Sol_140P5424R0018_Attach__002-Drawings.pdf
PDF 6 MB Posted
- Attached to
- DBC- REDUCE HUMIDITY LEVELS Federal contract opportunity
- Solicitation number
- 140P5424R0018
About this file
This document appears to be a set of architectural drawings and specifications for the renovation of the Daniel Beard Research Center Archives and Museum at Everglades National Park in Florida. The key details include:
The project involves 100% design plans and specifications for renovations to the facility, including HVAC system replacement, lighting upgrades, new fire protection systems, and architectural finishes. The drawings cover architectural, mechanical, electrical, and fire protection elements. The project is being procured by the National Park Service Southeast Region as Solicitation 140P5424R0018. The drawings provide technical details on the scope of work, such as the replacement of an existing HVAC system, installation of a new clean agent fire suppression system, and updating lighting and electrical systems. Specific information is provided on equipment, materials, installation requirements, and demolition work. The drawings also include a project schedule, phasing plan, and general notes for the contractor.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Sol_140P5424R0018_Amd_0002.pdf | ||
| Sol_140P5424R0005_Amend_0002_Attach__0005-_Q_and_A_0002.pdf | ||
| Sol_140P5424R0018_Amd_0001.pdf | ||
| Sol_140P5424R0018__Attach__0004-Past_Performance_Questionnaire.doc | DOC document | |
| Sol_140P5424R0018_Attach__001-SOW.pdf | ||
| Sol_140P5424R0018.pdf | ||
| Sol_140P5424R0018_Attach__003-WD_FL2024215.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
NORTH
MONROE CO.
CARD SO
UND RO
ADENVIRONMENTAL
KEY WEST
TO 1
CENTER
FLORIDA
BAY
BAY
FLAMINGO
V.C.
SABLE
CAPE
WHITEWATER
OCEAN
V.C.
SOUND
BARNES
MCLAUGHLIN
KEY
MEXICO
GULF OF
OCHOPEE
NAPLES
TO
EVERGLADES
COAST
GULF
V.C.
CITY
FORT MYERS
BIG CYPRESS29
TO
RESERVATION
FL
O
R
ID
A' S
TU
R
N
PI
KE
MONROE COUNTY
HIDDEN LAKE
CENTER
BEARD
DANIEL
LOOP
D
AD
E C
O U
N
TY
M O
N R
O E
C O
U N
TY
ROAD
TAMIAMI
PALM
ROYAL
CENTER
HQ.
RESEARCH
CITY
MAIN
V.C.
FLORIDA
CITY
LEISURE
HOMESTEAD
CHEKIKA
VALLEY
SHARK
MUCCOSUKEE
PRESERVE
COLLIER COUNTY
TAMIAMI TRAIL
NATIONAL
INDIAN
ATLANTIC
LARGO
KEY
NATIONAL
DADE CO.
PARK
BISCAYNE
DRIVECANAL
FORT LAUDERDALE
MIAMI
TO
UNESCO
EVERGLADES NATIONAL PARK
WORLD HERITAGE SITE
PARK OFFICIAL FOR LIMITATIONS.
FEDERAL GOVERNMENT. CHECK WITH LOCAL
PARK HAVE BEEN ACQUIRED BY THE
BOUNDARY OF THE EVERGLADES NATIONAL
NOT ALL LANDS INSIDE THE AUTHORIZED
NOTE
SWAMP OR SLOUGH
PUBLIC AIRPORTS
OBSERVATION TOWER
INFORMATION CENTER
RANGER STATION
PARK HEADQUARTERS
VISITOR CENTER
HQ.
V.C.
CREEK
LEGEND
PARK BOUNDARY
COUNTY LINE
BASIC DATA: BOUNDARY MAPS 160/20,013B 9/89; 160/20,012 3/85; PARK MINI FOLDER 1992; REVISED & REDRAWN 5/93. UPDATED 11/98. SGS.
MEXICO
OF
GULF
LE
E
C O
ATLANTIC
FLORIDA BAY
EVERGLADES
PARK
NATIONAL
KEY LARGO
OCEAN
NORTH MIAMI BEACH
FORT LAUDERDALE
H
EN
D R
Y C
O
KENDALL
PALM BEACH CO.
DADE CO.
BROWARD CO.
FLORIDA CITY
HOMESTEAD
PRINSTON
C O
LL
IE
R C
O
MONROE CO.
PRESERVE
NATIONAL
BIG CYPRESS
MIAMI
NATIONAL
BISCAYNE
PARK
HOLLYWOOD
SCALE IN MILES
10 0 10 20SOUTHERN
FLORIDA
SCALE IN MILES
SCALE IN KILOMETERS
5 0
15105
5 10 LOCATION WITHIN PARK
NAME OF PARK
TITLE OF SHEET
EVERGLADES NATIONAL PARK
PINE ISLAND DISTRICT
STATEREGION COUNTY
SOUTHEAST FLORIDAMIAMI-DADE
PMIS / PKG. NO.
SHEET
DRAWING NO.
OF
DATE:
TECH. REVIEW:
DRAWN:
DESIGNED:REVISIONS SUB SHEET NO.
NATIONAL PARK SERVICE
DENVER SERVICE CENTER
DEPARTMENT OF THE INTERIOR
UNITED STATES
W DEVINE
W DEVINE
MAY 15, 2023
179573
314045
DBC
CENTER
MAY 15, 2023
100% DESIGN
ARCHIVES / MUSEUM RENOVATIONS
Daniel Beard Building - Pine Island District
100% DESIGN COVER SHEET
INDEX OF DRAWINGS
SUB
SHEET TITLE OF SHEET
GR001 COVER SHEET
SHEET
GR
A-001 ARCHITECTURAL SPECIFICATIONS2
CEILING PLAN AND SECTIONS
A-501 ARCHITECTURAL DETAILS
M-001 MECHANICAL LEGEND
8 M-101 MECHANICAL DEMO PLAN
9 M-102 MECHANICAL FLOOR PLAN
10 M-501 MECHANICAL DETAILS
11 M-601 MECHANICAL SCHEDULES
12 E-001 ELECTRICAL LEGEND AND SCHEDULE
E-101 LIGHTING AND FIRE ALARM DEMO PLAN
E-102 POWER AND VOICE DATA DEMO PLAN
E-201 LIGHTING AND FIRE ALARM PLAN
16 E-202 POWER AND VOICE DATA PLAN
17 E-500 ELECTRICAL RISER DIAGRAM
F-001 FIRE PROTECTION LEGEND & CODES19
F-101 FIRE PROTECTION PLAN20
A-101 ARCHITECTURAL SITE PLAN
4 A-102
5 FINISH PLANA-103
E-600 LIGHTING FIXTURE CUT SHEETS
ARCHITECTURAL SPECIFICATIONS
LOCATION WITHIN PARK
NAME OF PARK
TITLE OF SHEET
EVERGLADES NATIONAL PARK
PINE ISLAND DISTRICT
STATEREGION COUNTY
SOUTHEAST FLORIDAMIAMI-DADE
DATE:
TECH. REVIEW:
DRAWN:
DESIGNED:REVISIONS SUB SHEET NO.
PMIS / PKG. NO.
SHEET
DRAWING NO.
OFAPRIL 21, 2023
179573
314045
A-
JB
JB
GENERAL NOTES
1. INFORMATION REGARDING EXISTING CONSTRUCTION OR
CONDITIONS IS BASED ON LIMITED FIELD OBSERVATION
WHICH MAY OR MAY NOT TRULY REFLECT THE EXISTING
CONDITIONS. THE CONTRACTOR SHALL BE RESPONSIBLE
FOR VERIFYING EXISTING CONDITIONS PRIOR TO
CONSTRUCTION.
2. FINAL PHASING WILL BE BASED ON OWNER
REQUIREMENTS AND THE ESTIMATED CONSTRUCTION
DURATION.
3. ALL WORK SHALL BE BASED ON THESE DRAWINGS AND
SPECIFICATIONS (PROOF OF CONCEPT ONLY), ALL TO THE
SATISFACTION OF THE ENGINEER/ARCHITECT AND
OWNER. CONTRACTOR SHALL MAKE
ENGINEER/ARCHITECT AND OWNER AWARE OF
DISCREPANCIES BETWEEN PLANS AND/OR
SPECIFICATIONS AND FIELD CONDITIONS UPON
DISCOVERY, IN WRITING.
4. REFERENCE TO STANDARD SPECIFICATIONS OF A
TECHNICAL SOCIETY, ORGANIZATION, ASSOCIATION, OR
TO CODES OF LOCAL OR STATE AUTHORITIES, SHALL
MEAN THE LATEST STANDARD, CODE, SPECIFICATION OR
TENTATIVE SPECIFICATION ADOPTED AT THE DATE OF
TAKING BIDS, UNLESS SPECIFICALLY STATED OTHERWISE.
5. CONTRACTOR SHALL KEEP PERMITS ON-SITE AND COMPLY
WITH ALL PROVISIONS OF THE PERMITS AND PROVIDE A
COPY TO THE ENGINEER/ARCHITECT AND OWNER PRIOR
TO BEGINNING WORK. CONTRACTOR SHALL ARRANGE AND
SCHEDULE ALL INSPECTIONS AND OBTAIN PERMIT
APPROVALS.
6. CONTRACTOR SHALL BE RESPONSIBLE FOR ALL PERMIT
RELATED INSPECTIONS.
7. CONTRACTOR SHALL HAVE COPIES OF THE PLANS,
SPECIFICATIONS, AND PERMITS FOR THIS PROJECT ON
THE SITE AT ALL TIMES, AND SHALL BE FAMILIAR WITH ALL
APPLICABLE STANDARDS AND SPECIFICATIONS.
8. ALL WORK SHALL BE IN ACCORDANCE WITH ALL FEDERAL,
STATE, AND LOCAL REGULATIONS AND ORDINANCES.
9. CONTRACTOR SHALL VERIFY ALL DIMENSIONS AND
ELEVATIONS SHOWN ON THE PLANS AND COMPARE ALL
PLANS FOR CONFORMANCE AS TO THE LAYOUT OF
DIMENSIONS AND ELEVATIONS. CONTRACTOR SHALL
NOTIFY ENGINEER/ARCHITECT OF ANY DISCREPANCIES
FOR CORRECTIVE ACTION PRIOR TO PROCEEDING WITH
WORK.
10. ENGINEER/ARCHITECT AND OWNER SHALL BE NOTIFIED OF
ANY UNANTICIPATED CONDITIONS THAT ARE
ENCOUNTERED AND WILL DETERMINE WHETHER DESIGN
CHANGES WILL BE REQUIRED.
11. THE USE OF CONSTRUCTION EQUIPMENT SHALL BE
RESTRICTED TO WEEKDAYS BETWEEN THE HOURS OF 7:00
AM AND 7:00 PM OR AS APPROVED IN WRITING. REPAIR
AREAS SHALL AESTHETICALLY MATCH EXISTING AS
CLOSELY AS POSSIBLE AND MATCH WILL BE VERIFIED BY
MOCKUPS WHEN CALLED FOR IN PROJECT
SPECIFICATIONS.
12. CONTRACTOR SHALL PROVIDE WEATHERPROOFING AND
DUST MITIGATION AT AREAS UNDER CONSTRUCTION.
13. FIELD CONDITIONS SHALL TAKE PRECEDENCE OVER
EXISTING DIMENSIONS NOTED ON DRAWINGS.
14. THE FIGURES SHOWN ON THE CONSTRUCTION DRAWINGS
ARE FOR REFERENCE AND GUIDANCE ONLY. THE SCOPE
OF WORK SHALL INCLUDE ALL APPLICABLE CONDITIONS
DESCRIBED IN THE CONSTRUCTION DOCUMENTS
WHETHER EXPLICIT OR IMPLIED AS VERIFIED IN THE FIELD
AND APPROVED BY A/E REPRESENTATIVE AND OWNER.
THE CONTRACTOR SHALL REPORT ANY UNFORESEEN
CONDITIONS OR ADDITIONAL REPAIR ITEMS NOT
IDENTIFIED DURING FIELD INVESTIGATION OR IN THE
CONSTRUCTION DOCUMENTS FOR OWNER A/E APPROVAL
PRIOR TO EXECUTING AND ADDITIONAL WORK BEYOND
THE BASE CONTRACT SCOPE OF WORK.
SAFETY NOTES
1. CONTRACTOR SHALL BE SOLELY AND COMPLETELY
RESPONSIBLE FOR CONDITIONS OF THE JOB SITE WITHIN
LIMITS OF WORK AT ALL TIMES IN CONFORMANCE WITH
ALL, LOCAL, STATE, AND FEDERAL REGULATIONS.
2. CONTRACTOR SHALL SUBMIT A PROJECT SPECIFIC
HEALTH AND SAFETY PLAN FOR REVIEW BY OWNER.
3. APPROPRIATE PERSONAL PROTECTIVE EQUIPMENT AND
FALL PROTECTION SYSTEMS (WHEN APPLICABLE) SHALL
BE WORN/USED IN ACCORDANCE WITH THE PROJECT
APPROVED HEALTH AND SAFETY PLAN.
UTILITY NOTES
1. CONTRACTOR SHALL PROTECT ALL EXISTING UTILITIES
AND WILL BE RESPONSIBLE FOR COST OF REPAIRS FOR
ANY DAMAGES CAUSED DURING CONSTRUCTION
ACTIVITIES.
SITE ACCESS
1. THE FACILITY WILL REMAIN OCCUPIED FOR THE DURATION
OF CONSTRUCTION.
2. CONTRACTOR SHALL MAINTAIN UNINTERRUPTED ACCESS
FOR THE EMPLOYEES TO THE FACILITY, AND COORDINATE
ACTIVITIES WITH THE OWNERS SCHEDULE.
PROTECTION OF EXISTING STRUCTURES
1. CONTRACTOR SHALL PROTECT AREAS OF THE BUILDING
THAT ARE NOT WITHIN THE PROJECT SCOPE.
EH
57A 57D
57B
57C
58A
58B
58C
58D
58E 58F
58G
T
SCREENED
PORCH
57E
VESTIBULE
FIRE SUPPRESSION
EQUIPMENT ROOM
HVAC
EQUIPMENT
ROOM
5'-2"6'-0"
9' -6
7"
5"
1'-1"1'-4"
1/
4"
A
A
ALIGN INTERIOR
WALL SURFACE
58F
58C
58E
A
SIM
A-501
EA-501
E
2 5
A-501 E
A-501 E
A-501 E
SIM
SIM
DETAIL G/A-501
1. INFILL WALL TO MATCH ADJACENT EXISTING.
2. WALL TO BE SEALED TO DECK ABOVE. SEAL ANY
PENETRATIONS THROUGH THE WALL AIR TIGHT.
3. REMOVE PORTION OF EXISTING WALL AND PATCH FOR
INSTALLATION OF NEW DOOR.
4. PROVIDE STUD AND SHEATHING INFILL AT WALL OPENING
SEE DETAIL G ON SHEET A-501.
5. PROVIDE NEW WEATHERSTRIPPING AT EXISTING DOOR
PERIMETER.
6. PROVIDE NEW MASONRY OPENING BELOW CONCRETE
BEAM FOR HVAC EXHAUST/INTAKE LOUVERS. SEE DETAIL J
ON SHEET A-501.
7. PATCH MASONRY WALL WHERE HVAC DUCT WORK HAS
BEEN REMOVED. REPAIR OPENING WITH NEW MASONRY
AND PAINT TO MATCH ADJACENT SURFACE.
1. FIELD VERIFY EXACT LOCATIONS OF EXISTING WALLS AND
OPENINGS.
2. FIELD COORDINATE WITH ELECTRICAL AND MECHANICAL
DISCIPLINES PRIOR TO START OF WORK.
3. REPAIR AND SEAL ANY OPENING IN THE EXISTING
PERIMETER WALLS OF FACILITIES 57 AND 58
4. DIMENSIONS ARE TO FACE OF FINISH AND EDGE OF DOOR
FRAMES UNLESS NOTED OTHERWISE.
GENERAL NOTES
KEY NOTES
LEGEND
WALL OR DOOR TO BE DEMOLISHED
NEW WALL OR WALL TO BE MODIFIED
LOCATION WITHIN PARK
NAME OF PARK
TITLE OF SHEET
EVERGLADES NATIONAL PARK
PINE ISLAND DISTRICT
STATEREGION COUNTY
SOUTHEAST FLORIDAMIAMI-DADE
DATE:
TECH. REVIEW:
DRAWN:
DESIGNED:REVISIONS SUB SHEET NO.
PMIS / PKG. NO.
SHEET
DRAWING NO.
OFAPRIL 21, 2023
179573
314045
WALL TYPE: SEE SHEET A501
DOOR NUMBER
A
JB
JB
SCALE: 3/16" = 1'-0"
FLOOR PLAN1
EH
0 4' 8' 12'
Scale: 3/16" = 1'-0"
ARCHITECTURAL SITE PLAN
A-
57B 57C
58A
58B
58C
58D
58E
58F
58G
SCREENED PORCH
57E
EXPOSED TO SHEATHING
EXISTING GYPBOARD
CEILING
A-102
A-102
2 2
A-501 D
EXISTING JOIST ABOVE
SHEATHING
1 BOUNDRY OF AREA TO RECIEVE
INSULATION ABOVE THE
EXISTING ROOF MEMBRANE
VESTIBULE
SEMI-PERMEABLE GYPSUM VAPOR
AND AIR BARRIER SHEATHING
SUSPENDED ACOUSTICAL
PANEL CEILING
INSTALL MINERAL WOOL BATT INSULATION
OVER EXISTING FIBERGLASS INSULATION
TO TOTAL R-VALUE OF R-30
EPOXY FLOORING WITH
INTEGRAL BASE
9'- 3"
SIMILAR
A-501
A A-501
A
A-501 B
A-501
B SIMILAR
58A588'- 8 1
/2"
EXISTING GYPBOARD
CEILING
EXISTING INSULATION AND
MOISTURE/AIR BARRIER
INSTALL MINERAL WOOL BATT INSULATION
OVER EXISTING FIBERGLASS INSULATION
TO TOTAL R-VALUE OF R-30
A-501 F
1. REMOVE EXISTING BATT INSULATION IN THE ATTIC ABOVE
EXISTING ROOF SYSTEM AND SAVE FOR REUSE, REPAIR
ALL OPENINGS IN THE MEMBRANE AND METAL DECK ROOF
SYSTEM WITH MINERAL WOOL BOARD INSULATION AND
SELF ADHERING SHEET AIR BARRIER TO BE AIR AND
VAPOR BARRIERS. REINSTALL EXISTING BATT INSULATION
AND INSTALL MINERAL WOOL BATT INSULATION TO OBTAIN
AN OVERALL INSULATION VALUE OF R-30.
2. EXISTING CEILING AND AIR/VAPOR BARRIER AT UNDERSIDE
OF ROOF JOIST TO REMAIN. REPAIR AS REQUIRED FOR
INSTALLATION OF LIGHTING, HVAC, AND FIRE PROTECTION
EQUIPMENT.
1. FIELD VERIFY EXACT LOCATIONS OF EXISTING WALLS AND
OPENINGS.
2. FIELD COORDINATE WITH ELECTRICAL AND MECHANICAL
DISCIPLINES PRIOR TO START OF WORK.
GENERAL NOTES
KEY NOTES
LEGEND
LOCATION WITHIN PARK
NAME OF PARK
TITLE OF SHEET
EVERGLADES NATIONAL PARK
PINE ISLAND DISTRICT
STATEREGION COUNTY
SOUTHEAST FLORIDAMIAMI-DADE
DATE:
TECH. REVIEW:
DRAWN:
DESIGNED:REVISIONS SUB SHEET NO.
PMIS / PKG. NO.
SHEET
DRAWING NO.
OFAPRIL 21, 2023
179573
314045
EXISTING CEILING MOUNTED LIGHT FIXTURE
REMOVED AND REPLACED WITH NEW FIXTURE
LAY-IN LIGHT FIXTURE
CEILING DIFUSER
JB
JB
SCALE: 3/16" = 1'-0"
REFLECTED CEILING PLAN1
SCALE: 3/16" = 1'-0"
SECTION ROOM 572
SCALE: 3/16" = 1'-0"
SECTION ROOM 58 AND 58A3
CEILING AC UNIT COORDINATE WITH
MECHANICAL
FIRE SUPRESSION SYSTEM PIPING
SEE FIRE PROTECTION DRAWINGS
0 4' 8' 12'
Scale: 3/16" = 1'-0"
EH
CEILING PLAN AND SECTIONS
A-
2 FOOT BY 4 FOOT SUSPENDED GRID
CEILING SYSTEM
57B
57C
58A
58B
58C
58D
58E 58F
58G
T
SCREENED
PORCH
57EEPOXY FLOORING
VESTIBULE
1. PROVIDE METAL TRANSITION STRIPS AT DOORWAY.
2. PROVIDE TRANSITION THRESHOLD AT EXTERIOR DOORS.
3. PAINT CEILING IN ITS ENTIRETY AFTER INSTALLATION OF
HVAC AND FIRE PROTECTION SYSTEM
4. PAINT ALL WALLS.
5. PREPARE AND PAINT EXISTING HOLLOW METAL DOORS
INTERIOR AND EXTERIOR PRIOR TO INSTALLATION OF
WEATHERSTRIPING AND REINSTALLATION OF SECURITY
HARDWARE.
1. REMOVE EXISTING FLOOR FINISHES IN AREAS RECEIVING
NEW FLOOR FINISHES AND PREPARE CONCRETE FOR EPOXY
FLOORING
2. TEMPORARILY REMOVE PLUMBING FIXTURES AS REQUIRED
FOR INSTALLATION OF THE EPOXY FLOORING, REINSTALL
FIXTURES UPON COMPLETION OF THE FLOORING.
GENERAL NOTES
KEY NOTES
LEGEND
LOCATION WITHIN PARK
NAME OF PARK
TITLE OF SHEET
EVERGLADES NATIONAL PARK
PINE ISLAND DISTRICT
STATEREGION COUNTY
SOUTHEAST FLORIDAMIAMI-DADE
DATE:
TECH. REVIEW:
DRAWN:
DESIGNED:REVISIONS SUB SHEET NO.
PMIS / PKG. NO.
SHEET
DRAWING NO.
OFAPRIL 21, 2023
179573
314045
EPOXY FLOORING
JB
JB
SCALE: 3/16" = 1'-0"
FINISH PLAN1
0 4' 8' 12'
Scale: 3/16" = 1'-0"
EH
FINISH PLAN
1-5/8 STUDS WIRED TO
EXISTING JOINT
MINIMUM 1-1/2 INCH FOIL
FACED MINERAL WOOL
BOARD INSULATION
NON-BITUMINOUS SELF
ADHERING SHEET AIR
BARRIER SEAL FOIL FACE TO
CONCRETE AND BLOCK WALL
GLASS MAT GYPSUM
SHEATHING, 5/8 INCH THICK
HAT CHANNELS 16 INCHES
O.C. WIRED TO JOIST
NON-BITUMINOUS SELF
ADHERING SHEET AIR BARRIER
SEAL SHEATHING FACE TO
CONCRETE AND BLOCK WALL
EDGE ANGLE CONTINUOUS
EXISTING WOOD ROOF TRUSS
EXISTING BATT INSULATION
EXISTING MEMBRANE ROOF
SYSTEM AND INSULATION
EXISTING METAL DECK
EXISTING METAL JOIST
4"
9 GA SUSPENSION WIRE PER
CEILING GRID MANUFACTURERS
REQUIREMENTS CONNECT TO
TOP CORD OF JOIST PRIOR TO
INSTALLATION OF SHEATHING
ACOUSTICAL PANEL
SUSPENDED CEILING
SYSTEMEXISTING GYPBOARD ON
WOOD FURRING
EXISTING METAL FURRING
MAY BE USED IF IN
EXCELLENT CONDITION
SEAL ALL PENETRATIONS AND
SECUREMENT SCREWS WITH
SEALANT
SEAL ALL PENETRATIONS WITH
SELF ADHERING SHEET AIR
BARRIER
NONBITUMINOUS SELF
ADHERING SHEET AIR
BARRIER SEAL FOIL FACE TO
METAL DECK AND JOIST
MINERAL WOOL BATT
INSULATIONOVER EXISTING
BATT INSULATION R-30 TOTAL
A-501 C
SHEATHING CONTINUOUS IN
AREAS 57 THROUGH 57E
EXISTING WALL
EXISTING GYPBOARD ON
WOOD FURRING
CONTINUOUS PRESSURE TREATED
WOOD BLOCKING SET ON VAPOR
BARRIER BEHIND EPOXY BASE
4"
RESINOUS EPOXY FLOORING
WITH INTEGRAL BASE
EXISTING CONCRETE FLOOR
PROVIDE SEALANT
CLOSURES AT ALL
EXTERIOR PENETRATIONS
ALUMINUM VENT CONTINUOS
ALONG WALL AT EPOXY FLOORING
EXISTING BATT INSULATION
EXISTING MEMBRANE ROOF
SYSTEM AND INSULATION
EXISTING METAL DECK
EXISTING METAL JOIST
NON-BITUMINOUS SELF
ADHERING SHEET AIR BARRIER
SEAL FOIL FACE TO METAL DECK
AND JOIST
SEAL ALL PENETRATIONS WITH
SELF ADHERING SHEET AIR
BARRIER
MINIMUM 1-1/2 INCH FOIL
FACED MINERAL WOOL BOARD
INSULATION BEYOND CONTIN.
ALONG EDGE
AT JOIST DOUBLE ANGLE
PROVIDE BACKER ROD AND
SEALANT TO CLOSE
OPENING TO AIR BARRIER
HAT CHANNELS 16 INCHES
O.C. WIRED TO JOIST
GLASS MAT GYPSUM
SHEATHING, 5/8 INCH THICK
DOOR SCHEDULE
DOOR
SIZE
HEIGHT
4'-0"
FRAME
DOOR
NO.
WIDTH MAT.
HD SET
THICK TYPE
2" 2"2" 2" 2"2"
DOOR TYPE
BA
ADD LOUVER 20X20
7'-0" 1-3/4" WOOD
MAT.
A HM
58C 58E 58F
4'-0" 7'-0" 1-3/4" WOOD A HM
3'-0" 7'-0" 1-3/4" WOOD A HM
3'-0" 7'-0" 1-3/4" WOOD B HM
3'-0" 7'-0" 1-3/4" WOOD B HM
EX WOOD EX
EX WOOD EX
EX WOOD EX
EX WOOD EX
TYPE
NO.
SLIP-ON
SLIP-ON
SLIP-ON
SLIP-ON
SLIP-ON
REMARKS
ADD LOUVER
ADD LOUVER
ADD LOUVER
12X10 14X14 12X10
3"
2'- 9"
GLASS MAT GYPSUM
SHEATHING, 5/8 INCH
THICK
HAT CHANNELS AND
SHEATHING
NON-BITUMINOUS SELF
ADHERING SHEET AIR
BARRIER, SEAL SHEATHING
FACE TO CONCRETE AND
BLOCK WALL
NON-BITUMINOUS SELF
ADHERING SHEET AIR
BARRIER, SEAL SHEATHING
FACE TO STEEL DECK
SEALANT
ACOUSTICAL PANEL
CEILING
EXISTING WALL
EXISTING METAL DECK AND ROOFING
EXISTING GYPSUM BOARD
CEILING ROOMS 58, 58A, 58B
GYPSUM SHEATHING
SUSPENDED ACOUSTICAL
PANEL CEILING
EPOXY FLOORING
WITH INTEGRAL BASE
WHERE SHOWN ON
FINISH PLAN
DEFLECTION TRACK
PROVIDE FURRING
CROSS SUPPORT AT
TOP OF WALL 18" O.C.
BRIDGING CONTINUOUS
AT CEILING LEVEL
3-5/8 INCH METAL
STUDS 16"O.C
5/8 INCH MOISTURE/MOLD
RESISTANT TYPE X
GYPSUM BOARD BOTH
SIDES
4"
3-5/8 INCH BATT MINERAL
WOOL INSULATION
SEALANT BOTH SIDES
MINERAL WOOL INSULATION
INSTALLED ABOVE EXISTING
BATT INSULATION R-30 TOTAL
MINIMUM 1-1/2 INCH FOIL FACED
MINERAL WOOL BOARD
INSULATION INSTALLED IN THE
FLUTES OF THE DECK TO THE
WALL AND 6 INCHES DOWN THE
WALL
NON-BITUMINOUS SELF
ADHERING SHEET AIR BARRIER
SEAL FOIL FACE TO CONCRETE,
METAL DECK AND JOIST
GLASS MAT GYPSUM
SHEATHING, 5/8 INCH THICK
HAT CHANNELS 16 INCHES
O.C. WIRED TO JOIST
NON-BITUMINOUS SELF
ADHERING SHEET AIR BARRIER
SEAL SHEATHING FACE TO
CONCRETE AND BLOCK WALL
EDGE ANGLE CONTINUOUS
SEAL ALL PENETRATIONS WITH
SELF ADHERING SHEET AIR
BARRIER
6" 4"
ACOUSTICAL
PANEL
CEILING
EXISTING
METAL DECK
EXISTING CONCRETE BEAM
EXISTING CONCRETE
BLOCK WALL
REPAIR AND SEAL AIR TIGHT EXISTING
(2) 1/2 LAYERS OF RIGID INSULATION
OVER PLASTIC AIR MOISTURE
BARRIER WHERE NEW SYSTEMS ARE
MOUNTED TO JOIST ABOVE
EXISTING METAL JOIST
REPAIR EXISTING GYPSUM BOARD
CEILING AND SEAL AIRTIGHT
WHERE NEW SYSTEMS ARE
ATTACHED OR PENETRATE
SUSPENDED GYPBOARD CEILING
SEAL WALL OPENING ON
ROOM 57E SIDE WITH 1-5/8
INCH STUDS AND SHEATHING,
SEAL AIR TIGHT TO EXISTING
BLOCK WALL
SEAL PENETRATIONS
THROUGH SHEATHING AIR
TIGHT
4"SHEATHING
OVERLAP TYP
FILL CELLS BELOW OPENING
SOLID WITH GROUT
PROVIDE PERIMETER
SEALANT AROUND OPENING
20 GA. STAINLESS STEEL SILL
PAN WIITH DRIP EDGE SET IN
SEALANT
EXHAUST OR INTAKE LOUVER
SEE MECHANICAL
20 GA. STAINLESS STEEL
HEAD FLASHING FULL DEPTH
OF BEAM WITH UP TURNED
INTERIOR LIP AND DRIP EDGE
SEALANT ABOVE AND BELOW
HEAD FLASHING
LOCATION WITHIN PARK
NAME OF PARK
TITLE OF SHEET
EVERGLADES NATIONAL PARK
PINE ISLAND DISTRICT
STATEREGION COUNTY
SOUTHEAST FLORIDAMIAMI-DADE
DATE:
TECH. REVIEW:
DRAWN:
DESIGNED:REVISIONS SUB SHEET NO.
PMIS / PKG. NO.
SHEET
DRAWING NO.
OFAPRIL 21, 2023
179573
314045
JB
JB
SCALE: 1-1/2" = 1'-0"
DETAILA
SCALE: 1-1/2" = 1'-0"
DETAILB
SCALE: 1/4" = 1'-0"
DOOR SCHEDULEI
SCALE: 1-1/2" = 1'-0"
DETAILD
SCALE: 1-1/2" = 1'-0"
DETAILE
SCALE: 3" = 1'-0"
DETAILC
0 1/2' 1' 1 1/2'
Scale: 1 1/2" = 1'-0"
0 3" 6" 9"
Scale: 3" = 1'-0"
0 1' 2' 4'
Scale: 1/2" = 1'-0"
0 2' 4' 8'
Scale: 1/4" = 1'-0"
SCALE: 1/2" = 1'-0"
WALL TYPE AH
SCALE: 1/2" = 1'-0"
DETAILF
SCALE: 1/2" = 1'-0"
DETAILG
SCALE: 1-1/2" = 1'-0"
DETAILJ
EH
ARCHITECTURAL DETAILS
MECHANICAL LEGEND
M-
LOCATION WITHIN PARK
NAME OF PARK
TITLE OF SHEET
EVERGLADES NATIONAL PARK
PINE ISLAND DISTRICT
STATEREGION COUNTY
SOUTHEAST FLORIDAMIAMI-DADE
DATE:
TECH. REVIEW:
DRAWN:
DESIGNED:REVISIONS SUB SHEET NO.
PMIS / PKG. NO.
SHEET
DRAWING NO.
OFMAY 15, 2023
179573
314045
@ AT
A AMP
ABS ACRYLONITRILE BUTADIENE STYRENE PLASTIC
ABV ABOVE
AC AIR CONDITIONING / AIR CONDITIONER
ACM ASBESTOS-CONTAINING MATERIAL
AD ACCESS DOOR
ADA AMERICANS WITH DISABILITIES ACT
AF AIR FILTER
AFF ABOVE FINISHED FLOOR
AFM AIR FLOW MEASURING STATION
AHJ AUTHORITY HAVING JURISDICTION
AHU AIR HANDLING UNIT
AL ACOUSTICAL LINER
ALC AUTOMATED LOGIC CONTROLS
AMB AMBIENT
AP ACCESS PANEL
APD AIR PRESSURE DROP
APPROX APPROXIMATELY
AS AIR SEPARATOR
ASSY ASSEMBLY
ATC AUTOMATIC TEMPERATURE CONTROL
ATT ACOUSTICAL ATTENUATOR
AV AUTOMATIC VENT
B BOILER
BAS BUILDING AUTOMATED SYSTEM
BDD BACKDRAFT DAMPER
BHP BRAKE HORSEPOWER
BLDG BUILDING
BOD BOTTOM OF DUCT
BOT BOTTOM
BTUH BTU PER HOUR
C CENTERLINE
CA COMPRESSED AIR
CAP CAPACITY
CD CONDENSATE DRAIN
CFM CUBIC FEET PER MINUTE
CH CHILLER
CHW CHILLED WATER
CHWR CHILLED WATER RETURN
CHWS CHILLED WATER SUPPLY
CLG CEILING
CO CLEAN OUT, CARBON MONOXIDE
COL COLUMN
CONC CONCRETE
COND CONDENSATE
CONN CONNECTION
CONT CONTINUATION
CP CONTROL PANEL, CONDENSATE PUMP
CPF CHEMICAL POT FEEDER
CR CHEMICAL RETURN
CS CHEMICAL SUPPLY
CT COOLING TOWER
CU CONDENSING UNIT
CV CONTROL VALVE
Cv CONTROL VALVE RATING
CND CONDENSER WATER
CNDR CONDENSER WATER RETURN
CNDS CONDENSER WATER SUPPLY
D DRAIN
dB DECIBELS
DB DRY BULB
DCW DOMESTIC COLD WATER
DH DESICCANT WHEEL UNIT
DDC DIRECT DIGITAL CONTROL
Ø, DIA DIAMETER
DIFF DIFFERENTIAL, DIFFUSER
DISCH DISCHARGE
DN DOWN
DOM DOMESTIC
DPS DIFFERENTIAL PRESSURE SENSOR
DWG DRAWING
DWGS DRAWINGS
E ELECTRICAL, EXHAUST, EXISTING
EA EXHAUST AIR, EACH
EAT ENTERING AIR TEMPERATURE
EC ELECTRICAL CONTRACTOR
EDH ELECTRIC DUCT HEATER
EER ENERGY EFFICIENT RATIO
EF EXHAUST FAN
EH ELECTRIC HEATER
ELEC ELECTRIC, ELECTRICAL
ELEV ELEVATION
ENT ENTERING
EPDM ETHYLENE PROPYLENE DIENE MEMBRANE
EQUIP EQUIPMENT
ERU ENERGY RECOVERY UNIT
ESP EXTERNAL STATIC PRESSURE
ET EXPANSION TANK
EVAP EVAPORATOR
EWT ENTERING WATER TEMPERATURE
EXH EXHAUST
EXIST EXISTING
EXT EXPANSION TANK
EXP EXPANSION
F FAN, DEGREES FAHRENHEIT
FA FRESH AIR
FAI FRESH AIR INTAKE
FC FIELD CONTROLLER
FCO FLOOR CLEANOUT
FCU FAN COIL UNIT
FD FIRE DAMPER, FLOOR DRAIN
FF FINISH FLOOR
FIX FIXTURE
FLA FULL LOAD AMPS
Φ FLAT OVAL
FLR FLOOR
FOB FLAT ON BOTTOM
FOT FLAT ON TOP
FS FLOAT SWITCH
FZ FREEZESTAT
G GAS
GA GAUGE
GAL GALLONS
GALV GALVANIZED
GC GENERAL CONTRACTOR
GP GENERAL PURPOSE
GPH GALLONS PER HOUR
GPM GALLONS PER MINUTE
GIH GRAVITY INTAKE HOOD
GRH GRAVITY RELIEF HOOD
GV GATE VALVE
GSM GALVANIZED SHEET METAL
GYP GYPSUM WALLBOARD
H HUMIDITY
HC HEATING COIL
HD HOOD
HHW HEATING HOT WATER
HHWR HEATING HOT WATER RETURN
HHWS HEATING HOT WATER SUPPLY
HOA HAND-OFF-AUTOMATIC
HOR HORIZONTAL
HP HORSEPOWER, HIGH PRESSURE
HR HOUR
HT HEIGHT
HVAC HEATING, VENTILATING AND AIR CONDITIONING
HWP HOT WATER PUMP
HZ HERTZ
ID INSIDE DIAMETER
IGH INFRARED GAS HEATER
IN INCHES
INDIR INDIRECT WASTE
KW KILOWATT
L LENGTH, LOUVER
LAT LEAVING AIR TEMPERATURE
LDB LEAVING DRY BULB
LF LINEAR FEET
LG LONG
LPR LOW PRESSURE STEAM RETURN
LPS LOW PRESSURE STEAM SUPPLY
LOC LOCATION, LOCATED
LRA LOCKED ROTOR AMPS
LVG LEAVING
LWB LEAVING WET BULB
LWT LEAVING WATER TEMPERATURE
M MECHANICAL
MANUF MANUFACTURER
MAU MAKE-UP AIR UNIT
MAX MAXIMUM
MAX PD MAXIMUM PRESSURE DROP
MBH 1000 BTU PER HOUR
MCA MAXIMUM CIRCUIT AMPS
MECH MECHANICAL
MFG MANUFACTURER
MIN MINIMUM, MINUTES
MNTD MOUNTED
MOCP MAXIMUM OVERCURRENT PROTECTION
MOD MOTOR OPERATED DAMPER
MUA MAKE-UP AIR
MUW MAKE-UP WATER
MVD MANUAL VOLUME DAMPER
N/A NOT APPLICABLE
NATL NATURAL
NC NORMALLY CLOSED, NOISE CRITERIA
NEC NATIONAL ELECTRIC CODE
NG NATURAL GAS
NFPA NATIONAL FIRE PROTECTION ASSOCIATION
NIC NOT IN CONTRACT
NO NORMALLY OPEN, NUMBER
NTS NOT TO SCALE
OA OUTSIDE AIR
OAI OUTSIDE AIR INTAKE
OAT OUTSIDE AIR TEMPERATURE
OBD OPPOSED BLADE DAMPER
OD OUTSIDE DIAMETER
OED OPEN ENDED DUCT
P PUMP, PITCH
PD PRESSURE DROP
PLMB PLUMBING
PRESS PRESSURE
PRV PRESSURE REDUCING VALVE
PSI POUNDS PER SQUARE INCH
PSIG POUNDS PER SQUARE INCH GAUGE
PVC POLYVINYL CHLORIDE
QTY QUANTITY
R RADIUS, RETURN
RA RETURN AIR
RAG RETURN AIR GRILLE
RAT RETURN AIR TEMPERATURE
REF REFRIGERANT
REL RELIEF
REQD REQUIRED
RET RETURN
RH RELATIVE HUMIDITY
RL REFRIGERANT LIQUID
RLA RATED LOAD AMPS
RM ROOM
RPM REVOLUTIONS PER MINUTE
S SUPPLY DIFFUSER
SA SUPPLY AIR
SCR SCREEN
SF SQUARE FOOT
SIM SIMILAR
SOV SHUT OFF VALVE
SP STATIC PRESSURE
SPH STATIC PRESSURE HIGH LIMIT
SPL STATIC PRESSURE LOW LIMIT
SPS STATIC PRESSURE SENSOR
SQ SQUARE
SQFT SQUARE FEET
SS STAINLESS STEEL
STL STEEL
SUP SUPPLY
T-STAT THERMOSTAT
TC TOTAL COOLING
TEMP TEMPERATURE
THK THICK, THICKNESS
TG TRANSFER GRILLE
TRANS TRANSITION
TSP TOTAL STATIC PRESSURE
TYP TYPICAL
UM UTILITY METER
UNO UNLESS NOTED OTHERWISE
USACE US ARMY CORPS OF ENGINEERS
V VENT
VAV VARIABLE AIR VOLUME
VD VOLUME DAMPER
VEL VELOCITY
VTR VENT THROUGH ROOF
W WIDTH, WATT
W/ WITH
WB WET BULB
WC WATER COLUMN
WG WATER GAUGE
WH WATER HEATER
WMS WIRE MESH SCREEN
WPD WATER PRESSURE DROP
WS WATER SOFTENER
ABBREVIATIONS
1. DRAWINGS SHOW APPROXIMATE SIZE AND LOCATION OF ALL HVAC EQUIPMENT AND APPURTENANCES. HOWEVER, ALL EQUIPMENT AND APPURTENANCES NECESSARY FOR COMPLETE AND OPERATIONAL INSTALLATION MAY NOT BE SHOWN. CONTRACTOR SHALL PROVIDE ALL EQUIPMENT AND APPURTENANCES REQUIRED FOR A COMPLETE AND OPERATIONAL SYSTEM. DUCTWORK AND PIPING LAYOUTS SHOWN ON THE DRAWINGS ARE DIAGRAMMATIC. CONTRACTOR SHALL BE FULLY RESPONSIBLE TO DETERMINE THE EXACT ROUTING OF THE DUCTWORK AND PIPING IN ACCORDANCE WITH THE ACTUAL FIELD CONDITIONS AND
CONSTRAINTS.
2. THE CONTRACTOR SHALL VISIT THE SITE AND VERIFY ALL EXISTING CONDITIONS IN THE FIELD BEFORE STARTING CONSTRUCTION. WORK TO BE DONE SHALL BE ALL INCLUSIVE AND ANY WORK NOT SPECIFICALLY MENTIONED BUT REASONABLY IMPLIED SHALL BE INCLUDED. THE INSTALLATION OF HVAC SYSTEM SHALL BE COMPLETE IN ALL RESPECTS AS REQUIRED BY THE CONTRACT DOCUMENTS. PERFORM ALL WORK
REQUIRED TO TIE IN NEW WORK TO EXISTING WORK.
3. FLOOR PLANS AND ROOM LAYOUTS ARE BASED ON THE LATEST AVAILABLE DOCUMENTS AT THE TIME OF DESIGN. CONTRACTOR SHALL VERIFY ALL CURRENT LAYOUTS AT TIME OF SHOP DRAWINGS AND CREATE
ACCURATE WORKING DRAWINGS PRIOR TO SUBMISSION OF EQUIPMENT, ETC.
4. THE CONTRACTOR SHALL COMPLY WITH ALL APPLICABLE FEDERAL, STATE AND MUNICIPAL LAWS AND ORDINANCES.
5. WHERE THE WORDS "FURNISH", "PROVIDE", OR "INSTALL" ARE USED EITHER SINGLY OR IN COMBINATION, THESE WORDS ARE HEREBY INTERPRETED TO MEAN "FURNISH AND INSTALL" OR "PROVIDE AND INSTALL" INCLUDING ALL REQUIRED EQUIPMENT, MATERIALS, AND ASSOCIATED WORK UNLESS SPECIFICALLY NOTED OTHERWISE.
6. THE CONTRACTOR SHALL KEEP AT ALL TIMES THE PROPERTY, ROOF, AND BUILDING FREE FROM TRASH AND DIRT WHICH MAY BE CAUSED BY THEMSELVES OR THEIR SUBCONTRACTORS. THE CONTRACTOR SHALL MAINTAIN THEIR OWN DUMPSTERS ON THE SITE AS REQUIRED FOR THEIR WORK. DUMPSTERS RETAINED BY THE FACILITY SHALL NOT BE USED BY THE CONTRACTOR. NO RUBBISH OR MATERIAL SHALL BE ALLOWED TO
ACCUMULATE IN THE BUILDING, ON THE ROOF, OR ON THE PROPERTY.
7. THE CONTRACTOR SHALL FURNISH THE LABOR AND MATERIAL INCLUDED IN HIS CONTRACT IN AMPLE TIME AND SUFFICIENT QUANTITIES SO THAT ALL WORK MAY BE COMPLETED WITHIN THE DESIGNATED TIME
LIMITS.
8. CONSTRUCTION WASTE TO BE REMOVED AND DISPOSED OF AS PER THE SOW. CONTRACTOR SHALL PROVIDE OWNERSHIP WITH THE FIRST RIGHT OF REFUSAL FOR CERTAIN REUSABLE ITEMS TO INCLUDE BUT NOT
LIMITED TO MOTORS.
9. CONTRACTOR SHALL INSTALL DDC TEMPERATURE CONTROL SYSTEM COMPONENTS AS INDICATED ON THE DRAWINGS AND AS REQUIRED THROUGHOUT THE BUILDING FOR COMPLETE SYSTEMS. WORK SHALL BE ALL INCLUSIVE INCLUDING DEMOLITION, FURNISHING AND INSTALLATION OF NEW CONTROL DEVICES, EQUIPMENT, PANELS, COMPUTER SOFTWARE AND HARDWARE. SEE CONTROL DRAWINGS AND SPECS FOR ADDITIONAL INFORMATION. PATCH AND FINISH ALL SURFACES AFFECTED BY THIS WORK TO MATCH ADJACENT AREAS.
10. ANY INTERIOR PENETRATIONS SHALL BE PATCHED TO MATCH EXISTING SURFACES. PROVIDE ESCUTCHEON PLATES FOR ALL EXPOSED PIPE AND CONDUIT PENETRATIONS. SEAL AROUND ALL DUCT SLAB, WALL, AND PARTITION PENETRATIONS. PRIOR TO ANY STRUCTURAL WALL PENETRATIONS, THE CONTRACTOR SHALL VERIFY AND CONFIRM WHETHER THE WALL IS RATED AND MAKE NECESSARY MODIFICATIONS TO ACCOUNT FOR RATED WALLS AS NEEDED. THIS SHALL INCLUDE ANY FIRE DAMPER, COMBINATION FIRE-SMOKE DAMPER, AND/OR FIRE CAULKING AND SEALING AS REQUIRED TO MAINTAIN THE ASSOCIATED FIRE RATING.
11. CONTRACTOR SHALL BALANCE AND ADJUST THE AIR SIDE OF THE NEW AND MODIFIED HVAC SYSTEMS WHICH ARE PART OF THIS CONTRACT. ADJUST EQUIPMENT TO VALUES SHOWN ON THE PLANS, DETAILS, AND IN
THE SCHEDULES. PROVIDE DETAILED BALANCING REPORTS PER TECHNICAL SPECIFICATIONS.
12. INSTALL ALL EQUIPMENT TO ALLOW REQUIRED MINIMUM ACCESS TO CONTROL PANELS AND ALL COMPONENTS WHICH WOULD REQUIRE SERVICE OR MAINTENANCE AS RECOMMENDED BY THE MANUFACTURER. ALL PRODUCTS SHALL BE INSTALLED PER MANUFACTURER'S INSTRUCTIONS AND RECOMMENDATIONS. PROVIDE LABELING FOR EQUIPMENT AND PIPING.
GENERAL NOTES
NOTE: ABBREVIATIONS ON THIS SHEET MAY NOT ALL BE USED WITHIN THIS SET OF PROJECT DOCUMENTS.
(FOR 4-WAY THROW ARROWS NOT SHOWN)
DIRECTION SHOWN BY ARROWS
CEILING SUPPLY DIFFUSER W/ THROW
SEQUENCE NUMBER
CFM
VOLUME DAMPER
REVISION (LETTER)
FLEXIBLE CONNECTOR
DIRECTION OF AIR FLOW EXHAUST
PUMP
STARTER/DISCONNECT
ROOF VENTILATOR, EXHAUST
FLEXIBLE DUCT
SQUARE ELBOW WITH TURNING VANES
CONNECT TO EXISTING
MOTORIZED DAMPER, OPPOSED BLADE
MOTORIZED DAMPER, PARALLEL BLADE
FIRE / SMOKE DAMPER
FIRE DAMPER
DIRECTION OF AIR FLOW
CENTRIFUGAL FAN
ACCESS DOOR
SUPPLY DIFFUSER, REGISTER, GRILLE
RETURN GRILLE, REGISTER
KEY NOTE (NUMBER)
DIFFUSER, REGISTER OR GRILLE
SYMBOL PER ABBREVIATION LIST
AD
EQUIPMENT SEQUENCE NUMBER
SWITCH
M
M
S
A
DOOR UNDERCUT
B
D1
DETAIL NUMBER
MECHANICAL SYMBOLS
TYPE DEMO UP TO THIS POINT
PIPE CROSS-SECTIONAL VIEW
PROJECT SPECIFIC SYMBOLS
THERMOSTATT
FD
F/S
EXISTING TO REMAIN
REMOVAL / DEMOLITION
NEW WORK
HIDDEN ITEMS
DUCT UP - SEE UPPER LEVEL DWG FOR
CONTINUATION
DUCT DOWN - SEE LOWER LEVEL DWG FOR
CONTINUATION
NOTE: SYMBOLS AND LEGENDS ON THIS SHEET MAY
NOT ALL BE USED WITHIN THIS SET OF PROJECT
DOCUMENTS.
RETURN AIR REGISTER OR GRILLE
SEQUENCE NUMBER
WIDTH x HEIGH
WIDTH x HEIGHT
WxH
WxH
S-1
HHW
R-1
EXHAUST GRILLE, REGISTER
MECHANICAL EQUIPMENT EXISTING TO REMAIN
WALL/DOOR GRILLE, REGISTER
COMBINATION THERMOSTAT/HUMIDISTATTH
INTERNALLY LINED DUCTWORK
TB
LG
SW
VD
DWG
VIEW
SECTION VIEW
1. SPLIT SYSTEMS: WHEN THE SPACE IS NOT IN FIRE ALARM AND THE UNIT SMOKE DETECTOR
DOES NOT DETECT SMOKE, THE UNIT SHALL OPERATEAS FOLLOWS:
a. UNOCCUPIED MODE: THE OA DAMPER SHALL SHUT. THE UNIT SHALL CYCLE
COMPRESSORS TO MAINTAIN SPACE COOLING UNOCCUPIED SET POINT AND SHALL
ENERGIZE THE REVERSING VALVE AND CYCLE COMPRESSORS TO MAINTAIN SPACE
HEATING UNOCCUPIED SETPOINT.
b. OCCUPIED MODE: THE UNIT SHALL OPEN ITS OUTSIDE AIR DAMPER TO THE MINIMUM
OUTSIDE AIR POSITION. THE UNIT SHALL CYCLE THE COMPRESSORS TO MEET THE SPACE
COOLING OCCUPIED SETPOINT AND SHALL ENERGIZE THE REVERSING VALVE AND CYCLE
COMPRESSORS TO MAINTAIN SPACE HEATING OCCUPIED SETPOINT.
SEQUENCE OF OPERATIONS
13. ALL BRANCH DUCTWORK SHALL BE THE SAME SIZE AS THE DIFFUSER CONNECTION SERVED UNLESS NOTED OTHERWISE.
14. DUCT DIMENSIONS SHOWN ARE INSIDE CLEAR DIMENSIONS.
15. MAINTAIN DUCTWORK LEVEL AS HIGH AS POSSIBLE TO THE UNDERSIDE OF STRUCTURE WHILE CONSIDERING SPACE ABOVE FOR PIPING, CONDUIT, AND INSULATION AS NECESSARY. COORDINATE DUCTWORK WITH FIRE PROTECTION, ELECTRICAL AND OTHER TRADES. MAKE OFFSETS AND TRANSITIONS AS REQUIRED TO COORDINATE WITH OTHER TRADES.
16. PROVIDE A FLEXIBLE CONNECTION AT THE INTAKE AND DISCHARGE CONNECTION OF EACH AIR HANDLING UNIT AND FAN.
17. PROVIDE SMOOTH, FULL RADIUS ELBOWS IN SUPPLY, RETURN, AND EXHAUST SYSTEMS. WHERE SPACE IS LIMITED, PROVIDE 90° SQUARE ELBOWS WITH TURNING VANES. TURNING VANES SHALL NOT BE PROVIDED IN RETURN DUCT SYSTEMS.
18. CONTRACTOR SHALL PITCH CONDENSATE DRAIN PIPING AT MIN. 1/4" PER FOOT. ROUTE TO NEAREST DRAIN OR WHERE INDICATED ON PLANS.
19. PROVIDE FULL SIZE TRAPPED AND VENTED CONDENSATE PIPING ROUTED FROM EACH HVAC UNIT TO NEAREST DRAIN. REFER TO PLANS.
20. THE MECHANICAL CONTRACTOR SHALL MAKE CHANGES TO ANY PULLEYS, BELTS, AND/OR DAMPERS AS REQUIRED TO PROVIDE THE BALANCE OF AIR SYSTEMS AS SHOWN ON THE PLANS.
21. ACCESS SHALL BE PROVIDED WHERE MOTORS, FILTERS, CONTROL DEVICES, AND ANY OTHER EQUIPMENT REQUIRING ACCESS FOR SERVICING, REPAIRS, OR MAINTENANCE ARE LOCATED IN WALLS, CHASES, AND/OR ABOVE CEILING.
22. AS-BUILT DRAWINGS: PROVIDE RECORD DRAWINGS SHOWING WORK AS BUILT INCLUDING ALL CHANGES INITIATED BY CONTRACTOR OR OWNER ON COMPLETION OF PROJECT FOR ALL TRADES.
23. REFER TO ARCHITECTURAL DRAWINGS FOR EXACT SIZE, LOCATION AND MOUNTING HEIGHT OF ALL LOUVERS AND/OR EXTERIOR WALL MOUNTED DEVICES.
24. SUBMITTALS - SUBMIT THE FOLLOWING: FANS; SPLIT SYSTEMS; VIBRATION ISOLATION; GRILLES, REGISTERS, AND DIFFUSERS; LOUVERS; SHEET METAL DUCTWORK; PIPING; INSULATION; DUCT LINER; DAMPERS; FLEXIBLE DUCTWORK;
TEST AND BALANCE REPORT; COORDINATED SHOP DRAWINGS FOR REVIEW AND APPROVAL.
logan.grailer Stamp
ACAC
57A
57D
57B
57C
58A
58B
58C
58D
58E 58F
58G
AC
AHU
AHU
DH
DH
RAG
TG
AC
SCREENED
PORCH
41'-8"
T
T
1. DEMOLISH WALL-MOUNTED THERMOSTAT.
2. DEMO AHU AND ALL RELATED HVAC EQUIPMENT,
DUCTWORK, REF PIPING AND COND PIPING.
3. DEMO ALL EXPOSED DUCTWORK, AIR DISTRIBUTION
DEVICES, AND SUPPORTS WITHIN THE ROOM 58 AND
ASSOCIATED SPACES. PATCH HOLES IN GYP BOARD
CEILING FROM PREVIOUS SUPPORTS TO MATCH EXISTING
CONSTRUCTION.
4. DEMO ALL ABOVE CEILING DUCTWORK AND AIR
DISTRIBUTION DEVICES WITHIN ROOM 57 AND ASSOCIATED
SPACES
1. FIELD VERIFY EXACT LOCATIONS OF EXISTING DUCTWORK,
PIPING, AND EQUIPMENT.
2. FIELD COORDINATE WITH ARCHITECTURAL, STRUCTURAL,
AND ELECTRICAL DISCIPLINES PRIOR TO START OF WORK.
GENERAL NOTES
KEY NOTES
0 4' 8' 12'
Scale: 3/16" = 1'-0"
TB
LG
LOCATION WITHIN PARK
NAME OF PARK
TITLE OF SHEET
EVERGLADES NATIONAL PARK
PINE ISLAND DISTRICT
STATEREGION COUNTY
SOUTHEAST FLORIDAMIAMI-DADE
DATE:
TECH. REVIEW:
DRAWN:
DESIGNED:REVISIONS SUB SHEET NO.
PMIS / PKG. NO.
SHEET
DRAWING NO.
OFMAY 15, 2023
179573
314045
SCALE: 3/16" = 1'-0"
MECHANICAL DEMO PLAN1
DEMO DESICCANT
WHEEL UNIT,
DUCTWORK, AND
SUPPLY/INTAKE
GRILLES
EXISTING SIDEWALL
RETURN GRILLE TO
REMAIN
DEMO 24X16 EXTERIOR
LOUVER
SW
OUTDOOR CONDENSING
UNITS EXISTING TO
REMAIN (NIC)
MECHANICAL DEMO PLAN
M-
57C
58A
58B
58C
58D
58E 58F
58G
RAG
SCREENED
PORCH
T
57A 57D
57B
57C
57ETH
TH
1. MOTORIZED DAMPER (INTERLOCKED WITH AHU
OPERATION) AND VOLUME DAMPER IN OA DUCT BEFORE
CONNECTION TO RETURN PLENUM.
2. SUPPLY AIR DUCTS ALL MEET IN A CONNECTING
PIECE/PLENUM ABOVE AHU-2.
3. NEW DOOR GRILLE INSTALLED IN EXISTING DOOR. REFER
TO ARCH.
4. PLACE OUTDOOR UNIT ON 4" TALL CONCRETE
HOUSEKEEPING PAD. ANCHOR EQUIPMENT TO CONCRETE
PAD USING HURRICANE TIE-DOWN BRACKETS INSTALLED
IN ACCORDANCE WITH MIAMI-DADE AND FLORIDA
MECHANICAL CODE STANDARDS.
1. FIELD VERIFY EXACT LOCATIONS OF EXISTING DUCTWORK,
PIPING, AND EQUIPMENT.
2. FIELD COORDINATE WITH ARCHITECTURAL, STRUCTURAL,
AND ELECTRICAL DISCIPLINES PRIOR TO START OF WORK.
3. ALL SUPPLY AIR DUCTWORK FROM AHU-2 TO BE INTERNALLY
LINED.
4. ALL DIMENSIONS IN INCHES.
GENERAL NOTES
KEY NOTES
0 4' 8' 12'
Scale: 3/16" = 1'-0"
MECHANICAL FLOOR PLAN
M-
LOCATION WITHIN PARK
NAME OF PARK
TITLE OF SHEET
EVERGLADES NATIONAL PARK
PINE ISLAND DISTRICT
STATEREGION COUNTY
SOUTHEAST FLORIDAMIAMI-DADE
DATE:
TECH. REVIEW:
DRAWN:
DESIGNED:REVISIONS SUB SHEET NO.
PMIS / PKG. NO.
SHEET
DRAWING NO.
OFMAY 15, 2023
179573
314045
SCALE: 3/16" = 1'-0"
MECHANICAL FLOOR PLAN1
3/4" CONDENSATE OUT
THROUGH WALL OVER
SPLASH BLOCK
PROVIDE SPLASH
BLOCK FOR
CONDENSATE
DISCHARGE
EXISTING SIDEWALL
GRILLE TO REMAIN.
NEW VOLUME
DAMPER BEHIND
EXISTING GRILLE AND
FILTER. BALANCE
RETURN GRILLE TO
1400 CFM.
AHU
HP
HP
AHU
EF
24x24 24x24
R-1200 S-1
S-1
24x24 S-1
10x6 S-2
6x6 S-2
10x10 S-2
S-1
8x6 S-2
TYP 6 TYP 2
AC
HP
RS/L PIPING
OUTDOOR CONDENSING
UNITS EXISTING TO
REMAIN (NIC)
S-1
6x6 S-2
8x6 S-2
8x6 S-2
8x6 S-2
8x6 S-2
8x6 S-2
24x24
24x24 24x24
18x14
18x1416x1410x10 x1 x1 x1
8Ø
Ø
Ø
16x12 x8
8Ø8Ø
8Ø8Ø 8Ø
8Ø
6Ø
6Ø
RS/L PIPING
RS/L PIPING
6Ø
6Ø
6x6 S-2
6x6 S-2 x8
6Ø
6Ø
6Ø
8Ø8Ø8Ø
TB
LG
SW
LVR
LVR
LVR
8Ø
8Ø
6Ø
M-501
M-501
SUPPORT FROM STRUCTURE
NOT TO SCALE
PIPE THROUGH WALL DETAIL2
MECHANICAL DETAILS
M-
LOCATION WITHIN PARK
NAME OF PARK
TITLE OF SHEET
EVERGLADES NATIONAL PARK
PINE ISLAND DISTRICT
STATEREGION COUNTY
SOUTHEAST FLORIDAMIAMI-DADE
DATE:
TECH. REVIEW:
DRAWN:
DESIGNED:REVISIONS SUB SHEET NO.
PMIS / PKG. NO.
SHEET
DRAWING NO.
OFMAY 15, 2023
179573
314045
PACK ANNULAR SPACE WITH
MINERAL WOOL. SEAL ENDS WITH
ACOUSTICAL CAULK.
16 GAGE PIPE SLEEVE
METAL STUD CHANNEL FRAME
AROUND ON STUD WALLS
PIPE SEE
PLANS
FOR SIZE
POSITIVE ACTING CHROME
PLATED ESCUTCHEON
PLATES ON EXPOSED WALLS
ONLY
SPECIFIED INSULATION
STUD WALL OR
CONCRETE SEE PLANS
UNION
AHU-X
DRAW THRU
1 DIMENSION TO BE 1" GREATER THAN SUCTION
PRESSURE OF UNIT (IN W.G.)
2 DIMENSION TO BE 1/2 TOTAL PRESSURE OF UNIT (IN
W.G.)
BLOW THRU
1 DIMENSION TO BE 1"
2 DIMENSION TO BE EQUAL TO TOTAL PRESSURE OF
UNIT (IN W.G.)
TEE WITH SCREW PLUGS FOR CLEANING ACCESS
SCREW PLUG
MAINTAIN SERVICE ACCESS
TO SPLASH BLOCK1
NOT TO SCALE
CONDENSATE DRAIN/TRAP1
NOT TO SCALE
SUPPLY DIFFUSER DETAIL6
NOT TO SCALE
DUCT HANGER DETAIL7
2"Ø WASHER W/ DOUBLE NUT
STRAP RING CLAMP, 12 GAUGE x1-1/2"
WIDE GALV STEEL
3/8"Ø THREADED ROD
LOCK NUT BOTH SIDES
XX"Ø SPIRAL ROUND DUCT
NOT TO SCALE
VERTICAL AHU-1 SPLIT SYSTEM DETAIL4
SA DUCTRA DUCT
FLEXIBLE CONNECTOR
INDOOR AHU-1
FAN ACCESS SECTION
DISCONNECT SWITCH
REFRIGERANT PIPING. ROUTE TO
HEAT PUMP UNIT. SIZE PER
MANUFACTURER'S
RECOMMENDATIONS.
COIL SECTION
CONDENSATE DRAIN
CONNECTION
FILTER RACK24" TALL INSULATED MIXED AIR
SHEET METAL PLENUM
24" WIDE; COORDINATE LENGTH
WITH AVAILABLE CLOSET
DIMENSIONS AND DUCTWORK
CONNECTIONS
EXISTING FLOOR SLAB
NOT TO SCALE
VERTICAL AHU-2 SPLIT SYSTEM DETAIL5
SA DUCT OA DUCT
FLEXIBLE CONNECTOR
INDOOR AHU-2
FAN ACCESS SECTION
MANUAL DAMPER
MOTORIZED DAMPER
DISCONNECT SWITCH
REFRIGERANT PIPING. ROUTE TO
HEAT PUMP UNIT. SIZE PER
MANUFACTURER'S
RECOMMENDATIONS.
COIL SECTION
CONDENSATE DRAIN
CONNECTION
FILTER RACK
24" TALL INSULATED MIXED AIR
SHEET METAL PLENUM
24" WIDE; COORDINATE LENGTH
WITH AVAILABLE CLOSET
DIMENSIONS AND DUCTWORK
CONNECTIONS
EXISTING FLOOR SLAB
OA DUCT TAPS INTO RA DUCT
ABOVE THE CEILING
RA FROM SIDEWALL GRILLE
IN ROOM 58
RA DUCT TURNS INTO SIDE OF
SHEET METAL PLENUM
18"x18" ACCESS DOOR 18"x18" ACCESS DOOR
TB
LG
SW
DIFFUSER CORE
(WHERE SPECIFIED)
LAY-IN CEILING DIFFUSER/GRILLE HARD CEILING
(WHERE SPECIFIED)
FROM STRUCTURE ABOVE
SUPPORT FLEX DUCT
FLEX DUCT
TIGHTENING BAND
REPLACED BY DUCT COLLAR
WITH TAKE-OFFS
FOR RETURN AIR,
1-1/2 x DUCT RADIUS
MAKE BEND RADIUS
NOTE: FLEX DUCT IS
12 GA. STEEL
WIRE
SPIN-IN FITTING WITH DAMPER
DAMPER SHAFT SHALL BE
PARALLEL TO AIRFLOW IN MAIN
DUCT MAIN
SCALE: NTS
DUCT MOUNTED SUPPLY DIFFUSER AND RETURN GRILLE DETAIL3
DUCTWORK MAIN
RECTANGULAR DUCTWORK SHOE
MANUAL VOLUME DAMPER
SUPPLY DIFFUSER OR RETURN GRILLE
SA DIRECTION
RA DIRECTION
SEE PLANS FOR SIZE
24x16 RA DUCT
DISCHARGE SUPPLY PLENUM
FULL SIZE OF CABINET W/ 1"
INTERNAL LINER
DISCHARGE SUPPLY PLENUM
FULL SIZE OF CABINET W/ 1"
INTERNAL LINER
MECHANICAL SCHEDULES
M-
LOCATION WITHIN PARK
NAME OF PARK
TITLE OF SHEET
EVERGLADES NATIONAL PARK
PINE ISLAND DISTRICT
STATEREGION COUNTY
SOUTHEAST FLORIDAMIAMI-DADE
DATE:
TECH. REVIEW:
DRAWN:
DESIGNED:REVISIONS SUB SHEET NO.
PMIS / PKG. NO.
SHEET
DRAWING NO.
OFMAY 15, 2023
179573
314045
TB
LG
SW
E-
LIGHTING
ELECTRICAL SYMBOLS LEGEND
POWER SEE ELECTRICAL SPECIFICATIONS FOR MOUNTING HEIGHTS.
ABBREVIATIONS
J
J
EF
WP
WP
F
DUPLEX RECEPTACLE - SEE ELECTRICAL SPECIFICATIONS FOR MOUNTING HEIGHTS.
MOUNT 18" AFF (TYP.)
(WP) WEATHERPROOF
(H) HORIZONTALLY MOUNTED
(C) CEILING MOUNTED
AMPERES
AIR CONDITIONING
ALTERNATING CURRENT
ABOVE FINISHED FLOOR
ABOVE FINISHED GRADE
AUTHORITY HAVING JURISDICTION
AIR HANDLING UNIT
AMERICAN WIRE GAUGE
CONDUIT
COUNTER HEIGHT
CARBON MONOXIDE
CONCRETE
CONDUIT
COPPER
DISCONNECT
ENCLOSED CIRCUIT BREAKER
ELECTRICAL
EMERGENCY
ENERGY MANAGEMENT SYSTEM
ELECTRICAL METALLIC TUBING
EXHAUST FAN
ELECTRIC WATER COOLER
EXISTING
A A/C
AC
AFF
AFG
AHJ
AHU
AWG
C
CH
CM
CONC
COND
CU
DISC
ECB
ELEC
EM
EMS
EMT
EF
EWC
EX
FA
FACP
FBC
FMC
GFI
GND
GRC
HVAC
IMC
IWH
I.G.
J
KAIC
KCMIL
KVA
KW
LED
LTG
MC
MCP
MCU
MH
N
NA
FIRE ALARM
FIRE ALARM CONTROL PANEL
FLORIDA BUILDING CODE
FLEXIBLE METAL CONDUIT
GROUND FAULT INTERRUPTER
GROUND
GALVANIZED RIGID CONDUIT
HEATING, VENTILATING AND AIR
CONDITIONING
INSTANTANEOUS WATER HEATER
INTERMEDIATE METAL CONDUIT
ISOLATED GROUND
JUNCTION
(THOUSAND) AMPERE INTERRUPTING
CAPACITY
THOUSANDS OF CIRCULAR MILLS
KILOVOLT-AMPERES
KILOWATT
LIGHT EMITTING DIODE
LIGHTING
METAL CLAD
MOTOR CIRCUIT PROTECTION
MASTER CONTROL UNIT
MEAN HEIGHT
NEUTRAL
NOT APPLICABLE
DOUBLE DUPLEX RECEPTACLE. MOUNT 18" AFF (TYP.)
"GFI" DUPLEX RECEPTACLE/GROUND FAULT INTERRUPTING
"GFI" DUPLEX RECEPTACLE/GROUND FAULT INTERRUPTING/WEATHERPROOF COVER
"GFI" DOUBLE DUPLEX RECEPTACLE/GROUND FAULT INTERRUPTING
"GFI" DOUBLE DUPLEX RECEPTACLE/GROUND FAULT INTERRUPTING, COUNTER HEIGHT
DUPLEX RECEPTACLE - TOP HALF SWITCHED - MOUNT 18" AFF
DUPLEX RECEPTACLE, COUNTER HEIGHT = 5" ABOVE COUNTER TOP SPLASH
DOUBLE DUPLEX RECEPTACLE, COUNTER HEIGHT
DUPLEX RECEPTACLE - FLUSH MOUNTED IN FLOOR BOX.
DOUBLE DUPLEX RECEPTACLE MOUNTED TOGETHER IN A FLUSH MOUNTED FLOOR BOX.
SPECIAL PURPOSE OUTLET - COORDINATE EXACT NEMA CONFIGURATION AMPACITY RATING
AS INDICATED.
CEILING FAN JUNCTION BOX (SIZE AS REQUIRED PER N.E.C.).
WALL MOUNTED JUNCTION BOX (SIZE AS REQUIRED PER N.E.C.).
MOTOR
(EF) EXHAUST FAN
PHOTO CELL
ELECTRICAL SERVICE SHUNT TRIP BREAK GLASS STATION
SQUARE "D" CLASS#900 1-K15 W/ CLASS 9001-K25 STAINLESS STEEL COVER
PLATE. ENGRAVE "SERVICE DISCONNECT" MOUNT 7'-0" AFF./WEATHERPROOF HOUSING
GROUND BAR
NEC
NEMA
NFPA
NF
NIC
NL
O.C.
P
PNL
PVC
RGS
RM
RMC
RNC
SPD
SPEC
SS
TYP
UON
V W
WP
NATIONAL ELECTRICAL CODE
NATIONAL ELECTRICAL
MANUFACTURERS ASSOCIATION
NATIONAL FIRE PROTECTION
ASSOCIATION
NON-FUSED
NOT IN CONTRACT
NIGHT LIGHT
ON CENTER
POLE
PANELBOARD
POLYVINYL CHLORIDE
RIGID GALVANIZED STEEL
ROOM
RIGID METAL CONDUIT
RIGID NONMETALLIC CONDUIT
SURGE PROTECTION DEVICE
SPECIFICATION
STAINLESS STEEL
TYPICAL
UNLESS OTHERWISE NOTED
VOLTS
WIRE
WEATHERPROOF
GB
(SEE LIGHTING FIXTURE SCHEDULE)
SWITCHES
BRANCH CIRCUIT PANELBOARD, 120/208V, UNDER 250 VOLTS,
SURFACE MOUNTED, U.O.N.
BRANCH CIRCUIT PANELBOARD, 480/277V, SURFACE MOUNTED
U.O.N.
FUSED DISCONNECT SWITCH, 3-POLE, TOP NUMBER INDICATES
SWITCH RATING, ASTERISK INDICATES TO FUSE ACCORDING TO
MANUFACTURERS RECOMMENDATIONS. NEMA 1 RATED
INDOORS, NEMA 3R RATED OUTDOORS.
COMBINATION STARTER/DISCONNECT SWITCH, 3-POLE, 30AMP,
FUSED. NEMA SIZE 1 NEMA RATED INDOORS, NEMA 3R RATED
OUTDOORS.
UTILITY TRANSFORMER
HVAC/PLUMBING EQUIPMENT LABEL
303*
SERVICE, DISTRIBUTION, AND EQUIPMENT
TOGGLE-TYPE SWITCH - TOGGLE TYPE. SEE ELECTRICAL SPECIFICATIONS FOR
MOUNTING HEIGHTS. LOWER CASE LETTER INDICATES SWITCH LEG
CONTROLLED.
OS
OS
2X4 RECESSED LED, HATCHING INDICATES EMERGENCY FIXTURE
1X4 RECESSED LED, HATCHING INDICATES EMERGENCY FIXTURE
RECESSED DOWNLIGHT, HATCHING INDICATES EMERGENCY FIXTURE
WALL SCONCE - HATCHING INDICATES EMERGENCY FIXTURE
EXIT SIGN - SINGLE FACE- ARROW INDICATES DIRECTION OF EGRESS
(IF PRESENT) - CEILING MOUNTED UON
EXIT SIGN - SINGLE FACE - ARROW INDICATES DIRECTION OF EGRESS
(IF PRESENT) - WALL MOUNTED
EXIT SIGN - DOUBLE FACE - ARROW INDICATES DIRECTION OF EGRES
(IF PRESENT) - CEILING MOUNTED
COMBINATION EXIT SIGN/EMERGENCY LIGHT - HATCHING INDICATES
FACING, ARROWS INDICATE DIRECTION OF EGRESS (IF PRESENT),
CEILING MOUNTED UON
DUAL-HEAD EMERGENCY LIGHT WITH BATTERY BACKUP
C = CEILING MOUNTED
M MOTOR RATED SWITCH - 1 POLE OR 2 POLE AS REQUIRED. 30 AMP OR AS REQUIRED
BY CIRCUIT WITH INTEGRAL THERMAL OVERLOADS.
WALL MOUNTED DUAL-TECHNOLOGY LOW-VOLTAGE OCCUPANCY SENSOR SWITCH.
LOWER CASE LETTER INDICATES SWITCH LEG CONTROLLED. PROVIDE POWER PACKS
FOR SWITCH LEG.
CEILING MOUNTED DUAL-TECHNOLOGY LOW-VOLTAGE OCCUPANCY SENSOR SWITCH.
LOWER CASE (a) INDICATES SWITCH LEG CONTROLLED. PROVIDE POWER PACKS FOR
EACH SWITCH LEG.
PC
(3) 3 WAY
(4) 4 WAY
(2) DOUBLE POLE
(P) WITH PILOT LIGHT INDICATION
(D) DIMMER
(K) KEY
a
DATA/COMM/TELEVISION
DATA/COMM OUTLET WITH FLUSH MOUNTED 4-11/16" SQUARE
SINGLE GANG JUNCTION BOX. PROVIDE BLANK BUILDING
STANDARD COVER PLATE. EXTEND 1" CONCEALED CONDUIT TO
ABOVE ACCESSIBLE CEILING AND STUB-OUT WITH PLASTIC
BUSHING OR AS NOTED. INSTALL PULL WIRE.
CH = COUNTER HEIGHT.
TELEPHONE TERMINAL BOARD, 3/4" THICK x (LENGTH PER PLAN) x
8'-0" HIGH PLYWOOD BACKBOARD
TELEVISION COAXIAL OUTLET WITH FLUSH MOUNTED 4-11/16"
SQUARE SINGLE GANG JUNCTION BOX. PROVIDE BLANK BUILDING
STANDARD COVER PLATE. EXTEND 1" CONCEALED CONDUIT TO
ABOVE ACCESSIBLE CEILING AND STUB-OUT WITH PLASTIC
BUSHING, OR AS NOTED. INSTALL PULL WIRE.
COMBINATION POWER OUTLET AND DATA/COMM OUTLET
MOUNTED FLUSH IN FLOOR. PROVIDE POWER CIRCUIT AND EMPTY
3/4" DATA/COMM CONCEALED CONDUIT TO VERTICAL WALL FOR
ACCESS.
FLUSH MOUNTED 4-11/16" SQUARE SINGLE GANG JUNCTION BOX
FOR CARD READER. EXTEND 1" CONCEALED CONDUIT TO ABOVE
ACCESSIBLE CEILING AND STUB-OUT WITH PLASTIC BUSHING. OR
AS NOTED. INSTALL PULL WIRE.
TV
CR
LIGHTING FIXTURE SCHEDULE
TYPE
A
MANUFACTURER & CATALOG NO. DESCRIPTION LAMPS WATTS REMARKS
LED 40W
LIGHTING FIXTURE SCHEDULE NOTES:
ALL LAMPING COLOR TEMPERATURE SHALL BE 3500K MINIMUM FOR ALL LIGHTING FIXTURES.
REFER TO ARCHITECTURAL REFLECTED CEILING PLAN FOR EXACT FINAL LOCATION OF LIGHTING FIXTURES.
COORDINATE THE ACTUAL TYPE OF CEILING FOR EACH FIXTURE WITH ARCHITECTURAL REFLECTED CEILING PLANS AND
PROVIDE FIXTURE TRIM AS REQUIRED.
3.
4.
PROVIDE ALL DEVICES, DRYWALL FLANGES, MOUNTING EQUIPMENT, CHAIN, STRAIN RELIEFS, CLIPS, ESCUTCHEONS, PLATES AND STRUCTURAL SUPPORTS FOR THE INSTALLATION AND CONNECTION OF ALL LIGHTING FIXTURES.
1.
2.
NOTE: PROVIDE ALL REQUIRED MOUNTING HARDWARE AND WIRING TO CONNECT LIGHTING FIXTURES AT HOLLOW CORE, POST TENSION SLAB & STRUCTURAL STEEL LOCATIONS INCLUDING BOXES, HANGER BARS, STRUCTURAL APPROVED FASTENER'S AND UL APPROVED
CONNECTORS.
Z
VOLTS
120/277
5W AS APPROVED BY OWNER120LEDLED EMERGENCY LIGHT WITH 90 MIN. INTEGRAL EMERGENCY
BATTERY PACK
2'X4' FLAT PANEL LED
SURE-LITES: SEL-25-SD-SQ
Y 5W AS APPROVED BY OWNERLEDLED EMERGENCY LIGHT AND EXIT SIGN COMBO WITH 90 MIN.
INTEGRAL EMERGENCY BATTERY PACKSURE-LITES: APC-H-7-R-SQ 120/277
TGS LIGHTING: 8824WS-C-T-F-RM
XX
a
C 120/277 MOUNT TO WALL AT SAME HEIGHT AS FIXTURE REPLACED35WLED
PROVIDE SURFACE MOUNT KIT (OPTION SK) FOR FIXTURES
DESIGNATED FOR AREAS WITH HARD CEILINGS
COOPER METALUX: 4SNLED-LD5-48SL-UNV-L840-U-CD-1 4' SURFACE MOUNT LED STRIP
FIRE ALARM DEVICES
FAAP
FACP FIRE ALARM CONTROL SUB-PANEL, SURFACE MOUNTED UON
FIRE ALARM ANNUNCIATOR PANEL
CLEAN AGENT CONTROL PANEL
MANUAL FIRE ALARM PULL STATION
HORN/STROBE - WALL-MOUNTED, C = CEILING MOUNTED
STROBE - WALL-MOUNTED, C = CEILING MOUNTED
SMOKE DETECTOR, IONIZATION TYPE, CEILING MOUNTED
F
F
F
LOCATION WITHIN PARK
NAME OF PARK
TITLE OF SHEET
EVERGLADES NATIONAL PARK
PINE ISLAND DISTRICT
STATEREGION COUNTY
SOUTHEAST FLORIDAMIAMI-DADE
DATE:
TECH. REVIEW:
DRAWN:
DESIGNED:REVISIONS SUB SHEET NO.
PMIS / PKG. NO.
SHEET
DRAWING NO.
OFMAY 15, 2023
179573
314045
B 120/27740WLEDTGS LIGHTING: 8814WS-C-T-F-RM 1'X4' FLAT PANEL LED AS APPROVED BY OWNER a
AL
AL
MG
ELECTRICAL LEGEND AND SCHEDULE
E-
CACP
57A
57D
57B
57C
58A
58B
58C
58D
58E 58F
58G
SCREENED
PORCH
41'-8"
F F
F
F
F C
C
C C
C
C
F
F C
F C
1. EXISTING LIGHTING FIXTURES, EMERGENCY LIGHTS, AND
EXIT SIGNAGE IN THIS ROOM TO BE DEMOLISHED. REMOVE
FIXTURE, SUPPORTS AND APPURTENANCES. SECURE
EXISTING CIRCUITS FOR RECONNECTION TO
REPLACEMENT FIXTURES.
2. REMOVE EXISTING FIRE ALARM DEVICES FOR CEILING
DEMOLITION. SECURE DEVICES AND CONDUCTORS FOR
REINSTALLATION/RECONNECTION. REFER TO NEW WORK
PLAN ON SHEET E-201.
3. NOT USED
4. NOT USED
5. NOT USED
6. DEMOLISH EXISTING FIXTURE. ALL OTHER FIXTURES AND
SWITCHING FOR THIS LIGHTING CIRCUIT ARE EXISTING TO
REMAIN.
7. DEMOLISH EXISTING WALL SWITCH AND ALL ASSOCIATED
CONDUIT AND CONDUCTORS.
8. EXISTING FIRE ALARM DEVICE TO BE RELOCATED. REFER
TO SHEET E-201 FOR NEW LOCATION.
9. EXISTING LIGHTING FIXTURES, EMERGENCY LIGHTS, AND
EXIT SIGNAGE IN THIS ROOM TO BE DEMOLISHED. REMOVE
FIXTURE, SUPPORTS, APPURTENANCES, CONDUIT AND
WIRE. MAINTAIN POWER TO OTHER LIGHT FIXTURES TO
REMAIN THAT ARE OUTSIDE OF THE SCOPE OF WORK.
SWITCHING EXISTING TO REMAIN UON.
1. TRACE EXISTING FIXTURE CIRCUITS BACK TO HOST PANEL
PRIOR TO BEGINNING DEMOLITION WORK. LABEL LIGHTING
JUNCTION BOXES WITH PANEL AND CIRCUIT SERVING
LIGHTS.
2. FIELD VERIFY LOCATION AND COUNT OF EXISTING LIGHTING
FIXTURES BEFORE BEGINNING WORK.
3. UNLESS OTHERWISE NOTED, ALL SWITCHES ARE EXISTING
TO REMAIN FOR RECONNECTION TO NEW FIXTURES. REFER
TO SHEET E-201 FOR LIGHTING PLAN. CONTRACTOR TO
NOTE THE LIGHT FIXTURES AND DEVICES CONTROLLED BY
EACH SWITCH FOR RECONNECTION TO NEW LIGHT
FIXTURES.
GENERAL NOTES
KEY NOTES
SCALE: 3/16" = 1'-0"
LIGHTING AND FIRE ALARM DEMOLITION PLAN1
LOCATION WITHIN PARK
NAME OF PARK
TITLE OF SHEET
EVERGLADES NATIONAL PARK
PINE ISLAND DISTRICT
STATEREGION COUNTY
SOUTHEAST FLORIDAMIAMI-DADE
DATE:
TECH. REVIEW:
DRAWN:
DESIGNED:REVISIONS SUB SHEET NO.
PMIS / PKG. NO.
SHEET
DRAWING NO.
OFMAY 15, 2023
179573
314045
0 4' 8' 12'
Scale: 3/16" = 1'-0"
1 2 1 2
1 2
AL
AL
MG
LIGHTING AND FIRE ALARM DEMO PLAN
57A
57D
57B
57C
58A
58B
58C
58D
58E 58F
58G
AC
AHU
AHU
DH
DH
AC
SCREENED
PORCH
41'-8"
1. TRACE CIRCUITS FOR EXISTING POWER AND VOICE/DATA
DEVICES IN THIS AREA INCLUDING RECEPTACLES,
VOICE/DATA OUTLETS, EXHAUST FANS, ETC. INTERCEPT
EXISTING CIRCUITS TO DEVICES AND REROUTE TO NEW
PANEL 'D'. REFER TO SHEET E-202 FOR CIRCUITING.
2. DEMOLISH ALL EXISTING POWER AND VOICE/DATA DEVICES
INCLUDING RECEPTACLES, VOICE/DATA OUTLETS, EXHAUST
FANS, ETC. WITHIN THIS SPACE. REMOVE CONDUIT, WIRE,
AND SUPPORTS BACK TO SOURCE OR FIRST UPSTREAM
JUNCTION BOX OUTSIDE OF THE SCOPE OF WORK.
3. POWER DEVICES IN THIS ROOM ARE EXISTING TO REMAIN
AND WILL BE RE-FED FROM NEW PANEL 'D'. TRACE
CIRCUIT(S) AND NOTE ON PANEL SCHEDULE.
4. EXISTING AC UNIT TO BE DEMOLISHED. DISCONNECT
CONDUCTORS AND REMOVE CONDUIT, ELECTRICAL
DISCONNECT SWITCH, WIRING AND SUPPORTS BACK TO
SOURCE. MARK CIRCUIT BREAKER IN PANEL AS 'SPARE'.
5. EXISTING AHU ABOVE CEILING TO BE DEMOLISHED.
DISCONNECT UNIT AND REMOVE CONDUIT, WIRE, AND
FEEDERS BACK TO SOURCE. MARK CIRCUIT BREAKER IN
PANEL AS 'SPARE'.
6. DESICCANT WHEEL UNIT TO BE DEMOLISHED. DISCONNECT
UNIT AND REMOVE CONDUIT, ELECTRICAL DISCONNECT
SWITCH, WIRE, AND FEEDERS BACK TO SOURCE. MARK
CIRCUIT BREAKER IN PANEL AS 'SPARE.'
7. EXISTING DEHUMIDIFIER UNIT TO BE DEMOLISHED.
DISCONNECT UNIT AND REMOVE CONDUIT, WIRE, AND
BRANCH CIRCUIT BACK TO SOURCE. MARK CIRCUIT BREAKER
IN PANEL AS 'SPARE'.
8. EXISTING AHU IN CLOSET TO BE DEMOLISHED. DISCONNECT
UNIT AND REMOVE CONDUIT, WIRE, AND FEEDERS BACK TO
SOURCE. MARK CIRCUIT BREAKER IN PANEL AS 'SPARE'.
9. EXISTING PANEL 'MDP' TO REMAIN.
10. EXISTING PANEL FED FROM FUSED SWITCHBOARD TO
REMAIN.
11. EXISTING DISCONNECT SWITCH FOR FUSED SWITCHBOARD
TO REMAIN.
12. EXISTING FUSED SWITCHBOARD TO REMAIN.
1. TRACE EXISTING POWER CIRCUITS BACK TO HOST PANEL
PRIOR TO BEGINNING DEMOLITION WORK.
2. FIELD VERIFY LOCATION AND COUNT OF EXISTING DEVICES.
3. MAKE ALL NECESSARY CONNECTIONS AND EXTENSIONS OF
EXISTING CIRCUITS REQUIRED TO MAINTAIN POWER TO
DEVICES OUTSIDE OF THE SCOPE OF WORK THROUGHOUT
CONSTRUCTION.
GENERAL NOTES
KEY NOTES
SCALE: 3/16" = 1'-0"
POWER AND VOICE DATA DEMOLITION PLAN1
LOCATION WITHIN PARK
NAME OF PARK
TITLE OF SHEET
EVERGLADES NATIONAL PARK
PINE ISLAND DISTRICT
STATEREGION COUNTY
SOUTHEAST FLORIDAMIAMI-DADE
DATE:
TECH. REVIEW:
DRAWN:
DESIGNED:REVISIONS SUB SHEET NO.
PMIS / PKG. NO.
SHEET
DRAWING NO.
OFMAY 15, 2023
179573
314045
0 4' 8' 12'
Scale: 3/16" = 1'-0"
AL
AL
MG
POWER AND VOICE DATA DEMO PLAN
58A
58B
58C
58D
58E
58F
58G
SCREENED
PORCH
57A
57D
57B
57C
57E
58D A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A A
Y
A
Y
Y
Z
D-15 D-15 D-15 D-15
D-15 D-15 D-15 D-15
D-15 D-15 D-15 D-15
D-15
Y D-15
OS
OS
A
D-15 D-15
OS
D-15
A
A
A
D-153
D-15
D-15
A D-15
A
D-15
D-15
C C a b a b a b a b a b a b a b a bF F
F
F
F
C
C
C C
C
C Z
Z
B
A A
A
A
A A C
C
F
F C
F C
Y
Z
1. RECONNECT NEW FIXTURES TO EXISTING LIGHTING CIRCUITS
AND SWITCHING.
2. REINSTALL FIRE ALARM DEVICE IN REPLACEMENT CEILING AT
PREVIOUS LOCATION. EXTEND EXISTING FIRE ALARM
CONDUCTORS TO NEW CLEAN AGENT CONTROL PANEL IN
ROOM 58A AND RECONNECT. REFER TO SHEET E-202 FOR
LOCATION OF NEW CLEAN AGENT CONTROL PANEL. TYPICAL
FOR FOR ALL FIRE ALARM DEVICES UON.
3. REINSTALL FIRE ALARM DEVICE AT NEW LOCATION. EXTEND
EXISTING FIRE ALARM CONDUCTORS TO NEW CLEAN AGENT
CONTROL PANEL IN ROOM 58A AND RECONNECT. REFER TO
SHEET E-202 FOR LOCATION OF NEW CLEAN AGENT CONTROL
PANEL.
4. PROVIDE NEW SMOKE DETECTOR MOUNTED TO CEILING.
CONNECT TO NEW CLEAN AGENT CONTROL PANEL IN ROOM
58A. REFER TO SHEET E-202 FOR LOCATION OF NEW CLEAN
AGENT CONTROL PANEL.
1. UNLESS OTHERWISE NOTED CIRCUITS CONSIST OF (2) #12
AWG + #12 G IN 1/2" EMT CONDUIT.
2. PROVIDE UNSWITCHED HOT CONDUCTOR TO EMERGENCY
FIXTURES TO PROVIDE AUTOMATIC-ON OPERATION IN THE
CASE OF POWER LOSS.
3. FOR CLARITY, ONLY NEW SWITCHES ARE SHOWN. REFER TO
DRAWING E-101 FOR LOCATION OF ALL SWITCHING.
4. COORDINATE MOUNTING HEIGHTS OF LIGHT FIXTURES WITH
CEILING HEIGHTS ON ARCHITECTURAL PLANS FOR NEW
CEILINGS.
5. REFER TO SHEET F-001 FOR CLEAN AGENT SYSTEM FIRE
ALARM RISER DIAGRAM.
GENERAL NOTES
KEY NOTES
SCALE: 3/16" = 1'-0"
LIGHTING AND FIRE ALARM PLAN1
LOCATION WITHIN PARK
NAME OF PARK
TITLE OF SHEET
EVERGLADES NATIONAL PARK
PINE ISLAND DISTRICT
STATEREGION COUNTY
SOUTHEAST FLORIDAMIAMI-DADE
DATE:
TECH. REVIEW:
DRAWN:
DESIGNED:REVISIONS SUB SHEET NO.
PMIS / PKG. NO.
SHEET
DRAWING NO.
OFMAY 15, 2023
179573
314045
A A
A
A
A
A
A
A
A
A
A
A A
A
0 4' 8' 12'
Scale: 3/16" = 1'-0"
AL
AL
MG
LIGHTING AND FIRE ALARM PLAN
58A
58B
58C
58D
58E
58F
58G
RAG
SCREENED
PORCH
57A
57D
57B
57C
57E
58D
PANEL 'D'
D-1 D-1 D-1
D-3 D-3 D-3
D-1
D-1
D-3 D-5
D-3 D-3
D-3
D-5
D-7
D-7
D-9
D-9
D-11
D-13
D-13 D-6:8
ACD-17
D-17 D-17
D-17
D-17
D-17
D-19
D-19
D-21
D-21
D-21
WP
WP D-2:4 D-10:12
(2)#8 AWG + #8G IN
3/4" C.
(2)#12 AWG + #12G
IN 1/2" C.
(2)#8 AWG + #8G IN
3/4" C.
(2)#12 AWG + #12G
IN 1/2" C.
(2)#12 AWG + #12 G. IN
1/2" C.
D-14:16
D-18:20
FACP
CACP
J
J
D-24
D-22
(2)#12 AWG + #12G
IN 1/2" C.
(2)#12 AWG + #12G
IN 1/2" C.
1. EXISTING RECEPTACLES WITHIN THIS SPACE TO BE
RECONNECTED TO NEW PANEL 'D' LOCATED IN ROOM 57.
2. PROVIDE 60A, 240V RATED SAFETY SWITCH IN NEMA 3R
ENCLOSURE FOR HVAC.
3. AC-1 CASSETTE FOR MINI-SPLIT SYSTEM MOUNTED ABOVE
CEILING. UNIT IS POWERED FROM EXTERIOR UNIT HP-3.
ROUTE (2) #12 AWG + #12 G. IN 1/2"C TO EXTERIOR UNIT FOR
POWER.
4. EXHAUST FAN MOUNTED IN BATHROOM CEILING. CONNECT
TO BATHROOM LIGHTING CIRCUIT D-15. CONTROL VIA
BATHROOM LIGHT SWITCH. CONNECT FAN CONTROL RELAY
TO FIRE ALARM PANEL CONTACTOR FOR AUTOMATIC
SHUTDOWN DURING A FIRE ALARM EVENT.
This is the start of the file's text. The full file is on GovTribe.