This document contains questions and answers from a site visit for solicitation number 140P1523R0004 to replace the foundation and roof of the Grand Canyon National Park Community Library. The National Park Service requires fluid applied waterproofing for the new below-grade CMU walls, both interior and exterior. Control joints should be installed in the CMU at 25 feet or 1.5 times the wall height. Utilities less than 6 inches can be core drilled through the stem wall. The contractor must provide engineered designs for temporary shoring and lifting the building, sealed by an Arizona-licensed engineer. Work hours may be extended after regular hours for applying the fluid waterproofing with approval.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Sol_140P1523R0004_Amd_0002.pdf | ||
| B09-_P1523R0004_Amendment___1_Questions_and_Answers_0001.pdf | ||
| Sol_140P1523R0004_Amd_0001.pdf | ||
| Sol_140P1523R0004.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Solicitation # 140P1523R0004 Amendment# 2 Questions and Answers from Site Visit held on June 5th, 2023
General
1. Question: Please confirm CIM 1000 TG or Sika 7600 VG is an acceptable fluid applied waterproofing membrane for the CMU exterior walls.
Answer: Product submittals will be reviewed after award. Products conforming to the requirements of specification section 071416 will be approved
2. Question: Please confirm ONLY the exterior part of the CMU wall is being coated with new fluid applied waterproofing.
Answer: Thank you for this question. Please see “Revised S1 – Bid Question 18.pdf” for updated detail showing waterproofing on the interior face also
3. Question: How many cracks in the CMU wall should we assume? Typically an amount of 100 linear feet is where we start for a project of this size.
Answer: The CMU wall receiving cold fluid-applied waterproofing is new and shall not have cracks. Any cracks should be repaired at the contractors expense prior to applying waterproofing.
4. Question: Please advise what the current waterproofing membrane is on the exterior below grade CMU wall? Has it been tested for hazardous materials? If it is hazardous, please confirm the Park will hire another party to abate the hazardous materials.
Answer: In the interest of minimizing any potential delays, please cost this project assuming no hazardous materials are present in the waterproofing membrane. Proposals may include a include a subcontracted hazardous materials survey at the discretion of each prospective contractor. If such a survey reveals the presence of asbestos or other hazardous materials in the existing waterproofing membrane, a contract modification will facilitate this work.
5. Question: Fluid applied waterproofing will need to be installed during declining temperatures which could mean a work shift as late as 4pm to 12:30am. Please confirm if coordinated ahead of time, work can be done at any hour?
Answer: There are limitations on noise and lighting in the park after regular hours, and this project is close to a residential area of the park. However, NPS does not anticipate a need
United States Department of the Interior
NATIONAL PARK SERVICE
INTERMOUNTAIN REGION
Arizona Major Acquisition Buying Office
1824 South Thompson Street, Suite 200
Flagstaff AZ 86001 for noisy equipment or bright lighting for the fluid applied waterproofing portion of the work. Any related, noisy preparation work must take place during regular hours as noted in the Summary of Work. Work on the fluid applied waterproofing after hours will require Contracting Officer’s approval to proceed. Please see 011100 Summary of Work (1.8 Work Restrictions) and 015719.12 Noise & Acoustics Management for further guidance.
6. Question: Please confirm that the park understands that any substrate repairs or upgrades after the existing waterproofing at the below grade CMU wall is removed (including but not limited to: CMU block repairs, Spall Repairs, Void filling, Heavy pitting, etc...) will result in additional charges to repair prior to installing the new waterproofing. It is not possible to verify the existing condition of the CMU wall until the existing waterproofing is removed.
Answer: Waterproofing is to be applied to new CMU wall, not existing.
7. Question: It is common to have a 3rd party fill and water test the below grade areas prior to backfilling. Please confirm the park will hire a 3rd party to conduct the water testing of the newly installed membrane prior to backfilling.
Answer: 3rd party testing of waterproofing is not required for this project. If the contractor wishes to have 3rd party testing, the contractor shall engage with the testing agency.
8. Question: What is the check in process to the work site? Security check in each day? Special badging requirements for every employee?
Answer: Contractor and subcontractor employees may have to self-identify at the park entrance station if not using the designated bypass lane and may need to self-identify once inside the park or at the work site if asked by park staff. There is no additional security check in requirement, and there is no badging requirement. However, contractor staff with contractual authority should be available onsite, by email, or by telephone for verification purposes while work is taking place or while contractor or subcontractor employees are present.
*NO SOLICITATION CLAUSES WILL BE CHANGED WITH THIS AMENDMENT*.
DESIGN CRITERIA
1) BUILDING CODES: 2021 INTERNATIONAL BUILDING CODE
2) RISK CATEGORY II (STANDARD)
3) DESIGN LOADS:
a) ROOF DEAD LOAD: 15 PSF
b) ROOF SNOW LOAD: 42 PSF
c) GROUND SNOW LOAD, Pg = 60 PSF c)a) EXPOSURE FACTOR, Ce = 1.0 (PARTIALLY EXPOSED) c)b) THERMAL FACTOR, Ct = 1.0 (NOT OTHERWISE DEFINED) c)c) IMPORTANCE FACTOR, Is = 1.0
d) FLOOR DEAD LOAD: 15 PSF
e) FLOOR LIVE LOAD:
e)a) LIBRARY STACK ROOM 150 PSF (NON-REDUCIBLE)
f) WALL DEAD LOAD:
f)a) WOOD EXTERIOR WALL240 PLF f)b) CMU WALL 400 PLF
g) WIND SPEED, Vult = 115 MPH, EXPOSURE B
h) AS THE LATERAL SYSTEM OF THE BUILDING IS NOT IMPACTED DUE TO THE PROPOSED
MODIFICATIONS, A LATERAL LOAD ANALYSIS WAS NOT COMPLETED FOR THIS BUILDING.
FOUNDATION DESIGN
1) FOUNDATION DESIGN WAS PERFORMED WITHOUT A SITE SPECIFIC GEOTECHNICAL ENGINEERING
REPORT. BASED UPON OTHER GEOTECHNICAL ENGINEERING REPORTS IN THE SURROUNDING
AREA, IT IS ASSUMED THAT THE FOUNDATIONS WILL BEAR ON LIMESTONE BEDROCK.
CONTRACTOR SHALL REVIEW THE BEARING STRATUM WITH CONTRACTING OFFICER,
CONTRACTING OFFICERS REPRESENTATIVE, AND REGIONAL PROJECT MANAGER AFTER
EXCAVATION AND PRIOR TO FOUNDATION CONSTRUCTION.
2) FOUNDATION DESIGN IS BASED ON A MAXIMUM ALLOWABLE BEARING PRESSURE OF 4,000 PSF.
3) FROST DEPTH SHALL BE 30"
LIBRARY STACK LAYOUT
1) IN ACCORDANCE WITH THE 2021 INTERNATIONAL BUILDING CODE, DOUBLE-FACED LIBRARY BOOK
STACKS ARE SUBJECT TO THE FOLLOWING LIMITATIONS:
iw) THE NOMINAL BOOK STACK HEIGHT SHALL NOT EXCEED 7'-6”.
ix) THE NOMINAL SHELF DEPTH SHALL NOT EXCEED 12” FOR EACH FACE.
iy)PARALLEL ROWS OF DOUBLE-FACED BOOK STACKS SHALL BE SEPARATED BY AISLES NOT LESS
THAN 36” IN WIDTH
CONCRETE
1) REFER TO DIVISION 03 SPECIFICATIONS FOR PROJECT REQUIREMENTS FOR CONCRETE
CONSTRUCTION
MASONRY
1) REFER TO DIVISION 04 SPECIFICATIONS FOR PROJECT REQUIREMENTS FOR MASONRY
CONSTRUCTION
2) PROVIDE CONTROL JOINTS AT 25 FEET OR 1.5 TIMES THE HEIGHT OF THE WALL, WHICHEVER IS LESS. LOCATE JOINTS AT AREAS PRONE TO CRACKING, SUCH AS CHANGES IN WALL HEIGHT AND
ADJACENT TO OPENINGS. PROVIDE CONTROL JOINT LAYOUT FOR REVIEW AND APPROVAL. DO
NOT CONTINUE HORIZONTAL REINFORCING THROUGH THE CONTROL JOINT.
3) UTILITIES LESS THAN 6" DIAMETER THROUGH STEMWALL CAN BE CORE DRILLED. DO NOT CORE
DRILL THROUGH REINFORCED CELLS.
WOOD
1) REFER TO DIVISION 06 SPECIFICATIONS FOR PROJECT REQUIREMENTS FOR WOOD CONSTRUCTION.
2) CUT ENDS OF ALL PRESSURE TREATED FRAMING SHALL BE TREATED WITH PRESERVATIVE ON SITE.
MISCELLANEOUS
1) REFER TO DIVISION 01 SPECIFICATIONS FOR GENERAL PROJECT REQUIREMENTS.
2) REFER TO SPECIFICATIONS FOR SPECIAL INSPECTIONS.
3) CONTRACTOR TO PROVIDE ENGINEERED DESIGN FOR TEMPORARY SHORING. DESIGN SHALL BE SEALED BY AN ENGINEER LICENSED IN THE STATE OF ARIZONA AND SUBMITTED FOR REVIEW AND
APPROVAL.
BUILDING LIFTING
1) BUILDING LIFTING SHALL BE EXECUTED BY A QUALIFIED CONTRACTOR WITH AT LEAST 5 YEARS
EXPERIENCE WITH SIMILAR PROJECTS. SUBMIT QUALIFICATIONS FOR REVIEW AND APPROVAL.
2) CONTRACTOR TO PROVIDE ENGINEERED DESIGN FOR LIFTING STRUCTURE. DESIGN SHALL BE SEALED BY AN ENGINEER LICENSED IN THE STATE OF ARIZONA AND SUBMITTED FOR REVIEW AND
APPROVAL.
3) BUILDING TO BE LIFTED AND HELD IN PLACE DURING SELECTIVE DEMOLITION AND CONSTRUCTION
OF NEW FOUNDATIONS. FOUNDATIONS ARE SHOWN SQUARE BUT SHALL BE ADJUSTED TO
ACCOUNT FOR BUILDING IRREGULARITIES.
4) WHEN BUILDING IS LIFTED, EXPOSE ALL FLOOR FRAMING TO REMAIN AND REVIEW EXISTING
FRAMING WITH CONTRACTING OFFICER.
5) CONTRACTOR SHALL REPAIR ANY CRACKS IN FINISHES THAT OCCUR DURING BUILDING LIFTING.
APPLICABLE CODES & STANDARDS:
2021 INTERNATIONAL BUILDING CODE
2021 INTERNATIONAL EXISTING BUILDING CODE
2021 INTERNATIONAL ENERGY CONSERVATION CODE
SECRETARY OF THE INTERIOR'S STANDARDS AND GUIDELINES
FOR THE TREATMENT OF HISTORIC PROPERTIES
WORK CLASSIFICATION:
IEBC 202, HISTORIC BUILDING
IEBC 604, LEVEL III ALTERATION (GREATER THAN 50% OF
BUILDING AREA)
IEBC 801.4, NEW CONSTRUCTION ELEMENTS COMPONENTS,
SYSTEMS AND SPACE SHALL COMPLY WITH THE
REQUIREMENTS OF THE INTERNATIONAL BUILDING CODE.
OCCUPANCY CLASSIFICATION:
IBC 303.4, OCCUPANCY: ASSEMBLY GROUP A-3 (LIBRARIES. NO
CHANGE IN OCCUPANCY
GENERAL BUILDING HEIGHTS AND AREAS:
EXISTING HEIGHT: 24'-1" EXISTING AREA: 2,853 SF GROSS
PROPOSED HEIGHT: 24'-4" EXISTING AREA: 2,853 SF GROSS
(NO CHANGE TO AREA)
IBC 504.3 ALLOWABLE BUILDING HEIGHT IN FEET ABOVE GRADE
PLANE: 40'
CONSTRUCTION TYPE:
IBC 602.5, Type V-B (UNSPRINKLERED)
IBC 601 AND 705.5, REQUIRED FIRE RESISTANCE RATINGS
PRIMARY STRUCTURAL FRAME 0 HR
EXTERIOR BEARING WALLS 0 HR
INTERIOR BEARING WALLS 0 HR
EXTERIOR NON-BEARING WALLS 0 HR
INTERIOR NON-BEARING WALLS 0 HR
FLOOR CONSTRUCTION 0 HR
ROOF CONSTRUCTION 0 HR
MEANS OF EGRESS:
IBC 1004.5, OCCUPANT LOADS
ASSEMBLY (UNCONCENTRATED) 21
LIBRARY STACKS 7
LIBRARY READING ROOM 30
STORAGE 1
TOTAL BUILDING OCCUPANTS: 59
IBS 1005, MEANS OF EGRESS SIZING: 59 OCCUPANTS x .2 = LESS
THAN MINIMUM COMPONENT WIDTH
IBC 1006.2.1, TWO EXITS FROM ANY SPACE SHALL BE PROVIDED
WHERE THE DESIGN OCCUPANT LOAD EXCEEDS 49 OCCUPANTS.
3 EXITS PROVIDED. MAXIMUM COMMON PATH OF TRAVEL: 75'
IBC 1007.1.1, EXIT SEPARATION WHERE TWO EXITS ARE
REQUIRED, THEY SHALL BE PLACED A DISTANCE APART NOT
LESS THAN HALF OF THE LENGTH OF THE MAXIMUM OVERALL
DIAGONAL DIMENSION OF THE BUILDING OR AREA TO BE
SERVED.
ENERGY CONSERVATION:
IEBC C907.1, LEVEL 3 ALTERATIONS ARE PERMITTED WITHOUT
REQUIRING THE ENTIRE BUILDING OR STRUCTURE TO COMPLY
WITH THE ENERGY REQUIREMENTS OF THE IECC.
IECC C402.1.3, OPAQUE THERMAL ENVELOPE MINIMUM
REQUIREMENTS: FLOORS R-30 (NOTE: FOUNDATION WALLS ARE
OUTSIDE THERMAL ENVELOPE)
VENTILATION:
IBC 1201.4.1.2, NET AREA OF VENTILATION OPENINGS FOR
CRAWL SPACES WITH GROUND COVERED WITH CLASS I VAPOR
RETARDER SHALL NOT BE LESS THAN 1 SF PER 1500 SF OF
CRAWL SPACE: 2694
1500 SF = 1.796 SF VENTILATION REQUIRED (1.94
PROVIDED)
IBC 1202.4.3.1 CONTINUOUSLY OPERATED MECHANICAL
VENTILATION SHALL BE PROVIDED AT A RATE OF 1CF PER
MINUTE (CFM) FOR EACH 50 SF OF CRAWL SPACE
CRAWL SPACE: 2694
50 = 54 CFM (110 PROVIDED)
AutoCAD SHX Text
EXISTING JOISTS
AutoCAD SHX Text
EXISTING WALL STRUCTURE
AutoCAD SHX Text
EXISTING FLOOR
AutoCAD SHX Text
FINISHED GRADE
AutoCAD SHX Text EXISTING 2x4 TRIM
AutoCAD SHX Text
8" MASONRY WALL
AutoCAD SHX Text CLOSED CELL POLYETHYLENE SILL SEALER GASKET WITH SELF-ADHESIVE WATERPROOFING MEMBRANE, FULL WIDTH OF CMU
AutoCAD SHX Text
6" PERFORATEDFOUNDATION DRAIN, WRAP IN GEO-TEXTILE FABRIC
AutoCAD SHX Text
DRAIN ROCK
AutoCAD SHX Text
GEO-TEXTILE LINER
AutoCAD SHX Text PRESSURE TREATED 1x3 BATTENS AT 8"o.c. FASTENED TO CMU WALL WITH "x2- " MASONRY 14"x2- " MASONRY 14" MASONRY SCREWS AT 8"o.c.
AutoCAD SHX Text
FLUID APPLIED WATERPROOFING OVER ALL EXTERIOR CMU SURFACES
AutoCAD SHX Text
STAINLESS STEEL FLASHING PAINTED BLACK
AutoCAD SHX Text PRESSURE TREATED SPLIT LOG SLABS PLACED VERTICALLY. DIMENSIONS AND SPECIES TO MATCH EXISTING. PRIME AND PAINT TO MATCH EXISTING
AutoCAD SHX Text
DRAIN BOARD
AutoCAD SHX Text
EXISTING LOG
AutoCAD SHX Text
SEALANT
AutoCAD SHX Text
CONCRETE FOOTING
AutoCAD SHX Text
POLYETHYLENE VAPOR BARRIER TAPED AT ALL EDGES AND COLUMN PENETRATIONS
AutoCAD SHX Text
R30 BATT INSULATION
AutoCAD SHX Text
STAFF ROOM
AutoCAD SHX Text
READING ROOM
AutoCAD SHX Text
BOOK STACKS
AutoCAD SHX Text
READING ROOM
AutoCAD SHX Text
CHILDREN'S READING ROOM
AutoCAD SHX Text
CONFERENCE ROOM
AutoCAD SHX Text
STOR.
AutoCAD SHX Text
OCCUPANCY: READING ROOM LOAD FACTOR: 50 NET AREA: 81 SF OCCUPANT LOAD: 2
AutoCAD SHX Text OCCUPANCY: UNCONCENTRATED ASSEMBLY LOAD FACTOR: 15 NET AREA: 66 SF OCCUPANT LOAD: 5
AutoCAD SHX Text
OCCUPANCY: STACK AREA LOAD FACTOR: 100 GROSS AREA: 694 SF OCCUPANT LOAD: 7
AutoCAD SHX Text
OCCUPANCY: READING ROOM LOAD FACTOR: 50 NET AREA: 905 SF OCCUPANT LOAD: 19
AutoCAD SHX Text
OCCUPANCY: READING ROOM LOAD FACTOR: 50 NET AREA: 421 SF OCCUPANT LOAD: 9
AutoCAD SHX Text OCCUPANCY: UNCONCENTRATED ASSEMBLY LOAD FACTOR: 15 NET AREA: 237 SF OCCUPANT LOAD: 16
AutoCAD SHX Text
OCCUPANCY: STORAGE LOAD FACTOR: 300 GROSS AREA: 69 SF OCCUPANT LOAD: 1
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
DESIGNED:
AutoCAD SHX Text
TECH. REVIEW:
AutoCAD SHX Text
SUB SHEET NO.
AutoCAD SHX Text
PMIS/PKG NO.
AutoCAD SHX Text
DRAWING NO.
AutoCAD SHX Text
SHEET
AutoCAD SHX Text
OF
AutoCAD SHX Text
TITLE OF SHEET
AutoCAD SHX Text
GENERAL NOTES
AutoCAD SHX Text
AutoCAD SHX Text 180332
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
B. WARREN
AutoCAD SHX Text
V. FRIEDMAN
AutoCAD SHX Text
J. ROZINA/K. FOX
AutoCAD SHX Text 01/10/2023
AutoCAD SHX Text
GRAND CANYON NATIONAL PARK
AutoCAD SHX Text 182633
AutoCAD SHX Text S1
AutoCAD SHX Text
FOUNDATION SECTION WATERPROOFING AND INSULATION
AutoCAD SHX Text A
AutoCAD SHX Text S1
AutoCAD SHX Text
SCALE
AutoCAD SHX Text A
AutoCAD SHX Text
SCALE
AutoCAD SHX Text A
AutoCAD SHX Text
AutoCAD SHX Text
SCALE OF FEET
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 3/4" = 1'-0"
AutoCAD SHX Text
BUILDING CODE ANALYSIS
AutoCAD SHX Text
CODE PLAN
AutoCAD SHX Text B
AutoCAD SHX Text S1
AutoCAD SHX Text
SCALE: 1"=10'-0"
kafox Line kafox Callout
FLUID APPLIED CAPILLARY BREAK BETWEEN FOOTING AND FOUNDATION WALL
kafox Line kafox Callout
FLUID APPLIED WATERPROOFING OVER BELOW GRADE INTERIOR CMU SURFACES
| B09- P1523R0004 Amendment # 2 Questions and Answers |
| Revised S1 - Bid Question 18 |
| Sheets and Views |
| S1 |