Request_for_Information_0001.pdf

PDF 12 MB Posted

Attached to
AK-KODIAK NWR-VC HEATING OIL TANK
Solicitation number
140FS125Q0034
Issued by

About this file

This is a Q&A document with associated equipment documentation and photos related to a heating oil tank replacement project at the Kodiak Fish and Wildlife Visitor Center. The Q&A addresses technical specifications, clarifying that a UL2085 tank certification is acceptable in place of the originally specified UL2080, and providing details about fill port requirements (5-gallon spill container) and suction tube specifications (3/4" pipe). The document also clarifies drawing submission requirements of one hard copy on 2'x3' paper and one electronic copy.

The accompanying photos and equipment data sheet show the existing 1,000-gallon double-wall fuel oil tank manufactured by Ace Tank of Seattle, WA and supplied by Ferguson Enterprises. The tank is located outside the building and serves as a fuel oil reservoir. Engineering drawings show detailed specifications including dimensions (8' length, 5' diameter), connection points, and construction requirements. The existing tank appears weathered with visible rust, housed in a wooden enclosure with access panels. The documentation indicates annual leak inspection is the only required maintenance for the tank system.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Request for Information Q&A’s

Questions Answers Tank spec F921 / UL 142 and UL 2080. (Can the

2080 be changed to 2085) I cannot find a company that has that stamp (2080) also the tank size is strangely odd at 1100g, typically all tanks are 500, 1000, 1500 etc.

Yes, a UL2085 is Acceptable

Fill and suction tubes? Is unclear please provide context.

Fill port should have one of those 5-gallon spill containers attached

Suction tube is just piped in, looks like maybe 3/4" pipe.

Provide 24” x 36” Is unclear please provide context.

This is in reference to the drawings requirement on the SOW "Provide one hard copy on 2’X3’ paper and one electronic copy"

Do you have drawings associated with the heating oil tank? (see below)

I have attached the drawings for the existing tank as well as some photos (see below)

I EQUIPMENT DATA SHEET

I'" I

Equipment Item: Fuel Oil Tank

Function: Fuel Oil Reservoir

Location: Outside of Building

Designation:

Project: Kodiak Fish and Wildlife Visitor Center

Mode] No.: I ,000 Gallon Double Wall Tank

Manufacturer Address and Phone:

• Ace Tank

6703 E. Marginal Way South Seattle, WA 981 08 206-281-5000

I Preventive Maintenance Tasks:

Maintenance Free - Inspect annually for leaks

Nameplate Data:

Spare Parts Furnished and Other Information:

Serial No.:

Supplier Address and Phone:

Ferguson Enterprises 1977 E. Bogard Rd Wasilla, Alaska 99654 907-376-8765

File details come from the government source that posted it. Updated .