Questions_and_Answers_0001.pdf

PDF 92 KB Posted

Attached to
Replace Water Tanks @ BRCA Federal contract opportunity
Solicitation number
140P6426Q0066
Issued by
Department of the Interior National Park Service Midwest Region

About this file

This is a Questions and Answers (Q&A) document for federal solicitation 140P6426Q0066, Amendment 0001, concerning Water Tank Replacement at BRCA. The document addresses two clarifications submitted by potential offerors regarding the solicitation requirements.

Question 1 addresses the electrical specifications for the water heater installation. The solicitation initially referenced 208V power with allowance for single or three-phase configuration but did not provide existing heater specifications. The government clarified that existing units operate at 120 Volts, 60 Hz, drawing less than 5 Amps, with single-phase service only at all locations. Question 2 clarifies a discrepancy between page 3 and page 12 of the solicitation regarding water heater tank capacity—one reference specified 100-gallon propane and another specified 120-gallon electric. The government confirmed that the Statement of Work (SOW) has been updated to reflect a 120-Gallon minimum tank size as the correct specification for quotation purposes.

View the file

Other files for this federal contract opportunity

Other files attached to Replace Water Tanks @ BRCA, newest first.
File Type Posted
Sol_140P6426Q0066_Amd_0001.pdf PDF
Revised_SOW_-_Replace_WH_0001.pdf PDF
Price_Schedule_-_Replace_WH.xlsx XLSX spreadsheet
Price_Schedule_-_Replace_WH.pdf PDF
Technical_Questionnaire.docx DOCX document
Wage_Determination_-_Garfiled_Co.pdf PDF
Sol_140P6426Q0066.pdf PDF
SOW_-_Replace_WH.pdf PDF
Technical_Questionnaire.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Solicitation #: 140P6426Q0066

Amendment #: 0001

Water Tank Replacement – BRCA

Questions and Answers listed below:

QUESTIONS:

Question # Question Answer/Response 1.

The solicitation confirms 208V power and allows single or three-phase, but it does not provide existing heater kW ratings or phase confirmation.

Once on site, would you be able to verify the nameplate data (kW, phase, amps) on the existing heaters and coordinate final configuration accordingly?

Please confirm that this is acceptable so we can proceed with compliant supplier quotes.

Existing units are 120 Volts, 60 Hz, less than 5 Amps. Service to these locations are single phase only.

2.

On page 3, the requirement references a 100-gallon propane water heater, while on page 12, it mentions a 120-gallon electric water heater.

Could you please confirm which specification is correct and should be quoted for this requirement?

The SOW has been updated to to reflect the 120-Gallon minimum tank size.