1333ND26QNB610206 Questions and Answers Attachment 1.docx.pdf
PDF 87 KB Posted
- Attached to
- Fabrication, Design and Manufacturing IDIQ
- Solicitation number
- 1333ND26QNB610206
About this file
This file is a parameter setting and configuration document for a LeakSystemController Tuned Ladder22 device (Model UT35A-002-11-00/DC). The document contains detailed system data, setup parameters, operation parameters, and ladder program logic for a PID (Proportional-Integral-Derivative) control system.
The device is configured with PID control type featuring four setpoint groups and two PID groups. Key operational parameters include a 4-20mA analog input with a scale range of 0.00 to 10.00, control output cycle time of 600 seconds, and Ethernet connectivity with IP address 192.168.1.1, subnet mask 255.255.255.0, and port 502. The primary setpoint is configured at 6.10 with a high alarm limit of 7.50. PID Group 1 is tuned with a proportional band of 3.0%, integral time of 100 seconds, and reverse action control, while PID Group 2 uses 5.0% proportional band and 240-second integral time with 60-second derivative time. Four alarms are configured: Alarm-1 and Alarm-3 for high PV limits with energized output, and Alarm-2 and Alarm-4 for low PV limits. The ladder program includes input/output calculations and user logic for parameter comparisons and output control. This appears to be a technical configuration file rather than a solicitation or procurement document, with no associated pricing, delivery dates, or contractual requirements.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Amendment 0001 Combined Synopsis Solicitation.docx | DOCX document | |
| 1333ND26QNB610206 Amendment 0001.docx | DOCX document | |
| 1333ND26QNB610206 Final Questions and Answers.docx | DOCX document | |
| Final Solicitation Documents.zip | ZIP file |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
2026/06/24 09:36
File Information
Customer Name
Delivery Destination
Device Name
Model Name
Order No.
Serial Number
Author
Date Created
Specification Number
Revision No.
Function Overview
Memo
System Data
Name Set Value
Model and suffix codes : UT35A-002-11-00/DC
PARAMETER VERSION R1.06.03
LADDER SEQUENCE FUNCTION USE
MCU VERSION R1.06.04
DCU VERSION R1.02.01
ECU-1 VERSION R-.--.--
ECU-3 VERSION R1.01.02
ECU-4 VERSION R-.--.--
PRODUCT VERSION S11.01
Setup Parameter - CTL
D Register Symbol Name Set Value Unit
CNT_L1 CONTROL TYPE PID:PID control
SPGR. NUMBER OF SP GROUPS 4
ZON ZONE PID SELECTION 0:SP group number selection 1
PIDG. NUMBER OF PID GROUPS 2
Setup Parameter - PV
D Register Symbol Name Set Value Unit
IN PV INPUT TYPE 4-20:4.00 to 20.00mA
UNIT PV INPUT UNIT -:No unit
RH MAXIMUM VALUE OF PV INPUT RANGE 20.00
RL MINIMUM VALUE OF PV INPUT RANGE 4.00
SDP PV INPUT SCALE DECIMAL POINT POSITION 2:###.##
SH MAXIMUM VALUE OF PV INPUT SCALE 10.00
SL MINIMUM VALUE OF PV INPUT SCALE 0.00
BSL PV INPUT BURNOUT ACTION OFF:Disable
A.BS PV ANALOG INPUT BIAS 0.00
A.FL PV ANALOG INPUT FILTER OFF s
Setup Parameter - MPV_L1
D Register Symbol Name Set Value Unit
P.UNI_L1 CONTROL PV INPUT UNIT -:No unit
P.DP_L1 CONTROL PV INPUT DECIMAL POINT POSITION 2:###.##
P.RH_L1 MAXIMUM VALUE OF CONTROL PV INPUT RANGE 10.00
P.RL_L1 MINIMUM VALUE OF CONTROL PV INPUT RANGE 0.00
SPH_L1 SP HIGH LIMIT 10.00
SPL_L1 SP LOW LIMIT 0.00
Setup Parameter - OUT
D Register Symbol Name Set Value Unit
Setup Parameter - OUT
D Register Symbol Name Set Value Unit
OT.H HEATING-SIDE CONTROL OUTPUT SELECTION 02:OUT terminals
(current)
CT CONTROL OUTPUT CYCLE TIME 600.0 s
RTS RETRANSMISSION OUTPUT TYPE OF RET OUT1:OUT (Valve opening: 0 to 100 % in
Position proportional control)
O1RS RETRANSMISSION OUTPUT TYPE OF OUT OUT1:OUT (Valve
CURRENT OUTPUT opening: 0 to 100 % in
Position proportional control)
OU.A OUT CURRENT OUTPUT RANGE 4-20:4 to 20 mA
RET.A RET CURRENT OUTPUT RANGE 4-20:4 to 20 mA
Setup Parameter - ETHR_E3
D Register Symbol Name Set Value Unit
HSR_E3 HIGH-SPEED RESPONSE MODE 1
BPS_E3 BAUD RATE 38400:38.4k bps
PRI_E3 PARITY EVEN:Even
IP1_E3 IP ADDRESS 1 192
IP2_E3 IP ADDRESS 2 168
IP3_E3 IP ADDRESS 3 1
IP4_E3 IP ADDRESS 4 1
SM1_E3 SUBNET MASK 1 255
SM2_E3 SUBNET MASK 2 255
SM3_E3 SUBNET MASK 3 255
SM4_E3 SUBNET MASK 4 0
DG1_E3 DEFAULT GATEWAY 1 0
DG2_E3 DEFAULT GATEWAY 2 0
DG3_E3 DEFAULT GATEWAY 3 0
DG4_E3 DEFAULT GATEWAY 4 0
PRT_E3 PORT NUMBER 502
IPAR_E3 IP ACCESS RESTRICTION OFF:Disable
1.IP1_E3 PERMITTED IP ADDRESS 1-1 255
1.IP2_E3 PERMITTED IP ADDRESS 1-2 255
1.IP3_E3 PERMITTED IP ADDRESS 1-3 255
1.IP4_E3 PERMITTED IP ADDRESS 1-4 255
2.IP1_E3 PERMITTED IP ADDRESS 2-1 255
2.IP2_E3 PERMITTED IP ADDRESS 2-2 255
2.IP3_E3 PERMITTED IP ADDRESS 2-3 255
2.IP4_E3 PERMITTED IP ADDRESS 2-4 255
Setup Parameter - KEY
D Register Symbol Name Set Value Unit
Setup Parameter - KEY
D Register Symbol Name Set Value Unit
F1-K USER FUNCTION KEY-1 ACTION SETTING OFF:Disable
F2-K USER FUNCTION KEY-2 ACTION SETTING OFF:Disable
Fn-K USER FUNCTION KEY-N ACTION SETTING PID:PID tuning switch
Setup Parameter - DISP
D Register Symbol Name Set Value Unit
PCMD_L1 ACTIVE COLOR PV DISPLAY SWITCH 0:Fixed in white
BAR1 BAR-GRAPH DISPLAY REGISTRATION 5:Deviation
BDV_L1 BAR-GRAPH DEVIATION DISPLAY BAND 0.10
GUID GUIDE DISPLAY ON/OFF ON:Display
ECO ECONOMY MODE OFF:Disable
BRI BRIGHTNESS 3
MLSD LEAST SIGNIFICANT DIGITAL MASK OF PV OFF:With least
DISPLAY significant digit
MKTP METHOD FOR LEAST SIGNIFICANT DIGITAL MASK 0:Round down
OF PV DISPLAY
Setup Parameter - CSEL
D Register Symbol Name Set Value Unit
CS1 SELECT DISPLAY-1 REGISTRATION OFF
CS2 SELECT DISPLAY-2 REGISTRATION OFF
CS3 SELECT DISPLAY-3 REGISTRATION OFF
CS4 SELECT DISPLAY-4 REGISTRATION OFF
CS5 SELECT DISPLAY-5 REGISTRATION OFF
Setup Parameter - KLOC
D Register Symbol Name Set Value Unit
COM.W COMMUNICATION WRITE ENABLE/DISABLE OFF:Enable
DATA-L FRONT PANEL PARAMETER DATA KEY LOCK OFF:Unlock
A/M-L FRONT PANEL A/M KEY LOCK OFF:Unlock
Setup Parameter - DI.SL
D Register Symbol Name Set Value Unit
A/M-D AUTO/MAN SWITCH X_DI1
R/L_L1-D REMOTE/LOCAL SWITCH OFF
S/R-D STOP/RUN SWITCH X_DI2
AUTO-D SWITCH TO AUTO OFF
MAN-D SWITCH TO MAN OFF
REM_L1-D SWITCH TO REMOTE OFF
LCL_L1-D SWITCH TO LOCAL OFF
AT-D AUTO-TUNING START/STOP SWITCH OFF
LAT-D LATCH RELEASE OFF
LCD-D LCD BACKLIGHT ON/OFF SWITCH OFF
PVRW_L1-D PV RED/WHITE SWITCH OFF
Setup Parameter - DI.NU
D Register Symbol Name Set Value Unit
SP.B0-D BIT-0 OF SP NUMBER OFF
SP.B1-D BIT-1 OF SP NUMBER OFF
SP.B2-D BIT-2 OF SP NUMBER OFF
PN.B0-D BIT-0 OF PID NUMBER OFF
PN.B1-D BIT-1 OF PID NUMBER OFF
PN.B2-D BIT-2 OF PID NUMBER OFF
MP.B0_L1-D BIT-0 OF MANUAL PRESET OUTPUT NUMBER OFF
MP.B1_L1-D BIT-1 OF MANUAL PRESET OUTPUT NUMBER OFF
MP.B2_L1-D BIT-2 OF MANUAL PRESET OUTPUT NUMBER OFF
SP.BC-D BIT CHANGING METHOD OF SP NUMBER 0:Status switch 1
(Operation by key keystrokes or via communication is enabled according to the conditions.)
Setup Parameter - ALM
D Register Symbol Name Set Value Unit
AL1.S AL1 FUNCTION SELECTION ALO1_L1
AL2.S AL2 FUNCTION SELECTION ALO2_L1
AL3.S AL3 FUNCTION SELECTION ALO3_L1
OR.S OUT RELAY FUNCTION SELECTION OFF
Setup Parameter - SYS
D Register Symbol Name Set Value Unit
R.MD RESTART MODE CONT:Continue action set before power failure.
R.TM RESTART TIMER 0 s
EPO INPUT ERROR PRESET OUTPUT 0:Preset output
FREQ POWER FREQUENCY 60:60Hz
QSM QUICK SETTING MODE OFF
LANG GUIDE DISPLAY LANGUAGE ENG:English
Setup Parameter - LVL
D Register Symbol Name Set Value Unit
LEVL PARAMETER DISPLAY LEVEL STD:Standard setting mode
Operation Parameter - ALRM_L1
D Register Symbol Name Set Value Unit
AL1.T_L1 ALARM-1 TYPE 1:PV high limit
AL1.W_L1 ALARM-1 STAND-BY ACTION 1:With Stand-by action
AL1.D_L1 ALARM-1 ENERGIZED/DE-ENERGIZED 0:Energized
AL1.L_L1 ALARM-1 LATCH 1:Latch action 1
Operation Parameter - ALRM_L1
D Register Symbol Name Set Value Unit
AL2.T_L1 ALARM-2 TYPE 2:PV low limit
AL2.W_L1 ALARM-2 STAND-BY ACTION 0:Without Stand-by action
AL2.D_L1 ALARM-2 ENERGIZED/DE-ENERGIZED 0:Energized
AL2.L_L1 ALARM-2 LATCH 0:OFF
AL3.T_L1 ALARM-3 TYPE 1:PV high limit
AL3.W_L1 ALARM-3 STAND-BY ACTION 0:Without Stand-by action
AL3.D_L1 ALARM-3 ENERGIZED/DE-ENERGIZED 0:Energized
AL3.L_L1 ALARM-3 LATCH 0:OFF
AL4.T_L1 ALARM-4 TYPE 2:PV low limit
AL4.W_L1 ALARM-4 STAND-BY ACTION 0:Without Stand-by action
AL4.D_L1 ALARM-4 ENERGIZED/DE-ENERGIZED 0:Energized
AL4.L_L1 ALARM-4 LATCH 0:OFF
VT1_L1 PV VELOCITY ALARM TIME SETPOINT 1 1.00 m.s
VT2_L1 PV VELOCITY ALARM TIME SETPOINT 2 1.00 m.s
VT3_L1 PV VELOCITY ALARM TIME SETPOINT 3 1.00 m.s
VT4_L1 PV VELOCITY ALARM TIME SETPOINT 4 1.00 m.s
HY1_L1 ALARM-1 HYSTERESIS 0.10
HY2_L1 ALARM-2 HYSTERESIS 0.10
HY3_L1 ALARM-3 HYSTERESIS 0.10
HY4_L1 ALARM-4 HYSTERESIS 0.10
DYN1_L1 ALARM-1 ON-DELAY TIMER 0.00 m.s
DYN2_L1 ALARM-2 ON-DELAY TIMER 0.00 m.s
DYN3_L1 ALARM-3 ON-DELAY TIMER 0.00 m.s
DYN4_L1 ALARM-4 ON-DELAY TIMER 0.00 m.s
AMD_L1 ALARM MODE 0:Always active
Operation Parameter - SP_L1 - Group1
D Register Symbol Name Set Value Unit
SP_L1_1 TARGET SETPOINT 6.10
PIDN_L1_1 PID NUMBER SELECTION 1
A1_L1_1 ALARM-1 SETPOINT 7.50
A2_L1_1 ALARM-2 SETPOINT 0.00
A3_L1_1 ALARM-3 SETPOINT 0.00
A4_L1_1 ALARM-4 SETPOINT 0.00
Operation Parameter - SP_L1 - Group2
D Register Symbol Name Set Value Unit
SP_L1_2 TARGET SETPOINT 0.00
PIDN_L1_2 PID NUMBER SELECTION 1
A1_L1_2 ALARM-1 SETPOINT 0.00
A2_L1_2 ALARM-2 SETPOINT 0.00
Operation Parameter - SP_L1 - Group2
D Register Symbol Name Set Value Unit
A3_L1_2 ALARM-3 SETPOINT 0.00
A4_L1_2 ALARM-4 SETPOINT 0.00
Operation Parameter - SP_L1 - Group3
D Register Symbol Name Set Value Unit
SP_L1_3 TARGET SETPOINT 0.00
PIDN_L1_3 PID NUMBER SELECTION 1
A1_L1_3 ALARM-1 SETPOINT 0.00
A2_L1_3 ALARM-2 SETPOINT 0.00
A3_L1_3 ALARM-3 SETPOINT 0.00
A4_L1_3 ALARM-4 SETPOINT 0.00
Operation Parameter - SP_L1 - Group4
D Register Symbol Name Set Value Unit
SP_L1_4 TARGET SETPOINT 0.00
PIDN_L1_4 PID NUMBER SELECTION 1
A1_L1_4 ALARM-1 SETPOINT 0.00
A2_L1_4 ALARM-2 SETPOINT 0.00
A3_L1_4 ALARM-3 SETPOINT 0.00
A4_L1_4 ALARM-4 SETPOINT 0.00
Operation Parameter - SPS_L1
D Register Symbol Name Set Value Unit
RT_L1 REMOTE INPUT RATIO 1.000
RBS_L1 REMOTE INPUT BIAS 0.00
UPR_L1 SP RAMP-UP RATE OFF
DNR_L1 SP RAMP-DOWN RATE OFF
TMU_L1 SP RAMP-RATE TIME UNIT HOUR:Ramp-up rate or ramp-down rate per hour
SPT_L1 SP TRACKING SELECTION ON
PVT_L1 PV TRACKING SELECTION OFF
Operation Parameter - PVS_L1
D Register Symbol Name Set Value Unit
BS_L1 PV INPUT BIAS 0.00
FL_L1 PV INPUT FILTER OFF s
Operation Parameter - PID_L1 - Group1
D Register Symbol Name Set Value Unit
P_L1_1 PROPORTIONAL BAND 3.0 %
I_L1_1 INTEGRAL TIME 100 s
D_L1_1 DERIVATIVE TIME OFF s
OH_L1_1 CONTROL OUTPUT HIGH LIMIT 100.0 %
Operation Parameter - PID_L1 - Group1
D Register Symbol Name Set Value Unit
OL_L1_1 CONTROL OUTPUT LOW LIMIT 0.0 %
MR_L1_1 MANUAL RESET 50.0 %
DR_L1_1 DIRECT/REVERSE ACTION SWITCH RVS:Reverse action
PO_L1_1 PRESET OUTPUT 30.0 %
Operation Parameter - PID_L1 - Group2
D Register Symbol Name Set Value Unit
P_L1_2 PROPORTIONAL BAND 5.0 %
I_L1_2 INTEGRAL TIME 240 s
D_L1_2 DERIVATIVE TIME 60 s
OH_L1_2 CONTROL OUTPUT HIGH LIMIT 100.0 %
OL_L1_2 CONTROL OUTPUT LOW LIMIT 0.0 %
MR_L1_2 MANUAL RESET 50.0 %
DR_L1_2 DIRECT/REVERSE ACTION SWITCH RVS:Reverse action
PO_L1_2 PRESET OUTPUT 0.0 %
Operation Parameter - TUNE_L1
D Register Symbol Name Set Value Unit
SC_L1 SUPER FUNCTION 1:Overshoot suppressing function
(normal mode)
AT.TY_L1 AUTO-TUNING TYPE 1:Stability
AR_L1 ANTI-RESET WINDUP AUTO %
OPR_L1 OUTPUT VELOCITY LIMITER OFF %
MPON_L1 MANUAL PRESET OUTPUT NUMBER SELECTION OFF:Hold the control output in AUTO mode
(bumpless)
MPO1_L1 MANUAL PRESET OUTPUT 1 0.0 %
MPO2_L1 MANUAL PRESET OUTPUT 2 0.0 %
MPO3_L1 MANUAL PRESET OUTPUT 3 0.0 %
MPO4_L1 MANUAL PRESET OUTPUT 4 0.0 %
MPO5_L1 MANUAL PRESET OUTPUT 5 0.0 %
Operation Parameter - ZONE_L1
D Register Symbol Name Set Value Unit
RP1_L1 REFERENCE POINT 1 10.00
RHY_L1 ZONE PID SWITCHING HYSTERESIS 0.05
RDV_L1 REFERENCE DEVIATION OFF
Operation Parameter - PPAR
D Register Symbol Name Set Value Unit
P01D P01 DECIMAL POINT POSITION 1:####.#
P02D P02 DECIMAL POINT POSITION 1:####.#
P03D P03 DECIMAL POINT POSITION 0:#####
Operation Parameter - PPAR
D Register Symbol Name Set Value Unit
P04D P04 DECIMAL POINT POSITION 0:#####
P05D P05 DEICMAL POINT POSITION 0:#####
P06D P06 DECIMAL POINT POSITION 0:#####
P07D P07 DECIMAL POINT POSITION 0:#####
P08D P08 DECIMAL POINT POSITION 0:#####
P09D P09 DECIMAL POINT POSITION 0:#####
P10D P10 DECIMAL POINT POSITION 0:#####
P01 P01 PARAMETER 7.5
P02 P02 PARAMETER 0.0
P03 P03 PARAMETER 0
P04 P04 PARAMETER 0
P05 P05 PARAMETER 0
P06 P06 PARAMETER 0
P07 P07 PARAMETER 0
P08 P08 PARAMETER 0
P09 P09 PARAMETER 0
P10 P10 PARAMETER 0
Ladder Program Name:Logic Input Ladder Calculation PAGE1
Ladder Program Name:Logic Output Ladder Calculation PAGE1
Ladder Program Name:Logic User Ladder PAGE1
Constant Ladder Program Name:Logic
Constant Decimal point position
K01 0 0:#####
K02 0 0:#####
K03 0 0:#####
K04 0 0:#####
K05 0 0:#####
K06 0 0:#####
K07 0 0:#####
K08 0 0:#####
K09 0 0:#####
K10 0 0:#####
K11 0 0:#####
K12 0 0:#####
K13 0 0:#####
K14 0 0:#####
K15 0 0:#####
K16 0 0:#####
K17 0 0:#####
K18 0 0:#####
K19 0 0:#####
K20 0 0:#####
K21 0 0:#####
K22 0 0:#####
K23 0 0:#####
K24 0 0:#####
K25 0 0:#####
K26 0 0:#####
K27 0 0:#####
K28 0 0:#####
K29 0 0:#####
K30 0 0:#####