This document is a specifications document for federal construction renovation work at NIFC 300-JWH Suite 222/227. It comprises two sections addressing access control system installation and hardware requirements, dated August 2026.
Section 281000 (Access Control) establishes the overall access control system requirements, including installation, field quality control, system startup, and maintenance protocols. The system must provide means of regulating and controlling physical entry through electrical, electronic, and mechanical components, including card readers, data gathering panels (DGPs), electronic locks, and related devices. Key regulatory requirements mandate compliance with NFPA 70, NFPA 72, NFPA 1, NFPA 730, NFPA 731, and ICC IBC standards, with components listed and labeled by UL (UL CCN ALOV and UL CCN ALVY, including UL 294). The contractor must coordinate installation with existing campus systems, integrate with door hardware (Division 08), lighting controls (Section 260923), and fire-alarm systems (Section 283100). Field devices must be mounted per ADA-ABA accessibility guidelines, with analog cables limited to 1000 feet and digital cables to 300 feet. The contractor must provide a two-year extended warranty with full labor, materials, and equipment coverage from Substantial Completion, and a three-year manufacturer warranty for lithium-ion batteries covering materials only. Manufacturer's published installation instructions and comprehensive testing procedures must be submitted as closeout documentation.
Section 281400 (Access Control System Hardware) specifies the head-end units, power supplies, battery chargers, and supplementary computer equipment. Access control system components must be obtained from a single manufacturer and include servers, data gathering panels, door controllers, and input/output interfaces with specified voltage (12-24 V dc), operating temperature ranges (32-158°F), and connectivity via CAT6A. Power supplies require 120 V ac input with 12-24 V dc output, network connection capabilities for remote supervision, enclosure locks with tamper switches, and built-in battery chargers. All hardware must comply with NFPA standards and UL listing criteria. The contractor must perform manufacturer-recommended tests and inspections witnessed by authorities having jurisdiction, complete startup checks, adjust printers and ribbon functions, and protect all components from construction damage. A three-year extended manufacturer warranty covering labor, materials, and equipment is required for hardware from Substantial Completion.
View the file
Other files
Show all 16
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Division Section Title Pages
SPECIFICATIONS GROUP
General Requirements Subgroup
DIVISION 01 - GENERAL REQUIREMENTS
011000 SUMMARY 3
012000 UNIT PRICES AND SCHEDULE OF VALUES 4
013200 CONSTRUCTION PROGRESS DOCUMENTATION 4
013300 SUBMITTAL PROCEDURES 7
014000 QUALITY REQUIREMENTS 8
015000 TEMPORARY FACILITIES AND CONTROLS 15
016000 PRODUCT REQUIREMENTS 5
017300 EXECUTION 8
017419 CONSTRUCTION WASTE MANAGEMENT AND DISPOSAL 9
017700 CLOSEOUT PROCEDURES 4
017839 PROJECT RECORD DOCUMENTS 2
019113 GENERAL COMMISSIONING REQUIREMENTS 16
Facility Construction Subgroup
DIVISION 02 - EXISTING CONDITIONS
024116 STRUCTURE DEMOLITION 5
DIVISION 06 - WOOD, PLASTICS, AND COMPOSITES
061000 ROUGH CARPENTRY 6
064116 PLASTIC-LAMINATE-CLAD ARCHITECTURAL CABINETS 6
DIVISION 08 - OPENINGS
081113 HOLLOW METAL DOORS AND FRAMES 8
081416 FLUSH WOOD DOORS 6
083113 ACCESS DOORS AND FRAMES 4
086200 UNIT SKYLIGHTS 6
087111 DOOR HARDWARE (DESCRIPTIVE SPECIFICATION) 13
088000 GLAZING 8
DIVISION 09 - FINISHES
092216 NON-STRUCTURAL METAL FRAMING 9
092900 GYPSUM BOARD 8
093013 CERAMIC TILING 10
095113 ACOUSTICAL PANEL CEILINGS 8
096513 RESILIENT BASE AND ACCESSORIES 5
096519 RESILIENT TILE FLOORING 6
096813 TILE CARPETING 7
099123 INTERIOR PAINTING 6
DIVISION 10 - SPECIALTIES
101423.16 ROOM-IDENTIFICATION PANEL SIGNAGE 5
102113.19 PLASTIC TOILET COMPARTMENTS 6
102800 TOILET, BATH, AND LAUNDRY ACCESSORIES 6
104413 FIRE PROTECTION CABINETS 5
104416 FIRE EXTINGUISHERS 3
DIVISION 12 - FURNISHINGS
123661.16 SOLID SURFACING COUNTERTOPS 4
Facility Services Subgroup
DIVISION 21 – FIRE SUPPRESSION
211313 FIRE SPRINKLER 16
DIVISION 22 - PLUMBING
220719 PLUMBING PIPING INSULATION 4
221116 DOMESTIC WATER PIPING 8
221316 SANITARY WASTE AND VENT PIPING 6
224100 PLUMBING FIXTURES 5
224216.13 COMMERCIAL LAVATORIES 5
DIVISION 23 - HEATING, VENTILATING, AND AIR CONDITIONING (HVAC)
230130.52 EXISTING HVAC AIR DISTRIBUTION SYSTEM CLEANING 6
230523 GENERAL-DUTY VALVES FOR HVAC PIPING 6
230529 HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT 4
230548 VIBRATION AND SEISMIC CONTROLS FOR HVAC 7
230593 TESTING, ADJUSTING, AND BALANCING FOR HVAC 11
230713 DUCT INSULATION 9
230719 HVAC PIPING INSULATION 11
230800 COMMISSIONING OF HVAC 10
230923 DIRECT DIGITAL CONTROL (DDC) SYSTEM FOR HVAC 18
230923.11 CONTROL VALVES 6
232113 HYDRONIC PIPING 7
232116 HYDRONIC PIPING SPECIALTIES 3
233113 METAL DUCTS 13
233300 AIR DUCT ACCESSORIES 5
233346 FLEXIBLE DUCTS 3
233400 HVAC FANS 6
233600 AIR TERMINAL UNITS 6
233713.13 AIR DIFFUSERS 2
233713.23 REGISTERS AND GRILLES 2
DIVISION 26 - ELECTRICAL
260519 LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES 5
260523 CONTROL-VOLTAGE ELECTRICAL POWER CABLES 7
260526 GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS 5
260529 HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS 4
260533.13 RACEWAYS AND BOXES FOR ELECTRICAL SYSTEMS 5
260544 SLEEVES AND SLEEVE SEALS FOR ELECTRICAL RACEWAYS AND CABLING 3
260553 IDENTIFICATION FOR ELECTRICAL SYSTEMS 3
260923 LIGHTING CONTROL DEVICES 9
262726 WIRING DEVICES 6
262816 ENCLOSED SWITCHES AND CIRCUIT BREAKERS 7
265119 LED INTERIOR LIGHTING 14
265213 EMERGENCY AND EXIT LIGHTING 4
281000 ACCESS CONTROL 6
281400 ACCESS CONTROL SYSTEM HARDWARE 7
DIVISION 27 - COMMUNICATIONS
270528 PATHWAYS FOR COMMUNICATIONS SYSTEMS 9
271000 STRUCTURED CABLING 15
DIVISION 28 - ELECTRONIC SAFETY AND SECURITY
283100 ADDRESSABLE FIRE-ALARM SYSTEMS 9
END OF TABLE OF CONTENTS
August 2026 ACCESS CONTROL
NIFC 300-JWH SUITE 222/227 RENOVATION 281000 - 1
PART 1 - GENERAL
1.1 SUMMARY
A. Section Includes:
1. Access control system.
1.2 DEFINITIONS
A. DGP: Data gathering panel.
B. NFC: Near field communications.
C. REX: Request-to-exit.
1.3 ACTION SUBMITTALS
A. Shop Drawings:
1. Head-end hardware, equipment, and device locations.
2. Block diagram and cable/conduit routing illustrating end-to-end system wiring.
3. End-to-end system communications details.
4. Secondary power calculations
B. Field quality-control reports.
1.4 INFORMATIONAL SUBMITTALS
A. Sample warranties.
1.5 CLOSEOUT SUBMITTALS
A. Manufacturers' Published Instructions: Record copy of official installation and testing instructions issued to Installer by manufacturer for the following:
1. Installation and programming instructions for operating system software, including all applicable software add-ons.
2. Installation and programming instructions for antivirus and security protection software.
3. Manufacturer's recommended setup and testing procedure for operating system software and applicable software add-ons.
NIFC 300-JWH SUITE 222/227 RENOVATION 281000 - 2
4. Troubleshooting instructions for operating system software and applicable software add-ons.
5. Manufacturer's recommended setup and testing procedure for antivirus and security protection software.
6. Troubleshooting instructions for antivirus and security protection software.
7. Installation instructions for access control system servers.
8. Installation instructions for access control system input/output interface.
9. Installation instructions for access control system door controllers.
10. Installation instructions for access control system workstation.
11. Installation instructions for access control system power supplies and battery chargers.
12. Manufacturer's recommended testing and inspection procedure for operation of access control system servers, panels, input/output interfaces, door controllers, and workstations.
13. Manufacturer's recommended testing and inspection procedure for operation of access control system power supplies and battery chargers.
14. Installation instructions for integrated credential readers and entry management devices.
15. Printing, programming, and handling instructions for access control credentials.
16. Installation instructions for electrified locking devices and accessories.
17. Installation instructions for egress management devices.
18. Installation instructions for electronic key management systems.
19. Manufacturer's recommended tests and inspections for integrated credential readers and entry management devices.
20. Manufacturer's recommended tests and inspections for electrified locking devices and accessories.
21. Manufacturer's recommended tests and inspections for egress management devices.
22. Manufacturer's recommended testing and inspection procedure for end-to-end operation of access control system software, hardware, and integrated hardware devices.
B. Warranty documentation.
1.6 WARRANTY FOR ACCESS CONTROL SYSTEM
A. Special Installer Extended Warranty: Installer warrants that fabricated and installed access control system performs in accordance with specified requirements and agrees to repair or replace components that fail to perform as specified within extended-warranty period.
1. Extended-Warranty Period: Two years from date of Substantial Completion; full coverage for labor, materials, and equipment.
NIFC 300-JWH SUITE 222/227 RENOVATION 281000 - 3
1.7 WARRANTY FOR BATTERIES
A. Special Manufacturer Extended Warranty for Batteries: Manufacturer warrants that batteries perform in accordance with specified requirements and agrees to provide repair or replacement of batteries that fail to perform as specified within warranted cycle life.
1. Initial Extended-Warranty Period for Li-ion Batteries: Three years from date of Substantial Completion; full coverage for materials only, free on board, freight prepaid.
PART 2 - PRODUCTS (Not Used)
PART 3 - EXECUTION
3.1 INSTALLATION OF ACCESS CONTROL SYSTEM
A. Description: Access control system provides a means of regulating or controlling physical entry into an area, or access to or use of a device by electrical, electronic, and/or mechanical means. Typical access control system includes a card reader at a controlled door, which reads a user credential and sends the collected data to a centrally located DGP over the cabling infrastructure. DGP may hold a user database onboard or may communicate with a user database over the
B. network. If user is authorized for acc
C. ess at a controlled door, DGP signals the electronic lock at the door to unlock. If user credential is not authorized according to user database, the door remains locked and access is denied. In addition to card readers and electronic locks, access control systems may include various other connected devices programmed for a desired function.
D. Performance Criteria:
1. Regulatory Requirements:
a. Components listed and labeled in accordance with NFPA 70 and NFPA 72, by qualified electrical testing laboratory recognized by authorities having jurisdiction, and marked for intended location and application.
b. Comply with NFPA 1, NFPA 730, NFPA 731, and ICC IBC.
c. Certification: Provide certificate, authorized under UL Certification Service, that access control system installation complies with installation requirements of UL CCN ALOV.
2. Listing Criteria: UL CCN ALOV and UL CCN ALVY; including UL 294.
3. Consult Government for resolution of conflicting requirements.
NIFC 300-JWH SUITE 222/227 RENOVATION 281000 - 4
E. Selection of Access Control System Components:
1. Provide the following with the access control system:
a. Access Control System Hardware
b. Security Door Hardware
c. Integrated Credential Readers and Entry Management
d. Access Control Credentials
e. Electrified Locking Devices and Accessories
f. Egress Management Devices
F. Special Techniques:
1. Comply with manufacturer's published instructions.
2. Mounting Heights: Mount field devices in accessible locations in accordance with
United States Access Board ADA-ABA Accessibility Guidelines standards.
3. Wiring Methods:
a. Backbone Cable Type: Single-mode fiber, multi-mode fiber, or copper.
b. Cable Type: Shielded.
c. Analog Maximum Cable Length: 1000 ft.
d. Digital Maximum Cable Length: 300 ft.
G. Interfaces with Other Work:
1. Coordinate installation of new access control system components with existing conditions.
2. Coordinate with applicable Division 08 Sections for interfacing access control system devices with door hardware.
3. Coordinate with Section 260923 "Lighting Control Devices" for interfacing access control system with lighting controls.
4. Coordinate with Section 283100 "Addressable Fire-Alarm Systems" for unlocking secured doors that are in exit ways, with or without delay.
H. Systems Integration:
1. Coordinate with Government to tie into the existing campus access control system, and for any system standards and support for final integration and acceptance.
NIFC 300-JWH SUITE 222/227 RENOVATION 281000 - 5
3.2 FIELD QUALITY CONTROL OF ACCESS CONTROL SYSTEM COMPONENTS
A. Field tests and inspections must be witnessed by authorities having jurisdiction.
B. Tests and Inspections:
1. Perform manufacturer's recommended tests and inspections for access control system components.
2. Perform tests and inspections for power supplies, batteries, and other standby power provisions.
3. Engage factory-authorized service representative to test end-to-end system connection and functionality.
4. Verify monitoring of access control system status and diagnostics information.
C. Nonconforming Work:
1. Access control equipment will be considered defective if it does not pass tests and inspections.
2. Remove and replace defective units and retest.
D. Collect, assemble, and submit test and inspection reports.
3.3 SYSTEM STARTUP
A. Perform startup service.
1. Complete installation and startup checks in accordance with manufacturer's published instructions.
3.4 ADJUSTING
A. Control Sensor Adjustments: Adjust control devices to suit actual occupied conditions.
1. For proximity motion sensors, verify operation at outer limits of detector range.
Set time delay to suit Owner's operations.
3.5 PROTECTION
A. After installation, protect access control system components from construction activities. Remove and replace items that are contaminated, defaced, damaged, or otherwise caused to be unfit for use prior to acceptance by Owner.
NIFC 300-JWH SUITE 222/227 RENOVATION 281000 - 6
3.6 MAINTENANCE
A. Control Sensor Readjustments: When requested within 12 months from date of Substantial Completion, provide on-site assistance in readjusting system to suit actual occupied conditions. Provide up to two visits to Project during other-than-normal occupancy hours for this purpose.
END OF SECTION 281000
August 2026 ACCESS CONTROL SYSTEM HARDWARE
NIFC 300-JWH SUITE 222/227 RENOVATION 281400 - 1
PART 1 - GENERAL
1.1 SUMMARY
A. Section Includes:
1. Access control system units.
2. Access control system power supplies and battery chargers.
3. Access control system supplementary computer equipment.
B. Related Requirements:
1. Section 281500 "Integrated Access Control Hardware Devices" for access control field devices controlled by hardware specified in this Section.
1.2 DEFINITIONS
A. DGP: Data gathering panel.
B. LAN: Local area network.
C. RAID: Redundant array of inexpensive disks; redundant array of independent disks.
D. RAM: Random-access memory.
E. WAN: Wide area network.
1.3 ACTION SUBMITTALS
A. Product Data:
1. Access control system units.
B. Shop Drawings:
1. Project general notes.
2. Hardware and equipment locations.
3. Block diagram and cable/conduit routing.
4. System communications details.
5. Hardware and equipment installation details.
6. Secondary power calculations.
C. Field quality-control reports.
NIFC 300-JWH SUITE 222/227 RENOVATION 281400 - 2
1.4 INFORMATIONAL SUBMITTALS
A. Manufacturers' Published Instructions: Record copy of official installation and testing instructions issued to Installer by manufacturer for the following:
1. Installation instructions for access control system servers.
2. Installation instructions for access control system DGPs.
3. Installation instructions for access control system input/output interface.
4. Installation instructions for access control system door controllers.
5. Installation instructions for access control system workstation.
6. Manufacturer's recommended testing and inspection procedure for operation of access control system servers, panels, input/output interfaces, door controllers, and workstations.
7. Installation instructions for access control system power supplies and battery chargers.
8. Manufacturer's recommended testing and inspection procedure for operation of access control system power supplies and battery chargers.
9. Manufacturer's recommended testing and inspection procedure for operation of access control system printers.
B. Sample warranties.
1.5 CLOSEOUT SUBMITTALS
A. Warranty documentation.
1.6 WARRANTY FOR ACCESS CONTROL SYSTEM HARDWARE
A. Special Manufacturer Extended Warranty: Manufacturer warrants that access control system hardware perform in accordance with specified requirements and agrees to provide repair or replacement of components or products that fail to perform as specified within extended-warranty period.
1. Initial Extended-Warranty Period: Three years from date of Substantial Completion; coverage for labor, materials, and equipment.
1.7 WARRANTY FOR BATTERIES
A. Special Manufacturer Extended Warranty for Batteries: Manufacturer warrants that batteries perform in accordance with specified requirements and agrees to provide repair or replacement of batteries that fail to perform as specified within extended-warranty period.
NIFC 300-JWH SUITE 222/227 RENOVATION 281400 - 3
PART 2 - PRODUCTS
2.1 ACCESS CONTROL SYSTEM UNITS
A. Description: This category covers head end units for access control systems, providing a means of regulating or controlling physical entry into an area, or access to or use of device by electrical, electronic, and/or mechanical means. Access control systems are investigated as complete configuration based upon manufacturer's specified system components. Access control systems are intended to comply with applicable life safety access and egress requirements.
B. Performance Criteria:
1. Regulatory Requirements:
a. Listed and labeled in accordance with NFPA 70 and NFPA 72, by qualified electrical testing laboratory recognized by authorities having jurisdiction, and marked for intended location and application.
b. Comply with NFPA 1, NFPA 730, NFPA 731, and ICC IBC.
2. Listing Criteria: UL CCN ALVY; including UL 294.
C. Access Control System Server
1. Coordinate with Government and tie into the existing campus system.
D. Access Control System DGPs
1. Coordinate with Government and tie into the existing campus system.
E. Access Control System Door Controllers
1. Source Limitations: Obtain products from single manufacturer.
2. Additional Characteristics:
a. Data ports for connection to LAN and downstream controllers.
b. Integral terminal blocks for connection of inputs/outputs to field devices.
c. Controller Inputs:
1) Auxiliary input.
2) Door contact.
3) Request to exit.
4) Cabinet tamper.
5) Power monitor.
d. Controller Outputs:
1) Auxiliary output.
NIFC 300-JWH SUITE 222/227 RENOVATION 281400 - 4
2) Door strike.
3) Door operators.
4) Credential readers.
3. Options:
a. Input Voltage: 12 to 24 V(dc).
b. Operating Temperature: 32 to 158 deg F (0 to 70 deg C).
c. Controller Communication: CAT6A.
d. Mounting: Cabinet mount.
F. Access Control System Input/Output Interface
1. Source Limitations: Obtain products from single manufacturer.
2. Additional Characteristics:
a. Input Voltage: 12 to 24 V(dc).
b. Operating Temperature: 32 to 158 deg F (0 to 70 deg C).
c. Data ports for connection to LAN and downstream panels/controllers.
d. Integral terminal blocks for connection of inputs/outputs to field devices.
e. Inputs:
1) Auxiliary inputs from building systems.
2) Door contact.
3) Request to exit.
4) Cabinet tamper.
5) Power monitor.
f. Outputs:
1) Auxiliary outputs to building systems.
2) Door strike.
3) Credential readers.
4) Audible devices.
3. Options:
a. Communication: CAT6A.
b. Mounting: Cabinet mount.
2.2 ACCESS CONTROL SYSTEM POWER SUPPLIES AND BATTERY CHARGERS
A. Description: This category covers power supplies and battery chargers for access control system units, controllers, input/output interfaces, workstations, printers, and encoders.
B. Performance Criteria:
NIFC 300-JWH SUITE 222/227 RENOVATION 281400 - 5
1. Regulatory Requirements:
a. Listed and labeled in accordance with NFPA 70 and NFPA 72, by qualified electrical testing laboratory recognized by authorities having jurisdiction, and marked for intended location and application.
b. Comply with NFPA 1, NFPA 730, NFPA 731, and ICC IBC.
2. Listing Criteria: UL CCN ALVY; including UL 294.
C. Access Control System Power Supply and Battery Charger:
1. Source Limitations: Obtain products from single manufacturer.
2. Additional Characteristics:
a. Input Voltage: 120 V(ac).
b. Output Voltage: 12 to 24 V(dc).
c. Operating Temperature: 32 to 120 deg F (0 to 49 deg C).
d. Network connection for remote supervision, management, and testing.
e. Enclosure lock with tamper switch and monitoring.
f. Built-in battery charger.
3. Accessories:
a. DIN rails for mounting.
2.3 ACCESS CONTROL SYSTEM SUPPLEMENTARY COMPUTER EQUIPMENT
A. Description: This category covers access control system supplementary computer equipment that does not inhibit safety or intended operation of access control system hardware devices when they are shut off, lose power, or otherwise fail.
B. Performance Criteria:
1. Regulatory Requirements:
a. Listed and labeled in accordance with NFPA 70 and NFPA 72, by qualified electrical testing laboratory recognized by authorities having jurisdiction, and marked for intended location and application.
2. Listing Criteria: UL CCN NWGQ; including UL 294.
PART 3 - EXECUTION
3.1 INSTALLATION OF ACCESS CONTROL SYSTEM HARDWARE
A. Comply with manufacturer's published instructions.
NIFC 300-JWH SUITE 222/227 RENOVATION 281400 - 6
B. Reference Standards:
1. Installation of Access Control System Hardware and Wiring: Unless more stringent requirements are specified in Contract Documents or manufacturers' published instructions, comply with requirements in guide information for
UL CCN ALVY.
2. Consult Government for resolution of conflicting requirements.
C. Interfaces with Other Work:
1. Coordinate installation of new products for access control system hardware with existing systems and conditions.
2. Coordinate with Section 281000 "Access Control" for physical and functional interfaces with access control system and for compliance with system-wide performance requirements.
3. Coordinate with Section 283100 "Addressable Fire-Alarm Systems" for interfacing security system inputs/outputs with fire-alarm system inputs/outputs.
D. Systems Integration:
1. Coordinate with Government to tie into the existing campus access control system, and for any system standards and support for final integration and acceptance.
3.2 FIELD QUALITY CONTROL OF ACCESS CONTROL SYSTEM HARDWARE
A. Field tests and inspections must be witnessed by authorities having jurisdiction.
B. Tests and Inspections:
1. Perform manufacturer's recommended tests and inspections.
C. Nonconforming Work:
1. Hardware and components will be considered defective if they do not pass tests and inspections.
2. Remove and replace defective units and retest.
D. Collect, assemble, and submit test and inspection reports.
3.3 SYSTEM STARTUP
A. Perform startup service.
1. Complete installation and startup checks in accordance with manufacturer's published instructions.
NIFC 300-JWH SUITE 222/227 RENOVATION 281400 - 7
3.4 ADJUSTING
A. Adjust printers and ribbons to function smoothly, and lubricate as recommended in writing by manufacturer.
3.5 PROTECTION
A. After installation, protect access control system hardware from construction activities.
Remove and replace items that are contaminated, defaced, damaged, or otherwise caused to be unfit for use prior to acceptance by Owner.
END OF SECTION 281400
| 281000 FL - Access Control.pdf |
| PART 1 - GENERAL |
| 1.1 SUMMARY |
| A. Section Includes: |
| 1. Access control system. |
| 1.2 DEFINITIONS |
| A. DGP: Data gathering panel. |
| B. NFC: Near field communications. |
| C. REX: Request-to-exit. |
| 1.3 ACTION SUBMITTALS |
| A. Shop Drawings: |
| 1. Head-end hardware, equipment, and device locations. |
| 2. Block diagram and cable/conduit routing illustrating end-to-end system wiring. |
| 3. End-to-end system communications details. |
| 4. Secondary power calculations |
B. Field quality-control reports.
| 1.4 INFORMATIONAL SUBMITTALS |
| A. Sample warranties. |
| 1.5 CLOSEOUT SUBMITTALS |
| A. Manufacturers' Published Instructions: Record copy of official installation and testing instructions issued to Installer by manufacturer for the following: |
| 1. Installation and programming instructions for operating system software, including all applicable software add-ons. |
| 2. Installation and programming instructions for antivirus and security protection software. |
| 3. Manufacturer's recommended setup and testing procedure for operating system software and applicable software add-ons. |
| 4. Troubleshooting instructions for operating system software and applicable software add-ons. |
| 5. Manufacturer's recommended setup and testing procedure for antivirus and security protection software. |
| 6. Troubleshooting instructions for antivirus and security protection software. |
| 7. Installation instructions for access control system servers. |
| 8. Installation instructions for access control system input/output interface. |
| 9. Installation instructions for access control system door controllers. |
| 10. Installation instructions for access control system workstation. |
| 11. Installation instructions for access control system power supplies and battery chargers. |
| 12. Manufacturer's recommended testing and inspection procedure for operation of access control system servers, panels, input/output interfaces, door controllers, and workstations. |
| 13. Manufacturer's recommended testing and inspection procedure for operation of access control system power supplies and battery chargers. |
| 14. Installation instructions for integrated credential readers and entry management devices. |
| 15. Printing, programming, and handling instructions for access control credentials. |
| 16. Installation instructions for electrified locking devices and accessories. |
| 17. Installation instructions for egress management devices. |
| 18. Installation instructions for electronic key management systems. |
| 19. Manufacturer's recommended tests and inspections for integrated credential readers and entry management devices. |
| 20. Manufacturer's recommended tests and inspections for electrified locking devices and accessories. |
| 21. Manufacturer's recommended tests and inspections for egress management devices. |
| 22. Manufacturer's recommended testing and inspection procedure for end-to-end operation of access control system software, hardware, and integrated hardware devices. |
B. Warranty documentation.
| 1.6 WARRANTY FOR ACCESS CONTROL SYSTEM |
| A. Special Installer Extended Warranty: Installer warrants that fabricated and installed access control system performs in accordance with specified requirements and agrees to repair or replace components that fail to perform as specified within exten... |
| 1. Extended-Warranty Period: Two years from date of Substantial Completion; full coverage for labor, materials, and equipment. |
| 1.7 WARRANTY FOR BATTERIES |
| A. Special Manufacturer Extended Warranty for Batteries: Manufacturer warrants that batteries perform in accordance with specified requirements and agrees to provide repair or replacement of batteries that fail to perform as specified within warranted... |
| 1. Initial Extended-Warranty Period for Li-ion Batteries: Three years from date of Substantial Completion; full coverage for materials only, free on board, freight prepaid. |
| PART 2 - PRODUCTS (Not Used) |
| PART 3 - EXECUTION |
| 3.1 INSTALLATION OF ACCESS CONTROL SYSTEM |
| A. Description: Access control system provides a means of regulating or controlling physical entry into an area, or access to or use of a device by electrical, electronic, and/or mechanical means. Typical access control system includes a card reader a... |
| B. network. If user is authorized for ac |
| C. ess at a controlled door, DGP signals the electronic lock at the door to unlock. If user credential is not authorized according to user database, the door remains locked and access is denied. In addition to card readers and electronic locks, access... |
| D. Performance Criteria: |
| 1. Regulatory Requirements: |
| a. Components listed and labeled in accordance with NFPA 70 and NFPA 72, by qualified electrical testing laboratory recognized by authorities having jurisdiction, and marked for intended location and application. |
| b. Comply with NFPA 1, NFPA 730, NFPA 731, and ICC IBC. |
| c. Certification: Provide certificate, authorized under UL Certification Service, that access control system installation complies with installation requirements of UL CCN ALOV. |
| 2. Listing Criteria: UL CCN ALOV and UL CCN ALVY; including UL 294. |
| 3. Consult Government for resolution of conflicting requirements. |
| E. Selection of Access Control System Components: |
| 1. Provide the following with the access control system: |
| a. Access Control System Hardware |
| b. Security Door Hardware |
| c. Integrated Credential Readers and Entry Management |
| d. Access Control Credentials |
| e. Electrified Locking Devices and Accessories |
| f. Egress Management Devices |
| F. Special Techniques: |
| 1. Comply with manufacturer's published instructions. |
| 2. Mounting Heights: Mount field devices in accessible locations in accordance with United States Access Board ADA-ABA Accessibility Guidelines standards. |
| 3. Wiring Methods: |
| a. Backbone Cable Type: Single-mode fiber, multi-mode fiber, or copper. |
| b. Cable Type: Shielded. |
| c. Analog Maximum Cable Length: 1000 ft. |
| d. Digital Maximum Cable Length: 300 ft. |
| G. Interfaces with Other Work: |
| 1. Coordinate installation of new access control system components with existing conditions. |
| 2. Coordinate with applicable Division 08 Sections for interfacing access control system devices with door hardware. |
| 3. Coordinate with Section 260923 "Lighting Control Devices" for interfacing access control system with lighting controls. |
| 4. Coordinate with Section 283100 "Addressable Fire-Alarm Systems" for unlocking secured doors that are in exit ways, with or without delay. |
| H. Systems Integration: |
| 1. Coordinate with Government to tie into the existing campus access control system, and for any system standards and support for final integration and acceptance. |
| 3.2 FIELD QUALITY CONTROL OF ACCESS CONTROL SYSTEM COMPONENTS |
| A. Field tests and inspections must be witnessed by authorities having jurisdiction. |
| B. Tests and Inspections: |
| 1. Perform manufacturer's recommended tests and inspections for access control system components. |
| 2. Perform tests and inspections for power supplies, batteries, and other standby power provisions. |
| 3. Engage factory-authorized service representative to test end-to-end system connection and functionality. |
| 4. Verify monitoring of access control system status and diagnostics information. |
| C. Nonconforming Work: |
| 1. Access control equipment will be considered defective if it does not pass tests and inspections. |
| 2. Remove and replace defective units and retest. |
D. Collect, assemble, and submit test and inspection reports.
| 3.3 SYSTEM STARTUP |
| A. Perform startup service. |
| 1. Complete installation and startup checks in accordance with manufacturer's published instructions. |
| 3.4 ADJUSTING |
| A. Control Sensor Adjustments: Adjust control devices to suit actual occupied conditions. |
| 1. For proximity motion sensors, verify operation at outer limits of detector range. Set time delay to suit Owner's operations. |
| 3.5 PROTECTION |
| A. After installation, protect access control system components from construction activities. Remove and replace items that are contaminated, defaced, damaged, or otherwise caused to be unfit for use prior to acceptance by Owner. |
| 3.6 MAINTENANCE |
| A. Control Sensor Readjustments: When requested within 12 months from date of Substantial Completion, provide on-site assistance in readjusting system to suit actual occupied conditions. Provide up to two visits to Project during other-than-normal occ... |
| 281400 FL - Access Control System Hardware.pdf |
| PART 1 - GENERAL |
| 1.1 SUMMARY |
| A. Section Includes: |
| 1. Access control system units. |
| 2. Access control system power supplies and battery chargers. |
| 3. Access control system supplementary computer equipment. |
| B. Related Requirements: |
| 1. Section 281500 "Integrated Access Control Hardware Devices" for access control field devices controlled by hardware specified in this Section. |
| 1.2 DEFINITIONS |
| A. DGP: Data gathering panel. |
| B. LAN: Local area network. |
| C. RAID: Redundant array of inexpensive disks; redundant array of independent disks. |
| D. RAM: Random-access memory. |
| E. WAN: Wide area network. |
| 1.3 ACTION SUBMITTALS |
| A. Product Data: |
| 1. Access control system units. |
| B. Shop Drawings: |
| 1. Project general notes. |
| 2. Hardware and equipment locations. |
| 3. Block diagram and cable/conduit routing. |
| 4. System communications details. |
| 5. Hardware and equipment installation details. |
| 6. Secondary power calculations. |
C. Field quality-control reports.
| 1.4 INFORMATIONAL SUBMITTALS |
| A. Manufacturers' Published Instructions: Record copy of official installation and testing instructions issued to Installer by manufacturer for the following: |
| 1. Installation instructions for access control system servers. |
| 2. Installation instructions for access control system DGPs. |
| 3. Installation instructions for access control system input/output interface. |
| 4. Installation instructions for access control system door controllers. |
| 5. Installation instructions for access control system workstation. |
| 6. Manufacturer's recommended testing and inspection procedure for operation of access control system servers, panels, input/output interfaces, door controllers, and workstations. |
| 7. Installation instructions for access control system power supplies and battery chargers. |
| 8. Manufacturer's recommended testing and inspection procedure for operation of access control system power supplies and battery chargers. |
| 9. Manufacturer's recommended testing and inspection procedure for operation of access control system printers. |
B. Sample warranties.
| 1.5 CLOSEOUT SUBMITTALS |
| A. Warranty documentation. |
| 1.6 WARRANTY FOR ACCESS CONTROL SYSTEM HARDWARE |
| A. Special Manufacturer Extended Warranty: Manufacturer warrants that access control system hardware perform in accordance with specified requirements and agrees to provide repair or replacement of components or products that fail to perform as specif... |
| 1. Initial Extended-Warranty Period: Three years from date of Substantial Completion; coverage for labor, materials, and equipment. |
| 1.7 WARRANTY FOR BATTERIES |
| A. Special Manufacturer Extended Warranty for Batteries: Manufacturer warrants that batteries perform in accordance with specified requirements and agrees to provide repair or replacement of batteries that fail to perform as specified within extended-... |
| PART 2 - PRODUCTS |
| 2.1 ACCESS CONTROL SYSTEM UNITS |
| A. Description: This category covers head end units for access control systems, providing a means of regulating or controlling physical entry into an area, or access to or use of device by electrical, electronic, and/or mechanical means. Access contro... |
| B. Performance Criteria: |
| 1. Regulatory Requirements: |
| a. Listed and labeled in accordance with NFPA 70 and NFPA 72, by qualified electrical testing laboratory recognized by authorities having jurisdiction, and marked for intended location and application. |
| b. Comply with NFPA 1, NFPA 730, NFPA 731, and ICC IBC. |
2. Listing Criteria: UL CCN ALVY; including UL 294.
| C. Access Control System Server |
| 1. Coordinate with Government and tie into the existing campus system. |
| D. Access Control System DGPs |
| 1. Coordinate with Government and tie into the existing campus system. |
| E. Access Control System Door Controllers |
| 1. Source Limitations: Obtain products from single manufacturer. |
| 2. Additional Characteristics: |
| a. Data ports for connection to LAN and downstream controllers. |
| b. Integral terminal blocks for connection of inputs/outputs to field devices. |
| c. Controller Inputs: |
| 1) Auxiliary input. |
| 2) Door contact. |
| 3) Request to exit. |
| 4) Cabinet tamper. |
| 5) Power monitor. |
| d. Controller Outputs: |
| 1) Auxiliary output. |
| 2) Door strike. |
| 3) Door operators. |
| 4) Credential readers. |
| 3. Options: |
| a. Input Voltage: 12 to 24 V(dc). |
| b. Operating Temperature: 32 to 158 deg F (0 to 70 deg C). |
| c. Controller Communication: CAT6A. |
| d. Mounting: Cabinet mount. |
| F. Access Control System Input/Output Interface |
| 1. Source Limitations: Obtain products from single manufacturer. |
| 2. Additional Characteristics: |
| a. Input Voltage: 12 to 24 V(dc). |
| b. Operating Temperature: 32 to 158 deg F (0 to 70 deg C). |
| c. Data ports for connection to LAN and downstream panels/controllers. |
| d. Integral terminal blocks for connection of inputs/outputs to field devices. |
| e. Inputs: |
| 1) Auxiliary inputs from building systems. |
| 2) Door contact. |
| 3) Request to exit. |
| 4) Cabinet tamper. |
| 5) Power monitor. |
| f. Outputs: |
| 1) Auxiliary outputs to building systems. |
| 2) Door strike. |
| 3) Credential readers. |
| 4) Audible devices. |
| 3. Options: |
| a. Communication: CAT6A. |
| b. Mounting: Cabinet mount. |
| 2.2 ACCESS CONTROL SYSTEM POWER SUPPLIES AND BATTERY CHARGERS |
| A. Description: This category covers power supplies and battery chargers for access control system units, controllers, input/output interfaces, workstations, printers, and encoders. |
| B. Performance Criteria: |
| 1. Regulatory Requirements: |
| a. Listed and labeled in accordance with NFPA 70 and NFPA 72, by qualified electrical testing laboratory recognized by authorities having jurisdiction, and marked for intended location and application. |
| b. Comply with NFPA 1, NFPA 730, NFPA 731, and ICC IBC. |
2. Listing Criteria: UL CCN ALVY; including UL 294.
| C. Access Control System Power Supply and Battery Charger: |
| 1. Source Limitations: Obtain products from single manufacturer. |
| 2. Additional Characteristics: |
| a. Input Voltage: 120 V(ac). |
| b. Output Voltage: 12 to 24 V(dc). |
| c. Operating Temperature: 32 to 120 deg F (0 to 49 deg C). |
| d. Network connection for remote supervision, management, and testing. |
| e. Enclosure lock with tamper switch and monitoring. |
| f. Built-in battery charger. |
| 3. Accessories: |
| a. DIN rails for mounting. |
| 2.3 ACCESS CONTROL SYSTEM SUPPLEMENTARY COMPUTER EQUIPMENT |
| A. Description: This category covers access control system supplementary computer equipment that does not inhibit safety or intended operation of access control system hardware devices when they are shut off, lose power, or otherwise fail. |
| B. Performance Criteria: |
| 1. Regulatory Requirements: |
| a. Listed and labeled in accordance with NFPA 70 and NFPA 72, by qualified electrical testing laboratory recognized by authorities having jurisdiction, and marked for intended location and application. |
2. Listing Criteria: UL CCN NWGQ; including UL 294.
| PART 3 - EXECUTION |
| 3.1 INSTALLATION OF ACCESS CONTROL SYSTEM HARDWARE |
| A. Comply with manufacturer's published instructions. |
| B. Reference Standards: |
| 1. Installation of Access Control System Hardware and Wiring: Unless more stringent requirements are specified in Contract Documents or manufacturers' published instructions, comply with requirements in guide information for UL CCN ALVY. |
| 2. Consult Government for resolution of conflicting requirements. |
| C. Interfaces with Other Work: |
| 1. Coordinate installation of new products for access control system hardware with existing systems and conditions. |
| 2. Coordinate with Section 281000 "Access Control" for physical and functional interfaces with access control system and for compliance with system-wide performance requirements. |
| 3. Coordinate with Section 283100 "Addressable Fire-Alarm Systems" for interfacing security system inputs/outputs with fire-alarm system inputs/outputs. |
| D. Systems Integration: |
| 1. Coordinate with Government to tie into the existing campus access control system, and for any system standards and support for final integration and acceptance. |
| 3.2 FIELD QUALITY CONTROL OF ACCESS CONTROL SYSTEM HARDWARE |
| A. Field tests and inspections must be witnessed by authorities having jurisdiction. |
| B. Tests and Inspections: |
| 1. Perform manufacturer's recommended tests and inspections. |
| C. Nonconforming Work: |
| 1. Hardware and components will be considered defective if they do not pass tests and inspections. |
| 2. Remove and replace defective units and retest. |
D. Collect, assemble, and submit test and inspection reports.
| 3.3 SYSTEM STARTUP |
| A. Perform startup service. |
| 1. Complete installation and startup checks in accordance with manufacturer's published instructions. |
| 3.4 ADJUSTING |
| A. Adjust printers and ribbons to function smoothly, and lubricate as recommended in writing by manufacturer. |
| 3.5 PROTECTION |
| A. After installation, protect access control system hardware from construction activities. Remove and replace items that are contaminated, defaced, damaged, or otherwise caused to be unfit for use prior to acceptance by Owner. |