Questions_and_Answers_0001.pdf
PDF 92 KB Posted
- Attached to
- Replace Water Tanks @ BRCA Federal contract opportunity
- Solicitation number
- 140P6426Q0066
About this file
This is a Questions and Answers (Q&A) document for federal solicitation 140P6426Q0066, Amendment 0001, concerning Water Tank Replacement at BRCA. The document addresses two clarifications submitted by potential offerors regarding the solicitation requirements.
Question 1 addresses the electrical specifications for the water heater installation. The solicitation initially referenced 208V power with allowance for single or three-phase configuration but did not provide existing heater specifications. The government clarified that existing units operate at 120 Volts, 60 Hz, drawing less than 5 Amps, with single-phase service only at all locations. Question 2 clarifies a discrepancy between page 3 and page 12 of the solicitation regarding water heater tank capacity—one reference specified 100-gallon propane and another specified 120-gallon electric. The government confirmed that the Statement of Work (SOW) has been updated to reflect a 120-Gallon minimum tank size as the correct specification for quotation purposes.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Sol_140P6426Q0066_Amd_0001.pdf | ||
| Revised_SOW_-_Replace_WH_0001.pdf | ||
| Price_Schedule_-_Replace_WH.xlsx | XLSX spreadsheet | |
| Price_Schedule_-_Replace_WH.pdf | ||
| Technical_Questionnaire.docx | DOCX document | |
| Wage_Determination_-_Garfiled_Co.pdf | ||
| Sol_140P6426Q0066.pdf | ||
| SOW_-_Replace_WH.pdf | ||
| Technical_Questionnaire.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Solicitation #: 140P6426Q0066
Amendment #: 0001
Water Tank Replacement – BRCA
Questions and Answers listed below:
QUESTIONS:
Question # Question Answer/Response 1.
The solicitation confirms 208V power and allows single or three-phase, but it does not provide existing heater kW ratings or phase confirmation.
Once on site, would you be able to verify the nameplate data (kW, phase, amps) on the existing heaters and coordinate final configuration accordingly?
Please confirm that this is acceptable so we can proceed with compliant supplier quotes.
Existing units are 120 Volts, 60 Hz, less than 5 Amps. Service to these locations are single phase only.
2.
On page 3, the requirement references a 100-gallon propane water heater, while on page 12, it mentions a 120-gallon electric water heater.
Could you please confirm which specification is correct and should be quoted for this requirement?
The SOW has been updated to to reflect the 120-Gallon minimum tank size.