Sol_140P5424R0018_Attach__002-Drawings.pdf

PDF 6 MB Posted

Attached to
DBC- REDUCE HUMIDITY LEVELS Federal contract opportunity
Solicitation number
140P5424R0018
Issued by
Department of the Interior National Park Service Southeast Region

About this file

This document appears to be a set of architectural drawings and specifications for the renovation of the Daniel Beard Research Center Archives and Museum at Everglades National Park in Florida. The key details include:

The project involves 100% design plans and specifications for renovations to the facility, including HVAC system replacement, lighting upgrades, new fire protection systems, and architectural finishes. The drawings cover architectural, mechanical, electrical, and fire protection elements. The project is being procured by the National Park Service Southeast Region as Solicitation 140P5424R0018. The drawings provide technical details on the scope of work, such as the replacement of an existing HVAC system, installation of a new clean agent fire suppression system, and updating lighting and electrical systems. Specific information is provided on equipment, materials, installation requirements, and demolition work. The drawings also include a project schedule, phasing plan, and general notes for the contractor.

View the file

Other files for this federal contract opportunity

Other files attached to DBC- REDUCE HUMIDITY LEVELS, newest first.
File Type Posted
Sol_140P5424R0018_Amd_0002.pdf PDF
Sol_140P5424R0005_Amend_0002_Attach__0005-_Q_and_A_0002.pdf PDF
Sol_140P5424R0018_Amd_0001.pdf PDF
Sol_140P5424R0018__Attach__0004-Past_Performance_Questionnaire.doc DOC document
Sol_140P5424R0018_Attach__001-SOW.pdf PDF
Sol_140P5424R0018.pdf PDF
Sol_140P5424R0018_Attach__003-WD_FL2024215.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

NORTH

MONROE CO.

CARD SO

UND RO

ADENVIRONMENTAL

KEY WEST

TO 1

CENTER

FLORIDA

BAY

BAY

FLAMINGO

V.C.

SABLE

CAPE

WHITEWATER

OCEAN

V.C.

SOUND

BARNES

MCLAUGHLIN

KEY

MEXICO

GULF OF

OCHOPEE

NAPLES

TO

EVERGLADES

COAST

GULF

V.C.

CITY

FORT MYERS

BIG CYPRESS29

TO

RESERVATION

FL

O

R

ID

A' S

TU

R

N

PI

KE

MONROE COUNTY

HIDDEN LAKE

CENTER

BEARD

DANIEL

LOOP

D

AD

E C

O U

N

TY

M O

N R

O E

C O

U N

TY

ROAD

TAMIAMI

PALM

ROYAL

CENTER

HQ.

RESEARCH

CITY

MAIN

V.C.

FLORIDA

CITY

LEISURE

HOMESTEAD

CHEKIKA

VALLEY

SHARK

MUCCOSUKEE

PRESERVE

COLLIER COUNTY

TAMIAMI TRAIL

NATIONAL

INDIAN

ATLANTIC

LARGO

KEY

NATIONAL

DADE CO.

PARK

BISCAYNE

DRIVECANAL

FORT LAUDERDALE

MIAMI

TO

UNESCO

EVERGLADES NATIONAL PARK

WORLD HERITAGE SITE

PARK OFFICIAL FOR LIMITATIONS.

FEDERAL GOVERNMENT. CHECK WITH LOCAL

PARK HAVE BEEN ACQUIRED BY THE

BOUNDARY OF THE EVERGLADES NATIONAL

NOT ALL LANDS INSIDE THE AUTHORIZED

NOTE

SWAMP OR SLOUGH

PUBLIC AIRPORTS

OBSERVATION TOWER

INFORMATION CENTER

RANGER STATION

PARK HEADQUARTERS

VISITOR CENTER

HQ.

V.C.

CREEK

LEGEND

PARK BOUNDARY

COUNTY LINE

BASIC DATA: BOUNDARY MAPS 160/20,013B 9/89; 160/20,012 3/85; PARK MINI FOLDER 1992; REVISED & REDRAWN 5/93. UPDATED 11/98. SGS.

MEXICO

OF

GULF

LE

E

C O

ATLANTIC

FLORIDA BAY

EVERGLADES

PARK

NATIONAL

KEY LARGO

OCEAN

NORTH MIAMI BEACH

FORT LAUDERDALE

H

EN

D R

Y C

O

KENDALL

PALM BEACH CO.

DADE CO.

BROWARD CO.

FLORIDA CITY

HOMESTEAD

PRINSTON

C O

LL

IE

R C

O

MONROE CO.

PRESERVE

NATIONAL

BIG CYPRESS

MIAMI

NATIONAL

BISCAYNE

PARK

HOLLYWOOD

SCALE IN MILES

10 0 10 20SOUTHERN

FLORIDA

SCALE IN MILES

SCALE IN KILOMETERS

5 0

15105

5 10 LOCATION WITHIN PARK

NAME OF PARK

TITLE OF SHEET

EVERGLADES NATIONAL PARK

PINE ISLAND DISTRICT

STATEREGION COUNTY

SOUTHEAST FLORIDAMIAMI-DADE

PMIS / PKG. NO.

SHEET

DRAWING NO.

OF

DATE:

TECH. REVIEW:

DRAWN:

DESIGNED:REVISIONS SUB SHEET NO.

NATIONAL PARK SERVICE

DENVER SERVICE CENTER

DEPARTMENT OF THE INTERIOR

UNITED STATES

W DEVINE

W DEVINE

MAY 15, 2023

179573

314045

DBC

CENTER

MAY 15, 2023

100% DESIGN

ARCHIVES / MUSEUM RENOVATIONS

Daniel Beard Building - Pine Island District

100% DESIGN COVER SHEET

INDEX OF DRAWINGS

SUB

SHEET TITLE OF SHEET

GR001 COVER SHEET

SHEET

GR

A-001 ARCHITECTURAL SPECIFICATIONS2

CEILING PLAN AND SECTIONS

A-501 ARCHITECTURAL DETAILS

M-001 MECHANICAL LEGEND

8 M-101 MECHANICAL DEMO PLAN

9 M-102 MECHANICAL FLOOR PLAN

10 M-501 MECHANICAL DETAILS

11 M-601 MECHANICAL SCHEDULES

12 E-001 ELECTRICAL LEGEND AND SCHEDULE

E-101 LIGHTING AND FIRE ALARM DEMO PLAN

E-102 POWER AND VOICE DATA DEMO PLAN

E-201 LIGHTING AND FIRE ALARM PLAN

16 E-202 POWER AND VOICE DATA PLAN

17 E-500 ELECTRICAL RISER DIAGRAM

F-001 FIRE PROTECTION LEGEND & CODES19

F-101 FIRE PROTECTION PLAN20

A-101 ARCHITECTURAL SITE PLAN

4 A-102

5 FINISH PLANA-103

E-600 LIGHTING FIXTURE CUT SHEETS

ARCHITECTURAL SPECIFICATIONS

LOCATION WITHIN PARK

NAME OF PARK

TITLE OF SHEET

EVERGLADES NATIONAL PARK

PINE ISLAND DISTRICT

STATEREGION COUNTY

SOUTHEAST FLORIDAMIAMI-DADE

DATE:

TECH. REVIEW:

DRAWN:

DESIGNED:REVISIONS SUB SHEET NO.

PMIS / PKG. NO.

SHEET

DRAWING NO.

OFAPRIL 21, 2023

179573

314045

A-

JB

JB

GENERAL NOTES

1. INFORMATION REGARDING EXISTING CONSTRUCTION OR

CONDITIONS IS BASED ON LIMITED FIELD OBSERVATION

WHICH MAY OR MAY NOT TRULY REFLECT THE EXISTING

CONDITIONS. THE CONTRACTOR SHALL BE RESPONSIBLE

FOR VERIFYING EXISTING CONDITIONS PRIOR TO

CONSTRUCTION.

2. FINAL PHASING WILL BE BASED ON OWNER

REQUIREMENTS AND THE ESTIMATED CONSTRUCTION

DURATION.

3. ALL WORK SHALL BE BASED ON THESE DRAWINGS AND

SPECIFICATIONS (PROOF OF CONCEPT ONLY), ALL TO THE

SATISFACTION OF THE ENGINEER/ARCHITECT AND

OWNER. CONTRACTOR SHALL MAKE

ENGINEER/ARCHITECT AND OWNER AWARE OF

DISCREPANCIES BETWEEN PLANS AND/OR

SPECIFICATIONS AND FIELD CONDITIONS UPON

DISCOVERY, IN WRITING.

4. REFERENCE TO STANDARD SPECIFICATIONS OF A

TECHNICAL SOCIETY, ORGANIZATION, ASSOCIATION, OR

TO CODES OF LOCAL OR STATE AUTHORITIES, SHALL

MEAN THE LATEST STANDARD, CODE, SPECIFICATION OR

TENTATIVE SPECIFICATION ADOPTED AT THE DATE OF

TAKING BIDS, UNLESS SPECIFICALLY STATED OTHERWISE.

5. CONTRACTOR SHALL KEEP PERMITS ON-SITE AND COMPLY

WITH ALL PROVISIONS OF THE PERMITS AND PROVIDE A

COPY TO THE ENGINEER/ARCHITECT AND OWNER PRIOR

TO BEGINNING WORK. CONTRACTOR SHALL ARRANGE AND

SCHEDULE ALL INSPECTIONS AND OBTAIN PERMIT

APPROVALS.

6. CONTRACTOR SHALL BE RESPONSIBLE FOR ALL PERMIT

RELATED INSPECTIONS.

7. CONTRACTOR SHALL HAVE COPIES OF THE PLANS,

SPECIFICATIONS, AND PERMITS FOR THIS PROJECT ON

THE SITE AT ALL TIMES, AND SHALL BE FAMILIAR WITH ALL

APPLICABLE STANDARDS AND SPECIFICATIONS.

8. ALL WORK SHALL BE IN ACCORDANCE WITH ALL FEDERAL,

STATE, AND LOCAL REGULATIONS AND ORDINANCES.

9. CONTRACTOR SHALL VERIFY ALL DIMENSIONS AND

ELEVATIONS SHOWN ON THE PLANS AND COMPARE ALL

PLANS FOR CONFORMANCE AS TO THE LAYOUT OF

DIMENSIONS AND ELEVATIONS. CONTRACTOR SHALL

NOTIFY ENGINEER/ARCHITECT OF ANY DISCREPANCIES

FOR CORRECTIVE ACTION PRIOR TO PROCEEDING WITH

WORK.

10. ENGINEER/ARCHITECT AND OWNER SHALL BE NOTIFIED OF

ANY UNANTICIPATED CONDITIONS THAT ARE

ENCOUNTERED AND WILL DETERMINE WHETHER DESIGN

CHANGES WILL BE REQUIRED.

11. THE USE OF CONSTRUCTION EQUIPMENT SHALL BE

RESTRICTED TO WEEKDAYS BETWEEN THE HOURS OF 7:00

AM AND 7:00 PM OR AS APPROVED IN WRITING. REPAIR

AREAS SHALL AESTHETICALLY MATCH EXISTING AS

CLOSELY AS POSSIBLE AND MATCH WILL BE VERIFIED BY

MOCKUPS WHEN CALLED FOR IN PROJECT

SPECIFICATIONS.

12. CONTRACTOR SHALL PROVIDE WEATHERPROOFING AND

DUST MITIGATION AT AREAS UNDER CONSTRUCTION.

13. FIELD CONDITIONS SHALL TAKE PRECEDENCE OVER

EXISTING DIMENSIONS NOTED ON DRAWINGS.

14. THE FIGURES SHOWN ON THE CONSTRUCTION DRAWINGS

ARE FOR REFERENCE AND GUIDANCE ONLY. THE SCOPE

OF WORK SHALL INCLUDE ALL APPLICABLE CONDITIONS

DESCRIBED IN THE CONSTRUCTION DOCUMENTS

WHETHER EXPLICIT OR IMPLIED AS VERIFIED IN THE FIELD

AND APPROVED BY A/E REPRESENTATIVE AND OWNER.

THE CONTRACTOR SHALL REPORT ANY UNFORESEEN

CONDITIONS OR ADDITIONAL REPAIR ITEMS NOT

IDENTIFIED DURING FIELD INVESTIGATION OR IN THE

CONSTRUCTION DOCUMENTS FOR OWNER A/E APPROVAL

PRIOR TO EXECUTING AND ADDITIONAL WORK BEYOND

THE BASE CONTRACT SCOPE OF WORK.

SAFETY NOTES

1. CONTRACTOR SHALL BE SOLELY AND COMPLETELY

RESPONSIBLE FOR CONDITIONS OF THE JOB SITE WITHIN

LIMITS OF WORK AT ALL TIMES IN CONFORMANCE WITH

ALL, LOCAL, STATE, AND FEDERAL REGULATIONS.

2. CONTRACTOR SHALL SUBMIT A PROJECT SPECIFIC

HEALTH AND SAFETY PLAN FOR REVIEW BY OWNER.

3. APPROPRIATE PERSONAL PROTECTIVE EQUIPMENT AND

FALL PROTECTION SYSTEMS (WHEN APPLICABLE) SHALL

BE WORN/USED IN ACCORDANCE WITH THE PROJECT

APPROVED HEALTH AND SAFETY PLAN.

UTILITY NOTES

1. CONTRACTOR SHALL PROTECT ALL EXISTING UTILITIES

AND WILL BE RESPONSIBLE FOR COST OF REPAIRS FOR

ANY DAMAGES CAUSED DURING CONSTRUCTION

ACTIVITIES.

SITE ACCESS

1. THE FACILITY WILL REMAIN OCCUPIED FOR THE DURATION

OF CONSTRUCTION.

2. CONTRACTOR SHALL MAINTAIN UNINTERRUPTED ACCESS

FOR THE EMPLOYEES TO THE FACILITY, AND COORDINATE

ACTIVITIES WITH THE OWNERS SCHEDULE.

PROTECTION OF EXISTING STRUCTURES

1. CONTRACTOR SHALL PROTECT AREAS OF THE BUILDING

THAT ARE NOT WITHIN THE PROJECT SCOPE.

EH

57A 57D

57B

57C

58A

58B

58C

58D

58E 58F

58G

T

SCREENED

PORCH

57E

VESTIBULE

FIRE SUPPRESSION

EQUIPMENT ROOM

HVAC

EQUIPMENT

ROOM

5'-2"6'-0"

9' -6

7"

5"

1'-1"1'-4"

1/

4"

A

A

ALIGN INTERIOR

WALL SURFACE

58F

58C

58E

A

SIM

A-501

EA-501

E

2 5

A-501 E

A-501 E

A-501 E

SIM

SIM

DETAIL G/A-501

1. INFILL WALL TO MATCH ADJACENT EXISTING.

2. WALL TO BE SEALED TO DECK ABOVE. SEAL ANY

PENETRATIONS THROUGH THE WALL AIR TIGHT.

3. REMOVE PORTION OF EXISTING WALL AND PATCH FOR

INSTALLATION OF NEW DOOR.

4. PROVIDE STUD AND SHEATHING INFILL AT WALL OPENING

SEE DETAIL G ON SHEET A-501.

5. PROVIDE NEW WEATHERSTRIPPING AT EXISTING DOOR

PERIMETER.

6. PROVIDE NEW MASONRY OPENING BELOW CONCRETE

BEAM FOR HVAC EXHAUST/INTAKE LOUVERS. SEE DETAIL J

ON SHEET A-501.

7. PATCH MASONRY WALL WHERE HVAC DUCT WORK HAS

BEEN REMOVED. REPAIR OPENING WITH NEW MASONRY

AND PAINT TO MATCH ADJACENT SURFACE.

1. FIELD VERIFY EXACT LOCATIONS OF EXISTING WALLS AND

OPENINGS.

2. FIELD COORDINATE WITH ELECTRICAL AND MECHANICAL

DISCIPLINES PRIOR TO START OF WORK.

3. REPAIR AND SEAL ANY OPENING IN THE EXISTING

PERIMETER WALLS OF FACILITIES 57 AND 58

4. DIMENSIONS ARE TO FACE OF FINISH AND EDGE OF DOOR

FRAMES UNLESS NOTED OTHERWISE.

GENERAL NOTES

KEY NOTES

LEGEND

WALL OR DOOR TO BE DEMOLISHED

NEW WALL OR WALL TO BE MODIFIED

LOCATION WITHIN PARK

NAME OF PARK

TITLE OF SHEET

EVERGLADES NATIONAL PARK

PINE ISLAND DISTRICT

STATEREGION COUNTY

SOUTHEAST FLORIDAMIAMI-DADE

DATE:

TECH. REVIEW:

DRAWN:

DESIGNED:REVISIONS SUB SHEET NO.

PMIS / PKG. NO.

SHEET

DRAWING NO.

OFAPRIL 21, 2023

179573

314045

WALL TYPE: SEE SHEET A501

DOOR NUMBER

A

JB

JB

SCALE: 3/16" = 1'-0"

FLOOR PLAN1

EH

0 4' 8' 12'

Scale: 3/16" = 1'-0"

ARCHITECTURAL SITE PLAN

A-

57B 57C

58A

58B

58C

58D

58E

58F

58G

SCREENED PORCH

57E

EXPOSED TO SHEATHING

EXISTING GYPBOARD

CEILING

A-102

A-102

2 2

A-501 D

EXISTING JOIST ABOVE

SHEATHING

1 BOUNDRY OF AREA TO RECIEVE

INSULATION ABOVE THE

EXISTING ROOF MEMBRANE

VESTIBULE

SEMI-PERMEABLE GYPSUM VAPOR

AND AIR BARRIER SHEATHING

SUSPENDED ACOUSTICAL

PANEL CEILING

INSTALL MINERAL WOOL BATT INSULATION

OVER EXISTING FIBERGLASS INSULATION

TO TOTAL R-VALUE OF R-30

EPOXY FLOORING WITH

INTEGRAL BASE

9'- 3"

SIMILAR

A-501

A A-501

A

A-501 B

A-501

B SIMILAR

58A588'- 8 1

/2"

EXISTING GYPBOARD

CEILING

EXISTING INSULATION AND

MOISTURE/AIR BARRIER

INSTALL MINERAL WOOL BATT INSULATION

OVER EXISTING FIBERGLASS INSULATION

TO TOTAL R-VALUE OF R-30

A-501 F

1. REMOVE EXISTING BATT INSULATION IN THE ATTIC ABOVE

EXISTING ROOF SYSTEM AND SAVE FOR REUSE, REPAIR

ALL OPENINGS IN THE MEMBRANE AND METAL DECK ROOF

SYSTEM WITH MINERAL WOOL BOARD INSULATION AND

SELF ADHERING SHEET AIR BARRIER TO BE AIR AND

VAPOR BARRIERS. REINSTALL EXISTING BATT INSULATION

AND INSTALL MINERAL WOOL BATT INSULATION TO OBTAIN

AN OVERALL INSULATION VALUE OF R-30.

2. EXISTING CEILING AND AIR/VAPOR BARRIER AT UNDERSIDE

OF ROOF JOIST TO REMAIN. REPAIR AS REQUIRED FOR

INSTALLATION OF LIGHTING, HVAC, AND FIRE PROTECTION

EQUIPMENT.

1. FIELD VERIFY EXACT LOCATIONS OF EXISTING WALLS AND

OPENINGS.

2. FIELD COORDINATE WITH ELECTRICAL AND MECHANICAL

DISCIPLINES PRIOR TO START OF WORK.

GENERAL NOTES

KEY NOTES

LEGEND

LOCATION WITHIN PARK

NAME OF PARK

TITLE OF SHEET

EVERGLADES NATIONAL PARK

PINE ISLAND DISTRICT

STATEREGION COUNTY

SOUTHEAST FLORIDAMIAMI-DADE

DATE:

TECH. REVIEW:

DRAWN:

DESIGNED:REVISIONS SUB SHEET NO.

PMIS / PKG. NO.

SHEET

DRAWING NO.

OFAPRIL 21, 2023

179573

314045

EXISTING CEILING MOUNTED LIGHT FIXTURE

REMOVED AND REPLACED WITH NEW FIXTURE

LAY-IN LIGHT FIXTURE

CEILING DIFUSER

JB

JB

SCALE: 3/16" = 1'-0"

REFLECTED CEILING PLAN1

SCALE: 3/16" = 1'-0"

SECTION ROOM 572

SCALE: 3/16" = 1'-0"

SECTION ROOM 58 AND 58A3

CEILING AC UNIT COORDINATE WITH

MECHANICAL

FIRE SUPRESSION SYSTEM PIPING

SEE FIRE PROTECTION DRAWINGS

0 4' 8' 12'

Scale: 3/16" = 1'-0"

EH

CEILING PLAN AND SECTIONS

A-

2 FOOT BY 4 FOOT SUSPENDED GRID

CEILING SYSTEM

57B

57C

58A

58B

58C

58D

58E 58F

58G

T

SCREENED

PORCH

57EEPOXY FLOORING

VESTIBULE

1. PROVIDE METAL TRANSITION STRIPS AT DOORWAY.

2. PROVIDE TRANSITION THRESHOLD AT EXTERIOR DOORS.

3. PAINT CEILING IN ITS ENTIRETY AFTER INSTALLATION OF

HVAC AND FIRE PROTECTION SYSTEM

4. PAINT ALL WALLS.

5. PREPARE AND PAINT EXISTING HOLLOW METAL DOORS

INTERIOR AND EXTERIOR PRIOR TO INSTALLATION OF

WEATHERSTRIPING AND REINSTALLATION OF SECURITY

HARDWARE.

1. REMOVE EXISTING FLOOR FINISHES IN AREAS RECEIVING

NEW FLOOR FINISHES AND PREPARE CONCRETE FOR EPOXY

FLOORING

2. TEMPORARILY REMOVE PLUMBING FIXTURES AS REQUIRED

FOR INSTALLATION OF THE EPOXY FLOORING, REINSTALL

FIXTURES UPON COMPLETION OF THE FLOORING.

GENERAL NOTES

KEY NOTES

LEGEND

LOCATION WITHIN PARK

NAME OF PARK

TITLE OF SHEET

EVERGLADES NATIONAL PARK

PINE ISLAND DISTRICT

STATEREGION COUNTY

SOUTHEAST FLORIDAMIAMI-DADE

DATE:

TECH. REVIEW:

DRAWN:

DESIGNED:REVISIONS SUB SHEET NO.

PMIS / PKG. NO.

SHEET

DRAWING NO.

OFAPRIL 21, 2023

179573

314045

EPOXY FLOORING

JB

JB

SCALE: 3/16" = 1'-0"

FINISH PLAN1

0 4' 8' 12'

Scale: 3/16" = 1'-0"

EH

FINISH PLAN

1-5/8 STUDS WIRED TO

EXISTING JOINT

MINIMUM 1-1/2 INCH FOIL

FACED MINERAL WOOL

BOARD INSULATION

NON-BITUMINOUS SELF

ADHERING SHEET AIR

BARRIER SEAL FOIL FACE TO

CONCRETE AND BLOCK WALL

GLASS MAT GYPSUM

SHEATHING, 5/8 INCH THICK

HAT CHANNELS 16 INCHES

O.C. WIRED TO JOIST

NON-BITUMINOUS SELF

ADHERING SHEET AIR BARRIER

SEAL SHEATHING FACE TO

CONCRETE AND BLOCK WALL

EDGE ANGLE CONTINUOUS

EXISTING WOOD ROOF TRUSS

EXISTING BATT INSULATION

EXISTING MEMBRANE ROOF

SYSTEM AND INSULATION

EXISTING METAL DECK

EXISTING METAL JOIST

4"

9 GA SUSPENSION WIRE PER

CEILING GRID MANUFACTURERS

REQUIREMENTS CONNECT TO

TOP CORD OF JOIST PRIOR TO

INSTALLATION OF SHEATHING

ACOUSTICAL PANEL

SUSPENDED CEILING

SYSTEMEXISTING GYPBOARD ON

WOOD FURRING

EXISTING METAL FURRING

MAY BE USED IF IN

EXCELLENT CONDITION

SEAL ALL PENETRATIONS AND

SECUREMENT SCREWS WITH

SEALANT

SEAL ALL PENETRATIONS WITH

SELF ADHERING SHEET AIR

BARRIER

NONBITUMINOUS SELF

ADHERING SHEET AIR

BARRIER SEAL FOIL FACE TO

METAL DECK AND JOIST

MINERAL WOOL BATT

INSULATIONOVER EXISTING

BATT INSULATION R-30 TOTAL

A-501 C

SHEATHING CONTINUOUS IN

AREAS 57 THROUGH 57E

EXISTING WALL

EXISTING GYPBOARD ON

WOOD FURRING

CONTINUOUS PRESSURE TREATED

WOOD BLOCKING SET ON VAPOR

BARRIER BEHIND EPOXY BASE

4"

RESINOUS EPOXY FLOORING

WITH INTEGRAL BASE

EXISTING CONCRETE FLOOR

PROVIDE SEALANT

CLOSURES AT ALL

EXTERIOR PENETRATIONS

ALUMINUM VENT CONTINUOS

ALONG WALL AT EPOXY FLOORING

EXISTING BATT INSULATION

EXISTING MEMBRANE ROOF

SYSTEM AND INSULATION

EXISTING METAL DECK

EXISTING METAL JOIST

NON-BITUMINOUS SELF

ADHERING SHEET AIR BARRIER

SEAL FOIL FACE TO METAL DECK

AND JOIST

SEAL ALL PENETRATIONS WITH

SELF ADHERING SHEET AIR

BARRIER

MINIMUM 1-1/2 INCH FOIL

FACED MINERAL WOOL BOARD

INSULATION BEYOND CONTIN.

ALONG EDGE

AT JOIST DOUBLE ANGLE

PROVIDE BACKER ROD AND

SEALANT TO CLOSE

OPENING TO AIR BARRIER

HAT CHANNELS 16 INCHES

O.C. WIRED TO JOIST

GLASS MAT GYPSUM

SHEATHING, 5/8 INCH THICK

DOOR SCHEDULE

DOOR

SIZE

HEIGHT

4'-0"

FRAME

DOOR

NO.

WIDTH MAT.

HD SET

THICK TYPE

2" 2"2" 2" 2"2"

DOOR TYPE

BA

ADD LOUVER 20X20

7'-0" 1-3/4" WOOD

MAT.

A HM

58C 58E 58F

4'-0" 7'-0" 1-3/4" WOOD A HM

3'-0" 7'-0" 1-3/4" WOOD A HM

3'-0" 7'-0" 1-3/4" WOOD B HM

3'-0" 7'-0" 1-3/4" WOOD B HM

EX WOOD EX

EX WOOD EX

EX WOOD EX

EX WOOD EX

TYPE

NO.

SLIP-ON

SLIP-ON

SLIP-ON

SLIP-ON

SLIP-ON

REMARKS

ADD LOUVER

ADD LOUVER

ADD LOUVER

12X10 14X14 12X10

3"

2'- 9"

GLASS MAT GYPSUM

SHEATHING, 5/8 INCH

THICK

HAT CHANNELS AND

SHEATHING

NON-BITUMINOUS SELF

ADHERING SHEET AIR

BARRIER, SEAL SHEATHING

FACE TO CONCRETE AND

BLOCK WALL

NON-BITUMINOUS SELF

ADHERING SHEET AIR

BARRIER, SEAL SHEATHING

FACE TO STEEL DECK

SEALANT

ACOUSTICAL PANEL

CEILING

EXISTING WALL

EXISTING METAL DECK AND ROOFING

EXISTING GYPSUM BOARD

CEILING ROOMS 58, 58A, 58B

GYPSUM SHEATHING

SUSPENDED ACOUSTICAL

PANEL CEILING

EPOXY FLOORING

WITH INTEGRAL BASE

WHERE SHOWN ON

FINISH PLAN

DEFLECTION TRACK

PROVIDE FURRING

CROSS SUPPORT AT

TOP OF WALL 18" O.C.

BRIDGING CONTINUOUS

AT CEILING LEVEL

3-5/8 INCH METAL

STUDS 16"O.C

5/8 INCH MOISTURE/MOLD

RESISTANT TYPE X

GYPSUM BOARD BOTH

SIDES

4"

3-5/8 INCH BATT MINERAL

WOOL INSULATION

SEALANT BOTH SIDES

MINERAL WOOL INSULATION

INSTALLED ABOVE EXISTING

BATT INSULATION R-30 TOTAL

MINIMUM 1-1/2 INCH FOIL FACED

MINERAL WOOL BOARD

INSULATION INSTALLED IN THE

FLUTES OF THE DECK TO THE

WALL AND 6 INCHES DOWN THE

WALL

NON-BITUMINOUS SELF

ADHERING SHEET AIR BARRIER

SEAL FOIL FACE TO CONCRETE,

METAL DECK AND JOIST

GLASS MAT GYPSUM

SHEATHING, 5/8 INCH THICK

HAT CHANNELS 16 INCHES

O.C. WIRED TO JOIST

NON-BITUMINOUS SELF

ADHERING SHEET AIR BARRIER

SEAL SHEATHING FACE TO

CONCRETE AND BLOCK WALL

EDGE ANGLE CONTINUOUS

SEAL ALL PENETRATIONS WITH

SELF ADHERING SHEET AIR

BARRIER

6" 4"

ACOUSTICAL

PANEL

CEILING

EXISTING

METAL DECK

EXISTING CONCRETE BEAM

EXISTING CONCRETE

BLOCK WALL

REPAIR AND SEAL AIR TIGHT EXISTING

(2) 1/2 LAYERS OF RIGID INSULATION

OVER PLASTIC AIR MOISTURE

BARRIER WHERE NEW SYSTEMS ARE

MOUNTED TO JOIST ABOVE

EXISTING METAL JOIST

REPAIR EXISTING GYPSUM BOARD

CEILING AND SEAL AIRTIGHT

WHERE NEW SYSTEMS ARE

ATTACHED OR PENETRATE

SUSPENDED GYPBOARD CEILING

SEAL WALL OPENING ON

ROOM 57E SIDE WITH 1-5/8

INCH STUDS AND SHEATHING,

SEAL AIR TIGHT TO EXISTING

BLOCK WALL

SEAL PENETRATIONS

THROUGH SHEATHING AIR

TIGHT

4"SHEATHING

OVERLAP TYP

FILL CELLS BELOW OPENING

SOLID WITH GROUT

PROVIDE PERIMETER

SEALANT AROUND OPENING

20 GA. STAINLESS STEEL SILL

PAN WIITH DRIP EDGE SET IN

SEALANT

EXHAUST OR INTAKE LOUVER

SEE MECHANICAL

20 GA. STAINLESS STEEL

HEAD FLASHING FULL DEPTH

OF BEAM WITH UP TURNED

INTERIOR LIP AND DRIP EDGE

SEALANT ABOVE AND BELOW

HEAD FLASHING

LOCATION WITHIN PARK

NAME OF PARK

TITLE OF SHEET

EVERGLADES NATIONAL PARK

PINE ISLAND DISTRICT

STATEREGION COUNTY

SOUTHEAST FLORIDAMIAMI-DADE

DATE:

TECH. REVIEW:

DRAWN:

DESIGNED:REVISIONS SUB SHEET NO.

PMIS / PKG. NO.

SHEET

DRAWING NO.

OFAPRIL 21, 2023

179573

314045

JB

JB

SCALE: 1-1/2" = 1'-0"

DETAILA

SCALE: 1-1/2" = 1'-0"

DETAILB

SCALE: 1/4" = 1'-0"

DOOR SCHEDULEI

SCALE: 1-1/2" = 1'-0"

DETAILD

SCALE: 1-1/2" = 1'-0"

DETAILE

SCALE: 3" = 1'-0"

DETAILC

0 1/2' 1' 1 1/2'

Scale: 1 1/2" = 1'-0"

0 3" 6" 9"

Scale: 3" = 1'-0"

0 1' 2' 4'

Scale: 1/2" = 1'-0"

0 2' 4' 8'

Scale: 1/4" = 1'-0"

SCALE: 1/2" = 1'-0"

WALL TYPE AH

SCALE: 1/2" = 1'-0"

DETAILF

SCALE: 1/2" = 1'-0"

DETAILG

SCALE: 1-1/2" = 1'-0"

DETAILJ

EH

ARCHITECTURAL DETAILS

MECHANICAL LEGEND

M-

LOCATION WITHIN PARK

NAME OF PARK

TITLE OF SHEET

EVERGLADES NATIONAL PARK

PINE ISLAND DISTRICT

STATEREGION COUNTY

SOUTHEAST FLORIDAMIAMI-DADE

DATE:

TECH. REVIEW:

DRAWN:

DESIGNED:REVISIONS SUB SHEET NO.

PMIS / PKG. NO.

SHEET

DRAWING NO.

OFMAY 15, 2023

179573

314045

@ AT

A AMP

ABS ACRYLONITRILE BUTADIENE STYRENE PLASTIC

ABV ABOVE

AC AIR CONDITIONING / AIR CONDITIONER

ACM ASBESTOS-CONTAINING MATERIAL

AD ACCESS DOOR

ADA AMERICANS WITH DISABILITIES ACT

AF AIR FILTER

AFF ABOVE FINISHED FLOOR

AFM AIR FLOW MEASURING STATION

AHJ AUTHORITY HAVING JURISDICTION

AHU AIR HANDLING UNIT

AL ACOUSTICAL LINER

ALC AUTOMATED LOGIC CONTROLS

AMB AMBIENT

AP ACCESS PANEL

APD AIR PRESSURE DROP

APPROX APPROXIMATELY

AS AIR SEPARATOR

ASSY ASSEMBLY

ATC AUTOMATIC TEMPERATURE CONTROL

ATT ACOUSTICAL ATTENUATOR

AV AUTOMATIC VENT

B BOILER

BAS BUILDING AUTOMATED SYSTEM

BDD BACKDRAFT DAMPER

BHP BRAKE HORSEPOWER

BLDG BUILDING

BOD BOTTOM OF DUCT

BOT BOTTOM

BTUH BTU PER HOUR

C CENTERLINE

CA COMPRESSED AIR

CAP CAPACITY

CD CONDENSATE DRAIN

CFM CUBIC FEET PER MINUTE

CH CHILLER

CHW CHILLED WATER

CHWR CHILLED WATER RETURN

CHWS CHILLED WATER SUPPLY

CLG CEILING

CO CLEAN OUT, CARBON MONOXIDE

COL COLUMN

CONC CONCRETE

COND CONDENSATE

CONN CONNECTION

CONT CONTINUATION

CP CONTROL PANEL, CONDENSATE PUMP

CPF CHEMICAL POT FEEDER

CR CHEMICAL RETURN

CS CHEMICAL SUPPLY

CT COOLING TOWER

CU CONDENSING UNIT

CV CONTROL VALVE

Cv CONTROL VALVE RATING

CND CONDENSER WATER

CNDR CONDENSER WATER RETURN

CNDS CONDENSER WATER SUPPLY

D DRAIN

dB DECIBELS

DB DRY BULB

DCW DOMESTIC COLD WATER

DH DESICCANT WHEEL UNIT

DDC DIRECT DIGITAL CONTROL

Ø, DIA DIAMETER

DIFF DIFFERENTIAL, DIFFUSER

DISCH DISCHARGE

DN DOWN

DOM DOMESTIC

DPS DIFFERENTIAL PRESSURE SENSOR

DWG DRAWING

DWGS DRAWINGS

E ELECTRICAL, EXHAUST, EXISTING

EA EXHAUST AIR, EACH

EAT ENTERING AIR TEMPERATURE

EC ELECTRICAL CONTRACTOR

EDH ELECTRIC DUCT HEATER

EER ENERGY EFFICIENT RATIO

EF EXHAUST FAN

EH ELECTRIC HEATER

ELEC ELECTRIC, ELECTRICAL

ELEV ELEVATION

ENT ENTERING

EPDM ETHYLENE PROPYLENE DIENE MEMBRANE

EQUIP EQUIPMENT

ERU ENERGY RECOVERY UNIT

ESP EXTERNAL STATIC PRESSURE

ET EXPANSION TANK

EVAP EVAPORATOR

EWT ENTERING WATER TEMPERATURE

EXH EXHAUST

EXIST EXISTING

EXT EXPANSION TANK

EXP EXPANSION

F FAN, DEGREES FAHRENHEIT

FA FRESH AIR

FAI FRESH AIR INTAKE

FC FIELD CONTROLLER

FCO FLOOR CLEANOUT

FCU FAN COIL UNIT

FD FIRE DAMPER, FLOOR DRAIN

FF FINISH FLOOR

FIX FIXTURE

FLA FULL LOAD AMPS

Φ FLAT OVAL

FLR FLOOR

FOB FLAT ON BOTTOM

FOT FLAT ON TOP

FS FLOAT SWITCH

FZ FREEZESTAT

G GAS

GA GAUGE

GAL GALLONS

GALV GALVANIZED

GC GENERAL CONTRACTOR

GP GENERAL PURPOSE

GPH GALLONS PER HOUR

GPM GALLONS PER MINUTE

GIH GRAVITY INTAKE HOOD

GRH GRAVITY RELIEF HOOD

GV GATE VALVE

GSM GALVANIZED SHEET METAL

GYP GYPSUM WALLBOARD

H HUMIDITY

HC HEATING COIL

HD HOOD

HHW HEATING HOT WATER

HHWR HEATING HOT WATER RETURN

HHWS HEATING HOT WATER SUPPLY

HOA HAND-OFF-AUTOMATIC

HOR HORIZONTAL

HP HORSEPOWER, HIGH PRESSURE

HR HOUR

HT HEIGHT

HVAC HEATING, VENTILATING AND AIR CONDITIONING

HWP HOT WATER PUMP

HZ HERTZ

ID INSIDE DIAMETER

IGH INFRARED GAS HEATER

IN INCHES

INDIR INDIRECT WASTE

KW KILOWATT

L LENGTH, LOUVER

LAT LEAVING AIR TEMPERATURE

LDB LEAVING DRY BULB

LF LINEAR FEET

LG LONG

LPR LOW PRESSURE STEAM RETURN

LPS LOW PRESSURE STEAM SUPPLY

LOC LOCATION, LOCATED

LRA LOCKED ROTOR AMPS

LVG LEAVING

LWB LEAVING WET BULB

LWT LEAVING WATER TEMPERATURE

M MECHANICAL

MANUF MANUFACTURER

MAU MAKE-UP AIR UNIT

MAX MAXIMUM

MAX PD MAXIMUM PRESSURE DROP

MBH 1000 BTU PER HOUR

MCA MAXIMUM CIRCUIT AMPS

MECH MECHANICAL

MFG MANUFACTURER

MIN MINIMUM, MINUTES

MNTD MOUNTED

MOCP MAXIMUM OVERCURRENT PROTECTION

MOD MOTOR OPERATED DAMPER

MUA MAKE-UP AIR

MUW MAKE-UP WATER

MVD MANUAL VOLUME DAMPER

N/A NOT APPLICABLE

NATL NATURAL

NC NORMALLY CLOSED, NOISE CRITERIA

NEC NATIONAL ELECTRIC CODE

NG NATURAL GAS

NFPA NATIONAL FIRE PROTECTION ASSOCIATION

NIC NOT IN CONTRACT

NO NORMALLY OPEN, NUMBER

NTS NOT TO SCALE

OA OUTSIDE AIR

OAI OUTSIDE AIR INTAKE

OAT OUTSIDE AIR TEMPERATURE

OBD OPPOSED BLADE DAMPER

OD OUTSIDE DIAMETER

OED OPEN ENDED DUCT

P PUMP, PITCH

PD PRESSURE DROP

PLMB PLUMBING

PRESS PRESSURE

PRV PRESSURE REDUCING VALVE

PSI POUNDS PER SQUARE INCH

PSIG POUNDS PER SQUARE INCH GAUGE

PVC POLYVINYL CHLORIDE

QTY QUANTITY

R RADIUS, RETURN

RA RETURN AIR

RAG RETURN AIR GRILLE

RAT RETURN AIR TEMPERATURE

REF REFRIGERANT

REL RELIEF

REQD REQUIRED

RET RETURN

RH RELATIVE HUMIDITY

RL REFRIGERANT LIQUID

RLA RATED LOAD AMPS

RM ROOM

RPM REVOLUTIONS PER MINUTE

S SUPPLY DIFFUSER

SA SUPPLY AIR

SCR SCREEN

SF SQUARE FOOT

SIM SIMILAR

SOV SHUT OFF VALVE

SP STATIC PRESSURE

SPH STATIC PRESSURE HIGH LIMIT

SPL STATIC PRESSURE LOW LIMIT

SPS STATIC PRESSURE SENSOR

SQ SQUARE

SQFT SQUARE FEET

SS STAINLESS STEEL

STL STEEL

SUP SUPPLY

T-STAT THERMOSTAT

TC TOTAL COOLING

TEMP TEMPERATURE

THK THICK, THICKNESS

TG TRANSFER GRILLE

TRANS TRANSITION

TSP TOTAL STATIC PRESSURE

TYP TYPICAL

UM UTILITY METER

UNO UNLESS NOTED OTHERWISE

USACE US ARMY CORPS OF ENGINEERS

V VENT

VAV VARIABLE AIR VOLUME

VD VOLUME DAMPER

VEL VELOCITY

VTR VENT THROUGH ROOF

W WIDTH, WATT

W/ WITH

WB WET BULB

WC WATER COLUMN

WG WATER GAUGE

WH WATER HEATER

WMS WIRE MESH SCREEN

WPD WATER PRESSURE DROP

WS WATER SOFTENER

ABBREVIATIONS

1. DRAWINGS SHOW APPROXIMATE SIZE AND LOCATION OF ALL HVAC EQUIPMENT AND APPURTENANCES. HOWEVER, ALL EQUIPMENT AND APPURTENANCES NECESSARY FOR COMPLETE AND OPERATIONAL INSTALLATION MAY NOT BE SHOWN. CONTRACTOR SHALL PROVIDE ALL EQUIPMENT AND APPURTENANCES REQUIRED FOR A COMPLETE AND OPERATIONAL SYSTEM. DUCTWORK AND PIPING LAYOUTS SHOWN ON THE DRAWINGS ARE DIAGRAMMATIC. CONTRACTOR SHALL BE FULLY RESPONSIBLE TO DETERMINE THE EXACT ROUTING OF THE DUCTWORK AND PIPING IN ACCORDANCE WITH THE ACTUAL FIELD CONDITIONS AND

CONSTRAINTS.

2. THE CONTRACTOR SHALL VISIT THE SITE AND VERIFY ALL EXISTING CONDITIONS IN THE FIELD BEFORE STARTING CONSTRUCTION. WORK TO BE DONE SHALL BE ALL INCLUSIVE AND ANY WORK NOT SPECIFICALLY MENTIONED BUT REASONABLY IMPLIED SHALL BE INCLUDED. THE INSTALLATION OF HVAC SYSTEM SHALL BE COMPLETE IN ALL RESPECTS AS REQUIRED BY THE CONTRACT DOCUMENTS. PERFORM ALL WORK

REQUIRED TO TIE IN NEW WORK TO EXISTING WORK.

3. FLOOR PLANS AND ROOM LAYOUTS ARE BASED ON THE LATEST AVAILABLE DOCUMENTS AT THE TIME OF DESIGN. CONTRACTOR SHALL VERIFY ALL CURRENT LAYOUTS AT TIME OF SHOP DRAWINGS AND CREATE

ACCURATE WORKING DRAWINGS PRIOR TO SUBMISSION OF EQUIPMENT, ETC.

4. THE CONTRACTOR SHALL COMPLY WITH ALL APPLICABLE FEDERAL, STATE AND MUNICIPAL LAWS AND ORDINANCES.

5. WHERE THE WORDS "FURNISH", "PROVIDE", OR "INSTALL" ARE USED EITHER SINGLY OR IN COMBINATION, THESE WORDS ARE HEREBY INTERPRETED TO MEAN "FURNISH AND INSTALL" OR "PROVIDE AND INSTALL" INCLUDING ALL REQUIRED EQUIPMENT, MATERIALS, AND ASSOCIATED WORK UNLESS SPECIFICALLY NOTED OTHERWISE.

6. THE CONTRACTOR SHALL KEEP AT ALL TIMES THE PROPERTY, ROOF, AND BUILDING FREE FROM TRASH AND DIRT WHICH MAY BE CAUSED BY THEMSELVES OR THEIR SUBCONTRACTORS. THE CONTRACTOR SHALL MAINTAIN THEIR OWN DUMPSTERS ON THE SITE AS REQUIRED FOR THEIR WORK. DUMPSTERS RETAINED BY THE FACILITY SHALL NOT BE USED BY THE CONTRACTOR. NO RUBBISH OR MATERIAL SHALL BE ALLOWED TO

ACCUMULATE IN THE BUILDING, ON THE ROOF, OR ON THE PROPERTY.

7. THE CONTRACTOR SHALL FURNISH THE LABOR AND MATERIAL INCLUDED IN HIS CONTRACT IN AMPLE TIME AND SUFFICIENT QUANTITIES SO THAT ALL WORK MAY BE COMPLETED WITHIN THE DESIGNATED TIME

LIMITS.

8. CONSTRUCTION WASTE TO BE REMOVED AND DISPOSED OF AS PER THE SOW. CONTRACTOR SHALL PROVIDE OWNERSHIP WITH THE FIRST RIGHT OF REFUSAL FOR CERTAIN REUSABLE ITEMS TO INCLUDE BUT NOT

LIMITED TO MOTORS.

9. CONTRACTOR SHALL INSTALL DDC TEMPERATURE CONTROL SYSTEM COMPONENTS AS INDICATED ON THE DRAWINGS AND AS REQUIRED THROUGHOUT THE BUILDING FOR COMPLETE SYSTEMS. WORK SHALL BE ALL INCLUSIVE INCLUDING DEMOLITION, FURNISHING AND INSTALLATION OF NEW CONTROL DEVICES, EQUIPMENT, PANELS, COMPUTER SOFTWARE AND HARDWARE. SEE CONTROL DRAWINGS AND SPECS FOR ADDITIONAL INFORMATION. PATCH AND FINISH ALL SURFACES AFFECTED BY THIS WORK TO MATCH ADJACENT AREAS.

10. ANY INTERIOR PENETRATIONS SHALL BE PATCHED TO MATCH EXISTING SURFACES. PROVIDE ESCUTCHEON PLATES FOR ALL EXPOSED PIPE AND CONDUIT PENETRATIONS. SEAL AROUND ALL DUCT SLAB, WALL, AND PARTITION PENETRATIONS. PRIOR TO ANY STRUCTURAL WALL PENETRATIONS, THE CONTRACTOR SHALL VERIFY AND CONFIRM WHETHER THE WALL IS RATED AND MAKE NECESSARY MODIFICATIONS TO ACCOUNT FOR RATED WALLS AS NEEDED. THIS SHALL INCLUDE ANY FIRE DAMPER, COMBINATION FIRE-SMOKE DAMPER, AND/OR FIRE CAULKING AND SEALING AS REQUIRED TO MAINTAIN THE ASSOCIATED FIRE RATING.

11. CONTRACTOR SHALL BALANCE AND ADJUST THE AIR SIDE OF THE NEW AND MODIFIED HVAC SYSTEMS WHICH ARE PART OF THIS CONTRACT. ADJUST EQUIPMENT TO VALUES SHOWN ON THE PLANS, DETAILS, AND IN

THE SCHEDULES. PROVIDE DETAILED BALANCING REPORTS PER TECHNICAL SPECIFICATIONS.

12. INSTALL ALL EQUIPMENT TO ALLOW REQUIRED MINIMUM ACCESS TO CONTROL PANELS AND ALL COMPONENTS WHICH WOULD REQUIRE SERVICE OR MAINTENANCE AS RECOMMENDED BY THE MANUFACTURER. ALL PRODUCTS SHALL BE INSTALLED PER MANUFACTURER'S INSTRUCTIONS AND RECOMMENDATIONS. PROVIDE LABELING FOR EQUIPMENT AND PIPING.

GENERAL NOTES

NOTE: ABBREVIATIONS ON THIS SHEET MAY NOT ALL BE USED WITHIN THIS SET OF PROJECT DOCUMENTS.

(FOR 4-WAY THROW ARROWS NOT SHOWN)

DIRECTION SHOWN BY ARROWS

CEILING SUPPLY DIFFUSER W/ THROW

SEQUENCE NUMBER

CFM

VOLUME DAMPER

REVISION (LETTER)

FLEXIBLE CONNECTOR

DIRECTION OF AIR FLOW EXHAUST

PUMP

STARTER/DISCONNECT

ROOF VENTILATOR, EXHAUST

FLEXIBLE DUCT

SQUARE ELBOW WITH TURNING VANES

CONNECT TO EXISTING

MOTORIZED DAMPER, OPPOSED BLADE

MOTORIZED DAMPER, PARALLEL BLADE

FIRE / SMOKE DAMPER

FIRE DAMPER

DIRECTION OF AIR FLOW

CENTRIFUGAL FAN

ACCESS DOOR

SUPPLY DIFFUSER, REGISTER, GRILLE

RETURN GRILLE, REGISTER

KEY NOTE (NUMBER)

DIFFUSER, REGISTER OR GRILLE

SYMBOL PER ABBREVIATION LIST

AD

EQUIPMENT SEQUENCE NUMBER

SWITCH

M

M

S

A

DOOR UNDERCUT

B

D1

DETAIL NUMBER

MECHANICAL SYMBOLS

TYPE DEMO UP TO THIS POINT

PIPE CROSS-SECTIONAL VIEW

PROJECT SPECIFIC SYMBOLS

THERMOSTATT

FD

F/S

EXISTING TO REMAIN

REMOVAL / DEMOLITION

NEW WORK

HIDDEN ITEMS

DUCT UP - SEE UPPER LEVEL DWG FOR

CONTINUATION

DUCT DOWN - SEE LOWER LEVEL DWG FOR

CONTINUATION

NOTE: SYMBOLS AND LEGENDS ON THIS SHEET MAY

NOT ALL BE USED WITHIN THIS SET OF PROJECT

DOCUMENTS.

RETURN AIR REGISTER OR GRILLE

SEQUENCE NUMBER

WIDTH x HEIGH

WIDTH x HEIGHT

WxH

WxH

S-1

HHW

R-1

EXHAUST GRILLE, REGISTER

MECHANICAL EQUIPMENT EXISTING TO REMAIN

WALL/DOOR GRILLE, REGISTER

COMBINATION THERMOSTAT/HUMIDISTATTH

INTERNALLY LINED DUCTWORK

TB

LG

SW

VD

DWG

VIEW

SECTION VIEW

1. SPLIT SYSTEMS: WHEN THE SPACE IS NOT IN FIRE ALARM AND THE UNIT SMOKE DETECTOR

DOES NOT DETECT SMOKE, THE UNIT SHALL OPERATEAS FOLLOWS:

a. UNOCCUPIED MODE: THE OA DAMPER SHALL SHUT. THE UNIT SHALL CYCLE

COMPRESSORS TO MAINTAIN SPACE COOLING UNOCCUPIED SET POINT AND SHALL

ENERGIZE THE REVERSING VALVE AND CYCLE COMPRESSORS TO MAINTAIN SPACE

HEATING UNOCCUPIED SETPOINT.

b. OCCUPIED MODE: THE UNIT SHALL OPEN ITS OUTSIDE AIR DAMPER TO THE MINIMUM

OUTSIDE AIR POSITION. THE UNIT SHALL CYCLE THE COMPRESSORS TO MEET THE SPACE

COOLING OCCUPIED SETPOINT AND SHALL ENERGIZE THE REVERSING VALVE AND CYCLE

COMPRESSORS TO MAINTAIN SPACE HEATING OCCUPIED SETPOINT.

SEQUENCE OF OPERATIONS

13. ALL BRANCH DUCTWORK SHALL BE THE SAME SIZE AS THE DIFFUSER CONNECTION SERVED UNLESS NOTED OTHERWISE.

14. DUCT DIMENSIONS SHOWN ARE INSIDE CLEAR DIMENSIONS.

15. MAINTAIN DUCTWORK LEVEL AS HIGH AS POSSIBLE TO THE UNDERSIDE OF STRUCTURE WHILE CONSIDERING SPACE ABOVE FOR PIPING, CONDUIT, AND INSULATION AS NECESSARY. COORDINATE DUCTWORK WITH FIRE PROTECTION, ELECTRICAL AND OTHER TRADES. MAKE OFFSETS AND TRANSITIONS AS REQUIRED TO COORDINATE WITH OTHER TRADES.

16. PROVIDE A FLEXIBLE CONNECTION AT THE INTAKE AND DISCHARGE CONNECTION OF EACH AIR HANDLING UNIT AND FAN.

17. PROVIDE SMOOTH, FULL RADIUS ELBOWS IN SUPPLY, RETURN, AND EXHAUST SYSTEMS. WHERE SPACE IS LIMITED, PROVIDE 90° SQUARE ELBOWS WITH TURNING VANES. TURNING VANES SHALL NOT BE PROVIDED IN RETURN DUCT SYSTEMS.

18. CONTRACTOR SHALL PITCH CONDENSATE DRAIN PIPING AT MIN. 1/4" PER FOOT. ROUTE TO NEAREST DRAIN OR WHERE INDICATED ON PLANS.

19. PROVIDE FULL SIZE TRAPPED AND VENTED CONDENSATE PIPING ROUTED FROM EACH HVAC UNIT TO NEAREST DRAIN. REFER TO PLANS.

20. THE MECHANICAL CONTRACTOR SHALL MAKE CHANGES TO ANY PULLEYS, BELTS, AND/OR DAMPERS AS REQUIRED TO PROVIDE THE BALANCE OF AIR SYSTEMS AS SHOWN ON THE PLANS.

21. ACCESS SHALL BE PROVIDED WHERE MOTORS, FILTERS, CONTROL DEVICES, AND ANY OTHER EQUIPMENT REQUIRING ACCESS FOR SERVICING, REPAIRS, OR MAINTENANCE ARE LOCATED IN WALLS, CHASES, AND/OR ABOVE CEILING.

22. AS-BUILT DRAWINGS: PROVIDE RECORD DRAWINGS SHOWING WORK AS BUILT INCLUDING ALL CHANGES INITIATED BY CONTRACTOR OR OWNER ON COMPLETION OF PROJECT FOR ALL TRADES.

23. REFER TO ARCHITECTURAL DRAWINGS FOR EXACT SIZE, LOCATION AND MOUNTING HEIGHT OF ALL LOUVERS AND/OR EXTERIOR WALL MOUNTED DEVICES.

24. SUBMITTALS - SUBMIT THE FOLLOWING: FANS; SPLIT SYSTEMS; VIBRATION ISOLATION; GRILLES, REGISTERS, AND DIFFUSERS; LOUVERS; SHEET METAL DUCTWORK; PIPING; INSULATION; DUCT LINER; DAMPERS; FLEXIBLE DUCTWORK;

TEST AND BALANCE REPORT; COORDINATED SHOP DRAWINGS FOR REVIEW AND APPROVAL.

logan.grailer Stamp

ACAC

57A

57D

57B

57C

58A

58B

58C

58D

58E 58F

58G

AC

AHU

AHU

DH

DH

RAG

TG

AC

SCREENED

PORCH

41'-8"

T

T

1. DEMOLISH WALL-MOUNTED THERMOSTAT.

2. DEMO AHU AND ALL RELATED HVAC EQUIPMENT,

DUCTWORK, REF PIPING AND COND PIPING.

3. DEMO ALL EXPOSED DUCTWORK, AIR DISTRIBUTION

DEVICES, AND SUPPORTS WITHIN THE ROOM 58 AND

ASSOCIATED SPACES. PATCH HOLES IN GYP BOARD

CEILING FROM PREVIOUS SUPPORTS TO MATCH EXISTING

CONSTRUCTION.

4. DEMO ALL ABOVE CEILING DUCTWORK AND AIR

DISTRIBUTION DEVICES WITHIN ROOM 57 AND ASSOCIATED

SPACES

1. FIELD VERIFY EXACT LOCATIONS OF EXISTING DUCTWORK,

PIPING, AND EQUIPMENT.

2. FIELD COORDINATE WITH ARCHITECTURAL, STRUCTURAL,

AND ELECTRICAL DISCIPLINES PRIOR TO START OF WORK.

GENERAL NOTES

KEY NOTES

0 4' 8' 12'

Scale: 3/16" = 1'-0"

TB

LG

LOCATION WITHIN PARK

NAME OF PARK

TITLE OF SHEET

EVERGLADES NATIONAL PARK

PINE ISLAND DISTRICT

STATEREGION COUNTY

SOUTHEAST FLORIDAMIAMI-DADE

DATE:

TECH. REVIEW:

DRAWN:

DESIGNED:REVISIONS SUB SHEET NO.

PMIS / PKG. NO.

SHEET

DRAWING NO.

OFMAY 15, 2023

179573

314045

SCALE: 3/16" = 1'-0"

MECHANICAL DEMO PLAN1

DEMO DESICCANT

WHEEL UNIT,

DUCTWORK, AND

SUPPLY/INTAKE

GRILLES

EXISTING SIDEWALL

RETURN GRILLE TO

REMAIN

DEMO 24X16 EXTERIOR

LOUVER

SW

OUTDOOR CONDENSING

UNITS EXISTING TO

REMAIN (NIC)

MECHANICAL DEMO PLAN

M-

57C

58A

58B

58C

58D

58E 58F

58G

RAG

SCREENED

PORCH

T

57A 57D

57B

57C

57ETH

TH

1. MOTORIZED DAMPER (INTERLOCKED WITH AHU

OPERATION) AND VOLUME DAMPER IN OA DUCT BEFORE

CONNECTION TO RETURN PLENUM.

2. SUPPLY AIR DUCTS ALL MEET IN A CONNECTING

PIECE/PLENUM ABOVE AHU-2.

3. NEW DOOR GRILLE INSTALLED IN EXISTING DOOR. REFER

TO ARCH.

4. PLACE OUTDOOR UNIT ON 4" TALL CONCRETE

HOUSEKEEPING PAD. ANCHOR EQUIPMENT TO CONCRETE

PAD USING HURRICANE TIE-DOWN BRACKETS INSTALLED

IN ACCORDANCE WITH MIAMI-DADE AND FLORIDA

MECHANICAL CODE STANDARDS.

1. FIELD VERIFY EXACT LOCATIONS OF EXISTING DUCTWORK,

PIPING, AND EQUIPMENT.

2. FIELD COORDINATE WITH ARCHITECTURAL, STRUCTURAL,

AND ELECTRICAL DISCIPLINES PRIOR TO START OF WORK.

3. ALL SUPPLY AIR DUCTWORK FROM AHU-2 TO BE INTERNALLY

LINED.

4. ALL DIMENSIONS IN INCHES.

GENERAL NOTES

KEY NOTES

0 4' 8' 12'

Scale: 3/16" = 1'-0"

MECHANICAL FLOOR PLAN

M-

LOCATION WITHIN PARK

NAME OF PARK

TITLE OF SHEET

EVERGLADES NATIONAL PARK

PINE ISLAND DISTRICT

STATEREGION COUNTY

SOUTHEAST FLORIDAMIAMI-DADE

DATE:

TECH. REVIEW:

DRAWN:

DESIGNED:REVISIONS SUB SHEET NO.

PMIS / PKG. NO.

SHEET

DRAWING NO.

OFMAY 15, 2023

179573

314045

SCALE: 3/16" = 1'-0"

MECHANICAL FLOOR PLAN1

3/4" CONDENSATE OUT

THROUGH WALL OVER

SPLASH BLOCK

PROVIDE SPLASH

BLOCK FOR

CONDENSATE

DISCHARGE

EXISTING SIDEWALL

GRILLE TO REMAIN.

NEW VOLUME

DAMPER BEHIND

EXISTING GRILLE AND

FILTER. BALANCE

RETURN GRILLE TO

1400 CFM.

AHU

HP

HP

AHU

EF

24x24 24x24

R-1200 S-1

S-1

24x24 S-1

10x6 S-2

6x6 S-2

10x10 S-2

S-1

8x6 S-2

TYP 6 TYP 2

AC

HP

RS/L PIPING

OUTDOOR CONDENSING

UNITS EXISTING TO

REMAIN (NIC)

S-1

6x6 S-2

8x6 S-2

8x6 S-2

8x6 S-2

8x6 S-2

8x6 S-2

24x24

24x24 24x24

18x14

18x1416x1410x10 x1 x1 x1

8Ø

Ø

Ø

16x12 x8

8Ø8Ø

8Ø8Ø 8Ø

8Ø

6Ø

6Ø

RS/L PIPING

RS/L PIPING

6Ø

6Ø

6x6 S-2

6x6 S-2 x8

6Ø

6Ø

6Ø

8Ø8Ø8Ø

TB

LG

SW

LVR

LVR

LVR

8Ø

8Ø

6Ø

M-501

M-501

SUPPORT FROM STRUCTURE

NOT TO SCALE

PIPE THROUGH WALL DETAIL2

MECHANICAL DETAILS

M-

LOCATION WITHIN PARK

NAME OF PARK

TITLE OF SHEET

EVERGLADES NATIONAL PARK

PINE ISLAND DISTRICT

STATEREGION COUNTY

SOUTHEAST FLORIDAMIAMI-DADE

DATE:

TECH. REVIEW:

DRAWN:

DESIGNED:REVISIONS SUB SHEET NO.

PMIS / PKG. NO.

SHEET

DRAWING NO.

OFMAY 15, 2023

179573

314045

PACK ANNULAR SPACE WITH

MINERAL WOOL. SEAL ENDS WITH

ACOUSTICAL CAULK.

16 GAGE PIPE SLEEVE

METAL STUD CHANNEL FRAME

AROUND ON STUD WALLS

PIPE SEE

PLANS

FOR SIZE

POSITIVE ACTING CHROME

PLATED ESCUTCHEON

PLATES ON EXPOSED WALLS

ONLY

SPECIFIED INSULATION

STUD WALL OR

CONCRETE SEE PLANS

UNION

AHU-X

DRAW THRU

1 DIMENSION TO BE 1" GREATER THAN SUCTION

PRESSURE OF UNIT (IN W.G.)

2 DIMENSION TO BE 1/2 TOTAL PRESSURE OF UNIT (IN

W.G.)

BLOW THRU

1 DIMENSION TO BE 1"

2 DIMENSION TO BE EQUAL TO TOTAL PRESSURE OF

UNIT (IN W.G.)

TEE WITH SCREW PLUGS FOR CLEANING ACCESS

SCREW PLUG

MAINTAIN SERVICE ACCESS

TO SPLASH BLOCK1

NOT TO SCALE

CONDENSATE DRAIN/TRAP1

NOT TO SCALE

SUPPLY DIFFUSER DETAIL6

NOT TO SCALE

DUCT HANGER DETAIL7

2"Ø WASHER W/ DOUBLE NUT

STRAP RING CLAMP, 12 GAUGE x1-1/2"

WIDE GALV STEEL

3/8"Ø THREADED ROD

LOCK NUT BOTH SIDES

XX"Ø SPIRAL ROUND DUCT

NOT TO SCALE

VERTICAL AHU-1 SPLIT SYSTEM DETAIL4

SA DUCTRA DUCT

FLEXIBLE CONNECTOR

INDOOR AHU-1

FAN ACCESS SECTION

DISCONNECT SWITCH

REFRIGERANT PIPING. ROUTE TO

HEAT PUMP UNIT. SIZE PER

MANUFACTURER'S

RECOMMENDATIONS.

COIL SECTION

CONDENSATE DRAIN

CONNECTION

FILTER RACK24" TALL INSULATED MIXED AIR

SHEET METAL PLENUM

24" WIDE; COORDINATE LENGTH

WITH AVAILABLE CLOSET

DIMENSIONS AND DUCTWORK

CONNECTIONS

EXISTING FLOOR SLAB

NOT TO SCALE

VERTICAL AHU-2 SPLIT SYSTEM DETAIL5

SA DUCT OA DUCT

FLEXIBLE CONNECTOR

INDOOR AHU-2

FAN ACCESS SECTION

MANUAL DAMPER

MOTORIZED DAMPER

DISCONNECT SWITCH

REFRIGERANT PIPING. ROUTE TO

HEAT PUMP UNIT. SIZE PER

MANUFACTURER'S

RECOMMENDATIONS.

COIL SECTION

CONDENSATE DRAIN

CONNECTION

FILTER RACK

24" TALL INSULATED MIXED AIR

SHEET METAL PLENUM

24" WIDE; COORDINATE LENGTH

WITH AVAILABLE CLOSET

DIMENSIONS AND DUCTWORK

CONNECTIONS

EXISTING FLOOR SLAB

OA DUCT TAPS INTO RA DUCT

ABOVE THE CEILING

RA FROM SIDEWALL GRILLE

IN ROOM 58

RA DUCT TURNS INTO SIDE OF

SHEET METAL PLENUM

18"x18" ACCESS DOOR 18"x18" ACCESS DOOR

TB

LG

SW

DIFFUSER CORE

(WHERE SPECIFIED)

LAY-IN CEILING DIFFUSER/GRILLE HARD CEILING

(WHERE SPECIFIED)

FROM STRUCTURE ABOVE

SUPPORT FLEX DUCT

FLEX DUCT

TIGHTENING BAND

REPLACED BY DUCT COLLAR

WITH TAKE-OFFS

FOR RETURN AIR,

1-1/2 x DUCT RADIUS

MAKE BEND RADIUS

NOTE: FLEX DUCT IS

12 GA. STEEL

WIRE

SPIN-IN FITTING WITH DAMPER

DAMPER SHAFT SHALL BE

PARALLEL TO AIRFLOW IN MAIN

DUCT MAIN

SCALE: NTS

DUCT MOUNTED SUPPLY DIFFUSER AND RETURN GRILLE DETAIL3

DUCTWORK MAIN

RECTANGULAR DUCTWORK SHOE

MANUAL VOLUME DAMPER

SUPPLY DIFFUSER OR RETURN GRILLE

SA DIRECTION

RA DIRECTION

SEE PLANS FOR SIZE

24x16 RA DUCT

DISCHARGE SUPPLY PLENUM

FULL SIZE OF CABINET W/ 1"

INTERNAL LINER

DISCHARGE SUPPLY PLENUM

FULL SIZE OF CABINET W/ 1"

INTERNAL LINER

MECHANICAL SCHEDULES

M-

LOCATION WITHIN PARK

NAME OF PARK

TITLE OF SHEET

EVERGLADES NATIONAL PARK

PINE ISLAND DISTRICT

STATEREGION COUNTY

SOUTHEAST FLORIDAMIAMI-DADE

DATE:

TECH. REVIEW:

DRAWN:

DESIGNED:REVISIONS SUB SHEET NO.

PMIS / PKG. NO.

SHEET

DRAWING NO.

OFMAY 15, 2023

179573

314045

TB

LG

SW

E-

LIGHTING

ELECTRICAL SYMBOLS LEGEND

POWER SEE ELECTRICAL SPECIFICATIONS FOR MOUNTING HEIGHTS.

ABBREVIATIONS

J

J

EF

WP

WP

F

DUPLEX RECEPTACLE - SEE ELECTRICAL SPECIFICATIONS FOR MOUNTING HEIGHTS.

MOUNT 18" AFF (TYP.)

(WP) WEATHERPROOF

(H) HORIZONTALLY MOUNTED

(C) CEILING MOUNTED

AMPERES

AIR CONDITIONING

ALTERNATING CURRENT

ABOVE FINISHED FLOOR

ABOVE FINISHED GRADE

AUTHORITY HAVING JURISDICTION

AIR HANDLING UNIT

AMERICAN WIRE GAUGE

CONDUIT

COUNTER HEIGHT

CARBON MONOXIDE

CONCRETE

CONDUIT

COPPER

DISCONNECT

ENCLOSED CIRCUIT BREAKER

ELECTRICAL

EMERGENCY

ENERGY MANAGEMENT SYSTEM

ELECTRICAL METALLIC TUBING

EXHAUST FAN

ELECTRIC WATER COOLER

EXISTING

A A/C

AC

AFF

AFG

AHJ

AHU

AWG

C

CH

CM

CONC

COND

CU

DISC

ECB

ELEC

EM

EMS

EMT

EF

EWC

EX

FA

FACP

FBC

FMC

GFI

GND

GRC

HVAC

IMC

IWH

I.G.

J

KAIC

KCMIL

KVA

KW

LED

LTG

MC

MCP

MCU

MH

N

NA

FIRE ALARM

FIRE ALARM CONTROL PANEL

FLORIDA BUILDING CODE

FLEXIBLE METAL CONDUIT

GROUND FAULT INTERRUPTER

GROUND

GALVANIZED RIGID CONDUIT

HEATING, VENTILATING AND AIR

CONDITIONING

INSTANTANEOUS WATER HEATER

INTERMEDIATE METAL CONDUIT

ISOLATED GROUND

JUNCTION

(THOUSAND) AMPERE INTERRUPTING

CAPACITY

THOUSANDS OF CIRCULAR MILLS

KILOVOLT-AMPERES

KILOWATT

LIGHT EMITTING DIODE

LIGHTING

METAL CLAD

MOTOR CIRCUIT PROTECTION

MASTER CONTROL UNIT

MEAN HEIGHT

NEUTRAL

NOT APPLICABLE

DOUBLE DUPLEX RECEPTACLE. MOUNT 18" AFF (TYP.)

"GFI" DUPLEX RECEPTACLE/GROUND FAULT INTERRUPTING

"GFI" DUPLEX RECEPTACLE/GROUND FAULT INTERRUPTING/WEATHERPROOF COVER

"GFI" DOUBLE DUPLEX RECEPTACLE/GROUND FAULT INTERRUPTING

"GFI" DOUBLE DUPLEX RECEPTACLE/GROUND FAULT INTERRUPTING, COUNTER HEIGHT

DUPLEX RECEPTACLE - TOP HALF SWITCHED - MOUNT 18" AFF

DUPLEX RECEPTACLE, COUNTER HEIGHT = 5" ABOVE COUNTER TOP SPLASH

DOUBLE DUPLEX RECEPTACLE, COUNTER HEIGHT

DUPLEX RECEPTACLE - FLUSH MOUNTED IN FLOOR BOX.

DOUBLE DUPLEX RECEPTACLE MOUNTED TOGETHER IN A FLUSH MOUNTED FLOOR BOX.

SPECIAL PURPOSE OUTLET - COORDINATE EXACT NEMA CONFIGURATION AMPACITY RATING

AS INDICATED.

CEILING FAN JUNCTION BOX (SIZE AS REQUIRED PER N.E.C.).

WALL MOUNTED JUNCTION BOX (SIZE AS REQUIRED PER N.E.C.).

MOTOR

(EF) EXHAUST FAN

PHOTO CELL

ELECTRICAL SERVICE SHUNT TRIP BREAK GLASS STATION

SQUARE "D" CLASS#900 1-K15 W/ CLASS 9001-K25 STAINLESS STEEL COVER

PLATE. ENGRAVE "SERVICE DISCONNECT" MOUNT 7'-0" AFF./WEATHERPROOF HOUSING

GROUND BAR

NEC

NEMA

NFPA

NF

NIC

NL

O.C.

P

PNL

PVC

RGS

RM

RMC

RNC

SPD

SPEC

SS

TYP

UON

V W

WP

NATIONAL ELECTRICAL CODE

NATIONAL ELECTRICAL

MANUFACTURERS ASSOCIATION

NATIONAL FIRE PROTECTION

ASSOCIATION

NON-FUSED

NOT IN CONTRACT

NIGHT LIGHT

ON CENTER

POLE

PANELBOARD

POLYVINYL CHLORIDE

RIGID GALVANIZED STEEL

ROOM

RIGID METAL CONDUIT

RIGID NONMETALLIC CONDUIT

SURGE PROTECTION DEVICE

SPECIFICATION

STAINLESS STEEL

TYPICAL

UNLESS OTHERWISE NOTED

VOLTS

WIRE

WEATHERPROOF

GB

(SEE LIGHTING FIXTURE SCHEDULE)

SWITCHES

BRANCH CIRCUIT PANELBOARD, 120/208V, UNDER 250 VOLTS,

SURFACE MOUNTED, U.O.N.

BRANCH CIRCUIT PANELBOARD, 480/277V, SURFACE MOUNTED

U.O.N.

FUSED DISCONNECT SWITCH, 3-POLE, TOP NUMBER INDICATES

SWITCH RATING, ASTERISK INDICATES TO FUSE ACCORDING TO

MANUFACTURERS RECOMMENDATIONS. NEMA 1 RATED

INDOORS, NEMA 3R RATED OUTDOORS.

COMBINATION STARTER/DISCONNECT SWITCH, 3-POLE, 30AMP,

FUSED. NEMA SIZE 1 NEMA RATED INDOORS, NEMA 3R RATED

OUTDOORS.

UTILITY TRANSFORMER

HVAC/PLUMBING EQUIPMENT LABEL

303*

SERVICE, DISTRIBUTION, AND EQUIPMENT

TOGGLE-TYPE SWITCH - TOGGLE TYPE. SEE ELECTRICAL SPECIFICATIONS FOR

MOUNTING HEIGHTS. LOWER CASE LETTER INDICATES SWITCH LEG

CONTROLLED.

OS

OS

2X4 RECESSED LED, HATCHING INDICATES EMERGENCY FIXTURE

1X4 RECESSED LED, HATCHING INDICATES EMERGENCY FIXTURE

RECESSED DOWNLIGHT, HATCHING INDICATES EMERGENCY FIXTURE

WALL SCONCE - HATCHING INDICATES EMERGENCY FIXTURE

EXIT SIGN - SINGLE FACE- ARROW INDICATES DIRECTION OF EGRESS

(IF PRESENT) - CEILING MOUNTED UON

EXIT SIGN - SINGLE FACE - ARROW INDICATES DIRECTION OF EGRESS

(IF PRESENT) - WALL MOUNTED

EXIT SIGN - DOUBLE FACE - ARROW INDICATES DIRECTION OF EGRES

(IF PRESENT) - CEILING MOUNTED

COMBINATION EXIT SIGN/EMERGENCY LIGHT - HATCHING INDICATES

FACING, ARROWS INDICATE DIRECTION OF EGRESS (IF PRESENT),

CEILING MOUNTED UON

DUAL-HEAD EMERGENCY LIGHT WITH BATTERY BACKUP

C = CEILING MOUNTED

M MOTOR RATED SWITCH - 1 POLE OR 2 POLE AS REQUIRED. 30 AMP OR AS REQUIRED

BY CIRCUIT WITH INTEGRAL THERMAL OVERLOADS.

WALL MOUNTED DUAL-TECHNOLOGY LOW-VOLTAGE OCCUPANCY SENSOR SWITCH.

LOWER CASE LETTER INDICATES SWITCH LEG CONTROLLED. PROVIDE POWER PACKS

FOR SWITCH LEG.

CEILING MOUNTED DUAL-TECHNOLOGY LOW-VOLTAGE OCCUPANCY SENSOR SWITCH.

LOWER CASE (a) INDICATES SWITCH LEG CONTROLLED. PROVIDE POWER PACKS FOR

EACH SWITCH LEG.

PC

(3) 3 WAY

(4) 4 WAY

(2) DOUBLE POLE

(P) WITH PILOT LIGHT INDICATION

(D) DIMMER

(K) KEY

a

DATA/COMM/TELEVISION

DATA/COMM OUTLET WITH FLUSH MOUNTED 4-11/16" SQUARE

SINGLE GANG JUNCTION BOX. PROVIDE BLANK BUILDING

STANDARD COVER PLATE. EXTEND 1" CONCEALED CONDUIT TO

ABOVE ACCESSIBLE CEILING AND STUB-OUT WITH PLASTIC

BUSHING OR AS NOTED. INSTALL PULL WIRE.

CH = COUNTER HEIGHT.

TELEPHONE TERMINAL BOARD, 3/4" THICK x (LENGTH PER PLAN) x

8'-0" HIGH PLYWOOD BACKBOARD

TELEVISION COAXIAL OUTLET WITH FLUSH MOUNTED 4-11/16"

SQUARE SINGLE GANG JUNCTION BOX. PROVIDE BLANK BUILDING

STANDARD COVER PLATE. EXTEND 1" CONCEALED CONDUIT TO

ABOVE ACCESSIBLE CEILING AND STUB-OUT WITH PLASTIC

BUSHING, OR AS NOTED. INSTALL PULL WIRE.

COMBINATION POWER OUTLET AND DATA/COMM OUTLET

MOUNTED FLUSH IN FLOOR. PROVIDE POWER CIRCUIT AND EMPTY

3/4" DATA/COMM CONCEALED CONDUIT TO VERTICAL WALL FOR

ACCESS.

FLUSH MOUNTED 4-11/16" SQUARE SINGLE GANG JUNCTION BOX

FOR CARD READER. EXTEND 1" CONCEALED CONDUIT TO ABOVE

ACCESSIBLE CEILING AND STUB-OUT WITH PLASTIC BUSHING. OR

AS NOTED. INSTALL PULL WIRE.

TV

CR

LIGHTING FIXTURE SCHEDULE

TYPE

A

MANUFACTURER & CATALOG NO. DESCRIPTION LAMPS WATTS REMARKS

LED 40W

LIGHTING FIXTURE SCHEDULE NOTES:

ALL LAMPING COLOR TEMPERATURE SHALL BE 3500K MINIMUM FOR ALL LIGHTING FIXTURES.

REFER TO ARCHITECTURAL REFLECTED CEILING PLAN FOR EXACT FINAL LOCATION OF LIGHTING FIXTURES.

COORDINATE THE ACTUAL TYPE OF CEILING FOR EACH FIXTURE WITH ARCHITECTURAL REFLECTED CEILING PLANS AND

PROVIDE FIXTURE TRIM AS REQUIRED.

3.

4.

PROVIDE ALL DEVICES, DRYWALL FLANGES, MOUNTING EQUIPMENT, CHAIN, STRAIN RELIEFS, CLIPS, ESCUTCHEONS, PLATES AND STRUCTURAL SUPPORTS FOR THE INSTALLATION AND CONNECTION OF ALL LIGHTING FIXTURES.

1.

2.

NOTE: PROVIDE ALL REQUIRED MOUNTING HARDWARE AND WIRING TO CONNECT LIGHTING FIXTURES AT HOLLOW CORE, POST TENSION SLAB & STRUCTURAL STEEL LOCATIONS INCLUDING BOXES, HANGER BARS, STRUCTURAL APPROVED FASTENER'S AND UL APPROVED

CONNECTORS.

Z

VOLTS

120/277

5W AS APPROVED BY OWNER120LEDLED EMERGENCY LIGHT WITH 90 MIN. INTEGRAL EMERGENCY

BATTERY PACK

2'X4' FLAT PANEL LED

SURE-LITES: SEL-25-SD-SQ

Y 5W AS APPROVED BY OWNERLEDLED EMERGENCY LIGHT AND EXIT SIGN COMBO WITH 90 MIN.

INTEGRAL EMERGENCY BATTERY PACKSURE-LITES: APC-H-7-R-SQ 120/277

TGS LIGHTING: 8824WS-C-T-F-RM

XX

a

C 120/277 MOUNT TO WALL AT SAME HEIGHT AS FIXTURE REPLACED35WLED

PROVIDE SURFACE MOUNT KIT (OPTION SK) FOR FIXTURES

DESIGNATED FOR AREAS WITH HARD CEILINGS

COOPER METALUX: 4SNLED-LD5-48SL-UNV-L840-U-CD-1 4' SURFACE MOUNT LED STRIP

FIRE ALARM DEVICES

FAAP

FACP FIRE ALARM CONTROL SUB-PANEL, SURFACE MOUNTED UON

FIRE ALARM ANNUNCIATOR PANEL

CLEAN AGENT CONTROL PANEL

MANUAL FIRE ALARM PULL STATION

HORN/STROBE - WALL-MOUNTED, C = CEILING MOUNTED

STROBE - WALL-MOUNTED, C = CEILING MOUNTED

SMOKE DETECTOR, IONIZATION TYPE, CEILING MOUNTED

F

F

F

LOCATION WITHIN PARK

NAME OF PARK

TITLE OF SHEET

EVERGLADES NATIONAL PARK

PINE ISLAND DISTRICT

STATEREGION COUNTY

SOUTHEAST FLORIDAMIAMI-DADE

DATE:

TECH. REVIEW:

DRAWN:

DESIGNED:REVISIONS SUB SHEET NO.

PMIS / PKG. NO.

SHEET

DRAWING NO.

OFMAY 15, 2023

179573

314045

B 120/27740WLEDTGS LIGHTING: 8814WS-C-T-F-RM 1'X4' FLAT PANEL LED AS APPROVED BY OWNER a

AL

AL

MG

ELECTRICAL LEGEND AND SCHEDULE

E-

CACP

57A

57D

57B

57C

58A

58B

58C

58D

58E 58F

58G

SCREENED

PORCH

41'-8"

F F

F

F

F C

C

C C

C

C

F

F C

F C

1. EXISTING LIGHTING FIXTURES, EMERGENCY LIGHTS, AND

EXIT SIGNAGE IN THIS ROOM TO BE DEMOLISHED. REMOVE

FIXTURE, SUPPORTS AND APPURTENANCES. SECURE

EXISTING CIRCUITS FOR RECONNECTION TO

REPLACEMENT FIXTURES.

2. REMOVE EXISTING FIRE ALARM DEVICES FOR CEILING

DEMOLITION. SECURE DEVICES AND CONDUCTORS FOR

REINSTALLATION/RECONNECTION. REFER TO NEW WORK

PLAN ON SHEET E-201.

3. NOT USED

4. NOT USED

5. NOT USED

6. DEMOLISH EXISTING FIXTURE. ALL OTHER FIXTURES AND

SWITCHING FOR THIS LIGHTING CIRCUIT ARE EXISTING TO

REMAIN.

7. DEMOLISH EXISTING WALL SWITCH AND ALL ASSOCIATED

CONDUIT AND CONDUCTORS.

8. EXISTING FIRE ALARM DEVICE TO BE RELOCATED. REFER

TO SHEET E-201 FOR NEW LOCATION.

9. EXISTING LIGHTING FIXTURES, EMERGENCY LIGHTS, AND

EXIT SIGNAGE IN THIS ROOM TO BE DEMOLISHED. REMOVE

FIXTURE, SUPPORTS, APPURTENANCES, CONDUIT AND

WIRE. MAINTAIN POWER TO OTHER LIGHT FIXTURES TO

REMAIN THAT ARE OUTSIDE OF THE SCOPE OF WORK.

SWITCHING EXISTING TO REMAIN UON.

1. TRACE EXISTING FIXTURE CIRCUITS BACK TO HOST PANEL

PRIOR TO BEGINNING DEMOLITION WORK. LABEL LIGHTING

JUNCTION BOXES WITH PANEL AND CIRCUIT SERVING

LIGHTS.

2. FIELD VERIFY LOCATION AND COUNT OF EXISTING LIGHTING

FIXTURES BEFORE BEGINNING WORK.

3. UNLESS OTHERWISE NOTED, ALL SWITCHES ARE EXISTING

TO REMAIN FOR RECONNECTION TO NEW FIXTURES. REFER

TO SHEET E-201 FOR LIGHTING PLAN. CONTRACTOR TO

NOTE THE LIGHT FIXTURES AND DEVICES CONTROLLED BY

EACH SWITCH FOR RECONNECTION TO NEW LIGHT

FIXTURES.

GENERAL NOTES

KEY NOTES

SCALE: 3/16" = 1'-0"

LIGHTING AND FIRE ALARM DEMOLITION PLAN1

LOCATION WITHIN PARK

NAME OF PARK

TITLE OF SHEET

EVERGLADES NATIONAL PARK

PINE ISLAND DISTRICT

STATEREGION COUNTY

SOUTHEAST FLORIDAMIAMI-DADE

DATE:

TECH. REVIEW:

DRAWN:

DESIGNED:REVISIONS SUB SHEET NO.

PMIS / PKG. NO.

SHEET

DRAWING NO.

OFMAY 15, 2023

179573

314045

0 4' 8' 12'

Scale: 3/16" = 1'-0"

1 2 1 2

1 2

AL

AL

MG

LIGHTING AND FIRE ALARM DEMO PLAN

57A

57D

57B

57C

58A

58B

58C

58D

58E 58F

58G

AC

AHU

AHU

DH

DH

AC

SCREENED

PORCH

41'-8"

1. TRACE CIRCUITS FOR EXISTING POWER AND VOICE/DATA

DEVICES IN THIS AREA INCLUDING RECEPTACLES,

VOICE/DATA OUTLETS, EXHAUST FANS, ETC. INTERCEPT

EXISTING CIRCUITS TO DEVICES AND REROUTE TO NEW

PANEL 'D'. REFER TO SHEET E-202 FOR CIRCUITING.

2. DEMOLISH ALL EXISTING POWER AND VOICE/DATA DEVICES

INCLUDING RECEPTACLES, VOICE/DATA OUTLETS, EXHAUST

FANS, ETC. WITHIN THIS SPACE. REMOVE CONDUIT, WIRE,

AND SUPPORTS BACK TO SOURCE OR FIRST UPSTREAM

JUNCTION BOX OUTSIDE OF THE SCOPE OF WORK.

3. POWER DEVICES IN THIS ROOM ARE EXISTING TO REMAIN

AND WILL BE RE-FED FROM NEW PANEL 'D'. TRACE

CIRCUIT(S) AND NOTE ON PANEL SCHEDULE.

4. EXISTING AC UNIT TO BE DEMOLISHED. DISCONNECT

CONDUCTORS AND REMOVE CONDUIT, ELECTRICAL

DISCONNECT SWITCH, WIRING AND SUPPORTS BACK TO

SOURCE. MARK CIRCUIT BREAKER IN PANEL AS 'SPARE'.

5. EXISTING AHU ABOVE CEILING TO BE DEMOLISHED.

DISCONNECT UNIT AND REMOVE CONDUIT, WIRE, AND

FEEDERS BACK TO SOURCE. MARK CIRCUIT BREAKER IN

PANEL AS 'SPARE'.

6. DESICCANT WHEEL UNIT TO BE DEMOLISHED. DISCONNECT

UNIT AND REMOVE CONDUIT, ELECTRICAL DISCONNECT

SWITCH, WIRE, AND FEEDERS BACK TO SOURCE. MARK

CIRCUIT BREAKER IN PANEL AS 'SPARE.'

7. EXISTING DEHUMIDIFIER UNIT TO BE DEMOLISHED.

DISCONNECT UNIT AND REMOVE CONDUIT, WIRE, AND

BRANCH CIRCUIT BACK TO SOURCE. MARK CIRCUIT BREAKER

IN PANEL AS 'SPARE'.

8. EXISTING AHU IN CLOSET TO BE DEMOLISHED. DISCONNECT

UNIT AND REMOVE CONDUIT, WIRE, AND FEEDERS BACK TO

SOURCE. MARK CIRCUIT BREAKER IN PANEL AS 'SPARE'.

9. EXISTING PANEL 'MDP' TO REMAIN.

10. EXISTING PANEL FED FROM FUSED SWITCHBOARD TO

REMAIN.

11. EXISTING DISCONNECT SWITCH FOR FUSED SWITCHBOARD

TO REMAIN.

12. EXISTING FUSED SWITCHBOARD TO REMAIN.

1. TRACE EXISTING POWER CIRCUITS BACK TO HOST PANEL

PRIOR TO BEGINNING DEMOLITION WORK.

2. FIELD VERIFY LOCATION AND COUNT OF EXISTING DEVICES.

3. MAKE ALL NECESSARY CONNECTIONS AND EXTENSIONS OF

EXISTING CIRCUITS REQUIRED TO MAINTAIN POWER TO

DEVICES OUTSIDE OF THE SCOPE OF WORK THROUGHOUT

CONSTRUCTION.

GENERAL NOTES

KEY NOTES

SCALE: 3/16" = 1'-0"

POWER AND VOICE DATA DEMOLITION PLAN1

LOCATION WITHIN PARK

NAME OF PARK

TITLE OF SHEET

EVERGLADES NATIONAL PARK

PINE ISLAND DISTRICT

STATEREGION COUNTY

SOUTHEAST FLORIDAMIAMI-DADE

DATE:

TECH. REVIEW:

DRAWN:

DESIGNED:REVISIONS SUB SHEET NO.

PMIS / PKG. NO.

SHEET

DRAWING NO.

OFMAY 15, 2023

179573

314045

0 4' 8' 12'

Scale: 3/16" = 1'-0"

AL

AL

MG

POWER AND VOICE DATA DEMO PLAN

58A

58B

58C

58D

58E

58F

58G

SCREENED

PORCH

57A

57D

57B

57C

57E

58D A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A A

Y

A

Y

Y

Z

D-15 D-15 D-15 D-15

D-15 D-15 D-15 D-15

D-15 D-15 D-15 D-15

D-15

Y D-15

OS

OS

A

D-15 D-15

OS

D-15

A

A

A

D-153

D-15

D-15

A D-15

A

D-15

D-15

C C a b a b a b a b a b a b a b a bF F

F

F

F

C

C

C C

C

C Z

Z

B

A A

A

A

A A C

C

F

F C

F C

Y

Z

1. RECONNECT NEW FIXTURES TO EXISTING LIGHTING CIRCUITS

AND SWITCHING.

2. REINSTALL FIRE ALARM DEVICE IN REPLACEMENT CEILING AT

PREVIOUS LOCATION. EXTEND EXISTING FIRE ALARM

CONDUCTORS TO NEW CLEAN AGENT CONTROL PANEL IN

ROOM 58A AND RECONNECT. REFER TO SHEET E-202 FOR

LOCATION OF NEW CLEAN AGENT CONTROL PANEL. TYPICAL

FOR FOR ALL FIRE ALARM DEVICES UON.

3. REINSTALL FIRE ALARM DEVICE AT NEW LOCATION. EXTEND

EXISTING FIRE ALARM CONDUCTORS TO NEW CLEAN AGENT

CONTROL PANEL IN ROOM 58A AND RECONNECT. REFER TO

SHEET E-202 FOR LOCATION OF NEW CLEAN AGENT CONTROL

PANEL.

4. PROVIDE NEW SMOKE DETECTOR MOUNTED TO CEILING.

CONNECT TO NEW CLEAN AGENT CONTROL PANEL IN ROOM

58A. REFER TO SHEET E-202 FOR LOCATION OF NEW CLEAN

AGENT CONTROL PANEL.

1. UNLESS OTHERWISE NOTED CIRCUITS CONSIST OF (2) #12

AWG + #12 G IN 1/2" EMT CONDUIT.

2. PROVIDE UNSWITCHED HOT CONDUCTOR TO EMERGENCY

FIXTURES TO PROVIDE AUTOMATIC-ON OPERATION IN THE

CASE OF POWER LOSS.

3. FOR CLARITY, ONLY NEW SWITCHES ARE SHOWN. REFER TO

DRAWING E-101 FOR LOCATION OF ALL SWITCHING.

4. COORDINATE MOUNTING HEIGHTS OF LIGHT FIXTURES WITH

CEILING HEIGHTS ON ARCHITECTURAL PLANS FOR NEW

CEILINGS.

5. REFER TO SHEET F-001 FOR CLEAN AGENT SYSTEM FIRE

ALARM RISER DIAGRAM.

GENERAL NOTES

KEY NOTES

SCALE: 3/16" = 1'-0"

LIGHTING AND FIRE ALARM PLAN1

LOCATION WITHIN PARK

NAME OF PARK

TITLE OF SHEET

EVERGLADES NATIONAL PARK

PINE ISLAND DISTRICT

STATEREGION COUNTY

SOUTHEAST FLORIDAMIAMI-DADE

DATE:

TECH. REVIEW:

DRAWN:

DESIGNED:REVISIONS SUB SHEET NO.

PMIS / PKG. NO.

SHEET

DRAWING NO.

OFMAY 15, 2023

179573

314045

A A

A

A

A

A

A

A

A

A

A

A A

A

0 4' 8' 12'

Scale: 3/16" = 1'-0"

AL

AL

MG

LIGHTING AND FIRE ALARM PLAN

58A

58B

58C

58D

58E

58F

58G

RAG

SCREENED

PORCH

57A

57D

57B

57C

57E

58D

PANEL 'D'

D-1 D-1 D-1

D-3 D-3 D-3

D-1

D-1

D-3 D-5

D-3 D-3

D-3

D-5

D-7

D-7

D-9

D-9

D-11

D-13

D-13 D-6:8

ACD-17

D-17 D-17

D-17

D-17

D-17

D-19

D-19

D-21

D-21

D-21

WP

WP D-2:4 D-10:12

(2)#8 AWG + #8G IN

3/4" C.

(2)#12 AWG + #12G

IN 1/2" C.

(2)#8 AWG + #8G IN

3/4" C.

(2)#12 AWG + #12G

IN 1/2" C.

(2)#12 AWG + #12 G. IN

1/2" C.

D-14:16

D-18:20

FACP

CACP

J

J

D-24

D-22

(2)#12 AWG + #12G

IN 1/2" C.

(2)#12 AWG + #12G

IN 1/2" C.

1. EXISTING RECEPTACLES WITHIN THIS SPACE TO BE

RECONNECTED TO NEW PANEL 'D' LOCATED IN ROOM 57.

2. PROVIDE 60A, 240V RATED SAFETY SWITCH IN NEMA 3R

ENCLOSURE FOR HVAC.

3. AC-1 CASSETTE FOR MINI-SPLIT SYSTEM MOUNTED ABOVE

CEILING. UNIT IS POWERED FROM EXTERIOR UNIT HP-3.

ROUTE (2) #12 AWG + #12 G. IN 1/2"C TO EXTERIOR UNIT FOR

POWER.

4. EXHAUST FAN MOUNTED IN BATHROOM CEILING. CONNECT

TO BATHROOM LIGHTING CIRCUIT D-15. CONTROL VIA

BATHROOM LIGHT SWITCH. CONNECT FAN CONTROL RELAY

TO FIRE ALARM PANEL CONTACTOR FOR AUTOMATIC

SHUTDOWN DURING A FIRE ALARM EVENT.

This is the start of the file's text. The full file is on GovTribe.

File details come from the government source that posted it. Updated .