Questions_and_Answers_0002.pdf
PDF 191 KB Posted
- Attached to
- Fire System Inspection Service Federal contract opportunity
- Solicitation number
- 140P6425Q0071
About this file
This document is a Questions and Answers (Q&A) amendment for Solicitation #140P6425Q0071 for Fire System Inspections in the OZAR region. The amendment (P0002) addresses four key contractor inquiries regarding the solicitation, with responses indicating changes to the original Statement of Work (SOW) posted in amendment P0001. Specifically, the Q&A clarifies that: (1) all 86 fire extinguishers no longer need replacement, (2) only one lead technician needs NICET Level 2 certification for fire alarm inspections, (3) Appendix 1 contains the only available fire alarm testing information, and (4) the previously required Illinois Cross Connection Inspector Certification is no longer needed for properties located in Missouri.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Sol_140P6425Q0071_Amd_0002.pdf | ||
| Sol_140P6425Q0071_Amd_0001.pdf | ||
| Revised_Statment_of_Work_0001.pdf | ||
| Price_Schedule.xlsx | XLSX spreadsheet | |
| Statement_of_Work.pdf | ||
| Sol_140P6425Q0071.pdf | ||
| DOL_Wage_Determination.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Solicitation #: 140P6425Q0071
Amendment #: P0002
Fire System Inspections – OZAR
Questions and Answers listed below:
QUESTIONS:
Question # Question Answer/Response
1. Can you share any information on why all 86 extinguishers need to be replaced?
They no longer need to all be replaced. A revised Statement of Work was posted with amendment P0001.
2. NICET 2 Qualification for Fire Alarm inspectors: If multiple technicians are assigned for service is it acceptable if one tech holds a Nicet 2 while his helper has a level 1?
Or would all techs onsite be required to have LVl 2?
Just 1 or a lead technician would need to be. A revised Statement of Work was posted with amendment P0001.
3. I was unable to locate Attachment #1 detailing the fire alarm testing, including panel information and the number of devices linked to each panel
The wording was incorrect. The listing in Appendix 1 is the only available information. A revised Statement of Work was posted with amendment P0001.
4. Additionally, the documentation does not clarify why an Illinois Cross Connection Inspector Certification is required when all properties are located in Missouri.
It is not required. The qualifications have been changed. A revised Statement of Work was posted with amendment P0001.