B08_Solicitation_Attachment__4_Summit_Environmental_-_Indoor_Air_Quality_Investigation_and_Mold_Report_0001.pdf

PDF 5 MB Posted

Attached to
KY- Green River NWR Deconstruction and Mold Remed.
Solicitation number
140FC126Q0009
Issued by

About this file

This is an Indoor Air Quality Investigation Report prepared by Summit Environmental Services, Inc. for the U.S. Fish and Wildlife Service at their facility located at 10847 Green River Road #2 in Spotsville, Kentucky, dated June 10, 2025. The investigation was conducted in response to occupant complaints regarding possible indoor mold issues stemming from previous water intrusion events. Six non-viable air samples were collected from various interior locations (second floor southwest and northeast bedrooms, living room, and first floor near stairs) plus one exterior comparison sample, along with three surface tape samples from suspect materials including a hot water heater room ceiling, exposed blue Styrofoam wall insulation, and restroom shower fiberglass insulation. Laboratory analysis by Environmental Hazards Services (EHS) detected elevated levels of Penicillium/Aspergillus group spores in all five interior air samples compared to the exterior baseline, with total spore counts ranging from 1,400 to 18,000 spores/m³. Specific mold spores identified in surface samples included Chaetomium, Trichoderma, Penicillium conidiophores, and Stachybotrys species.

Based on the analytical results and visual observations indicating elevated moisture levels (>15%) in first-floor baseplate areas and shower zones, the report recommends that a Professional Mold Remediation Company (PMRC) properly clean all surfaces and contents on both floors using HEPA vacuums and EPA-approved antimicrobial solutions while employing negative pressure enclosure protocols and respiratory protection for workers. Additional recommendations include disposing of loose drywall on the first floor before cleaning, utilizing dehumidifiers to dry all baseplates in the shower area and along the west wall, and properly cleaning the HVAC system. The report emphasizes that mold spore conditions are contingent upon building conditions and climate, with results valid only for the date collected. All laboratory work was conducted using direct light microscopy methods under AIHA LAP accreditation, with sample analysis and chain-of-custody documentation provided in appendices.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

927457-1 2nd floor – Center of southwest bedroom

927457-2 2nd floor – Center of living room

927457-3 2nd floor – Center of northeast (master) bedroom

927457-4 1st floor – Bottom of stairs – East

927457-5 1st floor – Back of stairs – West

927457-6 Outside – South of building – On sidewalk

927457-7 1st floor – Hot water heater room – Black stain on ceiling

927457-8 1st floor – On exposed blue Styrofoam wall insulaiton

927457-9 1st floor – Restroom –

Shower area – Stain on fiberglass insulation

1st floor – West wall – On exposed baseplate

1st floor – Restroom – Baseplate around shower

1st floor – Restroom – Baseplate around shower