A06_DRAWINGS_RATH_CH_ALARMS.pdf
PDF 727 KB Posted
- Attached to
- ROVA REPLACE ALARMS AT CH AND RATH Federal contract opportunity
- Solicitation number
- 140P4525Q0054
About this file
These architectural drawings detail the alarm systems design for the Vanderbilt Coach House at Roosevelt-Vanderbilt National Historical Park, focusing on intrusion detection and fire alarm installations. The documents include schematic plans for first and second floors, a security riser diagram, fire detection sequence of operations, and device location plans, specifically covering Option 01 for fire and security systems.
The technical drawings specify comprehensive alarm system components including motion detectors, door contacts, control panels, keypads, smoke detectors, and horn strobes across multiple building levels. Key design notes indicate requirements such as providing a complete working security system, demonstrating and training the owner on the system, establishing a telephone line backup, and ensuring a 72-hour battery backup capable of 20-minute standby alarm operation. The plans are prepared by the United States Department of the Interior, National Park Service, Denver Service Center, for the Vanderbilt Coach House location within the park.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Sol_140P4525Q0054.pdf | ||
| References_Worksheet_(1)_(1).doc | DOC document | |
| B03_NY20250007_072525.pdf | ||
| B08_Price_Schedule_Rath_and_CH_Alarms.docx | DOCX document | |
| A04__Statement.docx | DOCX document | |
| A04_Rath_CH_Alarm_SPECIFICATION.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
AutoCAD SHX Text
NATIONAL PARK SERVICE
AutoCAD SHX Text
DENVER SERVICE CENTER
AutoCAD SHX Text
UNITED STATES
AutoCAD SHX Text
DEPARTMENT OF THE INTERIOR
AutoCAD SHX Text
DRAWING NO.
AutoCAD SHX Text
REGION
AutoCAD SHX Text
COUNTY
AutoCAD SHX Text
STATE
AutoCAD SHX Text
NAME OF PARK
AutoCAD SHX Text
LOCATION WITHIN PARK
AutoCAD SHX Text
TITLE OF DRAWING
AutoCAD SHX Text
PKG.
AutoCAD SHX Text
NO.
AutoCAD SHX Text
OF
AutoCAD SHX Text
SHEET
AutoCAD SHX Text
COVER
AutoCAD SHX Text
VAMA AND HOFR RATH
AutoCAD SHX Text
ROVA
AutoCAD SHX Text
NER
AutoCAD SHX Text
DUTCHESS
AutoCAD SHX Text
NY
AutoCAD SHX Text
ALARM SYSTEMS
AutoCAD SHX Text
FIRE & INTRUSION DETECTION
AutoCAD SHX Text
RATH CURATORIAL STORAGE
AutoCAD SHX Text
VANDERBILT COACH HOUSE
AutoCAD SHX Text
INTRUSION DETECTION
OPTION 01 FIRE DETECTION
WORK/RESEARCH
AutoCAD SHX Text
AutoCAD SHX Text
PRIORITY I STORAGE
AutoCAD SHX Text
AutoCAD SHX Text
PRIORITY II STORAGE
AutoCAD SHX Text
AutoCAD SHX Text
REGISTRAR
AutoCAD SHX Text
AutoCAD SHX Text
SUPPLY
AutoCAD SHX Text
AutoCAD SHX Text
BREAK
AutoCAD SHX Text
AutoCAD SHX Text
ENTRY
AutoCAD SHX Text
AutoCAD SHX Text
UNISEX
AutoCAD SHX Text
AutoCAD SHX Text
MOVABLE STORAGE
AutoCAD SHX Text P
AutoCAD SHX Text P
AutoCAD SHX Text W
AutoCAD SHX Text T
AutoCAD SHX Text P
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
MECH/ELEC
AutoCAD SHX Text
AutoCAD SHX Text P
AutoCAD SHX Text
LAB
AutoCAD SHX Text
AutoCAD SHX Text A
AutoCAD SHX Text
FD1
AutoCAD SHX Text A
AutoCAD SHX Text
FD1
AutoCAD SHX Text B
AutoCAD SHX Text
FD1
AutoCAD SHX Text B
AutoCAD SHX Text
FD1
AutoCAD SHX Text N
AutoCAD SHX Text
AutoCAD SHX Text
FD1
AutoCAD SHX Text P
AutoCAD SHX Text T
AutoCAD SHX Text T
AutoCAD SHX Text
AutoCAD SHX Text
R-30 INSULATED METAL ROOF PANEL
AutoCAD SHX Text
BOMDESC
AutoCAD SHX Text
PARTNO
AutoCAD SHX Text
QTY
AutoCAD SHX Text
LF
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
TYPICAL SMOKE DETECTOR MOUNTED TO BOTTOM OF PURLON
AutoCAD SHX Text
TYPICAL SMOKE DETECTOR MOUNTED TO CEILING TILE
AutoCAD SHX Text
WORK/RESEARCH
AutoCAD SHX Text
AutoCAD SHX Text
REGISTRAR
AutoCAD SHX Text
AutoCAD SHX Text
SUPPLY
AutoCAD SHX Text
AutoCAD SHX Text
BREAK
AutoCAD SHX Text
AutoCAD SHX Text
ENTRY
AutoCAD SHX Text
AutoCAD SHX Text
UNISEX
AutoCAD SHX Text
AutoCAD SHX Text
FACP
AutoCAD SHX Text P
AutoCAD SHX Text P
AutoCAD SHX Text
AutoCAD SHX Text
LAB
AutoCAD SHX Text
AutoCAD SHX Text
TYPICAL SMOKE DETECTOR MOUNTED TO BOTTOM OF PURLON
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
LF
AutoCAD SHX Text
QTY
AutoCAD SHX Text
PARTNO
AutoCAD SHX Text
BOMDESC
AutoCAD SHX Text
FIRE DETECTION PLAN
AutoCAD SHX Text
FD1
AutoCAD SHX Text
FAV
AutoCAD SHX Text
FAV
AutoCAD SHX Text
DJV
AutoCAD SHX Text
KNOX BOX #3200 RECESSED MOUNT
AutoCAD SHX Text
SMOKE DETECTOR (PHOTOELECTRIC)
AutoCAD SHX Text
SYMBOL LEGEND
AutoCAD SHX Text
FIRE ALARM CONTROL PANEL
AutoCAD SHX Text
DEVICE WITH ### CANDELA STROBE
AutoCAD SHX Text
STROBE ONLY
AutoCAD SHX Text
MANUAL PULL STATION (DUAL ACTION 48" AFF)
AutoCAD SHX Text
HORN/STROBE
AutoCAD SHX Text
TAMPER SWITCH
AutoCAD SHX Text
FLOW SWITCH
AutoCAD SHX Text N
AutoCAD SHX Text W
AutoCAD SHX Text
AutoCAD SHX Text P
AutoCAD SHX Text
DOOR MAGNET
AutoCAD SHX Text T
AutoCAD SHX Text
HI/LOW PRESSURE SWITCH
AutoCAD SHX Text
FAP
AutoCAD SHX Text
SPRINKLER HEAD
AutoCAD SHX Text
HEAT DETECTOR
AutoCAD SHX Text
FD1
AutoCAD SHX Text
AutoCAD SHX Text
SCALE: NONE
AutoCAD SHX Text %%uTYPICAL DEVICE LOCATIONS
AutoCAD SHX Text
3' MINIMUM
AutoCAD SHX Text
STROBE
AutoCAD SHX Text
CEILING
AutoCAD SHX Text I
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text F
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text F
AutoCAD SHX Text I
AutoCAD SHX Text
AIR REGISTER
AutoCAD SHX Text F I R E
AutoCAD SHX Text
SMOKE OR HEAT DETECTOR
AutoCAD SHX Text
AUDIBLE/STROBE
AutoCAD SHX Text
PULL STATION
AutoCAD SHX Text
PULL DOWN
AutoCAD SHX Text P U S H
AutoCAD SHX Text
FIRE ALARM
AutoCAD SHX Text P
AutoCAD SHX Text
FD1
AutoCAD SHX Text
AutoCAD SHX Text %%uSCHEMATIC PLAN
AutoCAD SHX Text
FD1
AutoCAD SHX Text
AutoCAD SHX Text %%uBELOW SUSPENDED CEILING SCHEMATIC PLAN
AutoCAD SHX Text
FD1
AutoCAD SHX Text
AutoCAD SHX Text %%uA-A ELEVATION
AutoCAD SHX Text
FD1
AutoCAD SHX Text
AutoCAD SHX Text %%uB-B ELEVATION
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text KEY NOTES 1 FD CONTRACTOR TO COORDINATE WITH SPRINKLER CONTRACTOR FOR FD CONTRACTOR TO COORDINATE WITH SPRINKLER CONTRACTOR FOR EXACT QUANITIES OF TAMPER, FLOW, PRESSURE SWITCHES REQUIRED.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
SCALE OF FEET
AutoCAD SHX Text
SCALE OF FEET
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
SCALE OF FEET
AutoCAD SHX Text
SCALE OF FEET
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
RATH CURATORIAL
AutoCAD SHX Text
HOME OF FRANKLIN D. ROOSEVELT NHS
AutoCAD SHX Text 344220
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
DESIGNED:
AutoCAD SHX Text
TECH. REVIEW:
AutoCAD SHX Text
SUB SHEET NO.
AutoCAD SHX Text
PMIS/PKG NO.
AutoCAD SHX Text
DRAWING NO.
AutoCAD SHX Text
SHEET
AutoCAD SHX Text
OF
AutoCAD SHX Text
TITLE OF SHEET
AutoCAD SHX Text 4/11/2025
STORAGE
RATH CURATORIAL
AutoCAD SHX Text
HOME OF FRANKLIN D. ROOSEVELT NHS
AutoCAD SHX Text 344220
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
DESIGNED:
AutoCAD SHX Text
TECH. REVIEW:
AutoCAD SHX Text
SUB SHEET NO.
AutoCAD SHX Text
PMIS/PKG NO.
AutoCAD SHX Text
DRAWING NO.
AutoCAD SHX Text
SHEET
AutoCAD SHX Text
OF
AutoCAD SHX Text
TITLE OF SHEET
AutoCAD SHX Text 4/11/2025
AutoCAD SHX Text
STORAGE
AutoCAD SHX Text
FIRE DETECTION DIAG.
AutoCAD SHX Text
FD2
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
DUCT DETECTOR TEST SWITCH
AutoCAD SHX Text
3. ALARM VERIFICATION IS NOT PERMITTED ON MANUAL PULL STATIONS, OR FIRE SPRINKLER EQUIPMENT.
AutoCAD SHX Text
AUDIBLE/VISUAL APPLIANCE
AutoCAD SHX Text
GROUND FAULT
AutoCAD SHX Text
OPEN CIRCUIT
AutoCAD SHX Text
REMOVAL OF DEVICE
AutoCAD SHX Text
POOR/NO DEVICE RESPONSE
AutoCAD SHX Text
SHORT CIRCUIT
AutoCAD SHX Text
GROUND FAULT
AutoCAD SHX Text
SHORT CIRCUIT
AutoCAD SHX Text
OPEN CIRCUIT
AutoCAD SHX Text
SPRINKLER WATERFLOW SWITCH
AutoCAD SHX Text
SPRINKLER TAMPER SWITCH
AutoCAD SHX Text
MANUAL PULL STATION
AutoCAD SHX Text
DUCT SMOKE DETECTOR
AutoCAD SHX Text
COMBINATION SMOKE/HEAT DETECTOR
AutoCAD SHX Text
2. SYSTEM OPERATING INSTRUCTIONS ARE PRINTED ON THE FACP ADJACENT TO THE CONTROL BUTTONS.
AutoCAD SHX Text
REMOVAL OF SMOKE DETECTOR
AutoCAD SHX Text
DISPLAY YELLOW
AutoCAD SHX Text
ACTUATE AUDIBLE
AutoCAD SHX Text
LED ON DEVICE
AutoCAD SHX Text
AT FACP
AutoCAD SHX Text
SUPY. SIGNAL
AutoCAD SHX Text
MESSAGE WITH LOCATION,
AutoCAD SHX Text
AND LIGHT LED AT FACP
AutoCAD SHX Text
DISPLAY CUSTOM ALARM
AutoCAD SHX Text
DISPLAY CUSTOM SUPERVISORY
AutoCAD SHX Text
AND LIGHT LED AT FACP
AutoCAD SHX Text
MESSAGE WITH LOCATION,
AutoCAD SHX Text
AND LIGHT LED AT FACP
AutoCAD SHX Text
(BUZZER)
AutoCAD SHX Text
DAMPER CLOSED
AutoCAD SHX Text
SMOKE DOORS
AutoCAD SHX Text
RELEASE
AutoCAD SHX Text
OF SMOKE
AutoCAD SHX Text
CONFIRMATION SIGNAL
AutoCAD SHX Text %%uSYSTEM OPERATION NOTES:
AutoCAD SHX Text
1. THIS SYSTEM IS CAPABLE OF EVERY INITIATION DEVICE AND NOTIFICATION APPLIANCE ACTIVATING SIMULTANEOUSLY.
AutoCAD SHX Text
HVAC FANS
AutoCAD SHX Text
SHUT DOWN
AutoCAD SHX Text
VIA DACT
AutoCAD SHX Text
EVENT IN SYSTEM MEMORY
AutoCAD SHX Text
FACP STORES SUPERVISORY
AutoCAD SHX Text
AT REMOTE ANNUNCIATOR
AutoCAD SHX Text
DISPLAY ALARM CONDITION & LOCATION
AutoCAD SHX Text
STATION VIA DACT
AutoCAD SHX Text
SIGNAL REMOTE MONITORING
AutoCAD SHX Text
RESET THE FACP
AutoCAD SHX Text
STATION VIA DACT
AutoCAD SHX Text
SIGNAL REMOTE MONITORING
AutoCAD SHX Text
AT REMOTE ANNUNCIATOR
AutoCAD SHX Text
DISPLAY SUPERVISORY CONDITION & LOCATION
AutoCAD SHX Text
AT REMOTE ANNUNCIATOR
AutoCAD SHX Text
DISPLAY TROUBLE CONDITION & LOCATION
AutoCAD SHX Text
SIGNAL REMOTE MONITORING
AutoCAD SHX Text
STATION VIA DACT
AutoCAD SHX Text
SILENCE THE LOCAL
AutoCAD SHX Text
AUDIBLE SUPERVISORY
AutoCAD SHX Text
SIGNAL AT THE FACP
AutoCAD SHX Text
AUDIBLE/VISUAL APPLIANCES
AutoCAD SHX Text
PRESS AGAIN TO UNSILENCE & REACTIVATE
AutoCAD SHX Text
DISPLAY ALARM CONDITION & LOCATION
AutoCAD SHX Text
AT REMOTE ANNUNCIATOR
AutoCAD SHX Text
SIGNAL REMOTE
AutoCAD SHX Text
MONITORING STATION
AutoCAD SHX Text
DISPLAY SUPERVISORY CONDITION & LOCATION
AutoCAD SHX Text
AT REMOTE ANNUNCIATOR
AutoCAD SHX Text
SIGNAL REMOTE MONITORING
AutoCAD SHX Text
STATION VIA DACT
AutoCAD SHX Text
FACP STORES SUPERVISORY EVENT IN SYSTEM MEMORY
AutoCAD SHX Text
STATION VIA DACT
AutoCAD SHX Text
SIGNAL REMOTE MONITORING
AutoCAD SHX Text
AT REMOTE ANNUNCIATOR
AutoCAD SHX Text
DISPLAY TROUBLE CONDITION & LOCATION
AutoCAD SHX Text
RESET THE FACP
AutoCAD SHX Text
RESTORE THE DEVICE(S)
AutoCAD SHX Text
AND/OR APPLIANCES
AutoCAD SHX Text
RESTORE THE DEVICE(S)
AutoCAD SHX Text
RESET THE FACP
AutoCAD SHX Text
RESTORE THE DEVICE(S)
AutoCAD SHX Text
IN TROUBLE
AutoCAD SHX Text
AND/OR APPLIANCES
AutoCAD SHX Text
ACKNOWLEDGE THE DEVICE(S)
AutoCAD SHX Text
ACKNOWLEDGE THE DEVICE(S)
AutoCAD SHX Text
AND/OR APPLIANCES
AutoCAD SHX Text
IN SUPERVISORY CONDITION
AutoCAD SHX Text
VISUAL APPLIANCES
AutoCAD SHX Text
IN ALARM
AutoCAD SHX Text
ACKNOWLEDGE THE DEVICE(S)
AutoCAD SHX Text
ACTIVATE ALL AUDIBLE & VISUAL NOTIFICATION APPLIANCES
AutoCAD SHX Text
FACP STORES TROUBLE EVENT IN SYSTEM MEMORY
AutoCAD SHX Text
FIRE ALARM ACTION
AutoCAD SHX Text
RESET PROCEDURE
AutoCAD SHX Text
SILENCE THE AUDIBLE/
AutoCAD SHX Text
SIGNAL AT THE FACP
AutoCAD SHX Text
AUDIBLE SUPERVISORY
AutoCAD SHX Text
SILENCE THE LOCAL
AutoCAD SHX Text
DISPLAY YELLOW
AutoCAD SHX Text
LED ON DEVICE
AutoCAD SHX Text
AT FACP
AutoCAD SHX Text
TROUBLE SIGNAL
AutoCAD SHX Text
ACTUATE AUDIBLE
AutoCAD SHX Text
DISPLAY RED
AutoCAD SHX Text
LED ON DEVICE
AutoCAD SHX Text
POSITIVE ALARM
AutoCAD SHX Text
FACP ACTIVATES
AutoCAD SHX Text
SEQUENCE
AutoCAD SHX Text
FACP LOW BATTERY
AutoCAD SHX Text
OPEN CIRCUIT
AutoCAD SHX Text
GROUND FAULT
AutoCAD SHX Text
SHORT CIRCUIT
AutoCAD SHX Text
TROUBLE
AutoCAD SHX Text
FACP
AutoCAD SHX Text
SUPERVISORY
AutoCAD SHX Text
SPRINKLER TAMPER SWITCH
AutoCAD SHX Text
DEVICE(S) ACTIVATED
AutoCAD SHX Text
ALARM
AutoCAD SHX Text
MANUAL PULL STATION
AutoCAD SHX Text
COMBINATION SMOKE/HEAT DETECTOR
AutoCAD SHX Text
SPRINKLER WATERFLOW SWITCH
AutoCAD SHX Text
SPRINKLER TAMPER SWITCH CLOSED
AutoCAD SHX Text
FACP AC POWER FAILURE
AutoCAD SHX Text
SMOKE DETECTOR DIRTY
AutoCAD SHX Text
POOR/NO DEVICE RESPONSE
AutoCAD SHX Text
SIGNALING
AutoCAD SHX Text
EVENT
AutoCAD SHX Text
DEVICE TYPE
AutoCAD SHX Text
MESSAGE WITH LOCATION,
AutoCAD SHX Text
DISPLAY CUSTOM TROUBLE
AutoCAD SHX Text
NAC INDICATING CIRCUIT #2
AutoCAD SHX Text
NAC INDICATING CIRCUIT #1
AutoCAD SHX Text
(1) #14 TP
AutoCAD SHX Text
U-MHU-MCS
AutoCAD SHX Text
HORN/STROBE
AutoCAD SHX Text
DO NOT T-TAP
AutoCAD SHX Text
EOL 24K
AutoCAD SHX Text
DO NOT T-TAP
AutoCAD SHX Text
EOL 24K
AutoCAD SHX Text
STROBE
AutoCAD SHX Text
U-MCS
AutoCAD SHX Text
(1) #14 TP
AutoCAD SHX Text
U-MHU-MCS
AutoCAD SHX Text
HORN/STROBE
AutoCAD SHX Text
LOCATED:
AutoCAD SHX Text
DSC
AutoCAD SHX Text
BELOW FACP
AutoCAD SHX Text
EOL 2.2K
AutoCAD SHX Text
DO NOT T-TAP
AutoCAD SHX Text
EOL 2.2K
AutoCAD SHX Text
DO NOT T-TAP
AutoCAD SHX Text
ROOF
AutoCAD SHX Text
GROUND
AutoCAD SHX Text
DOOR HOLDER
AutoCAD SHX Text
SDH-2A
AutoCAD SHX Text
DOOR HOLDER
AutoCAD SHX Text
SDH-2A
AutoCAD SHX Text R
AutoCAD SHX Text
DB-X11RS
AutoCAD SHX Text
W/RELAY BASE
AutoCAD SHX Text R
AutoCAD SHX Text
DB-X11RS
AutoCAD SHX Text
W/RELAY BASE
AutoCAD SHX Text
ADDRESSABLE SMOKE
AutoCAD SHX Text
FP-11
AutoCAD SHX Text
ADDRESSABLE SMOKE
AutoCAD SHX Text
FP-11
AutoCAD SHX Text
MSI-20B
AutoCAD SHX Text
DOUBLE ACTION
AutoCAD SHX Text
MANUAL PULL STATION
AutoCAD SHX Text
MSI-20B
AutoCAD SHX Text
ADDRESSABLE SMOKE
AutoCAD SHX Text
FP-11
AutoCAD SHX Text
INITIATING SIGNAL LOOP #2
AutoCAD SHX Text
(1) #18 TSP
AutoCAD SHX Text
TRI-D
AutoCAD SHX Text T/R
AutoCAD SHX Text D
AutoCAD SHX Text
DUAL ADDRESSABLE INPUT
AutoCAD SHX Text
DOUBLE ACTION
AutoCAD SHX Text
MANUAL PULL STATION
AutoCAD SHX Text
TAMPER
AutoCAD SHX Text
FLOW
AutoCAD SHX Text
FACP
AutoCAD SHX Text
LOCATED IN:
AutoCAD SHX Text
INDICATING CIRCUIT #1
AutoCAD SHX Text
(1) #14 TP
AutoCAD SHX Text
MXL-IQ
AutoCAD SHX Text Entry
AutoCAD SHX Text
ADDRESSABLE SMOKE
AutoCAD SHX Text
FP-11
AutoCAD SHX Text
INITIATING SIGNAL LOOP #1
AutoCAD SHX Text
(1) #18 TSP
AutoCAD SHX Text
-MUST BE INSTALLED ON THE CIRCUIT INDICATED
AutoCAD SHX Text
-MUST HAVE AN EOL
AutoCAD SHX Text
-SHALL NOT BE T-TAPPED
AutoCAD SHX Text
SEQUENTIALLY BUT THEY:
AutoCAD SHX Text
THE ALARM SIGNAL DEVICES DO NOT HAVE TO BE WIRED
AutoCAD SHX Text
%%UINDICATION CIRCUITS NOTE:
AutoCAD SHX Text
-MAY HAVE UNIQUE ADDRESSES
AutoCAD SHX Text
THE ALARM INITIATION DEVICES DO NOT HAVE TO BE WIRED
AutoCAD SHX Text
-SHALL NOT BE T-TAPPED
AutoCAD SHX Text
-DO NOT HAVE AN EOL
AutoCAD SHX Text
-MUST BE INSTALLED ON THE LOOP INDICATED
AutoCAD SHX Text
%%UINITIATION LOOP NOTE:
AutoCAD SHX Text
SEQUENTIALLY BUT THEY:
AutoCAD SHX Text
PHONE
AutoCAD SHX Text
COMMUNICATOR
AutoCAD SHX Text
DIGITAL
AutoCAD SHX Text
(1) 18/2 T.S.P.- ALARM SIGNAL
AutoCAD SHX Text
(1) 18/2 T.S.P.- TROUBLE SIGNAL
AutoCAD SHX Text
MOUNT NEXT TO
AutoCAD SHX Text
FACP
AutoCAD SHX Text
PHONE LINES
AutoCAD SHX Text
DEDICATED
AutoCAD SHX Text
(1) 18/2 T.S.P.- SUPERVISORY SIGNAL
AutoCAD SHX Text
OVERALL ARRANGEMENT OF THE FIRE ALARM SYSTEM. FOR
AutoCAD SHX Text
THE FIRE ALARM RISER IS INTENDED TO BE SCHEMATIC ONLY.
AutoCAD SHX Text
IT IS A GENERALIZED REPRESENTATION INTENDED TO SHOW THE
AutoCAD SHX Text
%%URISER NOTE:
AutoCAD SHX Text
EXACT QUANTITIES, PLEASE REFER TO FIRE ALARM FLOOR PLANS
AutoCAD SHX Text
AND FIRE ALARM CALCULATIONS FOR THIS PROJECT.
AutoCAD SHX Text EOL's 4.7K
AutoCAD SHX Text
120VAC-60 HZ
AutoCAD SHX Text
POWER INPUT
AutoCAD SHX Text
DEDICATED
AutoCAD SHX Text
(1) 14/2 T.S.P.-POWER
AutoCAD SHX Text
INDICATING CIRCUIT #2
AutoCAD SHX Text
(1) #14 TP
AutoCAD SHX Text P
AutoCAD SHX Text P
AutoCAD SHX Text T
AutoCAD SHX Text W
AutoCAD SHX Text P
AutoCAD SHX Text
U-MCS
AutoCAD SHX Text
STROBE
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text T
AutoCAD SHX Text
TAMPER
AutoCAD SHX Text T
AutoCAD SHX Text
HI/LO PRESSURE
AutoCAD SHX Text
SPRINKLER PRESSURE SWITCH
AutoCAD SHX Text
SPRINKLER PRESSURE SW. CLOSED
AutoCAD SHX Text
DUCT SMOKE DETECTOR
AutoCAD SHX Text
DUCT SMOKE DETECTOR ACTIVATED
AutoCAD SHX Text
FD2
AutoCAD SHX Text
AutoCAD SHX Text SCALE: none
AutoCAD SHX Text %%uADDRESSABLE FIRE ALARM SEQUENCE OF OPERATIONS
AutoCAD SHX Text
FD2
AutoCAD SHX Text
AutoCAD SHX Text SCALE: none
%%uRISER DIAGRAM
WORK/RESEARCH
AutoCAD SHX Text
AutoCAD SHX Text
PRIORITY I STORAGE
AutoCAD SHX Text
AutoCAD SHX Text
PRIORITY II STORAGE
AutoCAD SHX Text
AutoCAD SHX Text
REGISTRAR
AutoCAD SHX Text
AutoCAD SHX Text
SUPPLY
AutoCAD SHX Text
AutoCAD SHX Text
BREAK
AutoCAD SHX Text
AutoCAD SHX Text
ENTRY
AutoCAD SHX Text
AutoCAD SHX Text
UNISEX
AutoCAD SHX Text
AutoCAD SHX Text
MOVABLE STORAGE
AutoCAD SHX Text
MECH/ELEC
AutoCAD SHX Text
AutoCAD SHX Text
LAB
AutoCAD SHX Text
AutoCAD SHX Text
DS
AutoCAD SHX Text
DS
AutoCAD SHX Text
DS
AutoCAD SHX Text
DS
AutoCAD SHX Text
DS
AutoCAD SHX Text
DS
AutoCAD SHX Text
DS
AutoCAD SHX Text K/P
AutoCAD SHX Text K/P
AutoCAD SHX Text K/P
AutoCAD SHX Text
DS
AutoCAD SHX Text
SAP
AutoCAD SHX Text K/P
AutoCAD SHX Text K/P
AutoCAD SHX Text
DS
AutoCAD SHX Text
DS
AutoCAD SHX Text
DS
AutoCAD SHX Text
DS
AutoCAD SHX Text
DS
AutoCAD SHX Text
DS
AutoCAD SHX Text
LOADING
AutoCAD SHX Text
AutoCAD SHX Text K/P
AutoCAD SHX Text K/P
AutoCAD SHX Text
RATH CURATORIAL
AutoCAD SHX Text
HOME OF FRANKLIN D. ROOSEVELT NHS
AutoCAD SHX Text 344220
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
DESIGNED:
AutoCAD SHX Text
TECH. REVIEW:
AutoCAD SHX Text
SUB SHEET NO.
AutoCAD SHX Text
PMIS/PKG NO.
AutoCAD SHX Text
DRAWING NO.
AutoCAD SHX Text
SHEET
AutoCAD SHX Text
OF
AutoCAD SHX Text
TITLE OF SHEET
AutoCAD SHX Text 4/11/2025
AutoCAD SHX Text
STORAGE
AutoCAD SHX Text
ES1
AutoCAD SHX Text
ES1
AutoCAD SHX Text
AutoCAD SHX Text %%uSCHEMATIC PLAN
AutoCAD SHX Text
ES1
AutoCAD SHX Text
AutoCAD SHX Text
SCALE: N/A
AutoCAD SHX Text %%uSECURITY RISER DIAGRAM
AutoCAD SHX Text
MOTION SENSOR
AutoCAD SHX Text
DOOR SWITCH
AutoCAD SHX Text
DS
AutoCAD SHX Text
SYMBOL LEGEND
AutoCAD SHX Text K/P
AutoCAD SHX Text
KEY PAD
AutoCAD SHX Text
ALARM SIREN-15'AFF
AutoCAD SHX Text
SECURITY ALARM PANEL
AutoCAD SHX Text
CONTROL
AutoCAD SHX Text
PANEL
AutoCAD SHX Text
DS
AutoCAD SHX Text
DS
AutoCAD SHX Text
DS
AutoCAD SHX Text w/COMMUNICATOR
AutoCAD SHX Text
PRIORITY II STORAGE
AutoCAD SHX Text
AutoCAD SHX Text
LOADING
AutoCAD SHX Text
AutoCAD SHX Text
REGISTRAR
AutoCAD SHX Text
AutoCAD SHX Text
ENTRY
AutoCAD SHX Text
AutoCAD SHX Text
SUPPLY
AutoCAD SHX Text
AutoCAD SHX Text
PRIORITY I STORAGE
AutoCAD SHX Text
AutoCAD SHX Text
DS
AutoCAD SHX Text
DS
AutoCAD SHX Text 120V
AutoCAD SHX Text
SUPPLY
AutoCAD SHX Text
POWER
AutoCAD SHX Text
TELEPHONE LINE
AutoCAD SHX Text
DS
AutoCAD SHX Text
DS
AutoCAD SHX Text
MECH/ELEC
AutoCAD SHX Text
AutoCAD SHX Text
WORK
AutoCAD SHX Text
AutoCAD SHX Text
DS
AutoCAD SHX Text
DS
AutoCAD SHX Text
DS
AutoCAD SHX Text
DS
AutoCAD SHX Text
DS
AutoCAD SHX Text
DS
AutoCAD SHX Text
DS
AutoCAD SHX Text
WORK/RESEARCH
AutoCAD SHX Text
AutoCAD SHX Text
EXTERIOR
AutoCAD SHX Text
PRIORITY I STORAGE
AutoCAD SHX Text
AutoCAD SHX Text
PRIORITY II STORAGE
AutoCAD SHX Text
AutoCAD SHX Text K/P
AutoCAD SHX Text
ENTRY
AutoCAD SHX Text
AutoCAD SHX Text K/P
AutoCAD SHX Text K/P
AutoCAD SHX Text K/P
AutoCAD SHX Text K/P
AutoCAD SHX Text
MECH/ELEC
AutoCAD SHX Text
AutoCAD SHX Text
LOADING
AutoCAD SHX Text
AutoCAD SHX Text SHEET NOTES 1 PROVIDE A COMPLETE WORKING SECURITY SYSTEM, PROVIDE A COMPLETE WORKING SECURITY SYSTEM, WHICH INCLUDES ALL ITEMS SHOWN AND ANY APERTINANCES REQUIRED. 2 AT COMPLETION, PROVIDE OWNER WITH SYSTEM AT COMPLETION, PROVIDE OWNER WITH SYSTEM DEMONSTRATION AND TRAINING. 3 PROVIDE TELEPHONE LINE TO TELEPHONE BACK PROVIDE TELEPHONE LINE TO TELEPHONE BACK BOARD. 4 PROVIDE BATTERY BACK-UP CAPABLE OF 72 HOURS PROVIDE BATTERY BACK-UP CAPABLE OF 72 HOURS OF STANDBY AND AT THE END OF THE STANDBY 20 MINUTES OF ALARM. 5 ALL WIRING SHALL MEET OR EXCEDE NFPA 70, 2002.ALL WIRING SHALL MEET OR EXCEDE NFPA 70, 2002.
AutoCAD SHX Text
BREAK
AutoCAD SHX Text
AutoCAD SHX Text
LAB
AutoCAD SHX Text
AutoCAD SHX Text
PARTITION #1
AutoCAD SHX Text
PARTITION #2
AutoCAD SHX Text
PARTITION #3
AutoCAD SHX Text
PARTITION #4
AutoCAD SHX Text
PRIORITY II STORAGE
AutoCAD SHX Text
AutoCAD SHX Text
PRIORITY I STORAGE
AutoCAD SHX Text
AutoCAD SHX Text K/P
AutoCAD SHX Text K/P
AutoCAD SHX Text
WORK/RESEARCH
AutoCAD SHX Text
AutoCAD SHX Text
SCALE OF FEET
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
SECURITY
AutoCAD SHX Text
ALARM
AutoCAD SHX Text
WIRELESS MOTION SENSOR
AutoCAD SHX Text GE Concord V4
AutoCAD SHX Text
SUPER.BUSS 2000 LCD
AutoCAD SHX Text
ALPHAMUNMERIC 360-746-01
AutoCAD SHX Text #600-1040
AutoCAD SHX Text
WOOD DOORS - GE #1085-N
AutoCAD SHX Text
STEEL DOORS - GE #1078C-N
AutoCAD SHX Text
EXTERIOR - GE AS395
AutoCAD SHX Text
INTERIOR - GEMPI-47
AutoCAD SHX Text
GE #60-639-95R
AutoCAD SHX Text
GE #RCR-A
INTRUSION DETECTION
INTRUSION VAMA Coach House RCP
AutoCAD SHX Text Basement VAMA Coach House RCP
AutoCAD SHX Text
FIRST FLOOR
AutoCAD SHX Text
NATIONAL PARK SERVICE
AutoCAD SHX Text
DENVER SERVICE CENTER
AutoCAD SHX Text
UNITED STATES
AutoCAD SHX Text
DEPARTMENT OF THE INTERIOR
AutoCAD SHX Text
DRAWING NO.
AutoCAD SHX Text
REGION
AutoCAD SHX Text
COUNTY
AutoCAD SHX Text
STATE
AutoCAD SHX Text
NAME OF PARK
AutoCAD SHX Text
LOCATION WITHIN PARK
AutoCAD SHX Text
TITLE OF DRAWING
AutoCAD SHX Text
PKG.
AutoCAD SHX Text
NO.
AutoCAD SHX Text
OF
AutoCAD SHX Text
SHEET
AutoCAD SHX Text
COACH HOUSE
AutoCAD SHX Text
VAMA
AutoCAD SHX Text
NER
AutoCAD SHX Text
DUTCHESS
AutoCAD SHX Text
NEW YORK
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
UP
AutoCAD SHX Text
KITCHEN
AutoCAD SHX Text
KP
AutoCAD SHX Text
CP
AutoCAD SHX Text
CP
AutoCAD SHX Text
KP
AutoCAD SHX Text
MOTION DETECTOR
AutoCAD SHX Text
DOOR CONTACTOR
AutoCAD SHX Text
CONTROL PANEL, DIALER, ETC.
KEYPAD
SECOND FLOOR PLAN
AutoCAD SHX Text
NATIONAL PARK SERVICE
AutoCAD SHX Text
DENVER SERVICE CENTER
AutoCAD SHX Text
UNITED STATES
AutoCAD SHX Text
DEPARTMENT OF THE INTERIOR
AutoCAD SHX Text
DRAWING NO.
AutoCAD SHX Text
REGION
AutoCAD SHX Text
COUNTY
AutoCAD SHX Text
STATE
AutoCAD SHX Text
NAME OF PARK
AutoCAD SHX Text
LOCATION WITHIN PARK
AutoCAD SHX Text
TITLE OF DRAWING
AutoCAD SHX Text
PKG.
AutoCAD SHX Text
NO.
AutoCAD SHX Text
OF
AutoCAD SHX Text
SHEET
AutoCAD SHX Text
COACH HOUSE
AutoCAD SHX Text
VANDERBILT
AutoCAD SHX Text
VAMA
AutoCAD SHX Text
NER
AutoCAD SHX Text
DUTCHESS
AutoCAD SHX Text
NEW YORK
INTRUSION
INTRUSION VAMA Coach House RCP
AutoCAD SHX Text Basement VAMA Coach House RCP
AutoCAD SHX Text P
AutoCAD SHX Text P
AutoCAD SHX Text
FACP
AutoCAD SHX Text P
AutoCAD SHX Text
KP
AutoCAD SHX Text
NATIONAL PARK SERVICE
AutoCAD SHX Text
DENVER SERVICE CENTER
AutoCAD SHX Text
UNITED STATES
AutoCAD SHX Text
DEPARTMENT OF THE INTERIOR
AutoCAD SHX Text
DRAWING NO.
AutoCAD SHX Text
REGION
AutoCAD SHX Text
COUNTY
AutoCAD SHX Text
STATE
AutoCAD SHX Text
NAME OF PARK
AutoCAD SHX Text
LOCATION WITHIN PARK
AutoCAD SHX Text
TITLE OF DRAWING
AutoCAD SHX Text
PKG.
AutoCAD SHX Text
NO.
AutoCAD SHX Text
OF
AutoCAD SHX Text
SHEET
AutoCAD SHX Text
COACH HOUSE RCP
AutoCAD SHX Text
OPTION 01 FIRE DEVICES
AutoCAD SHX Text
COACH HOUSE 1ST & BSMT
AutoCAD SHX Text
VANDERBILT
AutoCAD SHX Text
NER
AutoCAD SHX Text
DUTCHESS
AutoCAD SHX Text
NY
AutoCAD SHX Text
RCP
AutoCAD SHX Text GENERAL NOTES: 1. COORDINATE WITH COR TO SUBSTITUTE DEVICE TYPES BASED ON ROOM COORDINATE WITH COR TO SUBSTITUTE DEVICE TYPES BASED ON ROOM OR SPACE USAGE 2. FOLLOW PREVIOUS INSTALLATION'S EXPOSED/CONCEALED WIRING FOLLOW PREVIOUS INSTALLATION'S EXPOSED/CONCEALED WIRING PATTERN 3. ALLOW FOR UP TO THREE (3) ADDITIONAL NEW DEVICES TO BE ALLOW FOR UP TO THREE (3) ADDITIONAL NEW DEVICES TO BE PLACED IF NEEDED IN COORDINATION WITH COR.
AutoCAD SHX Text
HEAT DETECTOR
AutoCAD SHX Text
SMOKE DETECTOR
AutoCAD SHX Text
KEYPAD
AutoCAD SHX Text
CONTROL PANEL
AutoCAD SHX Text
HORN STROBE
AutoCAD SHX Text
PULL STATION
OPTION 01
NATIONAL PARK SERVICE
AutoCAD SHX Text
DENVER SERVICE CENTER
AutoCAD SHX Text
UNITED STATES
AutoCAD SHX Text
DEPARTMENT OF THE INTERIOR
AutoCAD SHX Text
DRAWING NO.
AutoCAD SHX Text
REGION
AutoCAD SHX Text
COUNTY
AutoCAD SHX Text
STATE
AutoCAD SHX Text
NAME OF PARK
AutoCAD SHX Text
LOCATION WITHIN PARK
AutoCAD SHX Text
TITLE OF DRAWING
AutoCAD SHX Text
PKG.
AutoCAD SHX Text
NO.
AutoCAD SHX Text
OF
AutoCAD SHX Text
SHEET
AutoCAD SHX Text
COACH HOUSE RCP
AutoCAD SHX Text
OPTION 01 FIRE DEVICES
AutoCAD SHX Text
COACH HOUSE 2ND
AutoCAD SHX Text
VANDERBILT
AutoCAD SHX Text
NER 01
AutoCAD SHX Text
DUTCHESS
AutoCAD SHX Text
NY
AutoCAD SHX Text
RCP
AutoCAD SHX Text GENERAL NOTES: 1. COORDINATE WITH COR TO SUBSTITUTE DEVICE COORDINATE WITH COR TO SUBSTITUTE DEVICE TYPES BASED ON ROOM OR SPACE USAGE 2. FOLLOW PREVIOUS INSTALLATION'S FOLLOW PREVIOUS INSTALLATION'S EXPOSED/CONCEALED WIRING PATTERN 3. ALLOW FOR UP TO THREE (3) ADDITIONAL ALLOW FOR UP TO THREE (3) ADDITIONAL NEW DEVICES TO BE PLACED IF NEEDED IN COORDINATION WITH COR.
AutoCAD SHX Text
SMOKE DET.
AutoCAD SHX Text
HORN STROBE
AutoCAD SHX Text
OPTION 01
OPTION 01
| ALARMS COVER |
| Sheets and Views |
| Layout1 |
| PLOT |
| RATH FD |
| Sheets and Views |
| FD1 - FIRE DETECTION PLAN |
| RATH FIRE DETECTION DIAG |
| Sheets and Views |
| FD2 - FIRE DETECTION |
| RATH INTRUSION |
| Sheets and Views |
| ES-1 |
| CH Intrusion-1st Flr |
| Sheets and Views |
| 1st Flr |
| CH Intrusion-2nd Flr |
| Sheets and Views |
| 2nd Flr |
| CH Alarms-First Fire |
| Sheets and Views |
| First Fire |
| CH Alarms-Second Fire |
| Sheets and Views |
| Second Fire |