Questions_and_Answers_Final_Final_0002.pdf
PDF 139 KB Posted
- Attached to
- WINNEMUCCA SECURITY CAMERA UPGRADE Federal contract opportunity
- Solicitation number
- 140L3921Q0098
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Sol_140L3921Q0098_Amd_0002.pdf | ||
| Figure_2__EmptyConduits_0001.pdf | ||
| Performance_Work_Statement_Updated_0001.pdf | ||
| Questions_and_Answers_Final_0001.pdf | ||
| Sol_140L3921Q0098_Amd_0001.pdf | ||
| DoL_WD_Humboldt_Co_NV.pdf | ||
| Figure_1_Map_Camera_Angles.pdf | ||
| Sol_140L3921Q0098.pdf | ||
| Performance_Work_Statement.docx | DOCX document |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Nevada Bureau of Land Management Solicitation: 140L3921Q0098_02 Questions and Answers Final Final
1. Are the lights on one photo‐volatic cell, the lights do not appear to be on an individual photovoltaic cell?
Lights appear to be on a single timer that is located inside of the shop building.
2. Is there consistent power at pole for cameras 1‐4? Is there consistent power at pole for cameras 2‐3?
Power is provided on a timer located in the shop building.
3. Where does the power to the photo‐volatic cell come from? Power comes from southeast end of site just to the west of the shop where power was recently trenched in when the gate was put onto power.
The assumption is it would take an electrician to switch the lights onto photovoltaic cells due to the high voltage.
4. Is there an empty conduit from the shop to the main building? There are two conduits which are in use from the southeast end of the site, see figure, one is for data and the other for electric. There should be enough room inside of these conduits to pull additional cable. The conduits are approximately 250 feet in length from the southeast end of the site to the shop.
5. Are we able to use any of the conduit paths from Main Building to the garage shop? There are two conduits, one for data and one for electric, from the southeast corner of the lot that should have room for additional power and data to be pulled. It is not known if conduit goes from the main building to the shop but if so then the contractor can use the conduits if they have sufficient capacity for the additional cables.
6. Can existing data conduit be used for any required new data lines? There are two conduits, one for data and one for electric, from the southeast corner of the lot that should have room for additional power and data to be pulled. It is not known if conduit goes from the main building to the shop but if so then the contractor can use the conduits if they have sufficient capacity for the additional cables.
7. Is conduit required at outdoor pole locations? This is currently not known.
8. Can we add an enclosure mounted near the existing access control panel in the shop? Yes, please submit in your technical approach part of the quote package and include any parts/materials in your total cost.
9. What is the minimum height for mounting security cameras? The cameras must be set high enough to provide full coverage of the areas indicated on the coverage figure but be high enough to not be obstructed when a large pickup truck parks near the cameras. It is estimated that the best mounting height will be approximately 15‐20 feet above ground level but will require the onsite PI’s approval. It is not anticipated that the cameras will need to be mounted on the top of the tall light poles.
10. Would you like the cameras and Point to Point radios to have surge suppression? Yes, please include this in you’re the technical approach portion of your quote.
11. Where have most of the break‐ins occurred? At the southeast end of the site and down the alleyway.
Nevada Bureau of Land Management Solicitation: 140L3921Q0098_02 Questions and Answers Final Final
12. Do you have good coverage of the east lot or was that an oversite? Yes, there is a good view of the east lot.
13. How should the cameras be mounted on the southwest corner of the building? Mounting on building should be in accordance with best practices and not require major modifications to the structure.
14. Did Avigilon help with the selection of cameras and angles needed? No, they were not used to help select cameras. All new equipment needs to be compatible with current recording and monitoring system to allow for full control and capabilities.
15. Did BLM use the tools provided by Avigilon to help select cameras? No, figure was developed by BLM
Staff using GIS.
16. Does the BLM want full coverage down the alleyway or are they more concerned with the east gate?
The BLM would prefer full coverage of the alleyway but some form of masking, whether physical or digital, would be needed to prevent the BLM from having to deal with legal consequences of having a view of private property.
17. Would you prefer masking or maybe a high‐powered lens which would show just the area provided down the alleyway? Masking, especially if it helps us stay away from custom lenses.
18. Does the BLM know if the shop and the building were constructed at the same time? The construction dates are unknown.
19. Is a solar battery without solar panels that is wired into the light poles an acceptable solution for power to the cameras, otherwise an electrician would be needed to install the timer and placing lights on a photovoltaic switch? The building is on a GSA lease so any electrical work will need to come through the
GSA. Vendors are encouraged to propose alternate technical solutions that are in line with industry standards and best practices and can achieve the stated requirements more efficiently. The BLM will evaluate the technical solutions for based on best value.
20. Do the existing cameras need moving or repositioning? The cameras need repositioning as opposed to relocating. We are trying to optimize area covered and most should only need minor (<300) adjustments to maximize overlap. We do not anticipate any needing to be moved.
21. Will 11 days of data storage meet the requirement? Vendor should optimize the data that is being provided by the cameras to the server. Additional storage will not need to be added within the scope of this contract. Vendor will be allowed to reduce resolution on cameras with PI’s approval to optimize the security coverage provided by the cameras.
22. Is more storage desirable? Right now, you are getting 11 days of recorded video. Vendors may include this cost as an option on your price quote, and not part of the total cost for meeting the Performance
Work Statement requirements.