Questions___Answers_0001.docx
DOCX document 13 KB Posted
- Attached to
- Repair of Cold Storage Bldg. Fergus Falls MN
- Solicitation number
- 140FC224Q0012
About this file
This document contains questions and answers regarding solicitation number 140FC224Q0012 for repair of a cold storage building in Fergus Falls, Minnesota issued by the Department of the Interior Fish and Wildlife Service. The solicitation requires sealing all twelve overhead and walk-in doors located in the building, as the statement of work applies to each door type. The correct measurements of the building are 66 feet by 166 feet, differing from the size stated in the original solicitation. Some pictures and draft drawings have been provided with the revised solicitation to supplement the requirements.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Bldg_Picture_1_0001.png | PNG image | |
| SOW_Cold_Storage_Building_Roof_Repair_v3_0001.docx | DOCX document | |
| Bldg_Picture_2_0001.png | PNG image | |
| Building_Drawings_0001.pdf | ||
| Sol_140FC224Q0012_Amd_0001.pdf | ||
| Wage_Determination_MN20220090.pdf | ||
| SOW_Cold_Storage_Builidng_Roof_Repair_v2.docx | DOCX document | |
| Provisions_and_Clauses.pdf | ||
| Sol_140FC224Q0012.pdf | ||
| Construction_Contract_Administration.docx | DOCX document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
The following questions were received for the solicitation:
1. The SOW calls for the contractor to seal the doors in the top corners, are we talking about the (4) walk doors as well as the (8) overhead doors or just the (4) walk doors?
A: Overhead and walk doors must be sealed, this means the SOW requirement is for all 12 doors.
2. Is the size of the building correct in the SOW? Field measurements differ from those stated.
A: SOW has been corrected to show correct measurements of 66’ by 166’.
3. Request for pictures, drawings, and measurements.
A: Some pictures are now included with the solicitation, and we are attaching draft drawings available.