This document contains an amendment to a solicitation for the MACA 217837 Mammoth Cave Hotel & Roof Rehab project. The National Park Service is seeking to rehabilitate the roof and perform other repairs at the Mammoth Cave Hotel located in Mammoth Cave, Kentucky. The solicitation is a total small business set-aside with a response due date of August 3rd, 2021. Through a series of questions and answers, the amendment provides clarifications on specifications, extends the response deadline by seven days, and approves the use of alternative materials. Details include allowing OSB sheathing, yellow pine lumber, and eliminating preservative treatment requirements. The document addresses contractor questions on subsurface conditions, limits of construction, and fire alarm system replacements.
View the file
Other files
Show all 23
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Amendment 4
| Question Set | Set Number | Question | Response |
| A |
Amendment 0001
| Posted 6/30/2021 | 1 | SF-1442 states proposals are to be submitted by 1200 (hour) local time 07/27/2021. Is this Mountain Daylight Time, Eastern Daylight Time or another time zone? | Due to system ambiguities during transmission, the due date for Proposal Submissions is clarified as follows: Proposal Submissions are due no later than 12:00 pm Mountain Daylight Time (MDT) on July 27th, 2021. The due date for Questions remains unchanged from ten (10) calendar days prior to the due date and time for Proposal Submissions, as noted above. | |
| 2 | There is an organized site visit scheduled for July 14th, 2021 however the solicitation does not list the time. Could you please provide the time for the site visit on July 14th? | Section L Provision 52.236-27 - "Site Visit (Construction) - Alternate I (Feb 1995)," is updated to reflect the time of the Organized Pre-Proposal Site Visit as follows: |
52.236-27 SITE VISIT (CONSTRUCTION) – ALTERNATE I (FEB 1995)
(a) The clauses at 52.236-2, Differing Site Conditions, and 52.236-3, Site Investigations and Conditions Affecting the Work, will be included in any contract awarded as a result of this solicitation. Accordingly, offerors or quoters are urged and expected to inspect the site where the work will be performed.
(b) An organized site visit has been scheduled for— July 14th, 2021 -- from 8:00 am to 12:00 pm Central Time (CT).
In order to properly plan for and accommodate those interested in participating in this organized site visit, the Government respectfully requests that an email be sent to the Contract Specialist (amber_hughes@nps.gov) and Contracting Officer (frank_camacho@nps.gov), no later than July 9th, 2021; to include the Name of the Firm; Number and Names of Participants; and respective Point-of-Contact information (email address/direct phone line).
(c) Participants will meet at— The Lodge at Mammoth Cave, 171 Hotel Road, Mammoth Cave, KY 42259.
(End of provision) B
Amendment 0002
Posted 7/9/2021 3 In the fire suppression section:
a. Line "a" does not specifically mention the onsite individuals must be certified/licensed, only the contractor. Is this correct that only the company must be certified/licensed?
b. Line "b" states the technician but be NICET III. Typically this person must be onsite at ALL times while sprinkler work is being performed. Please confirm this is correct.
| c. Line "c" states as approved by the AHJ. What is the process to be pre-approved by the AHJ. | NPS RM 58 Requires Fire Sprinkler Designer be a Fire Protection Engineer or NICET III. And the installer shall be a State or municipal certified/licensed sprinkler contractor or NICET II. The installer can have other people who do not posses this qualification help under the qualified persons supervision. Contractors may look into the pre-approval by the AHJ, but if your company does not already have the AHJs approval you should not consider yourself qualified without these credentials stated. | ||
| 4 | In the fire alarm system: |
a. Line "A" states that the fire alarm system shall be installed under the supervision of a person meeting the requirements. Typically this person must be onsite at ALL times while fire alarm work is being performed. A person in the office can be labeled a supervisor and not be onsite. Please verify the intent of this requirements.
| b. Line "1" does not specifically mention the onsite individuals must be certified/licensed. Only the contractor. Is this correct that only the company must be certified/licensed? | NPS RM 58 Requires Fire Alarm Designer be a Fire Protection Engineer or NICET III. And the installer be a State or municipal certified/licensed fire alarm contractor or Qualified by the manufacture or NICET II. The installer can have other people who do not posses this qualification help under the qualified persons supervision. The term used in 1.7 A "under the supervision of persons..." clearly indicates on site supervision is required. | |||
| 5 | We have seen this as an issue on our previous NPS projects. Most contractors are NICET certified for design but they do not have it for any of their field individuals. It is not required for work in KY. I want to make sure all the contractors have the same understanding of this requirement. | Noted: no further question was asked. | ||
| 6 | Would NPS, DSC Contracting Services Division consider extending past performance relevancy to 8 years? | No. Recency remains unchanged from "within the past six (6) years." | ||
| 7 | With regard to the past performance forms, it looks like we will need to send Attachment 4 for our references to complete. Do we need to send them to our references if a completed CPARS is in the system? | Factor 5 - Past Performance, Attachment 5 - Past Performance Questionnaire shall be sent to and completed by the Reference Customers' points-of-contact, regardless of a CPARS record existing or not. |
*Note, Attachment 4 - Project Experience Questionnaire corresponds to Factor 1 - Project Experience and shall be completed by the Offeror and submitted with this section of Volume I - Technical & Past Performance Proposal.
C
Amendment 0003
Posted
| 7/16/2021 | 8 | Based on how we read the earthwork specification, this site is considered unclassified on the excavation. Based on this do you have a subsurface investigation for this project ? We have to know about the rock excavation ECT. | No, there was no geotechnical sampling or testing conducted by the NPS for this project, therefore no geotechnical/subsurface report was not prepared for the project. | |
| 9 | Note #6 on sheet S1.6. It states that the trusses, purling, braces, etc. shall have preservative treatment. No details are provided that describe the treatment. | The preservative requirement will be eliminated and members will receive primer and sealer as per specification section 099300. Specification section 061800 will be revised to eliminate preservative treatment. | ||
| 10 | The specifications are calling for Douglas Fir Glue-Lam. Our subcontractor manufactures in Southern Yellow Pine. Douglas Fur cannot be treated correctly. | Southern Yellow Pine will be acceptable meeting 24F-1.8E minimum with balanced layup. Specification section 061800 will be revised to indicate SYP. | ||
| 11 | About the fireplace and the ability for it to throw some heat back into the room. |
Almost every custom fireplace we design for a commercial space will come with the Dual Pane Glass Cooling package, (especially a fireplace that will be in a National Park). The Dual Pane Glass Cooling will bring down the temp of the outer pane of glass and make it safe for the guests and children who may touch the glass.
So, when we do the Dual Pane Glass Cooling, we use a power vent fan up on top of the flue to vacuum out the heat from between the dual panes of glass, this excess heat gets dumped outside (through the flue) with the exhaust gasses. So there is no heat left to blow back into the room.
The Dual Pane Glass serves two purposes, first to cool the glass and second, to not overheat the room. With the Dual Pane Glass, you can run the fireplace all year around and not worry about overheating the room.
| Let me know if you have any other information on the main Indoor Outdoor fireplace and the second fireplace you mentioned... I can only find one. | This project has only one fireplace, located in the Southeast corner of Lobby 101. It is detailed on sheet A6.7. | |||
| 12 | We would have to do SYP Treated with MCA, CA-C or ACQ we do not treat Doug Fir and do not use oil base. Would you be willing to do a substitution? Or is the Doug Fir required? | The preservative requirement will be eliminated and members will receive primer and sealer as per specification section 099300. Specification section 061800 will be revised to eliminate preservative treatment. | ||
| D |
Amendment
Posted
| 7/21/2021 | 13 | Could the bid date be consider to be extended due to the current economic situation and delays being experienced obtaining subcontractor and material pricing? | A seven (7) calendar day extension is being granted, per Amendment 0004. Proposal Submissions are due no later than 12:00 pm Mountain Daylight Time (MDT) on August 3rd, 2021. | |
| 14 | Per sheet AC.2 Roof Types can 5/8” OSB be used in lieu of Plywood? | For Roof Types 2.01, 2.02, and 2.03, OSB is acceptable. | ||
| 15 | Per sheet AC.2 Roof Type 2.01, would ¾” T&G Wood Finish Ceiling be considered in lieu of 1 1/2“? | This is structural wood decking, 1-1/2" T&G is required. | ||
| 16 | Per Sheet S1.5 and S6.1 New Drilled Pier type DP24, would alternate pier types be consider for use on interior section of building due to the limitations on machinery and clearances needed for installation? | The existing building in this area will be demolished so clearances should be available for placement of the drilled piers indicated. | ||
| 17 | Per Spec 05 12 00-2 paragraph 1.4 Requires AISC certification for Fabricators, Installers, and Shop-Painting. Could RFP requirements be changed to allow for shops and erectors to perform the fabrication and erection in accordance with AISC standards and tested/inspected by Certified AWS and ASNT inspectors? | Specification paragraph 1.4 indicates that as an alternative, Code required special inspections is acceptable. | ||
| 18 | Per spec 061063-2 2.5 A the C2 requirement is an outdated requirement would the newer requirements using UC3B or UC4A be acceptable? | Yes, UC4A for Ground Contact/General Use. | ||
| 19 | 02 41 00 3.5 States Roofing: Remove no more existing roofing than what can be covered in one day by new roofing and so that building interior remains watertight and weathertight. Could this be modified to state any roof demo will need to remain watertight and weathertight at all times? | Comply with the requirements of the contract documents. | ||
| 20 | Limits of construction on sheet C2 does not allow enough room for equipment needed for demo, particularly behind the building. | Limits of construction needs to be approved by Park and Contracting Officer. | ||
| 21 | Spoils from excavations are to be stockpiled, will this be within the limits shown? | Excavated satisfactory soils are allowed to be stockpiled on site within limits of work at location approved by CO. Spoils and waste materials, including unsatisfactory soil, trash, and debris, are to be removed and legally disposed of them off Government's property. | ||
| 22 | Will additional space in the parking lot be available to be closed of for use of a crane during roof construction? | Limits of construction needs to be approved by Park and Contracting Officer. | ||
| 23 | Will a Geo report be provided in an amendment? If one is not available, what were the foundation designs based on? The drilling contractors that have been contacted are requesting in order to provide firm fixed pricing. | See general note 4 on sheet S0.2. Foundation designs were based on information from existing building drawings. The design depths and assumed bearing pressures will need to be verified by a geotechnical engineer. | ||
| 24 | Given this is a Firm Fixed Price contract and RFP states price shall be guaranteed for 90 days, will there be a FAR clause to cover unusual price increases due to pandemic issues? And will additional contract time be given in the event of material delays due to the pandemic? | There are no specific FAR clauses/provisions that cover unusual price increases/additional contract time for material delays, due to the COVID-19 Pandemic; therefore, any unusual price increases or additional contract time for material delays shall be addressed on a case-by-case basis, after Contract Award, during the Material Submittal Process. | ||
| 25 | Will additional proposal consideration be given for SBA underutilized business concerns such as HubZone? | This is a Total Small Business Set-Aside procurement; therefore, no additional FAR clauses/provisions giving proposal consideration for SBA underutilized business/HUBzone concerns apply to this acquisition. | ||
| 26 | If the bid date is extended will that also extend the deadline for additional questions? | No. The deadline for additional questions is not being extended. | ||
| 27 | For several of our relevant past performance projects, staff has retired or left the agency in which we would need to send the Past Performance form. No one currently at those agencies has any additional knowledge beyond what is already stated in the past PPQs and CPARs evaluations. Whom should we send these data sheets if required when no personnel familiar are with the agency? Are we able to submit past performance evaluations for these projects? | In this case, please provide a copy of the CPARS Evaluation in lieu of Attachment 5 - Past Performance Questionnaire, for Factor 5 - Past Performance. | ||
| 28 | Question on the fire alarm: The current control panel is a Potter PFC-6200. This control panel is discontinued and other than smoke sensors, there are no parts available for this line of panel any longer. |
Solution #1: We can install a new potter control panel that has parts that are supported and add a legacy card to communicate with the existing devices. These legacy devices will operate on their own “legacy loop” then Install new devices onto a new card on a separate new device loop. This would keep the old devices and new running concurrently.
This is the most cost effective solution, however if you need to replace any devices on the “legacy” side, there will need to be lots of wire running to the new loop because the legacy loop will only communicate to discontinued legacy parts.
| Solution #2: Install new potter system, and perform device swap to upgrade smoke detectors, pull stations and monitor modules to new device type, then swap panel. This would leave the notification appliances, and wiring alone. It would provide a like new system, with devices that would be completely covered under warranty. | If the control panel is discontinued and no parts are available, then one of the two proposed solutions would be necessary. | |||
| 29 | We are having trouble getting any response from Gault Stone and Brick company, called several times, left messages with no return calls?? Same is true for KY Kolor Building Stone? Are there other manufacturers we can call?? Can't quote their products if they will not respond. | Three stone quarriers are listed in the specification 04 43 13. Equal materials approved by the Contracting Officer are acceptable as specified. | ||
| E | ||||
| Pending Response/Amendment | 30 | Could the NPS please provide core cut descriptions of the various roof applications to be demo’d? We are specifically interested in the depth of what will be removed, what it is comprised of and the deck that it is on. | PENDING RESPONSE. | |
| 31 | Will there be another opportunity (or can one be scheduled) to view the site in person? | PENDING RESPONSE. |