITUS PAR ALL
RG 2 SEE PLANS SEE PLANS WALL/DUCT NOTE 3 STEEL - TITUS 272FL ALL
EG 1 SEE PLANS SEE PLANS CEILING NOTE 3 STEEL - TITUS 3FL ALL
NOTES:
1. REFER TO REFLECTED CEILING PLANS EXACT LOCATION. PROVIDE ALL FRAMES AND ACCESSORIES AS REQUIRED FOR PROPER INSTALLATION.
2. FLEXIBLE DUCTWORK SHALL BE THE SAME SIZE AS THE DIFFUSER NECK OR AN EQUIVALENT ROUND DUCT. FLEXIBLE DUCTWORK SHALL BE SUPPORTED TO PREVENT KINKS OR BENDS.
3. COLORS TO BE SELECTED TO MATCH EXISITNG BUILDING FINISHES.
4. PROVIDE OPPOSED BLADE DAMPERS FOR ALL GRILLES ON PLANS, UNLESS SHOWN WITH VOLUME DAMPER.
SPLIT SYSTEM AIR CONDITIONING UNIT SCHEDULE
UNIT IDENTIFICATION INDOOR UNIT
MANUFACTU
RER NOTES
MARK NUMBER ROOM(S) SERVED
COOLING
CAPACITY
(BTU/H)
HEATING
CAPACITY
(BTU/H)
AIRFLOW
(CFM)
FILTER
RATING
(MERV)
MOUNTING
CONDENSA
TE PUMP
REQUIRED
OPERATING
WEIGHT
(LBS.)
MODEL
NUMBER TAG
AMBIENT
DESIGN
TEMP (F)
ELECTRICAL OPERATING
WEIGHT
(LBS.)
MODEL
NUMBERVOLTS PHASE MOP
FC 4 ELEV. MACHINE ROOM 18.0 21.0 450 WASHABLE WALL YES - INTEGRAL 28 MSZ-GL18NA CU-4 115.0 208 1 14 15 121 MUZ-GL18NA MITSUBISHI ALL
FC 5 ELECTRICAL ROOM 18.0 21.0 450 WASHABLE WALL YES - INTEGRAL 28 MSZ-GL18NA CU-5 115.0 208 1 14 15 121 MUZ-GL18NA MITSUBISHI ALL
FC 6 PROJECTOR ROOM 18.0 21.0 450 WASHABLE WALL YES - INTEGRAL 28 MSZ-GL18NA CU-6 115.0 208 1 14 15 121 MUZ-GL18NA MITSUBISHI ALL
FC 7 STORAGE ROOM 18.0 21.0 450 WASHABLE WALL YES - INTEGRAL 28 MSZ-GL18NA CU-7 115.0 208 1 14 15 121 MUZ-GL18NA MITSUBISHI ALL
NOTES:
1. OUTDOOR UNIT POWERS INDOOR UNIT. PROVIDE ALL INTERCONNECTING WIRING BETWEEN THE INDOOR AND OUTDOOR UNITS. OUTDOOR UNIT POWERS CONDENSATE PUMP WITH SHUTOFF CAPIBLIITY. SINGLE POINT POWER FOR OUTDOOR, INDOOR, & CONDENSATE PUMP.
2. PROVIDE PIPE PORTAL AT ALL ROOF PENETRATIONS.
3. OUTDOOR UNIT TO BE MOUNTED ON ROOF CURB RAILS.
4. SPEED BASED ON [HIGH] SPEED. PROVIDE WIRED TEMPERATURE CONTROL
5. DISCONNECT BY DIV 26
6. CONDENSATE PUMP MAXIBLUE ADVANCED BLUE DIAMOND MINI CONDENSATE PUMP WITH RESERVOIR AND SENSOR. MODEL 110v - X87-771. CONNECT TO EXISTING CONDENSATE PIPING; CLEAN EXISTING DRAIN PIPE PRIOR TO INSTALLATION OF NEW PUMP.
7. SYSTEM SIZED FOR 2200 FT ELEVATION
ELECTRIC DUCT HEATER SCHEDULE
UNIT IDENTIFICATION ELEMENT ELECTRICAL
MANUFACTURER NOTES
MARK NUMBER SYSTEM ROOM(S) SERVED KW NO OF
STAGES VOLTS PHASE
(E) EH 2 AC-3 AUDITORIUM 30.0 4 480 3 INDEECO 1
(E) EH 3 AC-2 OFFICE/BASEMENT/RESTROOMS 20.0 4 480 3 INDEECO 1
(X) EH 4 AC-3 STORAGE 5.0 4 480 3 INDEECO 1,2
(N) EH 5 AC-2 RESTROOMS 12.0 1 480 3 INDEECO 1,3
NOTES:
1. ELECTRIC DUCT HEATERS SHOWN FOR REFERENCE ONLY. SCHEDULED INFORMATION IS TAKEN FROM AS-BUILTS.
2. ELECTRIC DUCT HEATER SHALL BE DEMOLISHED.
3. NEW ELECTRIC DUCT HEATER INSTALLED IN DUCTWORK. SEE DRAWINGS.
FAN SCHEDULE
UNIT IDENTIFICATION MAX
AIRFLOW
(CFM)
ESP
(IN-WG)
FAN WHEEL FAN MOTOR ELECTRICAL OPERATING
WEIGHT
(LBS.)
MANUFACTURER MODEL NUMBER NOTES
MARK NUMBER UNIT/AREA SERVED TYPE
SPEED
(RPM) BHP HP DRIVE TYPE VOLTS PHASE
EF 1 RESTROOMS 820 0.8 BLOWER 1,628 0.3 1/2 BELT 115 1 155 GREENHECK USF-10-B2 1,2,3,4
RF 2 AC-2 RETURN 4,050 1.0 INLINE 1,750 1.6 2 DIRECT 460 3 175 GREENHECK SQ-16-M2 1,2
PE 2 AC-2 POWERED EXHAUST 4,450 0.5 - - - 2 - 460 3 313 MICROMETL PECE-SRT05CB-D0DB-4L2-4 4
PE 3 AC-3 POWERED EXHAUST 4,450 0.5 - - - 2 - 460 3 313 MICROMETL PECE-SRT05CB-D0DB-4L2-4 4
PE 4 AC-4 POWERED EXHAUST 1,850 0.5 - - - 1/2 - 460 3 225 MICROMETL PECH-SRT12CB-D0DB-4LH-4 4
NOTES:
1. PROVIDE UNIT WITH BACKDRAFT DAMPER
2. PROVIDE UNIT WITH VFD WITH INTEGRAL DISCONNECT.
3. UPBLAST DISCHARGE POSITION
4. PROVIDE WITH MANUFACTURER'S CURB.
5. POWERED EXHAUST REQUIRES SEPARATE FIELD SUPPLIED DISCONNECTS BY DIV. 26.
DAT
WITH WIRELESS THERMOSTAT
ON ROOF CURB RAILS.
PROVIDE WIRED TEMPERATURE CONTROLWITH WIRELESS THERMOSTAT.
06/30/2022
FIN
AL D
RAFT
DAT
RAFT
SEQUENCE OF OPERATION:
APPLICABLE FOR AC-2, 3, AND 4
UNIT TO BE PROVIDED WITH MANUFACTURER'S STANDALONE CONTROL AND SHALL BE ABLE TO, AT A MINIIMUM, PERFORM THE FOLLOWING:
OCCUPIED/UNOCCUPIED DESIGNATION:
THE EQUIPMENT FACTORY CONTROLLER SHALL INITIATE OCCUPIED AND UNOCCUPIED MODES PER SCHEDULES FURNISHED BY THE OWNER.
WARM-UP/PRE-COOL MODE:
EQUIPMENT FACTORY CONTROLS SHALL PERFORM WARM-UP/PRE-COOL SEQUENCE BASED ON PROGRAMMED BUILDING OCCUPIED/UNOCCUPIED SCHEDULE. IF OCCUPIED SETPOINT IS MET PRIOR TO THE SCHEDULED OCCUPIED CHANGEOVER TIME BY MORE THAN THE OCCUPIED ENGAGEMENT ALLOWANCE SETPOINT, THE WARM-UP/PRE-COOL RUN-TIME SETPOINT SHALL BE ADJUSTED 5 MINUTES LATER. IF OCCUPIED SETPOINT IS NOT MET BY THE OCCUPIED MODE START TIME, THE WARM-UP/PRE-COOL RUN-TIME SETPOINT SHALL BE ADJUSTED BY 5 MINUTES EARLIER.
OCCUPIED MODE - SUPPLY FAN SPEED CONTROL:
EQUIPMENT FACTORY CONTROLS SHALL MODULATE SUPPLY FANS AS REQUIRED TO MAINTAIN THE SPACE TEMEPERATURE SETPOINT.
OCCUPIED MODE - RELIEF FAN SPEED CONTROL:
WHEN ECONOMIZER COOLING IS ENABLED, EQUIPMENT FACTORY CONTROLS SHALL MODULATE RELIEF FANS IN CONJUNCTION WITH OSA DAMPER POSITION.
OCCUPIED MODE - DISCHARGE TEMPERATURE CONTROL:
EQUIPMENT FACTORY CONTROLS SHALL CONTROL ECONOMIZER FUNCTION AND MECHANICAL COOLING/HEATING TO MAINTAIN DISCHARGE TEMPERATURE SETPOINT. IF SPACE SUPPLY FAN SPEED IS AT THE TEMPERATURE RESET HIGH LIMIT FOR A PERIOD GREATER THAN THE TEMPERATURE RESET TIME DELAY, THE DISCHARGE AIR TEMPERATURE SETPOINT SHALL BE LOWERED BY THE SUPPLY AIR RESET INCREMENT SET POINT. IF SUPPLY FAN SPEED IS AT OR BELOW THE TEMPERATURE RESET LOW LIMIT FOR A PERIOD GREATER THAN THE TEMPERATURE RESET TIME DELAY, DISCHARGE AIR TEMPERATURE SETPOINT SHALL BE INCREASED BY THE SUPPLY AIR RESET INCREMENT SET POINT. ONCE TEMPERATURE IS RESET, IT SHALL NOT RESET AGAIN UNTIL THE TEMPERATURE RESET TIME DELAY HAS BEEN
ACHIEVED.
ECONOMIZER/OUTSIDE AIR CONTROL:
EQUIPMENT FACTORY CONTROLS SHALL MODULATE OUTSIDE/RETURN AIR DAMPERS BETWEEN THE SCHEDULED MINIMUM OSA POSITION AND THE MIN OSA DCV RESET POSITION TO MAINTAIN CO2 SETPOINT, AND SHALL INCREASE OUTSIDE AIR FOR ECONOMIZER COOLING VIA DRY BULB TEMPERATURE CONTROL. CONTROL SHALL BE FULLY MODULATING. UPON DETECTION OF A CO2 SENSOR FAILURE, OUTSIDE AIR DAMPER POSITION SHALL BE SET TO THE MIN OSA DCV INCREASE POSITION, OR HIGHER AS INDICATED BY ECONOMIZER CONTROLS.
UNOCCUPIED MODE:
EQUIPMENT FACTORY CONTROLS SHALL START EQUIPMENT IN FULL RECIRCULATION MODE (UNLESS ECONOMIZER COOLING IS REQUIRED), AND MAINTAIN UNOCCUPIED SPACE TEMPERATURE SETPOINT.
PROVIDE ALL POINTS AS REQUIRED FOR A COMPLETE OPERATING SYSTEM, INCLUDING AT A MINIMUM,THE FOLLOWING:
• RETURN AIR TEMPERATURE SENSOR
• DISCHARGE AIR TEMPERATURE SENSOR
• OUTSIDE AIR TEMPERATURE SENSOR
• DIRTY FILTER ON/OFF SWITCH
• SUPPLY FAN STATUS
• SUPPLY FAN ON/OFF
• LEAVING COIL TEMPERATURE
• OUTDOOR AIRFLOW MONITORING STATION
• OUTDOOR AIR DAMPER CONTROL
• RETURN AIR DAMPER CONTROL
• ECONOMIZER CONTROL
• SPACE TEMPERATURE SETPOINT
• SPACE TEMPERATURE
• RETURN AIR CO2 SENSOR
ROOF
SUPPLY AIR MAIN
AC-X
SETPOINTS
DESIGNATION MINIMUM RANGE INITIAL SETPOINT
SUPPLY AIR RESET INCREMENT 0-5° F 1.0° F
SUPPLY AIR RESET TIME DELAY 1-10 MINUTES 5 MINUTES
SUPPLY AIR TEMPERATURE 0-80°F 55°F
WARM-UP/PRE-COOL RUN-TIME 0-180 MINUTES 60 MINUTES
TEMPERATURE RESET HIGH LIMIT 0-100% 95%
TEMPERATURE RESET LOW LIMIT 0-100% 70%
TEMPERATURE RESET TIME DELAY 0-120 MINUTES 5 MINUTES
CO2 LEVEL SETPOINT 0-2000 PPM 1000 PPM
T
STANDALONE
FACTORY MOUNTED
CONTROLLER
PROVIDE THERMOSTAT
DESIGNED TO WORK WITH THE
MANUFACTURER'S CONTROL
DAT
06/30/2022
FIN
AL D
RAFT
DAT
RAFT
T
FC CU
THERMOSTAT SETPOINTS
EA EA
MOTOR
EXHAUST
FAN
HOA
CONTROLLER
STANDALONE, 7-DAY PROGRAMMABLE CONTROLLER
WITH MANUAL OVERRIDE, AND A MINIMUM OF 3
PASSCODE PROTECTED SECURITY LEVELS
OUTDOOR UNITDUCTLESS FAN COIL
SPACE TEMPERATURE
SENSOR
NOTES:
1. APPLIES TO ALL SINGLE ZONE DUCTLESS SPLIT SYSTEMS
2. EQUIPMENT OPERATION BY LOCAL CONTROLLER
INITIAL SETPOINT
75° F55-80° F
MINIMUM RANGEDESIGNATION
SPACE TEMPERATURE
DAT
06/30/2022
FIN
AL D
RAFT
DAT
GENERAL ELECTRICAL NOTESABBREVIATIONS & DESCRIPTIONS
(RE: ALL ELECTRICAL SHEETS)
1. COLOR CODE WIRES AS FOLLOWS:
CONDUCTORS 120/208V 277/480V
PHASE A BLACK BROWN
PHASE B RED ORANGE
PHASE C BLUE YELLOW
NEUTRAL WHITE WHITE
GROUND GREEN GREEN
2. ALL SWITCHES TO BE 20 AMP 120 VOLT SPECIFICATION GRADE.
3. ALL POWER JUNCTION BOXES TO BE MARKED WITH PANEL NAME AND CIRCUIT
NUMBER WITH PERMANENT BLACK INK MARKER.
4. ALL WIRE SHALL BE STRANDED TYPE THHN/THWN, WIRE SIZE SHALL BE A MINIMUM
OF #12 AWG Cu UNLESS NOTED OTHERWISE ON PLANS. FOR LENGTHS OF 100' OR MORE, WIRE SIZE SHALL BE A MINIMUM OF #10 AWG Cu UNLESS NOTED OTHERWISE
ON PLANS.
5. ALL ELECTRICAL EQUIPMENT AND SYSTEMS SHALL BE INSTALLED IN ACCORDANCE
WITH THE NATIONAL ELECTRICAL CODE, INTERNATIONAL FIRE CODE, AND ALL
OTHER STATE AND LOCAL CODES. CONTRACTOR SHALL IMMEDIATELY NOTIFY NPS
COR IN WRITING IF PORTIONS OF THE DESIGN SET OR FIELD CONDITIONS DO NOT
MEET REQUIRED CODES.
6. ELECTRICAL DEVICES ARE SHOWN BOLD FOR NEW, BOLD/DASHED FOR DEMO &
RELOCATED AND MEDIUM/DASHED FOR EXISTING.
7. DIMENSIONED LENGTHS SHALL TAKE PRECEDENCE OVER SCALED LENGTHS.
8. COORDINATE WORK WITH ALL TRADES PRIOR TO INSTALLATION.
9. PROVIDE ACCURATE RED-LINED AS BUILT DRAWINGS TO THE GOVERNMENT UPON
PROJECT COMPLETION.
10. FURNISH AND INSTALL A COMPLETE ELECTRICAL SYSTEM AS DEPICTED FROM THE
PLANS AND SPECIFICATIONS. WORK IS TO BE COMPLETE AS NOTED OR IMPLIED,
NOT LIMITED TO WHAT IS SHOWN.
11. ALL DRAWINGS ARE SCHEMATIC IN NATURE AND ALL APPURTENANCES NOT
INDICATED TO MAKE A WORKING SYSTEM MUST BE INCLUDED IN THE
CONTRACTORS BID.
12. THE CONTRACTOR IS RESPONSIBLE TO IDENTIFY CONFLICTS, INCONSISTENCIES, OR
ITEMS WHERE DESIGN INTENT IS NOT CLEAR, IN WRITING TO THE NPS COR PRIOR
TO BID. BY SUBMITTING A BID ON THIS PROJECT, THE CONTRACTOR ACCEPTS THAT
ALL ITEMS ARE UNDERSTOOD AND ACCURATELY DEPICT DESIGN INTENT. NO
ADDITIONAL COST CAN BE RECOVERED (FOR DESIGN INTENT QUESTIONS/ISSUES)
BY THIS CONTRACTOR ONCE BIDS ARE ACCEPTED.
13. ALL MOUNTING HEIGHTS OF EQUIPMENT SHALL MEET ADA REQUIREMENTS UNLESS
OTHERWISE INDICATED.
14. MAINTAIN THE SAME WIRE SIZE FROM PANEL THROUGHOUT THE ENTIRE CIRCUIT
UNO.
15. COORDINATE ALL DEVICE/FIXTURE LOCATIONS AND SPECIFIC REQUIREMENTS WITH
THE GOVERNMENT PRIOR TO ROUGH-IN.
16. CONTRACTOR IS RESPONSIBLE TO REPAIR ANY DAMAGE CAUSED BY THIS
CONTRACTOR TO NEW/EXISTING BUILDING SYSTEMS AT NO ADDITIONAL COST TO
THE GOVERNMENT.
A AMPERES
AC ABOVE COUNTER; REFER
TO ARCHITECTURAL
ELEVATIONS FOR REQUIRED
HEIGHT.
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AF AMPERE FRAME
AHJ AUTHORITY HAVING
JURISDICTION
AT AMP TRIP
AWG AMERICAN WIRE GAUGE
C CONDUIT
CB CIRCUIT BREAKER
CKT CIRCUIT
CL CRITICAL LOAD
CO CONDUIT ONLY, PROVIDE
PULL-LINE
DC DIRECT CURRENT
DET DETAIL
(E) EXISTING
EF EXHAUST FAN
F FUSE
FVNR FULL VOLTAGE NON-REVERSING
G/GND GROUND
GFI GROUND FAULT INTERRUPTION
GFP GROUND FAULT PROTECTION
HH HANDHOLE
HID HIGH INTENSITY DISCHARGE
HOA HAND OFF AUTO
HP HOUSE PHONE
IC INTERRUPTING CAPACITY
IG ISOLATED GROUND
J/JB JUNCTION BOX
KW KILOWATT
KWH KILOWATT HOUR
M MAGNETIC CONTACTOR COIL
MB MAIN BREAKER
MCC MOTOR CONTROL CENTER
MLO MAIN LUGS ONLY
MS MOTOR STARTER
(N) NEW
N NEUTRAL
NC NORMALLY CLOSED
NCL NON CRITICAL LOAD
NEC NATIONAL ELECTRICAL CODE
NEMA NATIONAL ELECTRICAL
MANUFACTURERS ASSOCIATION
NIC NOT IN CONTRACT
NO NORMALLY OPEN
NTS NOT TO SCALE
OL OVERLOAD
OS OCCUPANCY SENSOR
OFCI OWNER FURNISHED
CONTRACTOR INSTALLED
P PHASE
PC PHOTOCELL
PVC POLYVINYL CHLORIDE
PWTS PUBLIC WATER
TREATMENT SYSTEM
RCPT RECEPTACLE
(R) RELOCATED
RE: REFER TO
SER SERVICE ENTRANCE RATED
SPST SINGLE POLE SINGLE THROW
TC TIME CLOCK
TDR TIME DELAY RELAY
TJB TERMINAL JUNCTION BOX
TSP TWISTED SHIELDED PAIR
TTB TELEPHONE TERMINAL BOARD
TVSS TRANSIENT VOLTAGE SURGE
SUPPRESSER
TYP TYPICAL
UH UNIT HEATER
UNO UNLESS NOTED OTHERWISE
V VOLT
VA VOLT AMPERE
VFD VARIABLE FREQUENCY DRIVE
WG PROVIDE PROTECTIVE WIRE
GUARD
WP WEATHER PROOF/NEMA 3R
XFMR TRANSFORMER
CIRCUIT CONCEALED IN
CEILING OR WALL.
3/4"C-2#12,1#12G UNO.
CIRCUIT CONCEALED IN
FLOOR OR UNDERGROUND.
3/4"C-2#10,1#10G UNO.
CONDUIT STUBBED OR SLEEVE,
CAPPED, AND MARKED WITH PULL CORD
BRANCH PANEL.
CIRCUIT BREAKER. SIZE
AND TYPE AS SPECIFIED.
A
JUNCTION BOX.
FLUSH MOUNTED
PANELBOARD/ENCLOSURE. SEE
E5.0 PANEL SCHEDULE FOR TYPE.
NON-FUSED DISCONNECT
SWITCH. SIZE AS INDICATED,
NEMA 1 UNO, 3 POLE UNO.
PANEL
J
MOTOR CONNECTION.
TRANSFORMER.
DUPLEX OUTLET. +18" AFF UNO.
3/4"C 2#12:C-1
1#12:GND
CONDUCTOR
QUANTITY
GROUNDING
CONDUCTOR
SIZE
RACEWAY
SIZE
CONDUCTOR SIZE
CIRCUIT NUMBER
PANEL
FOURPLEX OUTLET. +18" AFF UNO.
SMOKE DETECTOR
COMBINATION STARTER - SEE DRAWINGS
FOR SIZE AND ENCLOSURE RATINGS.
M METER AND BASE.
ELECTRICAL LEGEND
FUSED DISCONNECT SWITCH.
SIZE AS INDICATED, NEMA 1
UNO, 3 POLE UNO.
F
POWER SYSTEM DEVICE SYMBOLS
GFI OUTLET. +18" AFF UNO.
GFI OUTLET. ABOVE COUNTER
FOURPLEX GFI OUTLET. +18" AFF
UNO.
EQUIPMENT CONNECTION
CIRCUIT WIRING SYMBOLS
ONE-LINE DIAGRAM SYMBOLS
LOW VOLTAGE AND CONTROL SYMBOLS
M
SD
DUCT SMOKE DETECTORD
CONDUIT AND WIRE SIZE CALLOUT. SEE
SHEET E3.1 FOR CONDUIT/WIRE SCHEDULE.####
VFD VARIABLE FREQUENCY DRIVE.
04/28/2023
AutoCAD SHX Text
TITLE OF SHEET
AutoCAD SHX Text
DRAWING NO.
AutoCAD SHX Text
PMIS/PKG NO.
AutoCAD SHX Text
SHEET
AutoCAD SHX Text
OF
AutoCAD SHX Text
SUB SHEET NO.
AutoCAD SHX Text
DESIGNED:
AutoCAD SHX Text
TECH. REVIEW:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
REPLACE ALAN BIBLE VISITOR CENTER HVAC
AutoCAD SHX Text
LAKE MEAD NATIONAL RECREATION AREA
AutoCAD SHX Text
B. ANDERSON
AutoCAD SHX Text
M. SMITH
AutoCAD SHX Text
B. ANDERSON
AutoCAD SHX Text
APR 2023
AutoCAD SHX Text
AutoCAD SHX Text 25005A
AutoCAD SHX Text 228968
AutoCAD SHX Text 27/04/2023 16:49 JENNIFER CHEEK G:\CLIENTS\NPS\LAKE\228968\DRAWINGS\ELEC\E0.0 COVER SHEET.DWG
AutoCAD SHX Text
ELECTRICAL COVER SHEET
AutoCAD SHX Text E0.0
AutoCAD SHX Text
04/28/2023
STORAGE
AutoCAD SHX Text
AutoCAD SHX Text
STORAGE
AutoCAD SHX Text
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text
AutoCAD SHX Text
ELECTRICAL
AutoCAD SHX Text
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text
AutoCAD SHX Text
HALL
AutoCAD SHX Text
AutoCAD SHX Text
STAIR
AutoCAD SHX Text
AutoCAD SHX Text
STORAGE
AutoCAD SHX Text
AutoCAD SHX Text
UP
AutoCAD SHX Text
UP
AutoCAD SHX Text
UP
AutoCAD SHX Text
MECH.
AutoCAD SHX Text
ROOM
AutoCAD SHX Text
AutoCAD SHX Text
(E)DDC CONTROLLER
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text M
AutoCAD SHX Text
(E)DISTRIBUTION PANEL 'MDB' 800A, 480/277V 3 4W3 4W
AutoCAD SHX Text
(E)PANEL 'RA' 225A 208/120V 3 4W3 4W
AutoCAD SHX Text
(E)PANEL 'R' 225A 208/120V 3 4W3 4W
AutoCAD SHX Text (E)75kVA STEP DOWN TRANSFORMER, 480:208Y/120V 3 3
AutoCAD SHX Text
(E)MAIN SWITCHBOARD 1200A, 480Y/277V 3 3
AutoCAD SHX Text
(E)PV SYSTEM DISCONNECT
AutoCAD SHX Text
(E)PV REC METER
AutoCAD SHX Text T
AutoCAD SHX Text T
AutoCAD SHX Text T
AutoCAD SHX Text T
AutoCAD SHX Text
1. COORDINATE DISCONNECTION OF THE HVAC EQUIPMENT WITH THE COORDINATE DISCONNECTION OF THE HVAC EQUIPMENT WITH THE NPS COR AND THE HVAC CONTRACTOR. DISCONNECT EQUIPMENT AND MAKE SAFE FOLLOWING PROPER LOCK OUT/TAG OUT PROCEDURES. 2. RETAIN AND PROTECT EXISTING DEVICE/EQUIPMENT THROUGHOUT RETAIN AND PROTECT EXISTING DEVICE/EQUIPMENT THROUGHOUT CONSTRUCTION. 3. EXISTING DDC CONTROLLER TO BE DEMOLISHED. EXISTING DDC CONTROLLER TO BE DEMOLISHED. 4. DEMO EXISTING T-STAT LOCATION TO INCLUDE DEVICE, CABLING, DEMO EXISTING T-STAT LOCATION TO INCLUDE DEVICE, CABLING, J-BOX AND ASSOCIATED CONDUIT.
AutoCAD SHX Text
KEY NOTES:
AutoCAD SHX Text
PLAN VIEW - ELECTRICAL BASEMENT DEMOLITION PLAN
AutoCAD SHX Text
AutoCAD SHX Text 8'
AutoCAD SHX Text 8'
AutoCAD SHX Text 16'
AutoCAD SHX Text
SCALE OF FEET
AutoCAD SHX Text
TITLE OF SHEET
AutoCAD SHX Text
DRAWING NO.
AutoCAD SHX Text
PMIS/PKG NO.
AutoCAD SHX Text
SHEET
AutoCAD SHX Text
OF
AutoCAD SHX Text
SUB SHEET NO.
AutoCAD SHX Text
DESIGNED:
AutoCAD SHX Text
TECH. REVIEW:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
REPLACE ALAN BIBLE VISITOR CENTER HVAC
AutoCAD SHX Text
LAKE MEAD NATIONAL RECREATION AREA
AutoCAD SHX Text
B. ANDERSON
AutoCAD SHX Text
M. SMITH
AutoCAD SHX Text
B. ANDERSON
AutoCAD SHX Text
APR 2023
AutoCAD SHX Text
AutoCAD SHX Text 25005A
AutoCAD SHX Text 228968
AutoCAD SHX Text
SCALE: 1/8"=1'-0"
AutoCAD SHX Text 27/04/2023 16:50 JENNIFER CHEEK G:\CLIENTS\NPS\LAKE\228968\DRAWINGS\ELEC\E1.0 BSMT DEMOLITION PLAN.DWG
AutoCAD SHX Text
BASEMENT ELECTRICAL DEMOLITION PLAN
AutoCAD SHX Text E1.0
AutoCAD SHX Text
CU
EH
04/28/2023
AutoCAD SHX Text
FIXT_CODE
AutoCAD SHX Text
FU_TOTAL
AutoCAD SHX Text
FU_WASTE
AutoCAD SHX Text
FU_HOT
AutoCAD SHX Text
FU_COLD
AutoCAD SHX Text
FIXT_CODE
AutoCAD SHX Text
FU_TOTAL
AutoCAD SHX Text
FU_WASTE
AutoCAD SHX Text
FU_HOT
AutoCAD SHX Text
FU_COLD
AutoCAD SHX Text
PROJECTOR
AutoCAD SHX Text
ROOM
AutoCAD SHX Text
ACCESS
AutoCAD SHX Text
AutoCAD SHX Text
PATIO
AutoCAD SHX Text
AutoCAD SHX Text
EXHIBIT
AutoCAD SHX Text
HALL
AutoCAD SHX Text
AutoCAD SHX Text
HALL
AutoCAD SHX Text
AutoCAD SHX Text
LOBBY
AutoCAD SHX Text
AutoCAD SHX Text
HALL
AutoCAD SHX Text
AutoCAD SHX Text
AUDITORIUM
AutoCAD SHX Text
AutoCAD SHX Text
STORAGE
AutoCAD SHX Text
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text
AutoCAD SHX Text
WORK
AutoCAD SHX Text
ROOM
AutoCAD SHX Text
AutoCAD SHX Text
BREAK
AutoCAD SHX Text
ROOM
AutoCAD SHX Text
AutoCAD SHX Text
STORAGE
AutoCAD SHX Text
AutoCAD SHX Text
ARCADE
AutoCAD SHX Text
AutoCAD SHX Text
PATIO
AutoCAD SHX Text
AutoCAD SHX Text
WOMEN
AutoCAD SHX Text
AutoCAD SHX Text
MEN
AutoCAD SHX Text
AutoCAD SHX Text
JANITOR
AutoCAD SHX Text
AutoCAD SHX Text
DN
AutoCAD SHX Text
DN
AutoCAD SHX Text
LIBRARY
AutoCAD SHX Text
AutoCAD SHX Text
DN
AutoCAD SHX Text
DN
AutoCAD SHX Text
DN
AutoCAD SHX Text
DN
AutoCAD SHX Text
UNISEX
AutoCAD SHX Text
RESTROOM
AutoCAD SHX Text
AutoCAD SHX Text
MATERIAL
AutoCAD SHX Text
PRODUCT
AutoCAD SHX Text
TRADENAME
AutoCAD SHX Text
MODELNUMBER
AutoCAD SHX Text
(E)PANEL 'RB' 225A, 120/208V 3 4W
AutoCAD SHX Text
(E)SUB-PANEL TO PANEL 'RB'
AutoCAD SHX Text M
AutoCAD SHX Text
(E)CU-4 DISCONNECT
AutoCAD SHX Text (E)
AutoCAD SHX Text T
AutoCAD SHX Text F
AutoCAD SHX Text T
AutoCAD SHX Text T
AutoCAD SHX Text T
AutoCAD SHX Text (E)
AutoCAD SHX Text
1. COORDINATE DISCONNECTION OF THE HVAC EQUIPMENT WITH THE COORDINATE DISCONNECTION OF THE HVAC EQUIPMENT WITH THE NPS COR AND THE HVAC CONTRACTOR. DISCONNECT EQUIPMENT AND MAKE SAFE FOLLOWING PROPER LOCK OUT/TAG OUT PROCEDURES. 2. RETAIN AND PROTECT EXISTING DEVICE/EQUIPMENT THROUGHOUT RETAIN AND PROTECT EXISTING DEVICE/EQUIPMENT THROUGHOUT CONSTRUCTION. 3. DEMO EXISTING T-STAT LOCATION TO INCLUDE DEVICE, CABLING, DEMO EXISTING T-STAT LOCATION TO INCLUDE DEVICE, CABLING, J-BOX AND ASSOCIATED CONDUIT.
AutoCAD SHX Text
KEY NOTES:
AutoCAD SHX Text
PLAN VIEW - ELECTRICAL FIRST FLOOR DEMOLITION PLAN
AutoCAD SHX Text
AutoCAD SHX Text 8'
AutoCAD SHX Text 8'
AutoCAD SHX Text 16'
AutoCAD SHX Text
SCALE OF FEET
AutoCAD SHX Text
TITLE OF SHEET
AutoCAD SHX Text
DRAWING NO.
AutoCAD SHX Text
PMIS/PKG NO.
AutoCAD SHX Text
SHEET
AutoCAD SHX Text
OF
AutoCAD SHX Text
SUB SHEET NO.
AutoCAD SHX Text
DESIGNED:
AutoCAD SHX Text
TECH. REVIEW:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
REPLACE ALAN BIBLE VISITOR CENTER HVAC
AutoCAD SHX Text
LAKE MEAD NATIONAL RECREATION AREA
AutoCAD SHX Text
B. ANDERSON
AutoCAD SHX Text
M. SMITH
AutoCAD SHX Text
B. ANDERSON
AutoCAD SHX Text
APR 2023
AutoCAD SHX Text
AutoCAD SHX Text 25005A
AutoCAD SHX Text 228968
AutoCAD SHX Text
SCALE: 1/8"=1'-0"
AutoCAD SHX Text 27/04/2023 16:50 JENNIFER CHEEK G:\CLIENTS\NPS\LAKE\228968\DRAWINGS\ELEC\E1.1 FIRST FLOOR DEMO PLAN.DWG
AutoCAD SHX Text
FIRST FLOOR ELECTRICAL DEMOLITION PLAN
AutoCAD SHX Text E1.1
AutoCAD SHX Text
AC
AC 5
CU
RF
EF
AC
CU
AC
04/28/2023
AutoCAD SHX Text M
AutoCAD SHX Text M
AutoCAD SHX Text J
AutoCAD SHX Text
(E)AC-3 DISCONNECT
AutoCAD SHX Text
(E)EH-2 DISCONNECT
AutoCAD SHX Text
(E)EH-4 DISCONNECT
AutoCAD SHX Text J
AutoCAD SHX Text
(E)CU-6 DISCONNECT
AutoCAD SHX Text
(E)RTU-1 DISCONNECT
AutoCAD SHX Text M
AutoCAD SHX Text
(E)RTU-4 DISCONNECT
AutoCAD SHX Text
(E)RTU-2 DISCONNECT
AutoCAD SHX Text
(E) EH-1 DISCONNECT 30A/3P TRS20R
AutoCAD SHX Text (E)
AutoCAD SHX Text (E)
AutoCAD SHX Text (E)
AutoCAD SHX Text (E)
AutoCAD SHX Text (E)
AutoCAD SHX Text (E)
AutoCAD SHX Text (E)
AutoCAD SHX Text
(E)EH-3 DISCONNECT
AutoCAD SHX Text
(E)BOOSTER FAN (STARTER)
AutoCAD SHX Text
(E)CU-5 DISCONNECT
AutoCAD SHX Text (E)
AutoCAD SHX Text
GFCI
AutoCAD SHX Text
GFCI
AutoCAD SHX Text
GFCI
AutoCAD SHX Text
GFCI
AutoCAD SHX Text
(E)EH-4
AutoCAD SHX Text
(E)EH-3
AutoCAD SHX Text J
AutoCAD SHX Text M
AutoCAD SHX Text…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .