This document contains an analytical report and quality control summary from a laboratory analyzing drinking water samples for synthetic organic chemicals. The report provides results for samples from two wells (Well 646 and Well 647) taken for a client of the Division of Environmental, Cultural and Safety Management. Analysis was conducted for EPA methods 504.1, 300.0, 525.2, 531.2, 515.4, 548.1, and 549.2. No analytes were detected above reporting limits in any samples. Method blanks, laboratory control samples, and laboratory control sample duplicates met acceptance criteria. Sample receipt temperatures and holding times were compliant.

View the file

Other files

Show all 16

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

December 29, 2021

Division of Env. Cultural & Safety Mgmt.

Genevieve Henry

Dear Genevieve Henry:

RE: 093534005 ChiChiltah BS OrderNo.: 2111931

FAX: (505) 863-8369

TEL: (505) 863-8330

PO Box 1060 Room 130

Gallup, NM 87305

Hall Environmental Analysis Laboratory

4901 Hawkins NE

Albuquerque, NM 87109

Website: clients.hallenvironmental.com

TEL: 505-345-3975 FAX: 505-345-4107

Hall Environmental Analysis Laboratory received 2 sample(s) on 11/18/2021 for the analyses presented in the following report.

Andy Freeman

These were analyzed according to EPA procedures or equivalent. To access our accredited tests please go to www.hallenvironmental.com or the state specific web sites.

In order to properly interpret your results, it is imperative that you review this report in its entirety. See the sample checklist and/or the Chain of Custody for information regarding the sample receipt temperature and preservation. Data qualifiers or a narrative will be provided if the sample analysis or analytical quality control parameters require a flag.

When necessary, data qualifiers are provided on both the sample analysis report and the

QC summary report, both sections should be reviewed. All samples are reported, as received, unless otherwise indicated. Lab measurement of analytes considered field parameters that require analysis within 15 minutes of sampling such as pH and residual chlorine are qualified as being analyzed outside of the recommended holding time.

Please don't hesitate to contact HEAL for any additional information or clarifications.

ADHS Cert #AZ0682 -- NMED-DWB Cert #NM9425 -- NMED-Micro Cert #NM0901

Sincerely, Laboratory Manager

4901 Hawkins NE

Albuquerque, NM 87109

Location:

Matrix: Aqueous

Collection Date: 11/17/2021 11:30:00 AMFacility: 093534005

Analyses Result Qual Units

CLIENT: Division of Env. Cultural & Safety

Lab ID: 2111931-001

Client Sample ID: Well 646

12/29/2021

Analytical Report

2111931

Date Reported:

Lab Order:

Received Date: 11/18/2021 10:53:00 AM

Compliance Safe:

RL MCL DF

Hall Environmental Analysis Laboratory, Inc.

EPA METHOD 504.1: EDB/DBCP Analyst: JME

SDWIS Date Analyzed

1,2-Dibromo-3-chloropropane 11/22/2021 10:40:49 P0.019 µg/L 10.20ND2931

1,2-Dibromoethane 11/22/2021 10:40:49 P0.0095 µg/L 10.050ND2946

NOTES:

No trip blank was included with work order

EPA METHOD 300.0: ANIONS Analyst: CAS

SDWIS Date Analyzed

Nitrogen, Nitrite (As N) 11/18/2021 7:50:33 PM0.10 mg/L 11.0ND1041

Nitrogen, Nitrate (As N) 11/18/2021 7:50:33 PM0.10 mg/L 110ND1037

Qualifiers:

* Value exceeds Maximum Contaminant Level. B Analyte detected in the associated Method Blank

D Sample Diluted Due to Matrix E Estimated value

H Holding times for preparation or analysis exceeded J Analyte detected below quantitation limits

ND Not Detected at the Reporting Limit P Sample pH Not In Range

PQL Practical Quanitative Limit RL Reporting Limit

S % Recovery outside of range due to dilution or matrix interference

Location:

Matrix: Aqueous

Collection Date: 11/17/2021 10:50:00 AMFacility: 093534005

Analyses Result Qual Units

CLIENT: Division of Env. Cultural & Safety

Lab ID: 2111931-002

Client Sample ID: Well 647

12/29/2021

Analytical Report

2111931

Date Reported:

Lab Order:

Received Date: 11/18/2021 10:53:00 AM

Compliance Safe:

RL MCL DF

Hall Environmental Analysis Laboratory, Inc.

EPA METHOD 504.1: EDB/DBCP Analyst: JME

SDWIS Date Analyzed

1,2-Dibromo-3-chloropropane 11/22/2021 10:55:40 P0.019 µg/L 10.20ND2931

1,2-Dibromoethane 11/22/2021 10:55:40 P0.0093 µg/L 10.050ND2946

NOTES:

No trip blank was included with work order

EPA METHOD 300.0: ANIONS Analyst: CAS

SDWIS Date Analyzed

Nitrogen, Nitrite (As N) 11/18/2021 8:15:23 PM0.10 mg/L 11.0ND1041

Nitrogen, Nitrate (As N) 11/18/2021 8:15:23 PM0.10 mg/L 110ND1037

Qualifiers:

* Value exceeds Maximum Contaminant Level. B Analyte detected in the associated Method Blank

D Sample Diluted Due to Matrix E Estimated value

H Holding times for preparation or analysis exceeded J Analyte detected below quantitation limits

ND Not Detected at the Reporting Limit P Sample pH Not In Range

Anatek Labs, Inc.

1282 Alturas Drive - Moscow, ID 83843 - (208) 883-2839 - Fax (208) 8829246 - email moscow@anateklabs.com

504 E Sprague Ste. D - Spokane, WA 99202 - (509) 838-3999 - fax (509) 838-4433 - email spokane@anateklabs.com

Date Received:

Lab/Sample Number: MBK0644-01

Collect Date:

Lab Federal ID#:

Compliance Sample:

Sample Type:

Date Reported by Lab:

PWS#: PWS Name:

Replacement Sample:

Collection Time: 11:3011/17/2021

Hall Environmental Analysis Lab

12/23/202111/19/2021

See Below

Sample Point/ Location: 2111931-001C (Well 646) Tag#/Facility ID:

Contact Name: Andy Freeman Contact Phone: See Signature Page

ID00013Lab Federal ID#:

Public Drinking Water System Analysis Report

Synthetic Organic Chemical (SOC) Analysis Report:

QualifierMethodAnalystAnalyzedMRLMCLUnitsResultAnalyteFRDS

EPA 54711/24/21 4:07 BKP7002034 5.00Glyphosate ug/LND

EPA 50511/24/21 2:30 GPB22005 0.0100Endrin ug/LND

EPA 50511/24/21 2:30 GPB0.22010 0.0200Lindane (BHC-Gamma) ug/LND

EPA 50511/24/21 2:30 GPB402015 0.100Methoxychlor ug/LND

EPA 50511/24/21 2:30 GPB32020 1.00Toxaphene ug/LND

EPA 50511/24/21 2:30 GPB0.42065 0.0400Heptachlor ug/LND

EPA 50511/24/21 2:30 GPB0.22067 0.0200Heptachlor epoxide ug/LND

EPA 50511/24/21 2:30 GPB0.52383 0.500PCBs ug/LND

EPA 50511/24/21 2:30 GPB22959 0.200Chlordane ug/LND

1282 Alturas Drive - Moscow, ID 83843 - (208) 883-2839 - Fax (208) 8829246 - email moscow@anateklabs.com

504 E Sprague Ste. D - Spokane, WA 99202 - (509) 838-3999 - fax (509) 838-4433 - email spokane@anateklabs.com

Date Received:

Lab/Sample Number: MBK0644-02

Collect Date:

Lab Federal ID#:

Compliance Sample:

Sample Type:

Date Reported by Lab:

PWS#: PWS Name:

Replacement Sample:

Collection Time: 11:3011/17/2021

Hall Environmental Analysis Lab

12/23/202111/19/2021

See Below

Sample Point/ Location: 2111931-001D (Well 646) Tag#/Facility ID:

Contact Name: Andy Freeman Contact Phone: See Signature Page

ID00013Lab Federal ID#:

Public Drinking Water System Analysis Report

Synthetic Organic Chemical (SOC) Analysis Report:

QualifierMethodAnalystAnalyzedMRLMCLUnitsResultAnalyteFRDS

EPA 531.212/2/21 20:18 BKP2002036 2.00Oxamyl (Vydate) ug/LND

EPA 531.212/2/21 20:18 BKP402046 0.900Carbofuran ug/LND

1282 Alturas Drive - Moscow, ID 83843 - (208) 883-2839 - Fax (208) 8829246 - email moscow@anateklabs.com

504 E Sprague Ste. D - Spokane, WA 99202 - (509) 838-3999 - fax (509) 838-4433 - email spokane@anateklabs.com

Date Received:

Lab/Sample Number: MBK0644-03

Collect Date:

Lab Federal ID#:

Compliance Sample:

Sample Type:

Date Reported by Lab:

PWS#: PWS Name:

Replacement Sample:

Collection Time: 11:3011/17/2021

Hall Environmental Analysis Lab

12/23/202111/19/2021

See Below

Sample Point/ Location: 2111931-001E (Well 646) Tag#/Facility ID:

Contact Name: Andy Freeman Contact Phone: See Signature Page

ID00013Lab Federal ID#:

Public Drinking Water System Analysis Report

Synthetic Organic Chemical (SOC) Analysis Report:

QualifierMethodAnalystAnalyzedMRLMCLUnitsResultAnalyteFRDS

EPA 525.212/3/21 23:31 BMM4002035 0.600Di(2-ethylhexyl)adipate ug/LND

EPA 525.212/3/21 23:31 BMM42037 0.0700Simazine ug/LND

EPA 525.212/3/21 23:31 BMM62039 0.600Di(2-ethylhexl)phthalate ug/LND

EPA 525.212/3/21 23:31 BMM502042 0.100Hexachlorocyclopentadiene ug/LND

EPA 525.212/3/21 23:31 BMM32050 0.100Atrazine ug/LND

EPA 525.212/3/21 23:31 BMM22051 0.200Alachlor (Lasso) ug/LND

EPA 525.212/3/21 23:31 BMM12274 0.100Hexachlorobenzene ug/LND

EPA 525.212/3/21 23:31 BMM0.22306 0.0200Benzo[a]pyrene ug/LND

1282 Alturas Drive - Moscow, ID 83843 - (208) 883-2839 - Fax (208) 8829246 - email moscow@anateklabs.com

504 E Sprague Ste. D - Spokane, WA 99202 - (509) 838-3999 - fax (509) 838-4433 - email spokane@anateklabs.com

Date Received:

Lab/Sample Number: MBK0644-04

Collect Date:

Lab Federal ID#:

Compliance Sample:

Sample Type:

Date Reported by Lab:

PWS#: PWS Name:

Replacement Sample:

Collection Time: 11:3011/17/2021

Hall Environmental Analysis Lab

12/23/202111/19/2021

See Below

Sample Point/ Location: 2111931-001F (Well 646) Tag#/Facility ID:

Contact Name: Andy Freeman Contact Phone: See Signature Page

ID00013Lab Federal ID#:

Public Drinking Water System Analysis Report

Synthetic Organic Chemical (SOC) Analysis Report:

QualifierMethodAnalystAnalyzedMRLMCLUnitsResultAnalyteFRDS

EPA 548.112/2/21 12:07 GPB1002033 9.00Endothall ug/LND

EPA 515.411/30/21 20:16 SAT2002031 1.00Dalapon ug/LND

EPA 515.411/30/21 20:16 SAT5002040 0.100Picloram ug/LND

EPA 515.411/30/21 20:16 SAT72041 0.200Dinoseb ug/LND

EPA 515.411/30/21 20:16 SAT702105 0.1002,4-D ug/LND

EPA 515.411/30/21 20:16 SAT502110 0.2002,4,5-TP (Silvex) ug/LND

EPA 515.411/30/21 20:16 SAT12326 0.0400Pentachlorophenol ug/LND

1282 Alturas Drive - Moscow, ID 83843 - (208) 883-2839 - Fax (208) 8829246 - email moscow@anateklabs.com

504 E Sprague Ste. D - Spokane, WA 99202 - (509) 838-3999 - fax (509) 838-4433 - email spokane@anateklabs.com

Date Received:

Lab/Sample Number: MBK0644-05

Collect Date:

Lab Federal ID#:

Compliance Sample:

Sample Type:

Date Reported by Lab:

PWS#: PWS Name:

Replacement Sample:

Collection Time: 11:3011/16/2021

Hall Environmental Analysis Lab

12/23/202111/19/2021

See Below

Sample Point/ Location: 2111931-001G (Well 646) Tag#/Facility ID:

Contact Name: Andy Freeman Contact Phone: See Signature Page

ID00013Lab Federal ID#:

Public Drinking Water System Analysis Report

Synthetic Organic Chemical (SOC) Analysis Report:

QualifierMethodAnalystAnalyzedMRLMCLUnitsResultAnalyteFRDS

EPA 549.211/30/21 19:30 taz202032 0.400Diquat ug/LND

1282 Alturas Drive - Moscow, ID 83843 - (208) 883-2839 - Fax (208) 8829246 - email moscow@anateklabs.com

504 E Sprague Ste. D - Spokane, WA 99202 - (509) 838-3999 - fax (509) 838-4433 - email spokane@anateklabs.com

Date Received:

Lab/Sample Number: MBK0644-06

Collect Date:

Lab Federal ID#:

Compliance Sample:

Sample Type:

Date Reported by Lab:

PWS#: PWS Name:

Replacement Sample:

Collection Time: 10:5011/17/2021

Hall Environmental Analysis Lab

12/23/202111/19/2021

See Below

Sample Point/ Location: 2111931-002C (Well 647) Tag#/Facility ID:

Contact Name: Andy Freeman Contact Phone: See Signature Page

ID00013Lab Federal ID#:

Public Drinking Water System Analysis Report

Synthetic Organic Chemical (SOC) Analysis Report:

QualifierMethodAnalystAnalyzedMRLMCLUnitsResultAnalyteFRDS

EPA 54711/24/21 4:32 BKP7002034 5.00Glyphosate ug/LND

EPA 50511/24/21 2:52 GPB22005 0.0100Endrin ug/LND

EPA 50511/24/21 2:52 GPB0.22010 0.0200Lindane (BHC-Gamma) ug/LND

EPA 50511/24/21 2:52 GPB402015 0.100Methoxychlor ug/LND

EPA 50511/24/21 2:52 GPB32020 1.00Toxaphene ug/LND

EPA 50511/24/21 2:52 GPB0.42065 0.0400Heptachlor ug/LND

EPA 50511/24/21 2:52 GPB0.22067 0.0200Heptachlor epoxide ug/LND

EPA 50511/24/21 2:52 GPB0.52383 0.500PCBs ug/LND

EPA 50511/24/21 2:52 GPB22959 0.200Chlordane ug/LND

1282 Alturas Drive - Moscow, ID 83843 - (208) 883-2839 - Fax (208) 8829246 - email moscow@anateklabs.com

504 E Sprague Ste. D - Spokane, WA 99202 - (509) 838-3999 - fax (509) 838-4433 - email spokane@anateklabs.com

Date Received:

Lab/Sample Number: MBK0644-07

Collect Date:

Lab Federal ID#:

Compliance Sample:

Sample Type:

Date Reported by Lab:

PWS#: PWS Name:

Replacement Sample:

Collection Time: 10:5011/17/2021

Hall Environmental Analysis Lab

12/23/202111/19/2021

See Below

Sample Point/ Location: 2111931-002D (Well 647) Tag#/Facility ID:

Contact Name: Andy Freeman Contact Phone: See Signature Page

ID00013Lab Federal ID#:

Public Drinking Water System Analysis Report

Synthetic Organic Chemical (SOC) Analysis Report:

QualifierMethodAnalystAnalyzedMRLMCLUnitsResultAnalyteFRDS

EPA 531.212/2/21 21:13 BKP2002036 2.00Oxamyl (Vydate) ug/LND

EPA 531.212/2/21 21:13 BKP402046 0.900Carbofuran ug/LND

1282 Alturas Drive - Moscow, ID 83843 - (208) 883-2839 - Fax (208) 8829246 - email moscow@anateklabs.com

504 E Sprague Ste. D - Spokane, WA 99202 - (509) 838-3999 - fax (509) 838-4433 - email spokane@anateklabs.com

Date Received:

Lab/Sample Number: MBK0644-08

Collect Date:

Lab Federal ID#:

Compliance Sample:

Sample Type:

Date Reported by Lab:

PWS#: PWS Name:

Replacement Sample:

Collection Time: 10:5011/17/2021

Hall Environmental Analysis Lab

12/23/202111/19/2021

See Below

Sample Point/ Location: 2111931-002E (Well 647) Tag#/Facility ID:

Contact Name: Andy Freeman Contact Phone: See Signature Page

ID00013Lab Federal ID#:

Public Drinking Water System Analysis Report

Synthetic Organic Chemical (SOC) Analysis Report:

QualifierMethodAnalystAnalyzedMRLMCLUnitsResultAnalyteFRDS

EPA 525.212/4/21 0:06 BMM4002035 0.600Di(2-ethylhexyl)adipate ug/LND

EPA 525.212/4/21 0:06 BMM42037 0.0700Simazine ug/LND

EPA 525.212/4/21 0:06 BMM62039 0.600Di(2-ethylhexl)phthalate ug/LND

EPA 525.212/4/21 0:06 BMM502042 0.100Hexachlorocyclopentadiene ug/LND

EPA 525.212/4/21 0:06 BMM32050 0.100Atrazine ug/LND

EPA 525.212/4/21 0:06 BMM22051 0.200Alachlor (Lasso) ug/LND

EPA 525.212/4/21 0:06 BMM12274 0.100Hexachlorobenzene ug/LND

EPA 525.212/4/21 0:06 BMM0.22306 0.0200Benzo[a]pyrene ug/LND

1282 Alturas Drive - Moscow, ID 83843 - (208) 883-2839 - Fax (208) 8829246 - email moscow@anateklabs.com

504 E Sprague Ste. D - Spokane, WA 99202 - (509) 838-3999 - fax (509) 838-4433 - email spokane@anateklabs.com

Date Received:

Lab/Sample Number: MBK0644-09

Collect Date:

Lab Federal ID#:

Compliance Sample:

Sample Type:

Date Reported by Lab:

PWS#: PWS Name:

Replacement Sample:

Collection Time: 10:5011/17/2021

Hall Environmental Analysis Lab

12/23/202111/19/2021

See Below

Sample Point/ Location: 2111931-002F (Well 647) Tag#/Facility ID:

Contact Name: Andy Freeman Contact Phone: See Signature Page

ID00013Lab Federal ID#:

Public Drinking Water System Analysis Report

Synthetic Organic Chemical (SOC) Analysis Report:

QualifierMethodAnalystAnalyzedMRLMCLUnitsResultAnalyteFRDS

EPA 548.112/2/21 12:25 GPB1002033 9.00Endothall ug/LND

EPA 515.411/30/21 20:48 SAT2002031 1.00Dalapon ug/LND

EPA 515.411/30/21 20:48 SAT5002040 0.100Picloram ug/LND

EPA 515.411/30/21 20:48 SAT72041 0.200Dinoseb ug/LND

EPA 515.411/30/21 20:48 SAT702105 0.1002,4-D ug/LND

EPA 515.411/30/21 20:48 SAT502110 0.2002,4,5-TP (Silvex) ug/LND

EPA 515.411/30/21 20:48 SAT12326 0.0400Pentachlorophenol ug/LND

1282 Alturas Drive - Moscow, ID 83843 - (208) 883-2839 - Fax (208) 8829246 - email moscow@anateklabs.com

504 E Sprague Ste. D - Spokane, WA 99202 - (509) 838-3999 - fax (509) 838-4433 - email spokane@anateklabs.com

Date Received:

Lab/Sample Number: MBK0644-10

Collect Date:

Lab Federal ID#:

Compliance Sample:

Sample Type:

Date Reported by Lab:

PWS#: PWS Name:

Replacement Sample:

Collection Time: 10:5011/17/2021

Hall Environmental Analysis Lab

12/23/202111/19/2021

See Below

Sample Point/ Location: 2111931-002G (Well 647) Tag#/Facility ID:

Contact Name: Andy Freeman Contact Phone: See Signature Page

ID00013Lab Federal ID#:

Public Drinking Water System Analysis Report

Synthetic Organic Chemical (SOC) Analysis Report:

QualifierMethodAnalystAnalyzedMRLMCLUnitsResultAnalyteFRDS

EPA 549.211/30/21 19:36 taz202032 0.400Diquat ug/LND

[TOC_1]Quality Assurance

Results[TOC] Authorized Signature, Justin Doty For Todd Taruscio, Laboratory Manager

Hall Environmental Analysis Lab

Albuquerque,NM 87109

Andy Freeman

4901 Hawkins NE Suite D

505-345-3975

The associated blank spike recovery was above laboratory/method acceptance limits. This analyte was not detected in the sample

L5

Matrix spike recovery was high due to a potential matrix effect.M13

Spike recovery value is unusable. Analyte concentration disproportionate to the spike level. Blank spike recovery acceptable.

M3

LFB/LFBD RPD exceeded the laboratory acceptance limit. Recovery met acceptance criteria.R7

PQL Practical Quantitation Limit

ND Not Detected

MCL EPA's Maximum Contaminant Level

Dry Sample results reported on a dry weight basis

* Not a certified analyte

RPD Relative Percent Difference

%REC Percent Recovery

Source Sample that was spiked or duplicated.

This report shall not be reproduced except in full, without the written approval of the laboratory

The results reported related only to the samples indicated.

STAMP_DATE_HERE

Mr. Andy Freeman Hall Environmental 4901 Hawkins NE Suite D Albuquerque, New Mexico 87109

Re: Routine Analysis Work Order: 19090

SDG: 2111931

Dear Mr. Freeman:

Cape Fear Analytical LLC (CFA) appreciates the opportunity to provide the enclosed analytical results for the sample(s) we received on November 19, 2021. This original data report has been prepared and reviewed in accordance with CFA’s standard operating procedures.

Our policy is to provide high quality, personalized analytical services to enable you to meet your analytical needs on time every time. We trust that you will find everything in order and to your satisfaction. If you have any questions, please do not hesitate to call me at 910-795-0421.

Sincerely, Cynde Larkins Project Manager

Purchase Order: IDIQ Pricing Enclosures

December 17, 2021

Page 1 of 20 Work Order: 19090

Page 2 of 20 Work Order: 19090

Page 3 of 20 Work Order: 19090

High Resolution Dioxins and Furans Analysis

Page 4 of 20 Work Order: 19090

Case Narrative

Page 5 of 20 Work Order: 19090

HDOX Case Narrative Hall Environmental Analysis Laboratory (HALL)

SDG 2111931

Work Order 19090

Method/Analysis Information

Product: TCDD Only by EPA Method 1613B in Liquids Analytical Method: EPA Method 1613B Extraction Method: SW846 3520C Analytical Batch Number: 48612 Clean Up Batch Number: 48610 Extraction Batch Number: 48609

Sample Analysis Samples were received at 5.5°C.

The following samples were analyzed using the analytical protocol as established in EPA Method 1613B:

Sample ID Client ID 12030841 Method Blank (MB) 12030842 Laboratory Control Sample (LCS) 12030843 Laboratory Control Sample Duplicate (LCSD) 19090001 2111931-001H Well 646 19090002 2111931-002H Well 647

The samples in this SDG were analyzed on an "as received" basis.

SOP Reference Procedure for preparation, analysis and reporting of analytical data are controlled by Cape Fear Analytical LLC (CFA) as Standard Operating Procedure (SOP). The data discussed in this narrative has been analyzed in accordance with CF-OA-E-002 REV# 20.

Raw data reports are processed and reviewed by the analyst using the TargetLynx software package.

Calibration Information

Initial Calibration All initial calibration requirements have been met for this sample delivery group (SDG).

Page 6 of 20 Work Order: 19090

Continuing Calibration Verification (CCV) Requirements All associated calibration verification standard(s) (CVS) met the acceptance criteria.

Quality Control (QC) Information

Certification Statement The test results presented in this document are certified to meet all requirements of the 2009 TNI Standard.

Method Blank (MB) Statement The MB(s) analyzed with this SDG met the acceptance criteria.

Surrogate Recoveries All surrogate recoveries were within the established acceptance criteria for this SDG.

Laboratory Control Sample (LCS) Recovery The LCS spike recoveries met the acceptance limits.

Laboratory Control Sample Duplicate (LCSD) Recovery The LCSD spike recoveries met the acceptance limits.

LCS/LCSD Relative Percent Difference (RPD) Statement The RPD(s) between the LCS and LCSD met the acceptance limits.

QC Sample Designation A matrix spike and matrix spike duplicate analysis was not required for this SDG.

Technical Information

Receipt Temperature Samples were received within temperature requirements.

Holding Time Specifications CFA assigns holding times based on the associated methodology, which assigns the date and time from sample collection. Those holding times expressed in hours are calculated in the AlphaLIMS system. Those holding times expressed as days expire at midnight on the day of expiration. All samples in this SDG met the specified holding time.

Preparation/Analytical Method Verification All procedures were performed as stated in the SOP.

Sample Dilutions The samples in this SDG did not require dilutions.

Sample Re-extraction/Re-analysis Re-extractions or re-analyses were not required in this SDG.

Page 7 of 20 Work Order: 19090

Miscellaneous Information

Manual Integrations Certain standards and QC samples required manual integrations to correctly position the baseline as set in the calibration standard injections. Where manual integrations were performed, copies of all manual integration peak profiles are included in the raw data section of this fraction.

Manual integrations were required for data files in this SDG.

System Configuration This analysis was performed on the following instrument configuration:

Instrument ID Instrument System

Configuration Column

ID Column Description

HRP763_1 Primary Dioxin Analysis Dioxin Analysis DB-5MS 60m x 0.25mm, 0.25um

Page 8 of 20 Work Order: 19090

Sample Data Summary

Page 9 of 20 Work Order: 19090

Cape Fear Analytical, LLC 3306 Kitty Hawk Road Suite 120, Wilmington, NC 28405 - (910) 795-0421 - www.capefearanalytical.com

Certificate of Analysis Report

HALL001 Hall Environmental Analysis Laboratory

Client SDG: 2111931 CFA Work Order: 19090

Cape Fear Analytical requires all analytical data to be verified by a qualified data reviewer.

The following data validator verified the information presented in this case narrative:

The Qualifiers in this report are defined as follows:

* A quality control analyte recovery is outside of specified acceptance criteria ** Analyte is a surrogate compound U Analyte was analyzed for, but not detected above the specified detection limit.

for

Signature: Name:

Date: Title:17 DEC 2021

Erin Suhrie

Data Validator

Review/Validation

Page 10 of 20 Work Order: 19090

Cape Fear Analytical LLC

Hi-Res Dioxins/Furans Certificate of Analysis

Sample Summary

December 17, 2021Report Date:

SDG Number: 2111931 Lab Sample ID: 19090001 Matrix: WATER

Date Received: 11/19/2021 10:50 Date Collected: 11/17/2021 11:30

Surrogate/Tracer recovery Recovery% Acceptable Limits

3.75U 3.75

Client: HALL001 Project: HALL00113

13C-2,3,7,8-TCDD

37Cl-2,3,7,8-TCDD

63.5

70.7

(31%-137%)

(42%-164%)

CAS No. Parmname ResultQual

Method: EPA Method 1613BBatch ID: 48612 Instrument: HRP763

Run Date: 12/15/2021 20:17 Analyst: MLL

Units pg/L

2111931-001H Well 646

1613B TCDD Water

Client ID:

Prep Date: Prep Aliquot:14-DEC-21 919.1 mL

Result Nominal pg/L pg/L

48609 SW846 3520C

As Received

Prep Method:

Prep Basis:

MDL

Dilution:

Comments:

U Analyte was analyzed for, but not detected above the specified detection limit.

Prep Batch:

b15dec21a-8Data File:

2,3,7,8-TCDD1746-01-6

Client Sample:

UnitsQual

PQL

10.9

Page 11 of 20 Work Order: 19090

Certificate of Analysis

Sample Summary

December 17, 2021Report Date:

SDG Number: 2111931 Lab Sample ID: 19090002 Matrix: WATER

Date Received: 11/19/2021 10:50 Date Collected: 11/17/2021 10:50

Surrogate/Tracer recovery Recovery% Acceptable Limits

3.63U 3.63

Client: HALL001 Project: HALL00113

13C-2,3,7,8-TCDD

37Cl-2,3,7,8-TCDD

59.5

65.1

(31%-137%)

(42%-164%)

CAS No. Parmname ResultQual

Method: EPA Method 1613BBatch ID: 48612 Instrument: HRP763

Run Date: 12/15/2021 21:07 Analyst: MLL

2111931-002H Well 647

1613B TCDD Water

Client ID:

Prep Date: Prep Aliquot:14-DEC-21 949.7 mL

Result Nominal pg/L pg/L

48609 SW846 3520C

As Received

Prep Method:

Prep Basis:

MDL

Dilution:

Comments:

U Analyte was analyzed for, but not detected above the specified detection limit.

Prep Batch:

b15dec21a-9Data File:

2,3,7,8-TCDD1746-01-6

Client Sample:

UnitsQual

PQL

10.5

Page 12 of 20 Work Order: 19090

Quality Control Summary

Page 13 of 20 Work Order: 19090

Surrogate Recovery Report Hi-Res Dioxins/Furans

Report Date: December 17, 2021

SDG Number: 2111931

Matrix Type: LIQUID

Surrogate Acceptance

Limits

67.7 73.0

71.9 73.5

69.1 74.8

63.5 70.7

59.5 65.1

12030842

12030843

12030841

19090001

19090002

Sample ID Client ID

LCS for batch 48609

LCSD for batch 48609

MB for batch 48609

2111931-001H Well 646

2111931-002H Well 647

(25%-141%) (37%-158%)

(25%-141%) (37%-158%)

(31%-137%) (42%-164%)

(31%-137%) (42%-164%)

(31%-137%) (42%-164%)

* Recovery outside Acceptance Limits # Column to be used to flag recovery values D Sample Diluted

Recovery

13C-2,3,7,8-TCDD

37Cl-2,3,7,8-TCDD

13C-2,3,7,8-TCDD

37Cl-2,3,7,8-TCDD

13C-2,3,7,8-TCDD

37Cl-2,3,7,8-TCDD

13C-2,3,7,8-TCDD

37Cl-2,3,7,8-TCDD

13C-2,3,7,8-TCDD

37Cl-2,3,7,8-TCDD

QUAL

Page 14 of 20 Work Order: 19090

Quality Control Summary Spike Recovery Report

Hi-Res Dioxins/Furans

Report Date: December 17, 2021

SDG Number: 2111931

Client ID: LCS for batch 48609

Lab Sample ID: 12030842

Matrix: WATER

Sample Type: Laboratory Control Sample

1746-01-6 2,3,7,8-TCDD 73-14682.6200 165LCS

CAS No. Parmname Acceptance

Limits Recovery

Amount Added pg/L

Spike Conc.

pg/L

Instrument: HRP763 Analyst: MLL

Analysis Date:

Prep Batch ID:

Batch ID:

12/15/2021 15:18

48612

Dilution: 1

48609

Page 15 of 20 Work Order: 19090

Quality Control Summary Spike Recovery Report

Hi-Res Dioxins/Furans

Report Date: December 17, 2021

SDG Number: 2111931

Client ID: LCSD for batch 48609

Lab Sample ID: 12030843

Matrix: WATER

Sample Type: Laboratory Control Sample Duplicate

1746-01-6 2,3,7,8-TCDD 73-14686.2200 172 0-204.32LCSD

CAS No. Parmname Acceptance

Limits Recovery

Amount Added pg/L

Spike Conc. Acceptance

Limits

RPD

pg/L

Instrument: HRP763 Analyst: MLL

Analysis Date:

Prep Batch ID:

Batch ID:

12/15/2021 16:08

48612

Dilution: 1

48609

Page 16 of 20 Work Order: 19090

Method Blank Summary

December 17, 2021Report Date:

SDG Number: 2111931 Client ID: MB for batch 48609

Lab Sample ID: 12030841

Matrix: WATERClient: HALL001

Client Sample ID Lab Sample ID File ID Date Analyzed LCS for batch 48609

LCSD for batch 48609

2111931-001H Well 646

2111931-002H Well 647

12/15/21

12/15/21

12/15/21

12/15/21 b15dec21a-2 b15dec21a-3 b15dec21a-8 b15dec21a-9

This method blank applies to the following samples and quality control samples:

Analyzed: 12/15/21 16:58Prep Date: 14-DEC-21

Data File: b15dec21a-4

Time Analyzed

12030842

12030843

19090001

19090002

Instrument ID: HRP763

Column:

Page 17 of 20 Work Order: 19090

Certificate of Analysis

Sample Summary

December 17, 2021Report Date:

SDG Number: 2111931 Lab Sample ID: 12030841 Matrix: WATER

Surrogate/Tracer recovery Recovery% Acceptable Limits

3.45U 3.45

Client: HALL001 Project: HALL00113

13C-2,3,7,8-TCDD

37Cl-2,3,7,8-TCDD

69.1

74.8

(31%-137%)

(42%-164%)

CAS No. Parmname ResultQual

Method: EPA Method 1613BBatch ID: 48612 Instrument: HRP763

Run Date: 12/15/2021 16:58 Analyst: MLL

MB for batch 48609

QC for batch 48609

Client ID:

Prep Date: Prep Aliquot:14-DEC-21 1000 mL

Result Nominal pg/L pg/L

48609 SW846 3520C

As Received

Prep Method:

Prep Basis:

MDL

Dilution:

Comments:

U Analyte was analyzed for, but not detected above the specified detection limit.

Prep Batch:

b15dec21a-4Data File:

2,3,7,8-TCDD1746-01-6

Client Sample:

UnitsQual

PQL

10.0

Page 18 of 20 Work Order: 19090

Certificate of Analysis

Sample Summary

December 17, 2021Report Date:

SDG Number: 2111931 Lab Sample ID: 12030842 Matrix: WATER

Surrogate/Tracer recovery Recovery% Acceptable Limits

165 3.45

Client: HALL001 Project: HALL00113

13C-2,3,7,8-TCDD

37Cl-2,3,7,8-TCDD

67.7

73.0

(25%-141%)

(37%-158%)

CAS No. Parmname ResultQual

Method: EPA Method 1613BBatch ID: 48612 Instrument: HRP763

Run Date: 12/15/2021 15:18 Analyst: MLL

LCS for batch 48609

QC for batch 48609

Client ID:

Prep Date: Prep Aliquot:14-DEC-21 1000 mL

Result Nominal pg/L pg/L

48609 SW846 3520C

As Received

Prep Method:

Prep Basis:

MDL

Dilution:

Comments:

Prep Batch:

b15dec21a-2Data File:

2,3,7,8-TCDD1746-01-6

Client Sample:

UnitsQual

PQL

Page 19 of 20 Work Order: 19090

Certificate of Analysis

Sample Summary

December 17, 2021Report Date:

SDG Number: 2111931 Lab Sample ID: 12030843 Matrix: WATER

Surrogate/Tracer recovery Recovery% Acceptable Limits

172 3.45

Client: HALL001 Project: HALL00113

13C-2,3,7,8-TCDD

37Cl-2,3,7,8-TCDD

71.9

73.5

(25%-141%)

(37%-158%)

CAS No. Parmname ResultQual

Method: EPA Method 1613BBatch ID: 48612 Instrument: HRP763

Run Date: 12/15/2021 16:08 Analyst: MLL

LCSD for batch 48609

QC for batch 48609

Client ID:

Prep Date: Prep Aliquot:14-DEC-21 1000 mL

Result Nominal pg/L pg/L

48609 SW846 3520C

As Received

Prep Method:

Prep Basis:

MDL

Dilution:

Comments:

Prep Batch:

b15dec21a-3Data File:

2,3,7,8-TCDD1746-01-6

Client Sample:

UnitsQual

PQL

Page 20 of 20 Work Order: 19090

Project: 093534005 ChiChiltah BS

Client: Division of Env. Cultural & Safety Mgmt.

29-Dec-21

QC SUMMARY REPORT

2111931WO#:

Hall Environmental Analysis Laboratory, Inc.

Sample ID: MB

Batch ID: R82971

Analysis Date: 11/18/2021Prep Date:

Analyte Result SPK value SPK Ref Val %REC %RPDLowLimit HighLimit RPDLimit Qual

Units: mg/L

PQL

Client ID: PBW RunNo: 82971

SeqNo: 2946143 mblkSampType: TestCode: EPA Method 300.0: Anions

Nitrogen, Nitrite (As N) 0.10ND

Nitrogen, Nitrate (As N) 0.10ND

Sample ID: LCS

Batch ID: R82971

Analysis Date: 11/18/2021Prep Date:

Analyte Result SPK value SPK Ref Val %REC %RPDLowLimit HighLimit RPDLimit Qual

Units: mg/L

PQL

Client ID: LCSW RunNo: 82971

SeqNo: 2946144 lcsSampType: TestCode: EPA Method 300.0: Anions

Nitrogen, Nitrite (As N) 1.000 94.6 90 1100.10 00.95

Nitrogen, Nitrate (As N) 2.500 98.4 90 1100.10 02.5

Qualifiers:

* Value exceeds Maximum Contaminant Level. B Analyte detected in the associated Method Blank

D Sample Diluted Due to Matrix E Estimated value

H Holding times for preparation or analysis exceeded J Analyte detected below quantitation limits

ND Not Detected at the Reporting Limit P Sample pH Not In Range

Project: 093534005 ChiChiltah BS

Client: Division of Env. Cultural & Safety Mgmt.

29-Dec-21

QC SUMMARY REPORT

2111931WO#:

Hall Environmental Analysis Laboratory, Inc.

Sample ID: MB-64075

Batch ID: 64075

Analysis Date: 11/22/2021Prep Date: 11/22/2021

Analyte Result SPK value SPK Ref Val %REC %RPDLowLimit HighLimit RPDLimit Qual

Units: µg/L

PQL

Client ID: PBW RunNo: 83041

SeqNo: 2949443

MBLKSampType: TestCode: EPA Method 504.1: EDB/DBCP

1,2-Dibromo-3-chloropropane 0.020ND

1,2-Dibromoethane 0.010ND

Sample ID: MB-64075

Batch ID: 64075

Analysis Date: 11/22/2021Prep Date: 11/22/2021

Analyte Result SPK value SPK Ref Val %REC %RPDLowLimit HighLimit RPDLimit Qual

Units: µg/L

PQL

Client ID: PBW RunNo: 83041

SeqNo: 2949446

MBLKSampType: TestCode: EPA Method 504.1: EDB/DBCP

1,2-Dibromo-3-chloropropane 0.020ND

1,2-Dibromoethane 0.010ND

Sample ID: LCS-64075

Batch ID: 64075

Analysis Date: 11/22/2021Prep Date: 11/22/2021

Analyte Result SPK value SPK Ref Val %REC %RPDLowLimit HighLimit RPDLimit Qual

Units: µg/L

PQL

Client ID: LCSW RunNo: 83041

SeqNo: 2949447

LCSSampType: TestCode: EPA Method 504.1: EDB/DBCP

1,2-Dibromo-3-chloropropane 0.1000 108 70 1300.020 00.11

1,2-Dibromoethane 0.1000 107 70 1300.010 00.11

Qualifiers:

* Value exceeds Maximum Contaminant Level. B Analyte detected in the associated Method Blank

D Sample Diluted Due to Matrix E Estimated value

H Holding times for preparation or analysis exceeded J Analyte detected below quantitation limits

ND Not Detected at the Reporting Limit P Sample pH Not In Range

File details come from the government source that posted it. Updated .