This document is a Standard Form 30 Amendment of Solicitation/Modification of Contract issued by the USGS OAG Denver Acquisition Branch on June 1, 2026, for solicitation number 140G0226R0008.

The amendment replaces a corrupted Statement of Work (SOW) file with a corrected version titled "SCOPE OF WORK - HYDRONIC SYSTEM UPGRADES" and updates primary point of contact information. The primary POC is changed from Karen LaBouff-Kind to Philip Robinson, with email changed to philip_robinson@ios.doi.gov and phone contact preference noted as "email preferable." The contract involves hydronic boiler system upgrades at the USGS Upper Midwest Environmental Sciences Center (UMESC) in La Crosse, Wisconsin. The scope requires replacement of three existing Thermal Solutions EVA3000BN1 boilers (3,000,000 BTU/hr non-condensing) with new standard efficiency boilers, including all venting, piping, electrical work, and integration with the existing Automated Logic WebCtrl Building Automation System. Key requirements include a 3:1 minimum turndown capacity, electric vent stack dampers with interlock functionality, connection of eight specific control points to the BAS, and 12-month warranty of workmanship from acceptance. The contractor must provide project design and schedule with the proposal, perform startup by a technician with three years' hydronic heating experience, maintain $1,000,000 liability insurance, and complete installation within 120 days of Notice to Proceed. The period of performance is July 25, 2026, through November 13, 2026, on a firm fixed-price basis. Selection will be based on Best Value considering past experience (three Wisconsin projects of $150,000+), personnel qualifications and licensure, detailed project plan, and price. Additional contacts include Technical POC Mark Goede (mgoede@usgs.gov), Admin POC Justin Littman (jlittman@usgs.gov), and Contract Specialist Philip Robinson (probinson@usgs.gov).

View the file

Other files for this federal contract opportunity

Other files attached to UMESC HYDRONIC BOILER REPLACEMENT, newest first.
File Type Posted
Sol_140G0226R0008_Amd_0002.pdf PDF
A04_FY26HydronicBoilers_SOW_0001.docx DOCX document
Sol_140G0226R0008.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Offers must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended, by one of the following methods:

(a) By completing items 8 and 15, and returning or (c) By separate letter or electronic communication which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGMENT TO BE RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY RESULT IN REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted, such change may be made by letter or electronic communication, provided each letter or electronic communication makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.

E. IMPORTANT: is not is required copies to the issuing office.

AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT 1. CONTRACT ID CODE

2. AMENDMENT/MODIFICATION NUMBER 3. EFFECTIVE DATE 4. REQUISITION/PURCHASE REQUISITION NUMBER 5. PROJECT NUMBER (If applicable)

7.ADMINISTERED BY (If other than Item 6) CODE

STANDARD FORM 30 (REV. 11/2016)

Prescribed by GSA FAR (48 CFR) 53.243

FACILITY CODE

9A. AMENDMENT OF SOLICITATION NUMBER

9B. DATED (SEE ITEM 11)

10A. MODIFICATION OF CONTRACT/ORDER NUMBER

10B. DATED (SEE ITEM 13)

11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS

The above numbered solicitation is amended as set forth in Item 14. is extended. is not extended.

12. ACCOUNTING AND APPROPRIATION DATA (If required) copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted;

13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS.

IT MODIFIES THE CONTRACT/ORDER NUMBER AS DESCRIBED IN ITEM 14.

CHECK ONE A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE CONTRACT ORDER

NUMBER IN ITEM 10A.

B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES (such as changes in paying office, appropriation data, etc.) SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(b).

C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:

D. OTHER (Specify type of modification and authority)

Except as provided herein, all terms and conditions of the document referenced in Item 9A or 10A, as heretofore changed, remains unchanged and in full force and effect.

15C. DATE SIGNED

15A. NAME AND TITLE OF SIGNER (Type or print)

16C. DATE SIGNED

16A. NAME AND TITLE OF CONTRACTING OFFICER (Type or print)

14. DESCRIPTION OF AMENDMENT/MODIFICATION (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)

PAGE

6. ISSUED BY CODE

8. NAME AND ADDRESS OF CONTRACTOR (Number, street, county, State and ZIP Code) (X)

CODE

15B. CONTRACTOR/OFFEROR

(Signature of person authorized to sign)

16B. UNITED STATES OF AMERICA

(Signature of Contracting Officer)

Previous edition unusable

PAGESOF

Contractor

The hour and date specified for receipt of Offers to sign this document and return

Karen La Bouff-Kind

See continuation page

USGS OAG DENVER ACQUISITION BRANCH

PO BOX 25046

204 DENVER FEDERAL CENTER

DENVER CO 80225-0046

USGS OAG DENVER ACQUISITION BRANCH

PO BOX 25046

DENVER CO 80225-0046

GDB

GDB

140G0226R0008

06/01/2026

06/01/2026

1 9

CONTINUATION SHEET

REFERENCE NO. OF DOCUMENT BEING CONTINUED PAGES

NAME OF OFFEROR OR CONTRACTOR

SUPPLIES/SERVICES

(B)

UNIT

(D)

UNIT PRICE

(E)

AMOUNT

(F)

OPTIONAL FORM 336 (4-86)

Sponsored by GSA FAR (48 CFR) 53.110

ITEM NO.

(A)

QUANTITY

(C)

NSN 7540-01-152-8067

140G0226R0008/0001

The purpose of this modification is to replace and corrupted SOW file and change the POC.

a. The Statement of Work (SOW) was a corrupted file and replaced with the attached version.

This file name is "Statement of Work (A04

FY26HydronicBoilers_SOW.docx). The document title is "SCOPE OF WORK - HYDRONIC SYSTEM

UPGRADES" and is seven (7) pages in length.

b. The Contact Information, Primary Point of

Contact (POC) is changed from "Karen

LaBouf-Kind" to "Philip Robinson".

c. Primary POC email is changed from "Karen

Labouff-kind@ios.doi.gov" to

"philip_robinson@ios.doi.gov".

d. Primary POC Phone number is changed from

"303-236-9315" to "email preferable".

e. All other terms and conditions remain unchanged.

Period of Performance: 07/25/2026 to

11/13/2026

AWARD TYPE: FIRM FIXED PRICE

TECHNICAL POC: MARK GOEDE, Email:

mgoede@usgs.gov

ADMIN POC: JUSTIM LITTMAN, Email:

jlittman@usgs.gov

CONTRACT SPECIALIST: PHILIP ROBINSON, Email:

probinson@usgs.gov

SCOPE OF WORK

HYDRONIC SYSTEM UPGRADES

1. GENERAL INFORMATION

a. Introduction The Department of the Interior (DOI), U.S. Geological Survey (USGS), Upper Midwest Environmental Sciences Center (UMESC) 2630 Fanta Reed Road, La Crosse, Wisconsin 54603 requires replacement of existing hydronic boilers and installation of new standard efficiency boilers and all appurtenances.

b. Background: The existing facility hot water system is served by three Thermal Solutions (Model Number EVA3000BN1) 3,000,000 BTU/hr non-condensing hot water boilers. The boilers have reached the end of their useful life and are in need of replacement.

c. Scope: Services, construction, to provide all equipment, labor, travel, and materials (unless otherwise provided herein) necessary replace existing hydronic boilers and any required changes to new boiler venting, all piping and appurtenances complete.

2. REFERENCE STANDARDS: Abbreviations of standards organizations referenced in other sections are as follows:

AABC Associated Air Balance Council ABMA American Boiler Manufacturers Association ADC Air Diffusion Council AGA American Gas Association AMCA Air Movement and Control Association ANSI American National Standards Institute ARI Air Conditioning and Refrigeration Institute ASHRAE American Society of Heating, Refrigerating and Air Conditioning Engineers ASME American Society of Mechanical Engineers ASTM American Society for Testing and Materials AWWA American Water Works Association AWS American Welding Society BMS Building Management System BACnet Building Automation Control Network MSTP Master-Slave Token Pass CSA Canadian Standards Association CSD Controls and Safety Devices CGA Compressed Gas Association CTI Cooling Tower Institute EPA Environmental Protection Agency GAMA Gas Appliance Manufacturers Association IEEE Institute of Electrical and Electronics Engineers ISA Instrument Society of America MCA Mechanical Contractors Association MICA Midwest Insulation Contractors Association MSS Manufacturer's Standardization Society of the Valve & Fitting Industry, Inc.

NBS National Bureau of Standards

NEBB National Environmental Balancing Bureau NEC National Electric Code NEMA National Electrical Manufacturers Association NFPA National Fire Protection Association SMACNA Sheet Metal and Air Conditioning Contractors' National Association. Inc.

UL Underwriters Laboratories Inc.

ASTM E814 Standard Test Method for Fire Tests of Through-Penetration Fire Stops ASTM E84 Standard Test Method for Surface Burning Characteristics of Building Materials UL1479 Fire Tests of Through-Penetration Firestops UL723 Surface Burning Characteristics of Building Materials TL USGS Technical Liaison COR Contracting Officer’s Representative

3. PROJECT REQUIREMENTS:

a. Project Submittals: Prior to construction, the Contractor shall present the proposed system layout to the TL for approval. Finished system will include venting, piping, power, instrumentation and wiring to connect new boilers complete to existing facility hydronic system. Contractor shall be responsible for connecting boiler controls to the existing Automated Logic Webctrl Building Automation System (BAS). Contractor shall install system complete, with all appurtenances fully installed per manufacturers guidelines and applicable codes to provide a complete working system.

b. Submit for all equipment required to complete this Requirement as a complete installed system. Mark general catalog sheets and drawings to indicate specific items being submitted and proper identification of equipment by name and/or number.

c. Before submitting electrically powered equipment, verify that the electrical power and control requirements for the equipment are in agreement with the existing site conditions and existing power supplied to the existing boilers and pumps. Include a statement on the shop drawing transmittal that the equipment submitted and the existing power available are in agreement.

d. Include wiring diagrams of electrically powered equipment.

e. New boilers shall meet or exceed specifications of existing boilers.

f. Demolition: Contractor shall demolish and remove the three existing Thermal

Solutions boilers. Any existing control sensors from facility BAS to be retained for reuse.

b. System Requirements: System shall meet or exceed the following minimum requirements:

i. New Boilers: Existing boilers are Thermal Solutions EVA3000BN1) 3,000,000 BTU/hr non-condensing hot water boilers. New boilers shall match specifications of existing boilers, including but not limited to:

1. Boiler shall have turndown capacity 3:1 or better.

2. Electrical requirements matching existing boilers.

3. Input/Output to/from BAS.

ii. Contractor shall be responsible for any system modifications, including but not limited to: piping, electrical and venting modifications, as needed to install new boilers.

iii. Contractor shall furnish complete and install all piping, venting, electrical, controls and safeties according to manufacturer’s guidelines and relevant building codes.

iv. Pumps: Contractor shall confirm that existing boiler loop pumps conform to manufacturers recommendations. If existing pumps are not in compliance with new boiler requirements, Contractor shall provide and install new pumps for each boiler that conform to each boiler requirements and manufacturer guidelines.

v. Venting: Contractor shall provide and install all venting. All material and work according to boiler manufacturers recommendations. Contractor shall include an electric vent stack damper on the stack outlet of each boiler sized and installed per boiler manufacturer recommendations. Stack damper shall be interlocked to the boiler start command such that the boiler shall not start unless the damper is proven open.

vi. Electrical: Contractor shall use existing power feeds at each boiler location. All electrical work to be installed complete. Contractor is responsible for ensuring all products are compatible with the existing electrical feeds.

vii. Controls shall interface to existing Automated Logic WebCtrl facility BAS. The following points for each boiler shall be hard wired to each boiler and be viewable, configurable and command able from the BAS:

1. Boiler Enable (Output)

2. Boiler Run Status (Input)

3. Boiler Alarm (Input)

4. Boiler Stack Damper Open/Closed Status (Input)

5. Boiler Circulating Pump Start/Stop (Output)

6. Boiler Circulating Pump Status (Input)

7. Boiler Outlet Temperature (Input)

8. Boiler Fire Rate (Output)

viii. Contractor shall be responsible for all wiring, Automate Logic Eikon logic programming, process hot water system graphics, and trend creation in WebCtrl.

c. General Requirements

i. Contractor shall be responsible for furnishing and installing all venting, piping, electrical, controls, enclosures, equipment, conduit, electrical and low voltage wiring as required to furnish a complete system.

ii. All installation work will conform to manufacturers recommendations, industry standards and local and state building codes. All work to be performed in a clean and workmanlike manner.

iii. The contractor shall include a draft design and tentative work schedule with their proposal and adhere to the contracted design and schedule once awarded.

Any deviation must be approved by the Contracting Officer (CO).

iv. Work shall be performed during regularly scheduled facility hours (7:30am- 4pm; Mon. – Fri.). However, if facility personnel will be negatively impacted by the work, after hours and weekend work may be authorized. Any work performed by the Contractor outside of normal facility hours must be coordinated with the USGS TL at least 48 hours in advance.

v. Coordinate work with the USGS TL to ensure any facility research equipment or studies are not interrupted or disturbed. Contractor will be responsible for any work performed as part of this contract that causes damage to existing equipment or negatively impacts ongoing research.

vi. All materials shall be installed in accordance with manufacturer’s recommendations and installation instructions.

vii. Contractor shall provide equipment as the Government deems necessary to minimize debris in and around work areas.

viii. Contractor shall daily clean areas and cover surfaces or equipment impacted by construction work and remove any debris created by the demolition and/or installation from this project.

ix. Contractor shall ensure that no damage occurs to the surrounding buildings or equipment. Contractor shall be responsible for any repair costs due to damage to surrounding equipment, infrastructure or piping caused by construction or demolition as part of this project.

x. Contractor shall carry a minimum of $1,000,000 liability insurance against potential facility and/or equipment damage.

xi. Contractor shall gain approval from the TL prior to entry into other areas of the facility not directly related to this project scope. Entry into offices, mechanical/electrical spaces and or laboratories without permission from USGS TL is prohibited.

xii. Contractors shall notify the TL of any issues affecting project completion or delivery dates as soon as practical but no later than 24 hours.

xiii. The TL shall identify circuits designated for Contractor tools use as part of this project. Contractor shall be responsible for providing portable generators for equipment requiring more than 120 volts ac as needed for Contractor electrical equipment.

d. Project Completion Documentation:

i. Final Inspection and Acceptance Criteria

1. Upon successful completion of the installation and prior to the Final Acceptance, the Contractor shall ensure that there are no apparent defects in the boiler system, and all mechanical, electrical and controls are fully installed and operational. Contractor shall perform startup and checkout of new boilers and associated new equipment. Equipment startup shall be performed by a technician with at least 3 years’ experience in service and startup of hydronic heating equipment. Contractor shall notify TL in writing or email requesting a site inspection for the purpose of formal acceptance of the completed work.

2. The Contractor shall notify the TL in writing to request a Final Inspection and Acceptance Test no later than 45 business days after receipt of the Notice to Proceed. All aspects of the work shall have been evaluated by the Contractor and found to be correctly installed and ready for final evaluation prior to the Contractor requesting the inspection.

3. Contractor shall provide, as part of closeout documentation, boiler combustion report, scaled plans with venting, electrical and piping showing location and reference schematic of heating and control equipment, including but not limited to pipe sizes, mounting heights and electrical conduit runs. Drawings shall be provided to the Government in AUTOCAD 2019 format.

4. Contractor shall also include all operation and maintenance manuals for all installed equipment.

5. Acceptance by the Government will be given only after the satisfactory completion of the work as outlined in this Scope of Work. Project acceptance can be issued only by the project Contracting Officer (CO).

ii. Warranty Work and Service

1. The Contractor shall warranty all workmanship to meet the specifications set forth in this SOW. Additionally, the Contractor shall warranty all Contractor workmanship for a (minimum) period of 12 months from the date of Government acceptance.

e. Deliverables

i. Installation of system to be complete within 120 days of notice to proceed.

4. SUPPORTING INFORMATION

d. Place of Performance: UMESC; 2630 Fanta Reed Rd. La Crosse, WI. Segment

C Boiler Room

e. Period of Performance: 120 days from notice to proceed.

f. Government Furnished Property (GFP): None.

g. Special Considerations

i. None.

1. SELECTION CRITERIA

a. Contractor shall be selected based on Best Value in accordance with the FAR

15.101-1 according to the following criteria (in order of decreasing importance):

i. Past Experience: Contractor shall provide references of a minimum of three (3) projects within the past 5 years involving installation of hydronic heating systems in the state of Wisconsin. Projects provided for reference shall be at least $150,000 in dollar value and scope. The Government will evaluate this factor based on the relevance of the listed projects indicated. Relevant elements include:

1. Installation of hydronic boilers 1,000 MBTU or larger – include name of boiler manufacturers

2. Work performed in federal or state institutions

3. Past Performance Questionnaire from customer

ii. Qualifications: Contractor shall provide a listing of personnel who will perform the Work on-site. Listing shall include personnel trade education, installation work experience, experience with startup and service of hydronic heating systems, and number of years employed with the Contractor. Installer must be licensed in applicable trades in the State of Wisconsin is a minimum for this requirement. The Government will evaluate this factor based on the installation staff who shall be performing this work on site. Required elements include but are not limited to:

1. Active licensure as trade journeyman / apprentice in State of Wisconsin

2. Years of installation / service experience

3. Professional trade certifications (OSHA, NEC, NFPA, etc.)

4. Years employed by the Contractor.

iii. Project Plan: Contractor shall submit a project schedule outlining proposed schedule of installation. Contractor shall include products and manufacturers intended to be used for this project. Contractor shall include plan for integrating existing system into existing facility BAS. The Government will evaluate this factor based on the Contractors proposed outline of Work to be performed. Elements must include but not limited to:

1. Proposed schedule of work to be performed

2. Contractors plan for removal of existing boilers and venting, including equipment to be used.

3. Proposed new boilers / pumps

4. Details on proposed Contractor Team (electrical, mechanical, controls subcontractors)

iv. Price: Contractor shall submit pricing for the following:

1. Installation of boiler system as outlined in the Scope of Work.

Amendment of solicitation/modification of contract
Contract ID code
Amendment/modification number
Effective date
Requisition/purchase requisition number
Project number
Issued by
Code
Administered by
Code
Name and address of contractor
Code
Facility code
Amendment of solicitation number
Dated
Modification of contract/order number
Dated
This item only applies to amendments of solicitations
Accounting and appropriation data
This item applies only to modifications of contracts/orders.
This change order is issued pursuant to:
The above numbered contract/order is modified to reflect the administrative changes
This supplemental agreement is entered into pursuant to authority of:
Other
Important:
Description of amendment/modification
Name and title of signer
Contractor/offeror
Date signed
Name and title of contracting officer
Signature of Contracting Officer
Date signed
Previous edition unusable
Standard form 30 (rev. 11/2016)
Continuation sheet
Reference Number
Name of Offeror or Contractor
OPTIONAL FORM 336 (4-86))

Sponsored by GSA FAR (48 CFR) 53.110

File details come from the government source that posted it. Updated .