GRAND CANYON NATIONAL PARK
GRAND CANYON, ARIZONA
Desert View Tank Rehabilitation
PMIS 230561
Amendment 002
NATIONAL PARK SERVICE
INTERMOUNTAIN REGION
May 5, 2021
1) Other Attachments – Posted via Amendment 001 are the Pre-Bid Sign-in Sheet, GRCA
Pruning Guidelines, and project Submittal Register.
2) Attachments included in this amendment –
i. 2021 Desert View Tank Report w/ Pictures
ii. Texas-Aquastore Exterior Platform Kit
3) Contractor Representative – Contractor may elect to have one representative onsite to cover multiple roles (safety, superintendent, quality control, environmental manager/coordinator).
4) Tank Information
a. Tank Manufacturer Contact Information:
i. Wick Baker, 602-620-2206, wick@bordermarketing.com
ii. John Pappalardo, 817-832-9794, jp@texas-aquastore.com
iii. Chad Callahan (technical), 903-870-5000 / 903-624-2805, chad@texas-aquastore.com
b. Tank was installed in 2000s. There is no lead-based paint.
c. Tank is typically one-half to three-quarters full.
d. Tank is required to remain in service during the work.
e. There are two existing sacrificial anodes inside the tank, believed to be magnesium. Refer to page 104 of the specifications, line 62 of the “Tank Parts
List” (bill of materials).
f. Tank access is through the top of the tank via the roof hatch.
5) Construction Water
a. Non-potable water is available at Grand Canyon Village.
b. Potable water is available at the Desert View location.
6) Vegetation Removal – Some tree pruning may be necessary when relocating the ladder.
Reference photo on Drawing C3. Follow the attached GRCA Pruning Guidelines. Tree removal is not permitted.
7) Sediment Removal –
a. When vacuuming the sediment out of the tank: properly store, remove, and dispose offsite at an approved landfill location. Contractor is not permitted to dispose sediment at the Park.
b. Estimated sediment depth less than one (1) inch. Refer to inspection report.
Volume can be determined using a tank diameter of forty (40) feet.
c. It is unknown if sediment removal has been done prior to this scope.
8) Exterior Seams Re-Sealing
a. Sealant Product Manus Sealer No. 98 may be discontinued; the newer product is
Manus 75 A-M. An equal single component urethane sealer product may be submitted for approval, or as recommended by the Manufacturer.
mailto:wick@bordermarketing.com mailto:jp@texas-aquastore.com mailto:chad@texas-aquastore.com mailto:chad@texas-aquastore.com
b. For estimated seam lengths, dimensions shown on drawing C2 are taken from the original shop drawings (see specification PDF pages 87-140). Roof panel seams can be estimated from the original shop drawings, p 112, 116, and 135 show the roof panel layout
9) Specifications Not Applicable to This Project
a. Specification 01 50 00 3.2.A.2 – Temporary water system.
b. Specification 01 50 00 3.2.B – Effluent Removal.
c. Specification 33 13 02 1.1.A – Installing a new interior ladder and re-sealing interior tank seams.
d. Page 141 of Specification Package, “Glass-Fused-to-Steel Bolted Water Tank, Tank Maintenance Repair”
i. This is a specification from the manufacturer is intended to show materials used for repair and maintenance. DISREGARD 1.1 “Scope of Work” on this document. However, Contractor is responsible for replacing bolt caps
(nuts) as necessary because of improvements shown on the drawings, such as ladder relocation, platform fastening, railing attachments, etc.
10) Fastening Accessories to the Tank
a. Texas-Aquastore has a standard manway platform kit that can be used in conjunction with the drawing in this project (reference attachment). It is recommended that personnel do not step on or over the roof access hatch. GRCA would be amenable to this smaller platform footprint as long as the intent of the project is met, and OSHA guidelines are followed.
b. Manufacturer recommends replacing existing tank bolts with correct length bolts on the brackets that attached to the tank wall and with the appropriate seals for mounting ladders, platform, and railings. Drilling new holes on panels is not permitted.
11) Permits – ADEQ permitting is not required for the scope of this project.
Grand Canyon National Park
Water Storage Facility 2021 ROV Inspection February 2021
US UNDERWATER
123 Sentry Drive • Mansfield, TX 76063 800.860.2178 www.usunderwaterservices.com http://www.usunderwaterservices.com/
CONSOR Engineers, LLC dba U.S. Underwater | 123 Sentry Drive, Mansfield, TX 76063 P: 817-447-7321, F: 817-447-0021, Toll: 800-860-2178
Statement of Certification
Grand Canyon National Park
Location: Grand Canyon Village, AZ
February 2021
This form certifies the inspections were completed on the above date for the facilities listed below:
[1] 153,000 Gallon Ground
U.S. Underwater certifies the work was completed in accordance with the American Water Works Association’s [AWWA] current standards [ANSI/AWWA c652-92] regarding disinfection procedures when conducting underwater activities in potable water storage facilities. All equipment used is designated for potable water use only.
Rachel Potter Director of Sales & Marketing CONSOR Engineers LLC, dba U.S. Underwater
Report Proposal March 10, 2021
Grand Canyon National Park P.O. Box 2168 Brenna White Mansfield, TX 76063 S Entrance Rd 1 800-860-2178 Grand Canyon Village, AZ 86023 P 817-447-7321 928-638-7906 F 817-447-0021 brenna_white@nps.gov aspinks@consoreng.com
U.S. Underwater Representative
Project
Ashleigh Spinks
The below recommendations are based on the results of the inspection and to comply with OSHA and/or AWWA standards. Please contact your U.S. Underwater Account Manager for a customized proposal.
Inspection Capacity Type Name Measurements
#1 153,000 Ground Desert View H: 15.5’ D: 42’
Label manway access hatch as a ‘confined space entry’ area Label water access hatch as a ‘confined space entry’ area Remove the 1/16”-1/4”, 100% coverage, of sandy silt sediment and metal tubing from the floor plates
Rust
Grades A
Description
Graphical Representation
No rusting or less than 0.01% of surface rusted
Unnecessary
Minute rusting less than 0.03% of
8B
Few isolated rust spots less than
0.1% of surface rusted
Less than 0.3% of surface rusted
6C
Extensive rust spots but less than
Rusting to the extent of 3% of
4D
Rusting to the extent of 10% of
3E
Approximately on sixth of the surface rusted 16%
Approximately one third of the surface rusted 33%
Approximately one half of the surface rusted 50%
References
Standard Method of Evaluating Degree of Rusting on
Painted Steel Surfaces – SSPC-Vis 2-82 & ASTM D 610-85 The graphical representations show examples of area percentages, which may be helpful in rust grading. The use of photographical reference standards requires the following precautions:
Some finishes are stained by rust. This staining must not be confused with the actual rusting involved.
Accumulated dirt or other material may make accurate determination of the degree of rusting difficult.
Certain types of deposited dirt that contain iron or iron compounds may cause surface discoloration that should not be mistaken for corrosion.
It must be realized that failure may vary over a given area and discretion must therefore be used in applying these reference standards.
In evaluating surfaces, consideration shall be given to the color of the finish coating, since failures will be more apparent on a finish that shows color contrast with rust, such as white, than on a similar color, such as iron oxide finish.
The photographic reference standards are not required for use of the rust-grade scale since the scale is based upon the percent of the area rusted and any method of assessing area rusted may be used to determine the rust grade.
1% of surface rusted
Ground Tank/Standpipe/Clearwell Inspection Grand Canyon National Park Inspection #1 / Desert View Complete
Failed items 3
Inspection Title Grand Canyon National Park Inspection #1
Client Specific Tank Name Desert View
Client Grand Canyon National Park
Job Number 206237.00
Prepared by Rov Two
Conducted on 9th Feb 2021 10:41 AM CST
Recommended Maintenance 3 failed
External Inspection
Was Manway Access Hatch Labeled 'Confined Space?' No
Recommend a 'confined space entry' placard be installed
External Inspection
Was Water Access Hatch Labeled 'Confined Space?' No
Recommend a 'confined space entry' placard be installed
Internal Inspection
Is Facility Free of Sediment/Debris? No
Recommend the 1/16"-1/4", 100% coverage, of sandy silt sediment and metal tubing be removed from the floor
External Inspection 2 failed
Reference Photo of Facility
Photo 1
Facility Type Ground
Facility Construction Metal- Bolted
Capacity 153K
Height 15.5’
Diameter 42’
Does Facility Extend Underground? No
Tank ID Plate? Yes
Tank ID Plate Photo
Photo 2
Tank Builder AquaStore
Year Built N/A
Lower Level
Condition of Intruder Protection Fence Good
Condition of Foundation Good
Photo of Foundation
Photo 3 Photo 4 Photo 5 Photo 6 Photo 7 Photo 8
Water Level Indicator Type(s) Manual/Visual
Electronic
SCADA
Condition of Water Level Indicator(s) Good
Photo of Water Level Indicator
Photo 9 Photo 10 Photo 11
Condition of Overflow Good
Does Overflow Extend to Ground/Accessible? Compliant
Does Overflow Flapper Seal? Compliant
Photo of Flapper
Photo 12 Photo 13 Photo 14
Overflow Diameter 8”
Condition of External Plumbing N/A
Condition of Sidewall Plates Good
Photo 15 Photo 16
Condition of Sidewall Protective Coating (SSPC Rating) 9
Condition of Side Manway Access Hatch Good
Photo of Side Manway Access Hatch
Photo 17
Size of Manway Access Hatch 30”
Was Manway Access Hatch Labeled 'Confined Space?' No
Recommend a 'confined space entry' placard be installed
Condition of External Ladder Good
Photo of External Ladder
Photo 18 Photo 19 Photo 20 Photo 21 Photo 22
Width of External Ladder 16”
Diameter of Rung 1 1/4”
Length of External Ladder 10’
Length of Standoff 9 1/2”
Condition of Intruder Protection Door Good
Photo of Intruder Protection Door
Photo 23
Condition of Fall Protection System Good
Photo of Fall Protection System
Photo 24
Upper Level U Photo of Roof Plates
Photo 25 Photo 26 Photo 27
Condition of Roof Plates Good
Condition of Roof Coating (SSPC Rating) 9
Condition of Anode Plates N/A
Photo of Water Access Hatch
Photo 28 Photo 29 Photo 30
Condition of Water Access Hatch Good
Size of Water Access Hatch 30”
Was Water Access Hatch Labeled 'Confined Space?' No
Recommend a 'confined space entry' placard be installed
Was Water Access Hatch Locked? Yes, Lock in Good Condition
Type of Roof Vent Mushroom Shape
Photo of Roof Vent
Photo 31 Photo 32 Photo 33
Condition of Roof Vent Good
Vent Circumference 24” square
Condition of Vent Screen Compliant
Internal Inspection 2 failed
Condition of Water Access Ladder No Ladder
Recommend a water access ladder be installed
Condition of Roof Supports Good
Condition of Water Level Indicator System Good
Condition of Overflow Good
Condition of Roof Plates Good
Condition of Roof Plates (SSPC Rating) 10
Condition of Cathodic Protection N/A
Condition of Sidewall Plates Good
Condition of Sidewall Plates (SSPC Rating) 8
Condition of Side Manway Access Good
Condition of Internal Plumbing Good
Condition of Floor Plates N/A
Condition of Floor Plates (SSPC Rating) N/A
Does Tank Have Baffles? No
Is Facility Free of Sediment/Debris? No
Recommend the 1/16"-1/4", 100% coverage, of sandy silt sediment and metal tubing be removed from the floor
Photo 34 Photo 35 Photo 36
Sediment/Debris Type Sandy Silt
Other Debris
Description of Debris Piece of square tubing
Sediment Depth 1/16”-1/4”
Percentage of Sediment Coverage 100%
Level of Staining Inside Facility Light
Clarity of Water Good
Quality of Water Good
Water Temperature Cool
Water Depth (Maximum) 15.5’
Water Depth (Actual) 14’
Additional Notes The overall condition of the seams are in good condition and no repairs are recommended
Inspector
Josh Boatright 9th Feb 2021 8:21 PM CST
UT Readings for Sidewall Plates in Inches:
1) .125
2) .125 3) .125 4) .125 5) .125 6) .125 7) .125 8) .125
9) .125
10) .125 11) .125 12) .125 13) .125 14) .125 15) .125 16) .125
Northside
Southside
Appendix Appendix
Photo 1
Photo 3
Photo 2
Photo 4
Photo 5
Photo 7
Photo 6
Photo 8
Photo 9
Photo 11
Photo 10
Photo 12
Photo 13
Photo 15
Photo 14
Photo 16
Photo 17
Photo 19
Photo 18
Photo 20
Photo 21
Photo 23
Photo 22
Photo 24
Photo 25
Photo 27
Photo 26
Photo 28
Photo 29
Photo 31
Photo 30
Photo 32
Photo 33
Photo 35
Photo 34
Photo 36