Sol_140P5424Q0011_Amend__0001_Attach__0002_-_Q_and_A_0001.pdf
PDF 344 KB Posted
- Attached to
- REPLACE GASOLINE & DIESEL FUEL SYSTEMS
- Solicitation number
- 140P5424Q0011
About this file
This document is a Question and Answer (Q&A) attachment to Solicitation 140P5424Q0011 for the replacement of gasoline and diesel fuel systems at the Pine Island facility. The key details are:
The solicitation requires the supply and installation of one 4,000-gallon gasoline fuel tank, one 4,000-gallon split gasoline and diesel fuel tank, and four Gas Boy dispensers (two per tank). The contractor shall also provide two sets of galvanized steel stairs with handrails. The existing concrete support slab may need to be extended to accommodate the tank size. If the existing slab is not large enough, the contractor must provide a plan to augment the slab as required. Fuel tanks can be demolished on-site, but the contractor must follow all environmental and safety regulations for proper disposal. Temporary double-walled 2,000-gallon fuel tanks may be used during construction to maintain operations. The contractor must complete an updated pricing schedule as part of their offer.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Sol_140P5424Q0011_Amd_0001.pdf | ||
| Sol_140P5424Q0011.pdf | ||
| Sol_140P5424Q0011_Attach__0001_-_SOW.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Ques ons & Answers‐ Sol 140P5424Q0011 Amendment 0001‐
A achment 0002
1. Please confirm tank supply specifica ons for UL 2085 Fireguard tanks. Are they horizontal cylindrical tanks?
Tanks shall be horizontal cylindrical tanks.
2. Do tanks require catwalks for top‐of‐tank access?
Tanks will require a ladder/ stair that would be adequate for top‐of‐tank inspec on.
3. SOW 5.0 General Scope. 5.1 states to install in exis ng loca ons, mounted to exis ng concrete support slab. The exis ng southwestern tank slab is not large enough for a 4,000‐gallon
Fireguard tank. Please advise.
As per market research, some tank dimensions for a 4000‐gallon tank are 7.5Ft W X
14.5Ft L. Exis ng slab measures 18Ft W X 19Ft L. The contractor shall provide a cut sheet and explana on accompanied by code/regula on of why the pad does not have adequate space. If NOT possible to use the exis ng slab, the contractor shall augment the concrete slab as required to install a new tank. This must be made clear in the quote.
4. Can tanks be demolished on site and then removed?
Fuel tanks CAN be demolished on site. Terms for doing so: DERM and or DEP must be contacted before demoli on of fuel tanks. The contractor shall abide by all
Environmental or safety codes/regula ons for the proper disposal of tanks. No remanence of old fuel tanks shall be le on site upon project comple on.
Note: SOW sec on 5.13 states to provide two temporary double-walled 2,000-gallon fuel tanks with pumps and dispensers (one gasoline, one diesel) in the Pine Island Maintenance Yard.
Exis ng fuel tanks may be used as temporary fuel tanks to keep opera ons running during construc on to facilitate the process.
5. Offerors must complete the new updated price schedule table on page 2 of this document and include the table with their offer along with the informa on addressing the evalua on factors.
B. Updated Price Schedule
Item
Number
Descrip on Quan ty UoM Price
10 One 4,000‐gallon gasoline fuel tank, one 4,000‐gallon split gasoline and diesel fuel tank, four Gas Boy dispensers (two per tank), and two sets of galvanized steel stairs with handrails per the SOW
1 Lump
Sum
Slab Extension Needed YES NO $
TOTAL $