This document contains drawings, specifications, and statements of work for the Repair TEC Physical Fitness Area project (PSXE 242020) for the Tennessee Air National Guard's 134th Air Refueling Wing. The project involves repairs and upgrades to the existing physical fitness area, including construction of new tennis/pickleball courts, a basketball court, sidewalks, lighting, and other site improvements. The solicitation number is W50S98-24-B-0009, and the Department of the Army Tennessee Army National Guard is the federal agency issuing the contract. A site visit is scheduled for August 30, 2024 at 2 PM with instructions provided in section 00 21 00 of the solicitation. The document includes detailed drawings, specifications, and construction details for the various project components.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
REPAIR TEC PHYSICAL FITNESS AREA
PSXE242020
TENNESSEE AIR NATIONAL GUARD
134TH AIR REFUELING WING
APRIL 2024
N.T.S.
LOCATION MAP
PROJECT
SITE
DRAWING LIST
C1.1 SITE LAYOUT PLAN
C1.2 SITE GRADING & DRAINAGE PLAN
C1.3 EROSION & SEDIMENT CONTROL PLAN - INITIAL
C1.4 EROSION & SEDIMENT CONTROL PLAN - FINAL
C2.1 DETAILS
C2.2 DETAILS
C2.3 DETAILS
C2.4 DETAILS
E1.2 SITE LAYOUT PLAN - LIGHTING
E2.1 ELECTRICAL SCHEDULES & SPECIFICATIONS
240 West Bessemer St. Alcoa, TN. 37701 Ph. (865) 980-3500
CIVIL ELECTRICAL
AutoCAD SHX Text
AutoCAD SHX Text
PELLISIPPI PKY
AutoCAD SHX Text
TOPSIDE RD
AutoCAD SHX Text
AutoCAD SHX Text
MARYVILLE PIKE
AutoCAD SHX Text
AutoCAD SHX Text
LOUISVILLE
AutoCAD SHX Text
MENTOR
AutoCAD SHX Text
AIR BASE RD
AutoCAD SHX Text
CALLAHAN RD
AutoCAD SHX Text
AutoCAD SHX Text
LOUISVILLE RD
AutoCAD SHX Text
W HUNT RD
AutoCAD SHX Text
W HUNT RD
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
ALCOA HWY
AutoCAD SHX Text
CUSICK RD
AutoCAD SHX Text
E HUNT RD
AutoCAD SHX Text
E BROADWAY AVE
AutoCAD SHX Text McARTHUR RD
AutoCAD SHX Text
MARYVILLE
AutoCAD SHX Text
METROPOLITAN
AutoCAD SHX Text
KNOXVILLE
AutoCAD SHX Text
AIRPORT AUTHORITY
AutoCAD SHX Text
AutoCAD SHX Text
FORT
AutoCAD SHX Text
LOUDON
AutoCAD SHX Text
LAKE
AutoCAD SHX Text
LIBERTY ST.
AutoCAD SHX Text
TENNESSEE AIR NATIONAL GUARD
AutoCAD SHX Text
BRISCOE DR.
AutoCAD SHX Text
AutoCAD SHX Text
FRONT GATE ENTRANCE TO TANG BASE
4 "W
R ep ai r
TE
C
P h ys ic al F it n es s
A re a
4t h A ir R ef u el in g W in g
PSXE242020
4.4.24
C1.1
S it e La yo u t Pl an
TCC
CJS
SCALE: 1" = '
0 30 60 90
BENCH MARK
ELECTRIC LINE
HIGH DENSITY POLYETHYLENE
CLEANOUT
DUCTILE IRON PIPE
SANITARY SEWER LINE
WATER LINE
CURB INLET
MANHOLE
FIRE HYDRANT
CATCH BASINS
WATER METER
VALVE
UTILITY-LIGHT POLE
GAS LINE
INTERMEDIATE CONTOUR
INDEX CONTOUR
ELECTRIC METER
ROUND AREA DRAIN
ELECTRIC TRANSFORMER
LIGHT POLE
STORM SEWER LINE
B.M.
LEGEND
EXISTING
NEW
COMMUNICATIONS DUCT BANK
8 9
10 116
5 4
6'
7'
19'
19'
9'
LIGHT DUTY PAVEMENT
G5
C2.2
SIDEWALK
G13 C2.2
122'
CONCRETE CURB
SEE DETAIL
G9 C2.2
BENCH & BOTTLE FILLER AREA
SEE DETAIL
ONLY
R3-5R
G1 C2.2
18'
18'
24'
10'R
15'R
15'R
MATCH NEW SIDEWALK
TO EXISTING (TYP.)
Point Northing Easting Description
COORDINATE TABLE
TENNIS COURT FENCE
A1
C2.3
8' RAMP
8' RAMP
CROSSWALK STRIPING
SEE DETAIL
35'R
K1 C2.2
MATCH NEW PAVEMENT
TO EXISTING
WATERLINEW
WATERLINE
CONNECTION
NEATLY SAWCUT & REMOVE
EXISTING SIDEWALK, TO INCLUDE
WIPEDOWNS. REPLACE WITH 27
LF+/- OF NEW SIDEWALK.
NOTES:
1. EXISTING TOPOGRAPHIC INFORMATION TAKEN FROM SURVEY
PERFORMED BY C2RL ENGINEERS, INC. DATED FEBRUARY 20, 2024.
DATUM: NAD83 - NAVD88
2. LOCATION OF THE EXISTING ABOVE GROUND AND UNDERGROUND
UTILITIES AND STRUCTURES INDICATED ARE APPROXIMATE ONLY, AND
THOSE INDICATED ARE NOT NECESSARILY ALL WHICH MAY EXIST ON
THE PROJECT SITE. CONTRACTOR SHALL DETERMINE ACTUAL
LOCATION OF ALL UTILITIES AND STRUCTURES ON THE PROJECT SITE
WHETHER THEY ARE INDICATED OR NOT. CONTRACTOR SHALL ASSUME
RESPONSIBILITY FOR ANY DAMAGE TO THE UTILITY LINES, WHETHER
SHOWN ON THE CONSTRUCTION PLANS OR NOT. CONTRACTOR SHALL
REQUEST A DIG PERMIT FROM WORK CONTROL (865)336-4219 PRIOR TO
ENGAGING IN ANY EXCAVATION OR PENETRATING THE GROUND IN ANY
WAY. CONTRACTOR SHALL ALSO CONTACT TENNESSEE ONE CALL
CENTER 811 FOR LOCATION OF ANY/ALL ELECTRICAL FACILITIES. THE
PRIMARY ELECTRICAL SERVICE ON BASE IS OWNED AND OPERATED BY
THE CITY OF ALCOA ELECTRIC SYSTEM. POC FOR THE ELECTRIC
SYSTEM IS MR. MIKE LINDSEY (865)380-4853.
3. ALL DISTURBED AREAS SHALL BE HAND-SMOOTHED TO MATCH
SURROUNDING GRADE. SOD IS REQUIRED FOR ALL DISTURBED AREAS.
A 4" LAYER OF TOPSOIL SHALL BE APPLIED ALONG WITH SOD.
4. ALL STRIPING SHALL BE IN ACCORDANCE WITH MUTCD LATEST VERSION.
5. CONTRACTOR SHALL ALIGN SIDEWALK EXPANSION JOINTS WITH CURB
EXPANSION JOINTS.
6. ALL NOVAPLAY SURFACES SHALL BE INSTALLED IN ACCORDANCE WITH
ALL MANUFACTURERS RECOMMENDATIONS.
7. EXISTING VALVE BOX COVERS, METER COVERS AND ANY OTHER
SURFACE UTILITY FEATURES SHALL BE ADJUSTED TO FINISHED GRADES
AS IMPACTED BY CONSTRUCTION.
545,862.61 2,561,674.04 CL DRIVE
545,803.56 2,561,652.04 CL DRIVE
545,877.59 2,561,561.44 CL DRIVE PC
545,858.23 2,561,545.62 RADIUS POINT
545,874.04 2,561,526.26 CL DRIVE PT
545,869.40 2,561,522.47 CL DRIVE PC
545,853.58 2,561,541.83 RADIUS POINT
545,834.22 2,561,526.01 CL DRIVE PT
545,776.01 2,561,597.25 CL DRIVE PC
545,795.37 2,561,613.07 RADIUS POINT
545,779.55 2,561,632.43 CL DRIVE PT
545,839.11 2,561,694.10 RADIUS POINT
545,857.99 2,561,643.51 RADIUS POINT
545,837.07 2,561,641.05 RADIUS POINT
545,823.88 2,561,635.07 RADIUS POINT
STAIRS
SEE DETAIL
A11 C2.3
ADA WARNING TILE (TYP.)
SEE DETAIL
L11 C2.3
CW
CW
CW CURB WIPEDOWN
H11 C2.3
CW
CW
B.M. 4 - NAIL
N. 545,828.91 E. 2,561,722.95
EL. 972.52
B.M. 3 - NAIL
N. 545,987.39 E. 2,561,257.83
EL. 969.75
52'
BASKETBALL COURT SURFACE
NOVABOND ON CONCRETE W/ NOVAPLAY II SURFACE
NOVATEX TEXTURED LINE PAINT
TENNIS COURT SURFACE
(NOVACRYLIC COMBINATION SYSTEM)
1. CP 761 CONCRETE PRIMER
2. NOVASURFACE ACRYLIC RESURFACER
3. NOVA COMBINATION SURFACE
ADJUST VALVE BOXES TO FINISHED
GRADE AND REPLACE IF TRAFFIC
GRADE COVERS ARE NEEDED
R1-1 (24"x24")
24" STOP
BAR
CAREFULLY PROTECT VOLLEYBALL COURT.
PROVIDE SIGNS INDICATING CONSTRUCTION
ZONE WITH NO PLAY ALLOWED.
BENCH (TYP.)
SEE DETAIL
G1 C2.2
545,826.40 2,561,511.87 COURTS LIMITS
545,778.39 2,561,472.64 COURTS LIMITS
545,888.48 2,561,337.90 COURTS LIMITS
545,936.49 2,561,377.13 COURTS LIMITS
EXISTING PAVEMENT & CURB
TO BE DEMOLISHED
NEATLY SAWCUT & REMOVE
92 LF +/- EXISTING SIDEWALK
6'
B.M. 2 - NAIL
N. 545,623.34 E. 2,561,204.41
EL. 972.56
B.M. 1 - NAIL
N. 545,505.74 E. 2,561,402.73
EL. 969.37
MATCH NEW CONCRETE
TO EXISTING
FOR COURT DIMENSIONS
SEE DETAILA1
C2.2
AutoCAD SHX Text
AC
AutoCAD SHX Text
CO
AutoCAD SHX Text
CO
AutoCAD SHX Text
CO
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text
8"DIP
AutoCAD SHX Text
8"DIP
AutoCAD SHX Text
8"DIP
AutoCAD SHX Text
8"DIP
AutoCAD SHX Text
8"DIP
AutoCAD SHX Text
6"DIP
AutoCAD SHX Text
8"TRANSITE
AutoCAD SHX Text
8"TRANSITE
AutoCAD SHX Text
6"DIP
AutoCAD SHX Text W
AutoCAD SHX Text T
AutoCAD SHX Text T
AutoCAD SHX Text
SAMH ABANDONED
AutoCAD SHX Text
8"DIP
AutoCAD SHX Text
6"PVC
AutoCAD SHX Text
6"PVC
AutoCAD SHX Text SAMH AG035 T.C. 969.72 Inv.(NE) 962.76 Inv.(NE Aband.) 965.33 Inv.(SE) 962.88 Inv.(SW) 962.76
AutoCAD SHX Text
8"PVC
AutoCAD SHX Text
8"DIP
AutoCAD SHX Text SAMH AG034 T.C. 966.49 Inv.(NE) 957.25 Inv.(NE Aband.) 961.09 Inv.(SW) 957.23
AutoCAD SHX Text
8"PVC
AutoCAD SHX Text
6"PVC
AutoCAD SHX Text
6"PVC
AutoCAD SHX Text
8"PVC
AutoCAD SHX Text
8"PVC
AutoCAD SHX Text SAMH AG082 T.C. 978.66 Inv.(NW) 967.08 Inv.(W) 967.04 Inv.(SW) 966.88
AutoCAD SHX Text
10"PVC
AutoCAD SHX Text
8"PVC
AutoCAD SHX Text
8"PVC
AutoCAD SHX Text
CO
AutoCAD SHX Text
UNDERGROUND CHAMBER LOCATION
AutoCAD SHX Text
TAKEN FROM DESIGN DRAWING
AutoCAD SHX Text
24"CMP
AutoCAD SHX Text Curb Inlet T.C. 965.38 Inv. 961.43
AutoCAD SHX Text
18"HDPE
AutoCAD SHX Text
30"RCP
AutoCAD SHX Text
30"RCP
AutoCAD SHX Text
12"HDPE
AutoCAD SHX Text
12"HDPE
AutoCAD SHX Text CB2x2 T.C. 967.06 Inv.(NE) 964.81 Inv.(SE) 964.94
AutoCAD SHX Text CB2x2 T.C. 967.62 Inv. 965.52
AutoCAD SHX Text
12"HDPE
AutoCAD SHX Text CB2x2 T.C. 968.55 Inv.(NE) 966.51
AutoCAD SHX Text
BLIND JUNCTION
AutoCAD SHX Text CB2x2 T.C. 968.65 Inv.(NE) 967.16
AutoCAD SHX Text
12"HDPE
AutoCAD SHX Text
24"CMP
AutoCAD SHX Text CB2x2 T.C. 971.63 Inv.(W) 966.48 Inv.(SE) 966.34 Inv.(SW) 966.41
AutoCAD SHX Text
15"HDPE
AutoCAD SHX Text
15"HDPE
AutoCAD SHX Text
15" HDPE
AutoCAD SHX Text
15" HDPE
AutoCAD SHX Text
15" HDPE
AutoCAD SHX Text
15" HDPE
AutoCAD SHX Text
15" HDPE
AutoCAD SHX Text
15" HDPE
AutoCAD SHX Text
15" HDPE
AutoCAD SHX Text
15" HDPE
AutoCAD SHX Text
15" HDPE
AutoCAD SHX Text
15" HDPE
AutoCAD SHX Text
15" HDPE
AutoCAD SHX Text
15" HDPE
AutoCAD SHX Text
15" HDPE
AutoCAD SHX Text
15" HDPE
AutoCAD SHX Text
15" HDPE
AutoCAD SHX Text CB2X3 T.C. 967.78 Inv. 965.86
AutoCAD SHX Text
36"RCP
AutoCAD SHX Text CB2x2 T.C. 968.30 Inv. 966.34
AutoCAD SHX Text
15" HDPE
AutoCAD SHX Text CB3x3 T.C. 968.55 Inv. In 965.38 Inv. Out 965.07
AutoCAD SHX Text
18" HDPE
AutoCAD SHX Text CB3x3 T.C. 968.89 Inv. In 964.82 Inv. Out 964.82
AutoCAD SHX Text
18" HDPE
AutoCAD SHX Text CB2x2 T.C. 964.06 Inv. In 961.47 Inv. Out 960.46
AutoCAD SHX Text
12" RCP
AutoCAD SHX Text CB2x3 T.C. 963.54 Inv. 957.29(NW) Inv. 954.18(NE) Inv. 954.16(SW) Inv. 958.24(SE)
AutoCAD SHX Text
36"RCP
AutoCAD SHX Text CB2X2 T.C. 962.60 Inv. In 958.40 Inv. Out 958.38
AutoCAD SHX Text
15" RCP
AutoCAD SHX Text
12" RCP
AutoCAD SHX Text CB2x2 T.C. 963.41 Inv. In 959.96 Inv. Out 959.96
AutoCAD SHX Text
12" RCP
AutoCAD SHX Text CB2x2 T.C. 963.52 Inv. In 960.89 Inv. Out 960.89
AutoCAD SHX Text
12" RCP
AutoCAD SHX Text
24"CMP
AutoCAD SHX Text
30"RCP
AutoCAD SHX Text
COMM.
AutoCAD SHX Text
COMM.
AutoCAD SHX Text
COMM.
AutoCAD SHX Text
COMM.
AutoCAD SHX Text
COMM. VAULT
AutoCAD SHX Text
COMM.
AutoCAD SHX Text
COMM.
AutoCAD SHX Text
ELECT.
AutoCAD SHX Text
ELECT.
AutoCAD SHX Text
SAMH AG083 (#2) T.C.=979.92 I.E.(N)=973.71 I.E.(SW)=972.77 I.E.(SE)=972.72
AutoCAD SHX Text Sidewalk
AutoCAD SHX Text Sidewalk
AutoCAD SHX Text Sidewalk
AutoCAD SHX Text Sidewalk
AutoCAD SHX Text Pull Up Bars
AutoCAD SHX Text Flag Pole
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text Sign
AutoCAD SHX Text
AutoCAD SHX Text
SAMH ABANDONED
AutoCAD SHX Text CB2x2 T.C. 965.68 Inv.(N) 959.44 Inv.(SW) 963.43 Inv.(SE) 958.96 Inv.(NE) 959.47 Inv.(NW) 959.44
AutoCAD SHX Text Existing Track
AutoCAD SHX Text Track
AutoCAD SHX Text
8"DIP
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
ELECT.
AutoCAD SHX Text Bleachers
AutoCAD SHX Text
BUILDING 207 F.F.E. 977.00
AutoCAD SHX Text Mon.
AutoCAD SHX Text Existing Volleyball Court
AutoCAD SHX Text Existing Parade Field
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
REVISIONS:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
PROJ. NO:
AutoCAD SHX Text
DRAWN:
AutoCAD SHX Text
CHECKED:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
SHEET NO.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text N
AutoCAD SHX Text M
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text L
AutoCAD SHX Text K
AutoCAD SHX Text J
AutoCAD SHX Text H
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text C
AutoCAD SHX Text B
AutoCAD SHX Text A
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text G
AutoCAD SHX Text 240 West Bessemer St. Alcoa, TN. 37701
AutoCAD SHX Text
ph. 865 980 3500 fax. 865 980 3555
AutoCAD SHX Text
COR
AutoCAD SHX Text H:\USPFO\47.242 - REPAIR TEC PHYSICAL FITNESS AREA\02-DRAWINGS\SHEETS\C1-1 SITE LAYOUT PLAN.DWGPLOTTED ON:April 17, 2024 11:21 AM BY:TIM CHILDRESSApril 17, 2024 11:21 AM BY:TIM CHILDRESS11:21 AM BY:TIM CHILDRESSBY:TIM CHILDRESSTIM CHILDRESS
AutoCAD SHX Text Knoxville, Tennessee
AutoCAD SHX Text Knoxville, Tennessee
AutoCAD SHX Text
HDPE
AutoCAD SHX Text
DIP
AutoCAD SHX Text
SS
AutoCAD SHX Text W
AutoCAD SHX Text G
AutoCAD SHX Text
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text W
AutoCAD SHX Text
CO
AutoCAD SHX Text T
AutoCAD SHX Text C
S
R ep ai r
TE
C
P h ys ic al F it n es s
A re a
4t h A ir R ef u el in g W in g
PSXE242020
4.4.24
C1.2
S it e G ra di n g
D ra in ag e
Pl an
SLC
CJS
SCALE: 1" = '
0 30 60 90
ELECTRIC LINE
HIGH DENSITY POLYETHYLENE
CLEANOUT
DUCTILE IRON PIPE
SANITARY SEWER LINE
WATER LINE
CURB INLET
MANHOLE
FIRE HYDRANT
CATCH BASINS
WATER METER
VALVE
UTILITY-LIGHT POLE
GAS LINE
INTERMEDIATE CONTOUR
INDEX CONTOUR
ELECTRIC METER
ROUND AREA DRAIN
ELECTRIC TRANSFORMER
LIGHT POLE
STORM SEWER LINE
LEGEND
EXISTING
NEW
COMMUNICATIONS DUCT BANK
STORM LINE
A1
C2.4
CURB INLET
A11 C2.4
NOTES:
1. ALL COORDINATES AND EXISTING CONDITIONS BASED ON BASE
MAPPING AERIAL SURVEY DATED 2022.
2. ALL UTILITIES TAKEN FROM BASE MAPPING SURVEY PERFORMED BY
C2RL ENGINEERS, INC.
3. LOCATION OF THE EXISTING ABOVE GROUND AND UNDERGROUND
UTILITIES AND STRUCTURES INDICATED ARE APPROXIMATE ONLY,
AND THOSE INDICATED ARE NOT NECESSARILY ALL WHICH MAY
EXIST ON THE PROJECT SITE. CONTRACTOR SHALL DETERMINE
ACTUAL LOCATION OF ALL UTILITIES AND STRUCTURES ON THE
PROJECT SITE WHETHER THEY ARE INDICATED OR NOT.
CONTRACTOR SHALL ASSUME RESPONSIBILITY FOR ANY DAMAGE
TO THE UTILITY LINES, WHETHER SHOWN ON THE CONSTRUCTION
PLANS OR NOT. CONTRACTOR SHALL REQUEST A DIG PERMIT FROM
WORK CONTROL (865)336-4219 PRIOR TO ENGAGING IN ANY
EXCAVATION OR PENETRATING THE GROUND IN ANY WAY.
CONTRACTOR SHALL ALSO CONTACT TENNESSEE ONE CALL
CENTER 811 FOR LOCATION OF ANY/ALL ELECTRICAL FACILITIES.
THE PRIMARY ELECTRICAL SERVICE ON BASE IS OWNED AND
OPERATED BY THE CITY OF ALCOA ELECTRIC SYSTEM. POC FOR
THE ELECTRIC SYSTEM IS MR. MIKE LINDSEY (865)380-4853.
4. ONCE ALL EARTH DISTURBING ACTIVITIES HAVE BEEN COMPLETED,
ALL DISTURBED AREAS SHALL BE STABILIZED WITH SOD OR
WASHED RIVER ROCK AS SOON AS PRACTICAL.
5. ALL DISTURBED AREAS SHALL BE HAND-SMOOTHED TO MATCH
SURROUNDING GRADE. IF SOD IS REQUIRED, A 4" LAYER OF
TOPSOIL SHALL BE APPLIED ALONG WITH SOD.
969.7
CI-1
28"Ø
T.C. 967.3
INV. OUT 965.7
970.8
969.7
969.5969.5
967.9
970.3
970.3 971.2
970.5969.7
969.6 969.9
966.5
969.31
12" HDPE
CONNECT NEW 12" HDPE
TO EXISTING STRUCTURE.
INV. IN 965.6
REMOVE FRAME AND
GRATE AND REPLACE
WITH SOLID LID. ADJUST
TOP OF CASTING.
T.C. 968.2
REMOVE FRAME AND
GRATE AND REPLACE
WITH SOLID LID.
AutoCAD SHX Text
AC
AutoCAD SHX Text
CO
AutoCAD SHX Text
CO
AutoCAD SHX Text
CO
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text
8"DIP
AutoCAD SHX Text
8"DIP
AutoCAD SHX Text
8"DIP
AutoCAD SHX Text
8"DIP
AutoCAD SHX Text
8"DIP
AutoCAD SHX Text
6"DIP
AutoCAD SHX Text
8"TRANSITE
AutoCAD SHX Text
8"TRANSITE
AutoCAD SHX Text
6"DIP
AutoCAD SHX Text W
AutoCAD SHX Text T
AutoCAD SHX Text T
AutoCAD SHX Text
SAMH ABANDONED
AutoCAD SHX Text
8"DIP
AutoCAD SHX Text
6"PVC
AutoCAD SHX Text
6"PVC
AutoCAD SHX Text SAMH AG035 T.C. 969.72 Inv.(NE) 962.76 Inv.(NE Aband.) 965.33 Inv.(SE) 962.88 Inv.(SW) 962.76
AutoCAD SHX Text
8"PVC
AutoCAD SHX Text
8"DIP
AutoCAD SHX Text SAMH AG034 T.C. 966.49 Inv.(NE) 957.25 Inv.(NE Aband.) 961.09 Inv.(SW) 957.23
AutoCAD SHX Text
8"PVC
AutoCAD SHX Text
8"PVC
AutoCAD SHX Text
8"PVC
AutoCAD SHX Text SAMH AG082 T.C. 978.66 Inv.(NW) 967.08 Inv.(W) 967.04 Inv.(SW) 966.88
AutoCAD SHX Text
10"PVC
AutoCAD SHX Text
8"PVC
AutoCAD SHX Text
8"PVC
AutoCAD SHX Text
CO
AutoCAD SHX Text
UNDERGROUND CHAMBER LOCATION
AutoCAD SHX Text
TAKEN FROM DESIGN DRAWING
AutoCAD SHX Text
24"CMP
AutoCAD SHX Text Curb Inlet T.C. 965.38 Inv. 961.43
AutoCAD SHX Text
18"HDPE
AutoCAD SHX Text
30"RCP
AutoCAD SHX Text
30"RCP
AutoCAD SHX Text
12"HDPE
AutoCAD SHX Text
12"HDPE
AutoCAD SHX Text CB2x2 T.C. 967.06 Inv.(NE) 964.81 Inv.(SE) 964.94
AutoCAD SHX Text CB2x2 T.C. 967.62 Inv. 965.52
AutoCAD SHX Text
12"HDPE
AutoCAD SHX Text CB2x2 T.C. 968.55 Inv.(NE) 966.51
AutoCAD SHX Text
BLIND JUNCTION
AutoCAD SHX Text CB2x2 T.C. 968.65 Inv.(NE) 967.16
AutoCAD SHX Text
12"HDPE
AutoCAD SHX Text
15"HDPE
AutoCAD SHX Text
15" HDPE
AutoCAD SHX Text
15" HDPE
AutoCAD SHX Text
15" HDPE
AutoCAD SHX Text
15" HDPE
AutoCAD SHX Text
15" HDPE
AutoCAD SHX Text
15" HDPE
AutoCAD SHX Text
15" HDPE
AutoCAD SHX Text
15" HDPE
AutoCAD SHX Text
15" HDPE
AutoCAD SHX Text
15" HDPE
AutoCAD SHX Text
15" HDPE
AutoCAD SHX Text
15" HDPE
AutoCAD SHX Text
15" HDPE
AutoCAD SHX Text
15" HDPE
AutoCAD SHX Text
15" HDPE
AutoCAD SHX Text CB2X3 T.C. 967.78 Inv. 965.86
AutoCAD SHX Text
36"RCP
AutoCAD SHX Text CB2x2 T.C. 968.30 Inv. 966.34
AutoCAD SHX Text
15" HDPE
AutoCAD SHX Text CB3x3 T.C. 968.55 Inv. In 965.38 Inv. Out 965.07
AutoCAD SHX Text
18" HDPE
AutoCAD SHX Text CB3x3 T.C. 968.89 Inv. In 964.82 Inv. Out 964.82
AutoCAD SHX Text
18" HDPE
AutoCAD SHX Text CB2x2 T.C. 964.06 Inv. In 961.47 Inv. Out 960.46
AutoCAD SHX Text
12" RCP
AutoCAD SHX Text CB2x3 T.C. 963.54 Inv. 957.29(NW) Inv. 954.18(NE) Inv. 954.16(SW) Inv. 958.24(SE)
AutoCAD SHX Text
36"RCP
AutoCAD SHX Text CB2X2 T.C. 962.60 Inv. In 958.40 Inv. Out 958.38
AutoCAD SHX Text
15" RCP
AutoCAD SHX Text
12" RCP
AutoCAD SHX Text CB2x2 T.C. 963.41 Inv. In 959.96 Inv. Out 959.96
AutoCAD SHX Text
12" RCP
AutoCAD SHX Text CB2x2 T.C. 963.52 Inv. In 960.89 Inv. Out 960.89
AutoCAD SHX Text
12" RCP
AutoCAD SHX Text
24"CMP
AutoCAD SHX Text
30"RCP
AutoCAD SHX Text
COMM.
AutoCAD SHX Text
COMM.
AutoCAD SHX Text
COMM.
AutoCAD SHX Text
COMM.
AutoCAD SHX Text
COMM. VAULT
AutoCAD SHX Text
COMM.
AutoCAD SHX Text
COMM.
AutoCAD SHX Text
ELECT.
AutoCAD SHX Text
SAMH AG083 (#2) T.C.=979.92 I.E.(N)=973.71 I.E.(SW)=972.77 I.E.(SE)=972.72
AutoCAD SHX Text Sidewalk
AutoCAD SHX Text Sidewalk
AutoCAD SHX Text Sidewalk
AutoCAD SHX Text Sidewalk
AutoCAD SHX Text NOTE: IF BRINGING IN BASE MAPPING UTILITIES PLEASE ADJUST ELEVATIONS TO CURRENT (EXISTING) TP10. (BASE MAPPING ELEVATIONS ARE ADJUSTED ELEVATIONS TO OPUS) OPUS TP10 N: 545717.183 E: 2561981.051 EL: 987.211
AutoCAD SHX Text Pull Up Bars
AutoCAD SHX Text Flag Pole
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text Sign
AutoCAD SHX Text
AutoCAD SHX Text
SAMH ABANDONED
AutoCAD SHX Text CB2x2 T.C. 965.68 Inv.(N) 959.44 Inv.(SW) 963.43 Inv.(SE) 958.96 Inv.(NE) 959.47 Inv.(NW) 959.44
AutoCAD SHX Text Existing Track
AutoCAD SHX Text Track
AutoCAD SHX Text
8"DIP
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
ELECT.
AutoCAD SHX Text Bleachers
AutoCAD SHX Text
BUILDING 207 F.F.E. 977.00
AutoCAD SHX Text Mon.
AutoCAD SHX Text Existing Volleyball Court
AutoCAD SHX Text Existing Parade Field
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
REVISIONS:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
PROJ. NO:
AutoCAD SHX Text
DRAWN:
AutoCAD SHX Text
CHECKED:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
SHEET NO.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text N
AutoCAD SHX Text M
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text L
AutoCAD SHX Text K
AutoCAD SHX Text J
AutoCAD SHX Text H
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text C
AutoCAD SHX Text B
AutoCAD SHX Text A
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text G
AutoCAD SHX Text 240 West Bessemer St. Alcoa, TN. 37701
AutoCAD SHX Text
ph. 865 980 3500 fax. 865 980 3555
AutoCAD SHX Text
COR
AutoCAD SHX Text H:\USPFO\47.242 - REPAIR TEC PHYSICAL FITNESS AREA\02-DRAWINGS\SHEETS\C1-2 SITE GRADING & DRAINAGE PLAN.DWG PLOTTED ON:April 17, 2024 11:22 AM BY:TIM CHILDRESSPLOTTED ON:April 17, 2024 11:22 AM BY:TIM CHILDRESSApril 17, 2024 11:22 AM BY:TIM CHILDRESS11:22 AM BY:TIM CHILDRESSBY:TIM CHILDRESSTIM CHILDRESS
AutoCAD SHX Text Knoxville, Tennessee
AutoCAD SHX Text Knoxville, Tennessee
AutoCAD SHX Text
HDPE
AutoCAD SHX Text
DIP
AutoCAD SHX Text
SS
AutoCAD SHX Text W
AutoCAD SHX Text G
AutoCAD SHX Text
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text W
AutoCAD SHX Text
CO
AutoCAD SHX Text T
AutoCAD SHX Text C
S
SF
SF
SF
SF
SF
SF
SF
R ep ai r
TE
C
P h ys ic al F it n es s
A re a
4t h A ir R ef u el in g W in g
PSXE242020
4.4.24
C1.3
E ro si on
S ed im en t
C on tr ol
P la n
I n it ia l
SLC
CJS
IP
IP
IP
CE
CONSTRUCTION ENTRANCE / EXIT TO BE
INSTALLED BEFORE GRADING
OPERATIONS COMMENCE
SF
SF
SCALE: 1" = '
0 30 60 90
NOTES:
1. ALL COORDINATES AND EXISTING CONDITIONS BASED ON BASE MAPPING
AERIAL SURVEY DATED 2022.
2. ALL UTILITIES TAKEN FROM BASE MAPPING SURVEY PERFORMED BY
C2RL ENGINEERS, INC.
3. LOCATION OF THE EXISTING ABOVE GROUND AND UNDERGROUND
UTILITIES AND STRUCTURES INDICATED ARE APPROXIMATE ONLY, AND
THOSE INDICATED ARE NOT NECESSARILY ALL WHICH MAY EXIST ON THE
PROJECT SITE. CONTRACTOR SHALL DETERMINE ACTUAL LOCATION OF
ALL UTILITIES AND STRUCTURES ON THE PROJECT SITE WHETHER THEY
ARE INDICATED OR NOT. CONTRACTOR SHALL ASSUME RESPONSIBILITY
FOR ANY DAMAGE TO THE UTILITY LINES, WHETHER SHOWN ON THE
CONSTRUCTION PLANS OR NOT. CONTRACTOR SHALL REQUEST A DIG
PERMIT FROM WORK CONTROL (865)336-4219 PRIOR TO ENGAGING IN
ANY EXCAVATION OR PENETRATING THE GROUND IN ANY WAY.
CONTRACTOR SHALL ALSO CONTACT TENNESSEE ONE CALL CENTER 811
FOR LOCATION OF ANY/ALL ELECTRICAL FACILITIES. THE PRIMARY
ELECTRICAL SERVICE ON BASE IS OWNED AND OPERATED BY THE CITY
OF ALCOA ELECTRIC SYSTEM. POC FOR THE ELECTRIC SYSTEM IS MR.
MIKE LINDSEY (865)380-4853.
4. ONCE ALL EARTH DISTURBING ACTIVITIES HAVE BEEN COMPLETED, ALL
DISTURBED AREAS SHALL BE STABILIZED WITH SOD OR WASHED RIVER
ROCK AS SOON AS PRACTICAL.
5. ALL DISTURBED AREAS SHALL BE HAND-SMOOTHED TO MATCH
SURROUNDING GRADE. IF SOD IS REQUIRED, A 4" LAYER OF TOPSOIL
SHALL BE APPLIED ALONG WITH SOD.
NOTE: SODDED AREAS ILLUSTRATED MAY NOT INCLUDE
ALL DISTURBED AREAS.
EROSION CONTROL NOTES
1. THE PURPOSE OF THIS EROSION CONTROL PLAN IS TO MINIMIZE EROSION
AND PREVENT SEDIMENT FROM LEAVING THE SITE DURING
CONSTRUCTION. THEREFORE, TDEC, THE ENGINEER, OR THE COR MAY
REQUIRE CHANGES BE MADE TO THIS PLAN AT ANY TIME.
2. EROSION PREVENTION AND SEDIMENT CONTROL BEST MANAGEMENT
PRACTICES SHALL FOLLOW THE APPROVED PLAN DETAILS AND THE
TENNESSEE EROSION AND SEDIMENT CONTROL HANDBOOK, LATEST
EDITION.
3. CONSTRUCTION MUST BE SEQUENCED TO MINIMIZE THE EXPOSURE TIME
OF GRADED OR DENUDED AREAS.
4. EROSION PREVENTION AND SEDIMENT CONTROL MEASURES MUST BE IN
PLACE (WHERE NEEDED) AND FUNCTIONAL BEFORE THE DAY'S WORK MAY
BEGIN AND MUST BE CONSTRUCTED AND MAINTAINED WHILE WORK IS
PROGRESSING UPSTREAM. TEMPORARY MEASURES MAY BE REMOVED AT
THE BEGINNING OF THE THE WORK DAY, BUT MUST BE REPLACED AT THE
END OF THE WORK DAY.
5. PRE-CONSTRUCTION VEGETATIVE GROUND COVER SHALL NOT BE
DESTROYED, REMOVED OR DISTURBED MORE THAN 15 DAYS PRIOR TO
WORK IN THAT AREA UNLESS THE AREA IS SEEDED OR MULCHED OR
OTHER TEMPORARY COVER INSTALLED.
6. CLEARING AND GRUBBING MUST BE HELD TO THE MINIMUM AREA
NECESSARY FOR INSTALLATION AND EQUIPMENT OPERATION. EXISTING
VEGETATION AT THE WORK AREA SHOULD BE PRESERVED TO THE
MAXIMUM EXTENT PRACTICABLE.
7. TEMPORARY SEEDING IS REQUIRED WHEN GRADING OPERATIONS ARE
TEMPORARILY HALTED FOR OVER 14 DAYS, AND ON ALL STOCKPILES.
PERMANENT SEEDING IS REQUIRED WHEN GRADING OPERATIONS ARE
COMPLETED AND/OR CONSTRUCTION OPERATIONS WILL NOT IMPACT THE
DISTURBED AREA.
8. CONTRACTOR SHALL SEED ANY AREAS THAT SHOW SIGNS OF EXCESSIVE
EROSION.
9. ALL SLOPES SHALL BE STABILIZED AS SOON AS THEY ARE AT FINISHED
GRADE.
10. LITTER, CONSTRUCTION DEBRIS AND CONSTRUCTION CHEMICALS
EXPOSED TO STORM WATER SHALL BE PICKED UP PRIOR TO ANTICIPATED
STORM EVENTS OR BEFORE BEING CARRIED OFF SITE BY WIND, OR
OTHERWISE PREVENTED FROM BECOMING A POLLUTANT SOURCE.
11. PLACEMENT OF PORT-A-POTTIES ON THE PROJECT SHALL NOT BE
LOCATED CLOSE TO STREAMS, WETLANDS OR STORM DRAINS.
12. A STORAGE AREA FOR CONSTRUCTION RELATED MATERIALS MUST BE
COORDINATED ON SITE WITH THE OWNER. THIS AREA WILL NEED TO HAVE
EROSION PREVENTION AND SEDIMENT CONTROL MEASURES INSTALLED
TO PREVENT DEBRIS AND TRASH FROM SPREADING OVER THE SITE. A
TRASH RECEPTACLE WITH A LID IS REQUIRED ON SITE. THESE STORAGE
AREAS AND RECEPTACLES SHALL BE PROPERLY MAINTAINED AND FREE
OF DEBRIS AND POLLUTANTS TO THE SITE THROUGHOUT CONSTRUCTION.
13. AFTER USE, MATERIALS USED FOR EROSION PREVENTION AND SEDIMENT
CONTROL (SUCH AS SILT FENCE) SHOULD BE REMOVED OR OTHERWISE
PREVENTED FROM BECOMING A POLLUTANT SOURCE.
14. SEDIMENT SHOULD BE REMOVED FROM SILT FENCES AND OTHER
SEDIMENT CONTROLS ONCE DESIGN CAPACITY HAS BEEN REDUCED BY
50%.
15. IF SEDIMENT ESCAPES CONSTRUCTION AREA, OFF SITE ACCUMULATIONS
THAT HAVE NOT REACHED A STREAM MUST BE REMOVED AT A
FREQUENCY SUFFICIENT TO MINIMIZE OFF-SITE IMPACTS. CONTRACTORS
SHALL NOT INITIATE REMEDIATION/RESTORATION OF A STREAM WITHOUT
CONSULTING TDEC FIRST. ARRANGEMENTS CONCERNING REMOVAL OF
SEDIMENT ON ADJOINING PROPERTY MUST BE SETTLED WITH THE
ADJOINING PROPERTY OWNER.
16. A RAIN GAUGE SHALL BE MAINTAINED ON SITE OR A REFERENCE SITE IS
TO BE USED FOR RECORDING DAILY RAINFALL AMOUNTS. THIS DATA MUST
BE RECORDED AND KEPT ON SITE.
17. THE FOLLOWING RECORDS MUST BE KEPT AT OR NEAR THE WORK AREA:
A. THE DATES WHEN MAJOR GRADING ACTIVITIES OCCUR.
B. THE DATES WHEN CONSTRUCTION ACTIVITIES TEMPORARILY
OR PERMANENTLY CEASE ON A PORTION OF THE SITE.
C. THE DATES WHEN STABILIZATION MEASURES ARE INITIATED.
D. TWICE WEEKLY AND OTHER INSPECTION RECORDS.
E. RAINFALL RECORDS.
18. A COPY OF THE SWPPP SHALL BE KEPT ON SITE IN A LOCATION
COORDINATED BETWEEN THE CONTRACTOR AND THE OWNER AND
VERIFIED PRIOR TO CONSTRUCTION.
SF TEMPORARY SILT FENCESFSF
J5
C2.4
LEGEND
IP INLET PROTECTION
J11 C2.4
CE CONSTRUCTION ENTRANCE / EXIT
A6
C2.4
AutoCAD SHX Text
AC
AutoCAD SHX Text
CO
AutoCAD SHX Text
CO
AutoCAD SHX Text
CO
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text
8"DIP
AutoCAD SHX Text
8"DIP
AutoCAD SHX Text
8"DIP
AutoCAD SHX Text
8"DIP
AutoCAD SHX Text
8"DIP
AutoCAD SHX Text
6"DIP
AutoCAD SHX Text
8"TRANSITE
AutoCAD SHX Text
8"TRANSITE
AutoCAD SHX Text
6"DIP
AutoCAD SHX Text W
AutoCAD SHX Text T
AutoCAD SHX Text T
AutoCAD SHX Text
SAMH ABANDONED
AutoCAD SHX Text
8"DIP
AutoCAD SHX Text
6"PVC
AutoCAD SHX Text
6"PVC
AutoCAD SHX Text SAMH AG035 T.C. 969.72 Inv.(NE) 962.76 Inv.(NE Aband.) 965.33 Inv.(SE) 962.88 Inv.(SW) 962.76
AutoCAD SHX Text
8"PVC
AutoCAD SHX Text
8"DIP
AutoCAD SHX Text SAMH AG034 T.C. 966.49 Inv.(NE) 957.25 Inv.(NE Aband.) 961.09 Inv.(SW) 957.23
AutoCAD SHX Text
8"PVC
AutoCAD SHX Text
8"PVC
AutoCAD SHX Text
8"PVC
AutoCAD SHX Text SAMH AG082 T.C. 978.66 Inv.(NW) 967.08 Inv.(W) 967.04 Inv.(SW) 966.88
AutoCAD SHX Text
10"PVC
AutoCAD SHX Text
8"PVC
AutoCAD SHX Text
8"PVC
AutoCAD SHX Text
CO
AutoCAD SHX Text
UNDERGROUND CHAMBER LOCATION
AutoCAD SHX Text
TAKEN FROM DESIGN DRAWING
AutoCAD SHX Text
24"CMP
AutoCAD SHX Text Curb Inlet T.C. 965.38 Inv. 961.43
AutoCAD SHX Text
18"HDPE
AutoCAD SHX Text
30"RCP
AutoCAD SHX Text
30"RCP
AutoCAD SHX Text
12"HDPE
AutoCAD SHX Text
12"HDPE
AutoCAD SHX Text CB2x2 T.C. 967.06 Inv.(NE) 964.81 Inv.(SE) 964.94
AutoCAD SHX Text CB2x2 T.C. 967.62 Inv. 965.52
AutoCAD SHX Text
12"HDPE
AutoCAD SHX Text CB2x2 T.C. 968.55 Inv.(NE) 966.51
AutoCAD SHX Text
BLIND JUNCTION
AutoCAD SHX Text CB2x2 T.C. 968.65 Inv.(NE) 967.16
AutoCAD SHX Text
12"HDPE
AutoCAD SHX Text
15"HDPE
AutoCAD SHX Text
15" HDPE
AutoCAD SHX Text
15" HDPE
AutoCAD SHX Text
15" HDPE
AutoCAD SHX Text
15" HDPE
AutoCAD SHX Text
15" HDPE
AutoCAD SHX Text
15" HDPE
AutoCAD SHX Text
15" HDPE
AutoCAD SHX Text
15" HDPE
AutoCAD SHX Text
15" HDPE
AutoCAD SHX Text
15" HDPE
AutoCAD SHX Text
15" HDPE
AutoCAD SHX Text
15" HDPE
AutoCAD SHX Text
15" HDPE
AutoCAD SHX Text
15" HDPE
AutoCAD SHX Text
15" HDPE
AutoCAD SHX Text CB2X3 T.C. 967.78 Inv. 965.86
AutoCAD SHX Text
36"RCP
AutoCAD SHX Text CB2x2 T.C. 968.30 Inv. 966.34
AutoCAD SHX Text
15" HDPE
AutoCAD SHX Text CB3x3 T.C. 968.55 Inv. In 965.38 Inv. Out 965.07
AutoCAD SHX Text
18" HDPE
AutoCAD SHX Text CB3x3 T.C. 968.89 Inv. In 964.82 Inv. Out 964.82
AutoCAD SHX Text
18" HDPE
AutoCAD SHX Text CB2x2 T.C. 964.06 Inv. In 961.47 Inv. Out 960.46
AutoCAD SHX Text
12" RCP
AutoCAD SHX Text CB2x3 T.C. 963.54 Inv. 957.29(NW) Inv. 954.18(NE) Inv. 954.16(SW) Inv. 958.24(SE)
AutoCAD SHX Text
36"RCP
AutoCAD SHX Text CB2X2 T.C. 962.60 Inv. In 958.40 Inv. Out 958.38
AutoCAD SHX Text
15" RCP
AutoCAD SHX Text
12" RCP
AutoCAD SHX Text CB2x2 T.C. 963.41 Inv. In 959.96 Inv. Out 959.96
AutoCAD SHX Text
12" RCP
AutoCAD SHX Text CB2x2 T.C. 963.52 Inv. In 960.89 Inv. Out 960.89
AutoCAD SHX Text
12" RCP
AutoCAD SHX Text
24"CMP
AutoCAD SHX Text
30"RCP
AutoCAD SHX Text
COMM.
AutoCAD SHX Text
COMM.
AutoCAD SHX Text
COMM.
AutoCAD SHX Text
COMM.
AutoCAD SHX Text
COMM. VAULT
AutoCAD SHX Text
COMM.
AutoCAD SHX Text
COMM.
AutoCAD SHX Text
ELECT.
AutoCAD SHX Text
SAMH AG083 (#2) T.C.=979.92 I.E.(N)=973.71 I.E.(SW)=972.77 I.E.(SE)=972.72
AutoCAD SHX Text Sidewalk
AutoCAD SHX Text Sidewalk
AutoCAD SHX Text Sidewalk
AutoCAD SHX Text Sidewalk
AutoCAD SHX Text NOTE: IF BRINGING IN BASE MAPPING UTILITIES PLEASE ADJUST ELEVATIONS TO CURRENT (EXISTING) TP10. (BASE MAPPING ELEVATIONS ARE ADJUSTED ELEVATIONS TO OPUS) OPUS TP10 N: 545717.183 E: 2561981.051 EL: 987.211
AutoCAD SHX Text Pull Up Bars
AutoCAD SHX Text Flag Pole
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text Sign
AutoCAD SHX Text
AutoCAD SHX Text
SAMH ABANDONED
AutoCAD SHX Text CB2x2 T.C. 965.68 Inv.(N) 959.44 Inv.(SW) 963.43 Inv.(SE) 958.96 Inv.(NE) 959.47 Inv.(NW) 959.44
AutoCAD SHX Text Existing Track
AutoCAD SHX Text Track
AutoCAD SHX Text
8"DIP
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
ELECT.
AutoCAD SHX Text Bleachers
AutoCAD SHX Text
BUILDING 207 F.F.E. 977.00
AutoCAD SHX Text Mon.
AutoCAD SHX Text Existing Volleyball Court
AutoCAD SHX Text Existing Parade Field
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
REVISIONS:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
PROJ. NO:
AutoCAD SHX Text
DRAWN:
AutoCAD SHX Text
CHECKED:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
SHEET NO.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text N
AutoCAD SHX Text M
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text L
AutoCAD SHX Text K
AutoCAD SHX Text J
AutoCAD SHX Text H
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text C
AutoCAD SHX Text B
AutoCAD SHX Text A
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text G
AutoCAD SHX Text 240 West Bessemer St. Alcoa, TN. 37701
AutoCAD SHX Text
ph. 865 980 3500 fax. 865 980 3555
AutoCAD SHX Text
COR
AutoCAD SHX Text H:\USPFO\47.242 - REPAIR TEC PHYSICAL FITNESS AREA\02-DRAWINGS\SHEETS\C1-3 EROSION & SEDIMENT CONTROL PLAN - INITIAL.DWG PLOTTED ON:April 17, 2024 11:22 AM BY:TIM CHILDRESSPLOTTED ON:April 17, 2024 11:22 AM BY:TIM CHILDRESSApril 17, 2024 11:22 AM BY:TIM CHILDRESS11:22 AM BY:TIM CHILDRESSBY:TIM CHILDRESSTIM CHILDRESS
AutoCAD SHX Text Knoxville, Tennessee
Knoxville, Tennessee
SF
SF
SF
SF
SF
SF
SF
R ep ai r
TE
C
P h ys ic al F it n es s
A re a
4t h A ir R ef u el in g W in g
PSXE242020
4.4.24
C1.4
E ro si on
S ed im en t
C on tr ol
P la n
F in al
SLC
CJS
SCALE: 1" = '
0 30 60 90
NOTES:
1. ALL COORDINATES AND EXISTING CONDITIONS BASED ON BASE MAPPING
AERIAL SURVEY DATED 2022.
2. ALL UTILITIES TAKEN FROM BASE MAPPING SURVEY PERFORMED BY
C2RL ENGINEERS, INC.
3. LOCATION OF THE EXISTING ABOVE GROUND AND UNDERGROUND
UTILITIES AND STRUCTURES INDICATED ARE APPROXIMATE ONLY, AND
THOSE INDICATED ARE NOT NECESSARILY ALL WHICH MAY EXIST ON THE
PROJECT SITE. CONTRACTOR SHALL DETERMINE ACTUAL LOCATION OF
ALL UTILITIES AND STRUCTURES ON THE PROJECT SITE WHETHER THEY
ARE INDICATED OR NOT. CONTRACTOR SHALL ASSUME RESPONSIBILITY
FOR ANY DAMAGE TO THE UTILITY LINES, WHETHER SHOWN ON THE
CONSTRUCTION PLANS OR NOT. CONTRACTOR SHALL REQUEST A DIG
PERMIT FROM WORK CONTROL (865)336-4219 PRIOR TO ENGAGING IN
ANY EXCAVATION OR PENETRATING THE GROUND IN ANY WAY.
CONTRACTOR SHALL ALSO CONTACT TENNESSEE ONE CALL CENTER 811
FOR LOCATION OF ANY/ALL ELECTRICAL FACILITIES. THE PRIMARY
ELECTRICAL SERVICE ON BASE IS OWNED AND OPERATED BY THE CITY
OF ALCOA ELECTRIC SYSTEM. POC FOR THE ELECTRIC SYSTEM IS MR.
MIKE LINDSEY (865)380-4853.
4. ONCE ALL EARTH DISTURBING ACTIVITIES HAVE BEEN COMPLETED, ALL
DISTURBED AREAS SHALL BE STABILIZED WITH SOD OR WASHED RIVER
ROCK AS SOON AS PRACTICAL.
5. ALL DISTURBED AREAS SHALL BE HAND-SMOOTHED TO MATCH
SURROUNDING GRADE. IF SOD IS REQUIRED, A 4" LAYER OF TOPSOIL
SHALL BE APPLIED ALONG WITH SOD.
NOTE: SODDED AREAS ILLUSTRATED MAY NOT INCLUDE
ALL DISTURBED AREAS.
EROSION CONTROL NOTES
1. THE PURPOSE OF THIS EROSION CONTROL PLAN IS TO MINIMIZE EROSION
AND PREVENT SEDIMENT FROM LEAVING THE SITE DURING
CONSTRUCTION. THEREFORE, TDEC, THE ENGINEER, OR THE COR MAY
REQUIRE CHANGES BE MADE TO THIS PLAN AT ANY TIME.
2. EROSION PREVENTION AND SEDIMENT CONTROL BEST MANAGEMENT
PRACTICES SHALL FOLLOW THE APPROVED PLAN DETAILS AND THE
TENNESSEE EROSION AND SEDIMENT CONTROL HANDBOOK, LATEST
EDITION.
3. CONSTRUCTION MUST BE SEQUENCED TO MINIMIZE THE EXPOSURE TIME
OF GRADED OR DENUDED AREAS.
4. EROSION PREVENTION AND SEDIMENT CONTROL MEASURES MUST BE IN
PLACE (WHERE NEEDED) AND FUNCTIONAL BEFORE THE DAY'S WORK MAY
BEGIN AND MUST BE CONSTRUCTED AND MAINTAINED WHILE WORK IS
PROGRESSING UPSTREAM. TEMPORARY MEASURES MAY BE REMOVED AT
THE BEGINNING OF THE THE WORK DAY, BUT MUST BE REPLACED AT THE
END OF THE WORK DAY.
5. PRE-CONSTRUCTION VEGETATIVE GROUND COVER SHALL NOT BE
DESTROYED, REMOVED OR DISTURBED MORE THAN 15 DAYS PRIOR TO
WORK IN THAT AREA UNLESS THE AREA IS SEEDED OR MULCHED OR
OTHER TEMPORARY COVER INSTALLED.
6. CLEARING AND GRUBBING MUST BE HELD TO THE MINIMUM AREA
NECESSARY FOR INSTALLATION AND EQUIPMENT OPERATION. EXISTING
VEGETATION AT THE WORK AREA SHOULD BE PRESERVED TO THE
MAXIMUM EXTENT PRACTICABLE.
7. TEMPORARY SEEDING IS REQUIRED WHEN GRADING OPERATIONS ARE
TEMPORARILY HALTED FOR OVER 14 DAYS, AND ON ALL STOCKPILES.
PERMANENT SEEDING IS REQUIRED WHEN GRADING OPERATIONS ARE
COMPLETED AND/OR CONSTRUCTION OPERATIONS WILL NOT IMPACT THE
DISTURBED AREA.
8. CONTRACTOR SHALL SEED ANY AREAS THAT SHOW SIGNS OF EXCESSIVE
EROSION.
9. ALL SLOPES SHALL BE STABILIZED AS SOON AS THEY ARE AT FINISHED
GRADE.
10. LITTER, CONSTRUCTION DEBRIS AND CONSTRUCTION CHEMICALS
EXPOSED TO STORM WATER SHALL BE PICKED UP PRIOR TO ANTICIPATED
STORM EVENTS OR BEFORE BEING CARRIED OFF SITE BY WIND, OR
OTHERWISE PREVENTED FROM BECOMING A POLLUTANT SOURCE.
11. PLACEMENT OF PORT-A-POTTIES ON THE PROJECT SHALL NOT BE
LOCATED CLOSE TO STREAMS, WETLANDS OR STORM DRAINS.
12. A STORAGE AREA FOR CONSTRUCTION RELATED MATERIALS MUST BE
COORDINATED ON SITE WITH THE OWNER. THIS AREA WILL NEED TO HAVE
EROSION PREVENTION AND SEDIMENT CONTROL MEASURES INSTALLED
TO PREVENT DEBRIS AND TRASH FROM SPREADING OVER THE SITE. A
TRASH RECEPTACLE WITH A LID IS REQUIRED ON SITE. THESE STORAGE
AREAS AND RECEPTACLES SHALL BE PROPERLY MAINTAINED AND FREE
OF DEBRIS AND POLLUTANTS TO THE SITE THROUGHOUT CONSTRUCTION.
13. AFTER USE, MATERIALS USED FOR EROSION PREVENTION AND SEDIMENT
CONTROL (SUCH AS SILT FENCE) SHOULD BE REMOVED OR OTHERWISE
PREVENTED FROM BECOMING A POLLUTANT SOURCE.
14. SEDIMENT SHOULD BE REMOVED FROM SILT FENCES AND OTHER
SEDIMENT CONTROLS ONCE DESIGN CAPACITY HAS BEEN REDUCED BY
50%.
15. IF SEDIMENT ESCAPES CONSTRUCTION AREA, OFF SITE ACCUMULATIONS
THAT HAVE NOT REACHED A STREAM MUST BE REMOVED AT A
FREQUENCY SUFFICIENT TO MINIMIZE OFF-SITE IMPACTS. CONTRACTORS
SHALL NOT INITIATE REMEDIATION/RESTORATION OF A STREAM WITHOUT
CONSULTING TDEC FIRST. ARRANGEMENTS CONCERNING REMOVAL OF
SEDIMENT ON ADJOINING PROPERTY MUST BE SETTLED WITH THE
ADJOINING PROPERTY OWNER.
16. A RAIN GAUGE SHALL BE MAINTAINED ON SITE OR A REFERENCE SITE IS
TO BE USED FOR RECORDING DAILY RAINFALL AMOUNTS. THIS DATA MUST
BE RECORDED AND KEPT ON SITE.
17. THE FOLLOWING RECORDS MUST BE KEPT AT OR NEAR THE WORK AREA:
A. THE DATES WHEN MAJOR GRADING ACTIVITIES OCCUR.
B. THE DATES WHEN CONSTRUCTION ACTIVITIES TEMPORARILY
OR PERMANENTLY CEASE ON A PORTION OF THE SITE.
C. THE DATES WHEN STABILIZATION MEASURES ARE INITIATED.
D. TWICE WEEKLY AND OTHER INSPECTION RECORDS.
E. RAINFALL RECORDS.
18. A COPY OF THE SWPPP SHALL BE KEPT ON SITE IN A LOCATION
COORDINATED BETWEEN THE CONTRACTOR AND THE OWNER AND
VERIFIED PRIOR TO CONSTRUCTION.
SF TEMPORARY SILT FENCESFSF
J5
C2.4
LEGEND
IP INLET PROTECTION
J11 C2.4
CE CONSTRUCTION ENTRANCE / EXIT
A6
C2.4
IP
IP
IP
IP
CE
CONSTRUCTION ENTRANCE / EXIT TO BE
MAINTAINED UNTIL SITE IS STABILIZED
AND PAVING OPERATIONS COMMENCE
SF
SF
AutoCAD SHX Text
AC
AutoCAD SHX Text
CO
AutoCAD SHX Text
CO
AutoCAD SHX Text
CO
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text
8"DIP
AutoCAD SHX Text
8"DIP
AutoCAD SHX Text
8"DIP
AutoCAD SHX Text
8"DIP
AutoCAD SHX Text
8"DIP
AutoCAD SHX Text
6"DIP
AutoCAD SHX Text
8"TRANSITE
AutoCAD SHX Text
8"TRANSITE
AutoCAD SHX Text
6"DIP
AutoCAD SHX Text W
AutoCAD SHX Text T
AutoCAD SHX Text T
AutoCAD SHX Text
SAMH ABANDONED
AutoCAD SHX Text
8"DIP
AutoCAD SHX Text
6"PVC
AutoCAD SHX Text
6"PVC
AutoCAD SHX Text SAMH AG035 T.C. 969.72 Inv.(NE) 962.76 Inv.(NE Aband.) 965.33 Inv.(SE) 962.88 Inv.(SW) 962.76
AutoCAD SHX Text
8"PVC
AutoCAD SHX Text
8"DIP
AutoCAD SHX Text SAMH AG034 T.C. 966.49 Inv.(NE) 957.25 Inv.(NE Aband.) 961.09 Inv.(SW) 957.23
AutoCAD SHX Text
8"PVC
AutoCAD SHX Text
8"PVC
AutoCAD SHX Text
8"PVC
AutoCAD SHX Text SAMH AG082 T.C. 978.66 Inv.(NW) 967.08 Inv.(W) 967.04 Inv.(SW) 966.88
AutoCAD SHX Text
10"PVC
AutoCAD SHX Text
8"PVC
AutoCAD SHX Text
8"PVC
AutoCAD SHX Text
CO
AutoCAD SHX Text
UNDERGROUND CHAMBER LOCATION
AutoCAD SHX Text
TAKEN FROM DESIGN DRAWING
AutoCAD SHX Text
24"CMP
AutoCAD SHX Text Curb Inlet T.C. 965.38 Inv. 961.43
AutoCAD SHX Text
18"HDPE
AutoCAD SHX Text
30"RCP
AutoCAD SHX Text
30"RCP
AutoCAD SHX Text
12"HDPE
AutoCAD SHX Text
12"HDPE
AutoCAD SHX Text CB2x2 T.C. 967.06 Inv.(NE) 964.81 Inv.(SE) 964.94
AutoCAD SHX Text CB2x2 T.C. 967.62 Inv. 965.52
AutoCAD SHX Text
12"HDPE
AutoCAD SHX Text CB2x2 T.C. 968.55 Inv.(NE) 966.51
AutoCAD SHX Text
BLIND JUNCTION
AutoCAD SHX Text CB2x2 T.C. 968.65 Inv.(NE) 967.16
AutoCAD SHX Text
12"HDPE
AutoCAD SHX Text
15"HDPE
AutoCAD SHX Text
15" HDPE
AutoCAD SHX Text
15" HDPE
AutoCAD SHX Text
15" HDPE
AutoCAD SHX Text
15" HDPE
AutoCAD SHX Text
15" HDPE
AutoCAD SHX Text
15" HDPE
AutoCAD SHX Text
15" HDPE
AutoCAD SHX Text
15" HDPE
AutoCAD SHX Text
15" HDPE
AutoCAD SHX Text
15" HDPE
AutoCAD SHX Text
15" HDPE
AutoCAD SHX Text
15" HDPE
AutoCAD SHX Text
15" HDPE
AutoCAD SHX Text
15" HDPE
AutoCAD SHX Text
15" HDPE
AutoCAD SHX Text CB2X3 T.C. 967.78 Inv. 965.86
AutoCAD SHX Text
36"RCP
AutoCAD SHX Text CB2x2 T.C. 968.30 Inv. 966.34
AutoCAD SHX Text
15" HDPE
AutoCAD SHX Text CB3x3 T.C. 968.55 Inv. In 965.38 Inv. Out 965.07
AutoCAD SHX Text
18" HDPE
AutoCAD SHX Text CB3x3 T.C. 968.89 Inv. In 964.82 Inv. Out 964.82
AutoCAD SHX Text
18" HDPE
AutoCAD SHX Text CB2x2 T.C. 964.06 Inv. In 961.47 Inv. Out 960.46
AutoCAD SHX Text
12" RCP
AutoCAD SHX Text CB2x3 T.C. 963.54 Inv. 957.29(NW) Inv. 954.18(NE) Inv. 954.16(SW) Inv. 958.24(SE)
AutoCAD SHX Text
36"RCP
AutoCAD SHX Text CB2X2 T.C. 962.60 Inv. In 958.40 Inv. Out 958.38
AutoCAD SHX Text
15" RCP
AutoCAD SHX Text
12" RCP
AutoCAD SHX Text CB2x2 T.C. 963.41 Inv. In 959.96 Inv. Out 959.96
AutoCAD SHX Text
12" RCP
AutoCAD SHX Text CB2x2 T.C. 963.52 Inv. In 960.89 Inv. Out 960.89
AutoCAD SHX Text
12" RCP
AutoCAD SHX Text
24"CMP
AutoCAD SHX Text
30"RCP
AutoCAD SHX Text
COMM.
AutoCAD SHX Text
COMM.
AutoCAD SHX Text
COMM.
AutoCAD SHX Text
COMM.
AutoCAD SHX Text
COMM. VAULT
AutoCAD SHX Text
COMM.
AutoCAD SHX Text
COMM.
AutoCAD SHX Text
ELECT.
AutoCAD SHX Text
SAMH AG083 (#2) T.C.=979.92 I.E.(N)=973.71 I.E.(SW)=972.77 I.E.(SE)=972.72
AutoCAD SHX Text Sidewalk
AutoCAD SHX Text Sidewalk
AutoCAD SHX Text Sidewalk
AutoCAD SHX Text Sidewalk
AutoCAD SHX Text NOTE: IF BRINGING IN BASE MAPPING UTILITIES PLEASE ADJUST ELEVATIONS TO CURRENT (EXISTING) TP10. (BASE MAPPING ELEVATIONS ARE ADJUSTED ELEVATIONS TO OPUS) OPUS TP10 N: 545717.183 E: 2561981.051 EL: 987.211
AutoCAD SHX Text Pull Up Bars
AutoCAD SHX Text Flag Pole
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text Sign
AutoCAD SHX Text
AutoCAD SHX Text
SAMH ABANDONED
AutoCAD SHX Text CB2x2 T.C. 965.68 Inv.(N) 959.44 Inv.(SW) 963.43 Inv.(SE) 958.96 Inv.(NE) 959.47 Inv.(NW) 959.44
AutoCAD SHX Text Existing Track
AutoCAD SHX Text Track
AutoCAD SHX Text
8"DIP
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
ELECT.
AutoCAD SHX Text Bleachers
AutoCAD SHX Text
BUILDING 207 F.F.E. 977.00
AutoCAD SHX Text Mon.
AutoCAD SHX Text Existing Volleyball Court
AutoCAD SHX Text Existing Parade Field
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
REVISIONS:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
PROJ. NO:
AutoCAD SHX Text
DRAWN:
AutoCAD SHX Text
CHECKED:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
SHEET NO.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text N
AutoCAD SHX Text M
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text L
AutoCAD SHX Text K
AutoCAD SHX Text J
AutoCAD SHX Text H
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text C
AutoCAD SHX Text B
AutoCAD SHX Text A
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text G
AutoCAD SHX Text 240 West Bessemer St. Alcoa, TN. 37701
AutoCAD SHX Text
ph. 865 980 3500 fax. 865 980 3555
AutoCAD SHX Text
COR
AutoCAD SHX Text H:\USPFO\47.242 - REPAIR TEC PHYSICAL FITNESS AREA\02-DRAWINGS\SHEETS\C1-4 EROSION & SEDIMENT CONTROL PLAN - FINAL.DWG PLOTTED ON:April 17, 2024 11:24 AM BY:TIM CHILDRESSPLOTTED ON:April 17, 2024 11:24 AM BY:TIM CHILDRESSApril 17, 2024 11:24 AM BY:TIM CHILDRESS11:24 AM BY:TIM CHILDRESSBY:TIM CHILDRESSTIM CHILDRESS
AutoCAD SHX Text Knoxville, Tennessee
R ep ai r
TE
C
P h ys ic al F it n es s
A re a
4t h A ir R ef u el in g W in g
PSXE242020
4.4.24
1. SLOPE AND ELEVATION REQUIREMENTS
ALL EXCAVATING, FILLING AND GRADING REQUIREMENTS AND COMPACTING WORK OF THE SUBBASE SHOULD BE PERFORMED SO THAT THE FINISHED SUBGRADE IS 4″-6″ ABOVE THE SURROUNDING GROUND AND SLOPES NOT LESS THAN 0.83% (1:120) AND NOT MORE THAN 0.1 1:100). EACH COURT MUST SLOPE IN A TRUE PLANE, PREFERABLY FROM SIDE TO SIDE (BUT FROM END TO END OR FROM CORNER TO CORNER ALSO ARE ACCEPTABLE), OR IN THE SHORTEST DIRECTION FOR GOOD DRAINAGE AND WATER RUNOFF. THE COURT SHOULD NEVER BE SLOPED FROM THE NET LINE TO THE BASELINE, FROM THE BASELINE TO THE NETLINE, FROM THE SIDES TO THE CENTERLINE OR FROM
THE CENTERLINE TO THE SIDES.
2. MOISTURE/VAPOR BARRIER
A MOISTURE/VAPOR BARRIER, CONSISTING OF POLYETHYLENE (10 MIL. MINIMUM THICKNESS) SHOULD BE INSTALLED PRIOR TO INSTALLATION OF ANY STEEL, CABLES, OR CONCRETE. OVERLAP POLYETHYLENE SHEETS AT LEAST 6″ AND TAPE JOINTS. ONCE IN PLACE NO VEHICULAR TRAFFIC SHOULD BE ALLOWED ON THE MOISTURE/VAPOR BARRIER NOR ANY OTHER OBJECT WHICH COULD PUNCTURE THE BARRIER OR OTHERWISE COMPROMISE THE INTEGRITY OF THE SURFACE. ALL CONCRETE SHALL BE PUMPED, NOT
DRIVEN ONTO THE COURT. EXCESSIVE LOADS AT ANY TIME ARE UNACCEPTABLE.
3. CEMENT
CEMENT (TYPE 1 OR 1A) SHOULD CONFORM TO ONE OF THE
STANDARD SPECIFICATIONS FOR PORTLAND CEMENT, ASTM C 150 OR SPECIFICATIONS FOR BLENDING HYDRAULIC CEMENTS, ASTM C 595, EXCLUDING SLAG CEMENTS TYPES S AND SA. DO NOT USE CURING COMPOUNDS.
4. AIR ENTRAINMENT
AIR ENTRAINMENT BY TOTAL VOLUME OF CONCRETE SHOULD BE:4 TO 6% FOR 1 1/2″ MAXIMUM SIZE COARSE AGGREGATE, 5 TO 7% FOR 3/4″ OR 1″ MAXIMUM SIZE COARSE AGGREGATE, 6 1/2 TO 8 1/2% FOR 3/8″ OR 1/2″ MAXIMUM SIZE COARSE AGGREGATE.
5. AGGREGATE
AGGREGATE SHOULD CONFORM TO STANDARD SPECIFICATIONS FOR CONCRETE AGGREGATES ASTM C 33. FOR CONCRETE WORK THAT IS 5″ THICK, THE NOMINAL SIZE OF THE COARSE AGGREGATE SHOULD NOT EXCEED 1 1/2″ AND FOR CONCRETE WORK THAT IS 4″ THICK, THE NOMINAL SIZE OF THE COARSE AGGREGATE SHOULD NOT BE GREATER THAN 1″. FLY ASH OR OTHER ADDITIVES ARE NOT ACCEPTABLE.
6. POST-TENSIONING
POST-TENSIONING MATERIAL SHOULD CONSIST OF SEVEN WIRE STRESS-RELIEVED STRANDS, CONFORMING TO ASTM A 416, WITH AN ULTIMATE STRENGTH OF 270 KSI. STRANDS SHOULD BE COATED WITH A PERMANENT RUST PREVENTATIVE LUBRICANT AND WRAPPED WITH PLASTIC SHEATHING. IF STRAND SHEATHING IS DAMAGED OR REMOVED, IT IS TO BE REPAIRED BY TAPING. A MAXIMUM OF 6″ EXPOSED STRAND IS PERMITTED AT THE ANCHOR. END ANCHORAGE DEVICES WILL CONFORM TO POST-TENSIONING INSTITUTE (PTI) SPECIFICATIONS.
ALL DEAD END ANCHORAGES MUST BE POWER SEATED. ALL STRANDS ARE TO BE SUPPORTED ON CHAIRS AND TIED AT ALL INTERSECTIONS OR SECURELY SUPPORTED IN BEAMS TO PREVENT VERTICAL AND HORIZONTAL MOVEMENT DURING CONCRETE PLACEMENT. CABLES SHOULD BE LAID OUT IN GRIDS NO GREATER THAN 4′ ON CENTER. CONCRETE MUST BE WELL CONSOLIDATED, ESPECIALLY IN THE VICINITY OF STRAND ANCHORAGES. STRANDS SHOULD BE ANCHORED AT 28.9 KIPS, BUT MAY BE INITIALLY STRESSED AT 33 KIPS. A 9” DIAMETER CENTERED ON THE STRAND AXIS BY A 36″ LENGTH SHOULD BE ALLOWED FOR STRESSING EQUIPMENT CLEARANCE. THE STRESSING PROCESS GENERATES TREMENDOUS PRESSURES AND EXTREME CARE SHOULD BE TAKEN TO PREVENT INJURY FROM OPERATOR ERROR OR FAILURE OF EQUIPMENT OR MATERIALS. SLABS SHOULD BE DESIGNED USING ACCEPTABLE ENGINEERING PRACTICES IN ACCORDANCE WITH THE AMERICAN CONCRETE INSTITUTE BUILDING CODE REQUIREMENTS FOR REINFORCED CONCRETE AND THE POST-TENSIONING INSTITUTE'S TENTATIVE SPECIFICATIONS FOR POST-TENSIONING MATERIALS. THE SOIL CONDITION AND PLASTICITY INDEX OF THE COURT SITE SHOULD BE CONSIDERED IN DETERMINING STRAND SPACINGS AND BEAM REQUIREMENTS.
7. FORMS
FORMS SHOULD BE SET ACCURATELY TO THE LINES AND GRADES INDICATED ON DRAWINGS AND SECURED TO PREVENT SETTLEMENT OR MOVEMENT DURING PLACING OF CONCRETE. FORMS SHOULD REMAIN IN PLACE UNTIL CONCRETE HAS TAKEN ITS FINAL SET.
8. CONCRETE PROPORTIONING AND MIXING
THE CONCRETE SHOULD HAVE A COMPRESSIVE STRENGTH OF NOT LESS THAN 3,000 PSI AT 28TH DAY AFTER CASTING. READY-MIXED CONCRETE SHOULD BE MIXED AND DELIVERED IN ACCORDANCE WITH ASTM C 94, SPECIFICATION FOR READY-MIXED CONCRETE WITH A 4″
MAXIMUM SLUMP.
9. PLACING AND FINISHING
CONCRETE SHALL BE PLACED BY PUMPING METHOD. AT LEAST A FULL COURT SHOULD BE
PLACED IN ONE CONTINUOUS OPERATION WITHOUT INTERVENING JOINTS OF ANY KIND. CONCRETE SHOULD BE SPREAD, CONSOLIDATE D, SCREEDED, BULL-FLOATED AND FINISHED IN ACCORDANCE WITH SECTION 7.2 OF ACI (AMERICAN CONCRETE INSTITUTE) STANDARD 302, RECOMMENDED PRACTICE FOR CONCRETE FLOOR AND SLAB CONSTRUCTION. WHEN CONCRETE IS SUFFICIENTLY SET TO WITHSTAND FOOT PRESSURE WITH ONLY ABOUT 1/4″ INDENTATION AND THE WATER SHEEN HAS LEFT THE SURFACE, THE SLAB SHOULD BE UNIFORMLY FINISHED BY POWER FLOATING AND TROWELING. THE FINAL FINISH TEXTURE SHOULD BE A MEDIUM BROOM FINISH UNLESS OTHERWISE SPECIFIED BY THE SURFACE MANUFACTURER. NO CURING COMPOUNDS SHOULD BE USED AT ANY TIME.
10. SURFACE TOLERANCES
THE FINISHED SURFACE OF THE COURT SHALL NOT VARY MORE THAN 1/8″ IN 10′ WHEN MEASURED IN ANY DIRECTION.
11. CURING
IMMEDIATELY AFTER FINISHING, THE CONCRETE SHOULD BE KEPT CONTINUOUSLY MOIST FOR 7 DAYS BY COVERING WITH POLYETHYLENE
FILM OR WATERPROOF CURING PAPER, OR BY SPRINKLING OR PONDING OR OTHER ACCEPTABLE COVERINGS. NO CURING COMPOUNDS SHOULD BE USED AT ANY TIME. CURING TIME SHOULD BE IN ACCORDANCE WITH SURFACING SYSTEM MANUFACTURER'S RECOMMENDATIONS. TIMING IS CRITICAL ON ALL OF THE ABOVE DUE TO THE POSSIBILITY OF DISTURBING THE FINISHED SURFACE.
POST-TENSIONED CONCRETE NOTES:
A1 TYPICAL NET LACING DIAGRAM
NOT TO SCALE
A4 TENNIS NET POST FOOTING
NOT TO SCALE
F1 TYPICAL SINGLE COURT LAYOUT PLAN
NOT TO SCALE
F4 TYPICAL SECTIONS POST-TENSIONED CONCRETE COURT PAVEMENT
NOT TO SCALE
J1 TENNIS NET CENTER STRAP ANCHOR
NOT TO SCALE
K11 TYPICAL TENNIS NET ELEVATIONS
NOT TO SCALE
COURT PAVEMENT
CENTER STRAP ANCHOR
CONCRETE FOOTING
COMPACTED CRUSHED
STONE BASE COURSE
COMPACTED SUBGRADE
SECTION
PLAN
12" Ø
15"-24"
6"
15" Ø
12" Ø15" Ø
CONCRETE FOOTING
(BELOW POST TENSIONED CONCRETE)
CENTER STRAP ANCHOR
ALIGN PIN WITH TENNIS NET
NET LINE
TYPICAL ELEVATION OF A PROPERLY LACED NET
NET LACING DIAGRAM
NOTE:
THE NET SHOULD BE INSTALLED
WITH A RECOMMENDED TENSION
OF 500 TO 550 LBS.
CENTER STRAP ANCHOR
CENTER STRAPNET POST TYP.
42' CENTER TO CENTER OF NET POSTS
21' 21'
3'-0"3'-6"
3'-0" 36' COURT WIDTH 3'-0"
120'
60'
MINIMUM COURT SIZE
TENNIS NET
NET POST LOCATIONS:
33'-0" ℄ TO ℄ SINGLES COURT
SECTION PLAN
NET POST
(LACING ROD OPTIONAL)
COURT
PAVEMENT
NET POST SET
IN SLEEVE
CONCRETE
FOOTING BASE
POUR TO STABLE
UNDISTURBED SOIL
NET
TIGHTENER
18" Ø
2'-6" SQ.
3'-6"
3'-0"
( OR TO
FROST DEPTH)
CONCRETE
FOOTING TOP
NET POST SET
IN SLEEVE
CONCRETE
FOOTING BASE
18" Ø2'-6" SQ.
SECTION THICKENED COURT EDGE
SECTION KEY JOINT AT NET LINE
POST TENSIONED CONCRETE SLAB
COMPACTED STRUCTURAL FILL
1/2" Ø CABLE
KEYED CONSTRUCTION JOINT ALIGNED WITH
TENNIS NET LINE. COORDINATE CAULK
MATERIAL WITH SURFACE MANUFACTURER.
6"
2"
10' MIN.
FLUSH CONCRETE MORTAR PATCH ALL
CABLE ANCHORS AFTER FINAL TIGHTENING
#4 BAR CONTINUOUS, TIED IN AT ANCHOR
CABLE (SPACING VARIES BASED ON SLAB SIZE)
FENCE POST
POST-TENSIONED
CONCRETE SLAB
COMPACTED
STRUCTURAL FILL
1/2" Ø CABLE
(2) #4 BARS CONTINUOUS
HORIZONTAL (2" MIN CLEAR)
THICKENED CONCRETE EDGE
AT FENCE POST (TYP.)
12" Ø
4"
C2.1
D et ai ls
LEN
JTG
4"
1'-6"
A4 C2.1
J1 C2.1
WATER STOP
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
REVISIONS:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
PROJ. NO:
AutoCAD SHX Text
DRAWN:
AutoCAD SHX Text
CHECKED:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
SHEET NO.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text N
AutoCAD SHX Text M
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text L
AutoCAD SHX Text K
AutoCAD SHX Text J
AutoCAD SHX Text H
Aut…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .