This document is an attachments package for a federal contract to replace underground electric service at Andrew Johnson National Historic Site. The project involves installing underground electrical conduits from an existing aboveground electrical box located in a wooded area to the basement of the Homestead building, eliminating the current above-ground service infrastructure. The electrical work includes providing new distribution panels, disconnect switches, and manual transfer switches as detailed in the basement plan electrical drawing. The contractor must chase conduits into the basement at an approximate location to be confirmed by the Contracting Officer in the field.
The attachments include site maps with aerial and ground-level photographs identifying the existing electrical box location and the approximate alignment for the underground conduit run, electrical as-built drawings showing the existing main disconnect switch in the basement and one-line diagram with legend and abbreviations, a basement plan drawing with detailed electrical new work specifications and notes, and Greenville Electric Authority (GEA) standard requirements for underground electric service to structures including trench specifications, conductor requirements, meter base installation standards, depth minimums of three feet with warning tape installation, coupling support specifications, and detailed trench cross-section diagrams for various configurations involving primary ducts, secondary ducts, communication cables, water/sewer lines, and encasement requirements.
View the file
Other files
Show all 12
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ATTACHMENTS
Replace Underground Electric
Andrew Johnson National Historic Site
Site Map
Approximate location where conduits must be chased into basement. Exact location to be identified by the Contracting Officer in the field.
Approximate location of existing aboveground electrical box
Location of Existing Electrical Box Approx. Alignment Where Conduits Must Be Chased Into Basement
Existing Aboveground Electrical Box
Existing Aboveground Electrical Box
Existing Main Disconnect Switch in Basement (shown on left)
Electric As Builts of Homestead Building - Includes Basement & One-Line Diagram
Greenville Electric Authority – Standard Underground Electric Service Requirements to a Structure
4 Feet Min.
6 Feet Max
3 Feet Min.
Ditch Depth
Expansion Coupling
Structure Wall
G E
A P
O
LE
Elbow
Strap Underneath Coupling
Strap (Alternate)
Strap
2-1/2" or 3" and 1"
STANDARD UNDERGROUND ELECTRIC
SERVICE REQUIREMENTS TO A STRUCTURE
100-200 AMP 120/240 Volt Single Phase
Greeneville Energy Authority 423-636-6200 www.mygea.net
NOTE: TO SCHEDULE A TRENCH INSPECTION,
CALL 423-636-6241.
SIDE WIRED/OFFSET
METER BASE
COMBINATION METER BASE
WITH DEDICATED CHASE FOR
UTILITY CONDUCTORS
*NOTE: NO LOAD
SIDE CONDUCTORS
ON LINE SIDE OF
METER BASE
**THE REQUIREMENTS OF THIS SPECIFICATION
ARE EFFECTIVE JANUARY 2, 2024 AND SUPERSEDE
ALL PREVIOUS PUBLICATIONS
8"
MAX DIST 215 FEET
NOTE: BEFORE GEA INSTALLS ANY FACILITIES ON PRIVATE PROPERTY, AN EASEMENT WILL NEED TO BE OBTAINED
A
B
C
C
C
D
E
G
B
B
*NOTE: 1 INCH COMMUNICATION DUCT NOT SHOWN IN ITS ENTIRETY FOR CLARITY
12"
Warning Tape
Warning Tape
F
Greenville Electric Authority – Trench Requirements