This document is Amendment 0003 to Solicitation No. 1333MF26Q0102, issued by the National Marine Fisheries Service (NMFS) Field Delegates on September 10, 2026, with an effective date of September 10, 2026. The amendment is not extended and responds to questions received during the solicitation period.
The solicitation addresses replacement of a defective Automatic Transfer Switch (ATS) controller at an NMFS facility. The existing equipment specifications are: Eaton ATC 300+ model ATC3C2X40400XDU (Serial #044447), 400 amps, 480 volts, with cabinet #478C642H01. The contractor must remove and dispose of the defective transfer switch controller and associated defective switchgear from the campus. The work involves replacing equipment that provides power to the Maintenance Building, Boiler, and AC Control Room. Work must be coordinated with Campus Point of Contact Michael Cordova to minimize operational disruption; ideally scheduling occurs during after-hours (5:00 PM or later), weekends, or non-campus work days to avoid campus air conditioning loss. The contractor is responsible for opening all electrical panels and must comply with applicable regulatory requirements set by city and state regulators. Campus personnel will provide escort services and unlock buildings, while field verification will be conducted jointly by both the contractor and facility personnel. Prints and files for existing systems will be made available to the awarded contractor on-site. The amendment includes 29 numbered Q&A responses clarifying scope, equipment details, inspection standards, access requirements, and documentation procedures for the electrical system work.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Combined_Synopsis_Solicitation_Amd_0004_Q_A_Corrections__1333MF26Q0102_(26-513)_0004.pdf | ||
| Sol_1333MF26Q0102_Amd_0004.pdf | ||
| Combined_Synopsis_Solicitation_Amd_0003_Q_A__1333MF26Q0102_(26-513)_0003.pdf | ||
| Sol_1333MF26Q0102_Amd_0002.pdf | ||
| Sol_1333MF26Q0102_Amd_0001.pdf | ||
| Sol_1333MF26Q0102.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Offers must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended, by one of the following methods:
(a) By completing items 8 and 15, and returning or (c) By separate letter or electronic communication which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGMENT TO BE RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY RESULT IN REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted, such change may be made by letter or electronic communication, provided each letter or electronic communication makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.
E. IMPORTANT: is not is required copies to the issuing office.
AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT 1. CONTRACT ID CODE
2. AMENDMENT/MODIFICATION NUMBER 3. EFFECTIVE DATE 4. REQUISITION/PURCHASE REQUISITION NUMBER 5. PROJECT NUMBER (If applicable)
7.ADMINISTERED BY (If other than Item 6) CODE
STANDARD FORM 30 (REV. 11/2016)
Prescribed by GSA FAR (48 CFR) 53.243
FACILITY CODE
9A. AMENDMENT OF SOLICITATION NUMBER
9B. DATED (SEE ITEM 11)
10A. MODIFICATION OF CONTRACT/ORDER NUMBER
10B. DATED (SEE ITEM 13)
11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS
The above numbered solicitation is amended as set forth in Item 14. is extended. is not extended.
12. ACCOUNTING AND APPROPRIATION DATA (If required) copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted;
13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS.
IT MODIFIES THE CONTRACT/ORDER NUMBER AS DESCRIBED IN ITEM 14.
CHECK ONE A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE CONTRACT ORDER
NUMBER IN ITEM 10A.
B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES (such as changes in paying office, appropriation data, etc.) SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(b).
C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:
D. OTHER (Specify type of modification and authority)
Except as provided herein, all terms and conditions of the document referenced in Item 9A or 10A, as heretofore changed, remains unchanged and in full force and effect.
15C. DATE SIGNED
15A. NAME AND TITLE OF SIGNER (Type or print)
16C. DATE SIGNED
16A. NAME AND TITLE OF CONTRACTING OFFICER (Type or print)
14. DESCRIPTION OF AMENDMENT/MODIFICATION (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)
PAGE
6. ISSUED BY CODE
8. NAME AND ADDRESS OF CONTRACTOR (Number, street, county, State and ZIP Code) (X)
CODE
15B. CONTRACTOR/OFFEROR
(Signature of person authorized to sign)
16B. UNITED STATES OF AMERICA
(Signature of Contracting Officer)
Previous edition unusable
PAGESOF
Contractor
The hour and date specified for receipt of Offers to sign this document and return
RAYNIER CAMERINO
See continuation page
NMFS Field Delegates
601 EAST 12TH STREET SUITE 1746
KANSAS CITY MO 64106
NMFS-FD
1333MF26Q0102
09/10/2026
08/29/2026
1 7
1333MF26Q0102 0003
Continued...
Continuation page from block 14.
The purpose of this amendment is to respond to the questions received for Solicitation No.
1333MF26Q0102
Combined Synopsis Solicitation No. 1333MF26Q0102 Response to Questions:
A separate attachment is provided under the file name "Combined Synopsis Solicitation Amd_0003 Q&A_ 1333MF26Q0102 (26-513)" to provide images that are not visible on the SF30 document.
1. If you wish us to quote the actual part, we would need a part number, please. Or a picture of the nameplate of the existing unit would be extremely helpful as well.
Make: Eaton ATC 300+ Model #: ATC3C2X40400XDU Serial Number #: 044447
2. There is no detail in the attachment about the ATS itself. Can you please provide the amperage, voltage, cabinet, bypass/non-bypass, SER rated, etc.?
AMPS: 400
Volts: 480 Cabinet # 478C642H01
3. I will need more details on what is existing to be able to provide pricing. Do you have the serial # off of the existing ATS that is being replaced? Are there any one-lines or specifications available?
Make: Eaton ATC 300+ Model #: ATC3C2X40400XDU Serial Number #: 044447 Line drawings or blue prints indicating routing of power lines into the campus would have to be cleared by security office as they are details about the critical infrastructure on the campus.
4. Please confirm the required ATS configuration, including transition type, service-entrance rating, and whether a 3-pole or 4-pole switched-neutral arrangement is required.
5. The RFQ states that the contractor shall remove and dispose of the existing ATS and “associated switchgear.” Please clarify which equipment is included in this scope and identify what must be removed, replaced, modified, or reconnected.
The contractor will remove the defective transfer switch controller and remove from the campus all packing material, defective parts that will be replaced (defective switch gear) that is associated with the project.
6. Please provide the maximum allowable electrical shutdown duration, any required outage windows, and whether temporary power is required during the replacement.
The transfer switch controller that is to be replaced provides power to the Maintenance Building, Boiler and AC Control Room. When power is cut for the replacement of the defective equipment the campus will be without Air Conditioning. Coordination with the Campus POC (Michael Cordova) will have to be made in advance so that staff members can be diverted from the campus. Ideally work can be accomplished either during after hours (starting at 5:00pm, weekend or non-campus work day.
With coordination the interruption of the day to day work can be minimalized.
7. Existing Power System Models:
Will the Government provide existing SKM or other power system models for each facility? If available, will the editable/native model files be provided to the awarded consultant?
Prints and files will be made available to awarded contractor for use on site.
8. Previous Study Reports and Drawings:
Are previous Arc Flash Studies, Protective Device Coordination Studies, Short-Circuit Studies, and electronic single-line diagrams available for review?
Sent directly to COR to large to attached here.
9. Access to Energized Equipment:
Will qualified Government personnel/electricians be responsible for opening all energized electrical equipment, including switchgear, switchboards, panelboards, MCCs, ATSs, transformers, and other equipment, during the site survey? Or is the consultant expected to provide qualified electricians to perform this work?
The campus personnel will open (unlock) the panels and buildings where the work will be performed, however, the opening all energized electrical equipment, including switchgear, switchboards, panelboards, MCCs, ATSs, transformers, and other equipment will be done by interested qualified parties.
10. Electrical Equipment Inventory:
Will the Government provide an existing electrical equipment inventory for each facility, including switchgear, switchboards, panelboards, MCCs, ATSs, transformers, disconnects, generators, and other major electrical equipment?
Listed in study sent to COR.
11. Electrical Inspection / Field Verification:
For the required electrical system inspection and field verification, please clarify the expected level of inspection. Is the consultant expected to perform only a visual inspection and collect nameplate data, or is a detailed internal inspection required?
The appropriate industry standard that will keep us in compliance and allow for the panels to be certified.
12. Is there a current SLD for the facility for the electrical distribution systems?
One is available on campus but not authorized to release, Prints and files will be made available to awarded contractor for use on site.
13. Are there One-line diagrams for new construction if not represented on Facility one lines available?
One is available on campus but not authorized to release, Prints and files will be made available to awarded contractor for use on site.
14. Is there a prior electrical study completed within the last 6 years that can be provided?
Last study was the ARC Flash Study conducted in 2023.
15. Is there a complete software model for the facility?
There is not a digital model available, only hard copy.
16. Is there an up-to-date electrical site plan for the facilities?
Yes
17. Will the center be coordinating and providing the current required utility information to execute the analysis?
Available on campus but not authorized to release, Prints and files will be made available to awarded contractor for use on site.
18. The SOW does not require an emergency power analysis, is this correct?
Yes
19. The SOW does not require a facility grounding assessment, is this correct?
Yes
20. Is there any electrical equipment located in places that would need to be surveyed oA hours or weekends?
No
21. Will a full-time escort be provided to unlock doors and show around the team during the Site Investigation?
Yes
22. Are any hot work permits, safety plans, or documentation required prior to being onsite and conduct the investigation on energized equipment?
It is the contractors requirement to be incompliance with applicable regulatory requirement set by the city and state regulators.
23. The SOW calls out “89 electrical panels which need to be certified as safe from Arc Flash.” As Arc Flash labels are to be installed on any equipment they maybe worked on while energized, does this number include the other electrical equipment that may require an Arc Flash Label?
Detailed listing of previous ARC Flash Certification was provided to COR (in separate document)
24. Who is to conduct the Required Field Verification for the final report? Is the Contractor walking it back down or is the station backchecking it?
It will be a joint verification.
25. Will there be reviews performed by the center and if so how many, when and duration?
What reviews are they referring to?
26. Will there be electricians provided to open the electrical equipment, or will the contractor need to provide their own?
It is the contractors responsibility to open all panels
27. Is there any access requirements to being onsite?
Each visit will require all personnel to sign-in in the appropriate building and be escorted to job site.
28. To allow time to factor in the responses to these RFIs and considering the upcoming holiday, would you please consider extending the due date?
All RFI’s have been answered, request no extensions.
29. We understand from Amendment 0001 that this is a new study and that electrical drawings, one-line diagrams, panel schedules, and campus maps are not currently available for distribution. Could you please confirm whether any other system information is available electronically, such as a partial equipment inventory, utility data, protective-device information, or equipment photographs? If no additional information is available, we will prepare our quotation using only the information currently posted on the solicitation portal and contained in the published solicitation documents and amendments.
Photos attached of equipment
| Amendment of solicitation/modification of contract |
| Contract ID code |
| Amendment/modification number |
| Effective date |
| Requisition/purchase requisition number |
| Project number |
| Issued by |
| Code |
| Administered by |
| Code |
| Name and address of contractor |
| Code |
| Facility code |
| Amendment of solicitation number |
| Dated |
| Modification of contract/order number |
| Dated |
| This item only applies to amendments of solicitations |
| Accounting and appropriation data |
| This item applies only to modifications of contracts/orders. |
| This change order is issued pursuant to: |
| The above numbered contract/order is modified to reflect the administrative changes |
| This supplemental agreement is entered into pursuant to authority of: |
| Other |
| Important: |
| Description of amendment/modification |
| Name and title of signer |
| Contractor/offeror |
| Date signed |
| Name and title of contracting officer |
| Signature of Contracting Officer |
| Date signed |
| Previous edition unusable |
| Standard form 30 (rev. 11/2016) |
File details come from the government source that posted it. Updated .