Solicitation 140P5122R0005, Amendment 0002 Questions and Answers
1. How many strands of fiber are required for each building?
Answer: The contractor is only required to run a 6 pair cable from the Visitor's Center to the maintenance building. AT&T is running the main line from the road to the Visitor's Center.
2. Do we need to install 2 separate 2” conduits from the main road to each building or can we install only 1, 2” from the main road to where the fiber route splits into 2 directions and then continue in individual conduits?
Answer: Only one two inch conduit is necessary from the main line to the maintenance building.
3. Under the safety requirements, items 3 and 4 are not listed?
Answer: Safety Items 3 and 4 were later omitted and is therefore a typo