132491_MECH_DWG.pdf
PDF 4 MB Posted
- Solicitation number
- W90VN824R0061
About this file
This document is a set of mechanical drawings and specifications for the repair of Quonset Hut Building S-1709 at Camp Casey in Korea. The key details include:
The mechanical scope of work involves repairing the heating, cooling, ventilation, and plumbing systems. This includes installing new split heat pump systems, electric wall heaters, air conditioning units, unit heaters, piping, insulation, controls, and related accessories. The ventilation system will be repaired by installing a new energy recovery ventilator, exhaust fans, ductwork, and intake louvers. The plumbing system will be repaired by installing a new electric domestic hot water heater, water cooler, domestic water piping, and plumbing fixtures. The drawings provide detailed schematics, equipment schedules, and installation instructions for the mechanical systems.
The overall project also includes civil, architectural, electrical, and structural repairs to the building. The contract opportunity is solicitation number W90VN824R0061, issued by the Department of the Army Materiel Command Army Contracting Command for the "Repair Quonset Hut Building S-1709, Camp Casey (MATOC Only)".
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 132491_STRC_DWG.pdf | ||
| 132491_ARCH_DWG.pdf | ||
| W90VN824R0061.pdf | ||
| 132491_ELEC_DWG.pdf | ||
| 132491-CIVIL_DWG.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
M-1
A
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
MECHANICAL
SYMBOLS
MECHANICAL MATERIAL INDICATIONS &
M E C H A N I C A L M A T E R I A L I N D I C A T I O N S & S Y M B O L S
NTS
PD
Pa
OS&Y
OXY
OD
OAIL
OA
QT
PRV
PPM
POL
POC
PLMB
PH
PG
RT
RPM
RH
RDTR
RA
R12, R22
QTY
A B B R E V I A T I O N S
SBM
SAN
SA
SCH
FLOWMETER, ORIFICEBUTTERFLY
REFRIGERANT LIQUID
CHILLED WATER SUPPLY
CHILLED WATER RETURN
AIR COOLED CONDENSING UNIT
AIR CONDITION UNIT (S)
APPARATUS DEW POINT
AIR CONDITION (-ING,-ED)
CHILLED/HOT WATER RETURN
AMERICAN WIRE GAUGE
PRESSURE, BAROMETRIC
CUBIC METER PER HOUR
CHILLED/HOT WATER SUPPLY
CAPACITYCAP
CONNECTION
CONTINUE
COMPRESSOR
CUBIC METER
CPRSR
CONN
CONT
CU M
CHILLED WATER
CAST IRON PIPE
CIRCUIT
CLASSIFICATION
COOLING LOAD
COEFFICIENT
COUNTER CLOCKWISE
CLASS
CLG LOAD
COEF
CMH
CIP
CCW
CHW
CKT
ACV ALARM CHECK VALVE
AVERAGEAVG
BOILING POINT
CENTIGRADE
BAROMETER(-TRIC)
BRAKE HORSEPOWER
BP
BHP
C
BARO PR
AWG
BARO
ALUMINUM
ALTITUDE
AMBIENT
AIR HANDLING UNIT
AMPERE(AMP, AMPS)
APPROXIMATEAPPROX
ALT
AMB
AMP
AIR COND
ADP
AL
AHU
AIR COOLED
ACCU
ACLD
ACU
CHR
C/HWR
C/HWS
CHS
RL
D DRAIN
DIAMETER, INSIDE
ISOMETRIC
IRON PIPE SIZE
JOULE
THERMAL CONDUCTIVITY
KILOGRAM
KILOGRAM PER SQ. CENTIMETER (GAUGE)
KILOGRAM PER SQ. CENTIMETER
KILOGRAM PER SQ. CENTIMETER (ABSOLUTE)
KILOCALORIE PER HOUR
EXPANSION JOINT
EXPLOSION PROOF
FIRE HOSE CABINET
FULL LOAD AMPERES
ENTERING WATER TEMP
EVAPORAT (-E,-ING,-ED,-OR)
EXTERNAL STATIC PRESSURE
FACE AREA OR FRESH AIRFA
FHC
FHY
FLA
FIRE HYDRANT
ESP
EXPJT
EWT
EVAP
EP
EQPT
ENT
EFF
EQUIPMENT
ENTERING
EFFICIENCY
KG/SQ CM
KG/SQ CM A
KG/SQ CM G
KG
KCAL/HR
J
K
ID
ISO
IPS
NO
N.O.
NIC
NPT
MPS
NC
N/A
N.C.
MAX
MIN
MPH
MM
NOT IN CONTRACT
NATIONAL TAPER PIPE (THREAD)
NUMBER
NORMALLY OPEN
MINIMUM OR MINUTE
METERS PER HOUR
METERS PER SECOND
NORMALLY CLOSED
NOISE CRITERIA
NOT APPLICABLE
MAXIMUM
MILLIMETER R
FEMALE PIPE THREAD
FUEL OIL
GALVANIZED STEEL
GAGE OR GAUGE
FIXTURE
FEED WATER PUMP
FACE VELOCITY
FLUSH VALVE
FREQUENCY
FIBERGLASS REINFORCED PLASTIC
HORIZONTAL
HOT WATER HEATER
HOT WATER
HOUR(S)
HORSEPOWER
MERCURY
HEAD
HOSE BIBB
HERTZ
GRAMS
FRPCWP CIRCULATING WATER PUMP
DIRECT EXPANSION
DRY PIPE VALVE
EQUIVALENT DIRECT RADIATION
ENTERING AIR TEMPERATURE
DOUBLE POLE DOUBLE THROW
DEWPOINT TEMPERATURE
DRY BULB TEMPERATURE
DECIBEL OR DRY BULB
DIESEL OILDO
ECON
ECC
EAT
EDR
DX
DPV
DPDT
DPT
ECONOMIZER
ECCENTRIC
o
DIFF
DIAG
DIA or
DIV
DBT
DB
DIFFERENCE
DIAGRAM
DIAMETER
DIVISION
DEGREE
HR
HORIZ
HWH
HW
HZ
HP
HG
HD
HB
GALVS
GA
GR
FXTR
FWP
FVEL
FV
CUBIC MILLIMETER
CLOCKWISE OR COLD WATER
COEFFICIENT, VALVE FLOWCv
CU MM
CW
PLUG VALVE
THREE WAY
FPT
FO
FREQ
GATE, ANGLE
GATE, GLOBE
GLOBE
GATE
CONTROL
KJ KILOJOULE
LH
LT
LWT
LPS
M
LL
LPD
LPH
LM
LAV
LAT
LBS
LG
KW
KWH
L
LATENT HEAT
LEAVING WATER TEMPERATURE
LITERS PER HOUR
LITERS PER SECOND
LAUNDRY TRAY
METERS
LIQUID LINE
LITERS PER DAY
LINEAR METER
LEAVING AIR TEMPERATURE
LAVATORY
POUNDS
LENGTH
KILOWATT
KILOWATT HOUR
LITERS
P
FLOWMETER, VENTURI
FLOW SWITCH
PRESSURE SWITCH
PRESSURE GAUGE AND COCK
PUMP (INDICATE USE)
STRAINER
STRAINER, BLOW OFF
KG/SM
KG/SM A
KG/SM G
PS
P
OFM
FS
VFM
KILOGRAM PER SQ. METER
KILOGRAM PER SQ. METER (ABSOLUTE)
KILOGRAM PER SQ. METER (GAUGE)
JACKET WATER RETURN
MEDIUM PRESSURE STEAM
MEDIUM PRESSURE CONDENSATE
LOW PRESSURE STEAM
LOW PRESSURE CONDENSATE
BOILER BLOW DOWN
PUMPED CONDENSATE
JACKET WATER SUPPLY
VACUUM PUMP DISCHARGE
FUEL OIL TANK VENT
CONDENSATE WATER SUPPLY
CONDENSATE WATER RETURN
MEDIUM TEMPERATURE HOT WATER SUPPLY
MEDIUM TEMPERATURE HOT WATER RETURN
LOW TEMPERATURE HOT WATER SUPPLY
LOW TEMPERATURE HOT WATER RETURN
PIPE TO BE REMOVED
REFRIGERANT DISCHARGE
REFRIGERANT SUCTION
LPS
CONTROL AIR MAIN
air conditioning and refrigeration
RD
RS
(NAME)E
(NAME)
M
EXISTING PIPE
COMPRESSED AIR
VACUUM (AIR)
HWR
VAC
A
MTWS
MTWR
HWS
FOD FUEL OIL DRAIN
FOR
CS
CR
FOV
FOG
FOS FUEL OIL SUPPLY
FUEL OIL RETURN
FUEL OIL GAUGE
PC
VPD
MU
LPC
BBD
MAKE UP WATER
MPS
MPC
JWR
JWS
heating
PIPING
CHECK, SWINGSANITARY DRAIN
PITCH OR PIPE, UP(U), DOWN(D)
FLOOR SINK (200mm x 200mm)
PIPE SLEEVE WITH FIRE STOPPING
VENT THRU ROOF
BFP
valves : (for selective actuators)
PLAN
HOSE BIBB
AIR LINEA
BALL
ELEV.
BACKFLOW PREVENTER
PIPE SLEEVE
(NAME)
ACID
200mm x 200mm
SURFACE CLEANOUT
FLOOR CLEANOUT
FLOOR DRAIN
CHEMICAL SUPPLY PIPES
FUNNEL DRAIN, OPEN
FCO
FD
SCO
FLOOR OR GRADE
FLOOR OR GRADE
CONDENSATE DRAIN BELOW
CONDENSATE DRAIN ABOVE
ACID WASTE
GASG
CD
CD
AIR VENT, MANUAL
AIR VENT, AUTOMATIC
W/ MEASURING TAP
EXPANSION LOOP
EXPANSION JOINT
BALL JOINT
ANCHOR, MAIN
ANCHOR, INTERMEDIATE
ALIGNMENT GUIDE
AIR SEPARATOR
FLEXIBLE CONNECTOR
SQUARE HEAD BALANCING COCK
EJ
S
MV
AVV
CHECK, NON-SLAM
CONTROL, ELECTRIC-PNEUMATIC
CONTROL, PNEUMATIC-ELECTRIC
QUICK OPENING
PRESSURE REDUCING
NEEDLE
LOCK SHIELD
HOSE END DRAIN
SAFETY
RELIEF
SQUARE HEAD BALANCING COCK
QUICK CLOSING, FUSIBLE LINK
R
S
PE
EP
plumbing
COLD WATER
HOT WATER RETURN
HOT WATER SUPPLY
VENT
MOTOR ELECTRIC
DIAPHRAGM
valves, special duty :
SOLENOIDS
valve actuators
M
FDAD
SUCTIONQUANTITY SUCT
TONS OF REFRIGERATION
TEMPERATURE DIFFERENCE
HEAT TRANSFER COEFFICIENT
SANITARY
SUBMERSIBLE
SUPPLY AIR
SCHEDULE
RADIATOR
REFRIGERATION TON
REVOLUTIONS PER MINUTE
RELATIVE HUMIDITY
RETURN AIR
THERMAL RESISTANCE
REFRIGERANT (12, 22, ETC)
TYPICALTYP
URINAL
UNIT HEATER
UR
UH
U
THERMOSTAT
THICKNESS
THERMOMETER
TEMPERATURE
SYMBOL
TSTAT
TONS
THERM
THK
TEMP
TD
SYM
SINGLE POLE DOUBLE THROW
LPH, STANDARD CONDITIONS
LPS, STANDARD CONDITIONS
LPD, STANDARD CONDITIONS
SAYBOLT SECONDS UNIVERSAL
SAYBOLT SECONDS FUROL
SENSIBLE HEATOUTSIDE AIR INTAKE LOUVER SH
PRESSURE DROP OR DIFFERENCE
PRESSURE REDUCING VALVE
PHASE (ELECTRIC)
PERCENT
PARTS PER MILLION
POINT OF CONNECTION
PLUMBING
PETROLEUM, OIL AND LUBRICANTS
QUART
OUTSIDE SCREW & YOKE
DIAMETER, OUTSIDE
PRESSURE GAGE
POLE
PASCAL
OXYGEN
SPRINKLERSPR
STEEL
STANDARD
STEAM
SQUARE
STAINLESS STEEL
STORAGESTOR
STL
STD
ST
SSU
SST
SSF
SQ
SENSIBLE LOAD
STATIC PRESSURE
SQUARE METER
SPECIFICATION
SPDT
SPEC
SM
SP
SLPH
SLPS
SLPD
SL
ALARM CHECK VALVE
SIDEWALL SPRINKLER
PENDENT SPRINKLER
UPRIGHT SPRINKLER
FIRE DEPARTMENT CONNECTION
PRE-ACTION VALVE
NOT TO SCALE
OUTSIDE AIR
(2-WAY SHOWN)
DRY-PIPE VALVE
SECOND
SAFETY FACTOR
SPECIFIC GRAVITYSG
SF
SEC
VARIABLE AIR VOLUMEVAV
VENTILATION
PRESSURE, DYNAMIC(VELOCITY)
WATER-COOLED
WATER CLOSET
WATTHOUR OR WATER HEATER
WET BULB TEMPERATURE
WATERPROOF
WSHR
WCLD
WTRPRF
WH
WT
W/
WD
WC
WBT
WEIGHT
WITH
WASHER
WIDTH
VP
VOL
WB
W
VISC
VERT
VENT
VEL
VOLUME
WET BULB
WATT
VISCOSITY
VERTICAL
VELOCITY
MANUAL VOLUME DAMPER
SMOKE DAMPER (PROVIDE ACCESS DOOR)
PNEUMATIC OPERATED DAMPER
VLV
V
VAC
M
VALVE
VOLT
VACUUM
SPLITTER DAMPER
SD
AD
VD
grilles, registers and diffusers :
SG
SR
600/300
300x150
200mm NCD
FIGURE IS ON TOP
810mm x 400mm dampers
ELBOW, TURNED DOWN
REDUCER, CONCENTRIC
REDUCER, ECCENTRIC (STRAIGHT, INVERT)
REDUCER, ECCENTRIC (STRAIGHT, DOWN)
TEE, OUTLET DOWN
TEE, SINGLE SWEEP
sprinkler
UNION, SCREWED
UNION, FLANGED
TEE, OUTLET UP
TEE
LATERAL
CONNECTION, BOTTOM
CONNECTION, TOP
ELBOW, TURNED UP
BUSHING
CAP
WELDED
FLANGED
SOLDERED
SCREWED BELL AND SPIGOT
SOLVENT CEMENT
SOUND ATTENUATOR
DETECTORS, FIRE AND/OR SMOKE
ELECTRIC MOTOR OPERATED DAMPER
FIRE DAMPER (PROVIDE ACCESS DOOR)
BACKDRAFT DAMPER
BDD
S
TRANSITION
TURNING VANES
SF
CHANGE OF ELEVATION, RISE(R), DOWN(D)
DUCT SECTION, NEGATIVE PRESS., FIRST
ACCESS DOOR, VERTICAL OR HORIZONTAL
COWL, (GOOSENECK) AND FLASHING
ACOUSTICAL LINING
FLEXIBLE DUCT
FLEXIBLE CONNECTIONFC
FIGURE IS ON TOP
R
AD
47.2
TG
94.4
UC 13mm
DG
500/300L
DUCT WORK
810mm x 400mm
810mm x 400mm
THERMOSTAT, ELECTRIC
TRAP, ELECTRIC (INDICATE TYPE)
fitting :
R
THERMOMETER
EXHAUST AIR GRILLE OR REGISTER, CEILING
DUCT SECTION, POSITIVE PRESS., FIRST
DIRECTION OF FLOW
SR
DIFFUSER, LINEAR
RETURN AIR GRILLE OR REGISTER, CEILING
CEILING DIFFUSER, SQUARE TYPE
CEILING DIFFUSER, ROUND TYPE (200mm
(600mm x 300mmH, 472 LPS)
UNDERCUT DOOR (13mm, 47.2 LPS)
DOOR GRILLE (300mmx150mmH)
NECK DIAMETER)
TRANSFER GRILLE ASSEMBLY
LOUVER, DOOR OR WALL
(500mmWx300mmH, 94.4 LPS)
RG
RR
SUPPLY AIR GRILLE OR REGISTER, SIDEWALL
EXHAUST AIR GRILLE OR REGISTER, CEILING
SUPPLY AIR GRILLE OR REGISTER, CEILING
ER
SG
EG
EXISTING WORK TO BE REMOVED.
POINT OF CONNECTION NEW TO EXISTING
OR END OF DEMOLITION WORK
EXISTING WORK TO REMAIN.(E)
(R) REMOVE EXIST WORK
C
A
CHONG, ST
REPAIR QUONSET HUT BUILDING S-1709
CAMP CASEY
132491
M-2
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
MECHANICAL
SCOPE OF WORK MECHANICAL GENERAL NOTES
3. MARK ALL EXPOSED INTERIOR PIPING AT 8 METER(26 FT) INTERVALS, WITH PLASTIC WRAPAROUND TYPE PIPE LABLES
CONFORMING TO ASME/ANSI A13,1-1996 "SCHEME FOR IDENTIFICATION OF PIPING SYSTEMS", INDICATING THE TYPE
OF FLUID CARRIED AND DIRECTION OF FLOW. LABELS ARE NOT REQUIRED ON SPRINKLER SYSTEM BRANCH LINES AND
PIPES LESS THAN 50MM (2 INCHES) IN NOMINAL.
4. PROVIDE ALL SEISMIC PROTECTION MEASURES FOR THE FIRE PROTECTION SYSTEM IAW NFPA 13 FOR "PROTECTION OF
PIPING AGAINST DAMAGE WHERE SUBJECT TO EARTHQUAKES". INCLUDING, BUT NOT LIMITED TO, SWAY BRACINGS, FLEXIBLE COUPLINGS, CLEARANCES, AND SEPARATION ASSEMBLES.
5. PROVIDE LABEL TAG INDICATING "NORMALLY OPEN" OR "NORMALLY CLOSED" ON ALL VALVES INCLUDING AND NOT LIMITED
TO ALL RISER AND TRIM, SECTIONAL VALVES, INSPECTIORS TEST VALVES AND DRAINS.
6. SPRINKLERS WITH O-RINGS ARE NOT PERMITTED. PLUG TYPE TAMPER SWITCH SHALL NOT BE USED.
7. INSATLL SYSTEM TEST CONNECTION ON WET PIPE SYSTEM AND SHALL BE LOCATED AT THE MOST REMOTE BRANCH LINE.
8. ALL VALVES ON WET PIPE SYSTEM SHALL MEET NFPA 13 REQUIREMENT.
9. THE CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING ALL EXISTING CONDITION AND DIMENSIONS PRIOR TO
COMMENCING ANY CONSTRUCTION OR RENOVATION.
10. THE CONTRACTOR SHALL VERIFY EXISTING CONDITIONS FOR NEW WORK SUCH AS EQUIPMENT & SERVICE CLEARANCE, EQUIPMENT PAD SIZE, INSTALLATION LOCATIONS, AND ADDITIONAL ITEMS.
13. CONNECT TO EXISTING SYSTEM SHALL BE DONE IN SUCH A MANNER AS NOT DAMAGE THE EXISTING EQUIPMENT ANY
14. CONTRACTOR SHALL SUBMIT MANUFACTURERS INSTALLATION SHOP DRAWINGS FOR APPROVAL BY GOVERNMENT.
15. FOR O & MA PROJECTS, KOREA, OCTOBER 1, 2003 DEPARTMENT OF THE ARMY FORM AS A PART OF THIS PROJECT. THE
DETAILS WILL BE UTILIZED WHILE PERFORMING THE MECHANICAL SCOPE OF WORK AT NO ADDITIONAL COST TO THE U.S.
GOVERNMENT.
16. SOME DETAILS SHOWN ON THIS CONTRACT DRAWINGS MAY NOT MATCH EXACT FIELD CONDITIONS. SUCH DETAILS SHALL BE
PREPARED IN THE FIELD BY THE CONTRACTOR ACCORDING TO ACTUAL FIELD CONDITIONS AND SUBMITTED TO THE
CONTRACTING OFFICER FOR APPROVAL.
17. ALL MECHANICAL SYSTEMS SHALL BE TESTED, ADJUSTED AND BALANCED BY THE CONTRACTOR IN STRICT ACCORDANCE WITH
APPLICABLE SECTIONS OF DIVISION 22 & 23 - MECHANICAL, O & MA STANDARD TECHNICAL SPECIFICATIONS FOR
MISCELLANEOUS PROJECTS, KOREA. THE HVAC TESTING, ADJUSTING AND BALANCING (TAB) REPORT SHALL BE SUBMITTED
TO THE PROJECT COR FOR GOVERNMENT REVIEW AND APPROVAL.
18. ALL SUPPLY, RETURN AND EXHAUST AIR DUCTWORK SHALL BE CONSTRUCTED ACCORDING TO SMACNA STATIC PRESSURE
CALSS 500PA AND DUCTWORK SHALL MEET THE REQUIREMENTS OF SEAL CLASS C.
28. PROVIDE VOLUME DAMPERS ON DUCTWORK BRANCH LINES WHETHER SHOWN ON THE DRAWINGS OR NOT.
PROVIDE REMOTELY ACTUATED DAMPERS IN AREAS WITH GYPBOARD OR CONCEALED CEILINGS.
30. ANY PIPES THAT PENETRATE FIRE RATED WALL (EXISTING/NEW) SHALL BE SEALED PER SPEC.
31. LOCATION AND SIZES OF EXISTING EQUIPMENT, DUCTWORK, PIPING, ETC. APPROXIMATE AND SHALL BE VERIFIED
AT THE JOB SITE.
1. THE EQUIPMENT SHOWN ARE SUGGESTED LOCATIONS HOWEVER FINAL LAYOUT SHALL BE IN ACCORDANCE
WITH APPLICABLE CODES, MANUFACTURER'S RECOMMENDATIONS, AND EQUIPMENT LISTINGS. CONTRACTOR
SHALL COORDINATE SPRINKLER HEADS LOCATIONS WITH, LIGHTING FIXTURES, AND HVAC DEVICES. ALL EQUIPMENT
SHALL BE UL LISTED AND/OR FM APPROVED IN ACCORDANCE WITH NFPA 13, NFPA 20 AND THE PROJECT SPECIFICATION.
2. THE CLEARANCES AROUND PIPE PENETRATION AT FIRE RATED WALLS AND/OR FLOOR SHALL BE PROPERLY SEALED
WITH APPROVED FIRE STOPPING MATERIAL IAW SPECIFICATION 07 84 00.
11. THE CONTRACTOR SHALL BE RESPONSIBLE TO CONSTRUCT OR REPAIR ALL DAMAGES TO EXISTING AREAS
CAUSED BY THIS PROJECT AND TO MATCH CONDITION TO ADJACENT AREAS AS DIRECTED BY THE CONTRACTING OFFICER.
19. PROVIDE ACCESS PANELS TO ALL CONCEALED VALVES, DAMPERS, AND EQUIPMENT. PROVIDE ACCESS DOORS
IN DUCTS AT ALL AUTOMATIC CONTROL DAMPERS, FIRE DAMPERS, FIRE/SMOKE DAMPERS, DUCT SMOKE
DETECTOR, BACKDRAFT DAMPERS AND FOR ANY ITEM INDISE DUCTS REQUIRING SERVICING OR INSPECTION
12"X12" ACCESS PANELS FOR TWO VALVES. COORDINATE THE LOCATION OF ACCESS PANEL TO INSURE THAT
THE EQUIPMENT CAN BE MAINTAINED ADEQUATELY. PROVIDE REMOTELY ACTUATED DAMPERS IN AREA WITH
WITH GYPBOARD OR CONCEALED CEILINGS.
20. INSTALL CONDENSATE DRAINS AT A MINIMUM SLOPE OF 1 / 4INCH PER 1FOOT. INSULATE ALL SEWER PIPING
RECEIVING AIR CONDITIONING CONDENSATE DRAINS, OR ANY OTHER COLD LIQUID WHICH MAY CREATE
CONDENSATION, FROM SINK BODIES EXPOSED TO AIR BELOW THE FLOOR.
21. PROVIDE TURNING VANES IN ALL ELBOWS THAT CHANGE AIR DIRECTION MORE THAN 30 DEGREES OR USE
RADIUS ELBOWS. PROVIDE AIR SPLITTER DAMPERS AT ALL BRANCH TAKE-OFFS FROM THE MAIN DUCT.
PROVIDE SPIN-IN TYPE FITTINGS AT ALL ROUND DUCT TAKE-OFFS FROM SQUARE OR RECTANGULAR MAINS.
22. PIPING SYSTEM SHALL BE FLUSHED, PURGED & CLEANED PER SPECS REQUIREMENTS AND FLUSHED UNTIL
ALL WATER BEING FLUSHED IS CLEAR AS TAP WATER.
23. ALL CONDENSATE DRAINS FROM COOLING UNIT (AS NOTED ON THE DRAWINGS) SHALL BE PROVIDED WITH
SHUT-OFF VALVE WITHIN 1M OF THE UNIT.
24. DISPOSAL OF CONSTRUCTION DEBRIS, WASTE MATERIALS, MATERIALS RESULTING FROM DEMOLITION ACTIVITIES, AND THE LIKE SHALL BE DONE BY THE CONTRACTOR AT NO ADDITIONAL COST TO THE U.S. GOVERNMENT.
25. ALL EQUIPMENT CONNECTIONS TO DUCTWORK SHALL HAVE A MIN. OF 100MM OF REINFORCED CANVAS FLEXIBLE
DUCTWORK FOR VIBRATION ISOLATION.
26. PROVIDE DIFFUSERS AND GRILLE FRAMES COMPATIBLE WITH ARCHITECTURAL CEILING TYPES, REFER TO
ARCHHITECTURAL DRAWINGS FOR CEILING TYPES.
27. PROVIDE FIRE DAMPERS AT ALL DUCT PENETRATIONS THROUGH FIRE RATED WALLS AND FLOORS. FIRE DAMPER
RATINGS SHALL BE COMPATIBLE WITH THE FIRE WALL OR FLOOR. FIRE DAMPERS SHALL BE UL LISTED.
29. THE MECHANICAL/CONTROLS CONTRACTOR SHALL PROVIDE ALL THE WIRINGS, RELAYS, CONTROLLERS, CONDUITS
AND ALL NECESSARY ACCESSORIES FOR H.V.A.C CONTROLS.
32. NO MECHANICAL WORK CAN BE STARTED WITHOUT AN APPROVED SHOP DRAWINGS. SHOP DRAWING SHALL NOT
BE THE EXACT DUPLICATION OF THE CONTRACT DRAWING.
EQUIPMENT, DUCT WORK, PIPING ETC. DAMAGED DUE TO THE WORK PERFORMED UNDER THIS CONTRACT SHALL
BE REPAIRED OR REPLACED BY THIS CONTRACTOR.
12. THE CONTRACTOR SHALL BE RESPONSIBLE FOR REMOVAL AND REINSTALLATION OF ALL OBSTRUCTIONS AS
NECESSARY TO ALLOW FOR INSTALLATION AND REPLACEMENT OF MECHANICAL AND FIRE PROTECTION SYSTEM AT
NO ADDITIONAL COST TO THE GOVERNMENT, INCLUDING, BUT NOT NECESSARILY LIMITED TO ITEMS SUCH AS WALLS, CEILLING, ROOF, PIPE, DUCT, EQUIPMENT AND ELECTRICAL ITEMS.
33. PRIOR TO INSTALL NEW HVAC AND PLUMBING PIPING CONTRACTOR MUST COORDINATE WITH THE EXIST
DUCTWORK AND PIPING ELEVATION/LOCATION. IF THE EXIST DUCT ELEVATION IS CONFLICTED WITH NEW PIPING
INSTALLATION. REMOVE THE EXIST DUCTWORK AND INSTALL NEW DUCTWORK AND MAKE ALL NECESSARY DUCT
CONNECTION TO FUNCTION AS ORIGINALLY INTENDED.
MECHANICAL GENERAL NOTES AND
SCOPE OF WORK
WORK CLASS "K" (REPAIR AND MAINTENANCE WORK)
INCLUDING PLUMBING FIXTURES, AND ALL ASSOCIATED ACCESSORIES AS SHOWN ON DRAWINGS.
INSULATION, SEWER AND VENT PIPING SYSTEM, WATER HAMMER ARRESTS, FLOOR DRAIN, FLOOR CLEANOUT
ELEC. WATER COOLER, DOMESTIC HOT WATER RECIRC. PUMP, DOMESTIC COLD AND HOT WATER PIPING SYSTEM,
3. REPAIR THE PLUMBING SYSTEM BY INSTALLING NEW ELECTRIC DOMESTIC HOT WATRE HEATER, MOTORIZED DAMPER AND ALL ASSOCIATED ACCESSORIES FOR VENTILATION SYSTEM AS SHOWN ON DRAWINGS.
CONTROLS, DIFFUSERS, REGISTER, DUCTS, INSULATIONS, OUTSIDE AIR INTAKE LOUVER WITH BIRDSCREEN,
2. REPAIR THE VENTILATION SYSTEM BY INSTALLING NEW ENERGY RECOVERY VENTILATOR, EXHAUST FANS, FOR HVAC SYSTEM AS SHOWN ON DRAWINGS
INSULATIONS, CONTROLS, EQUIPMENT SUPPORT (CONC. PAD), AND ALL ASSOCIATED ACCESSORIES
ELECREIC WALL HEATER, SPLIT AIR CONDITIONING UNIT, ELECTRIC UNIT HEATER, VALVES, PIPING,
1. REPAIR THE HEATING AND COOLING SYSTEM BY INSTALLING NEW SPLIT HEAT PUMP SYSTEM, CHONG, ST
REPAIR QUONSET HUT BUILDING S-1709
M-3
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
MECHANICAL
MECHANICAL EQUIPMENT SCHEDULE - 1
NOTE :
REQUIRMENTS.
ACTUAL QUANTITIES BASED ON THE CONTRACT DOCUMENT
THE CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING
QUANTITIES ARE SHOWN FOR ESTIMATING PURPOSE ONLY,
M E C H A N I C A L E Q U I P M E N T S C H E D U L E - 1
SYMBOL ZONE DESCRIPTION
AS PER MANUFACTURER RECOMMENDATIONS.
3 SIMILAR TO LG MULTI V 5 MODEL ARUM288BTE5 OR APPROVED EQUAL.
REFRIGERANT
TYPE
HEATING CAPACITY SHALL BE BASED ON 8 DEG C
T Y P EITEM NO SERVICE
HEATING CAP.
(BTU/H)
REMARKSQTY.
OUTDOOR SPLIT SYSTEM HEAT PUMP UNIT
COOLING CAPACITY SHALL BE BASED ON 35 DEG C21NOTES :
(BTU/H)
COOLING CAP.
TYPE
REFRIGERANT
HEATING CAPACITY SHALL BE BASED ON 8 DEG C
COOLING CAP.
(BTU/H)
NOTES : 1 2 COOLING CAPACITY SHALL BE BASED ON 35 DEG CALL HEAT PUMP UNITS REFRIGERANT PIPING SHALL BE INSTALLED
INDOOR SPLIT SYSTEM HEAT PUMP UNIT
QTY. REMARKS
POWER INPUT
(W)
VOLT/PH/HZ
(BTU/H)
HEATING CAP. CFM
SERVICEITEM NO T Y P E
COMPRESSOR
TYPE
ELECTRICAL
MOP(A) MCA(A) QTY
FAN
TYPE QTY
(H/M/L)
VOLT/PH/HZ
3 SIMILAR TO LG MULTIV MODEL ARNU183TSA4 OR APPROVED EQUAL.
ELECTRICAL DATA
MCA MOP
3YEARS WARRENTY
AS PER MANUFACTURER RECOMMENDATIONS.
ALL HEAT PUMP UNITS REFRIGERANT PIPING SHALL BE INSTALLED 3YEARS WARRENTY
HPU
4-WAY CEILING CASSETTE TYPE5 OFFICE-1,2,3,4,5(102,103,104,105,106)
31 221,50019,100 70 208/ 1/ 60417/381/348 R-410A2-WAY CEILING CASSETTE TYPE3 STORAGE(112),CORRIDOR(110) 0.84 15
51 221,50019,100 79 208/ 1/ 60735/653/556 R-410A 15
4-WAY CEILING CASSETTE TYPE2 CONFERENCE RM(111)
4 SIMILAR TO LG MULTIV MODEL ARNU243TSA4 OR APPROVED EQUAL. 5 SIMILAR TO LG MULTIV MODEL ARNU183TAA4 OR APPROVED EQUAL.
324,000288,000 R-410A
ENERGY RECOVERY VENTILATION
321MULTI V 5 HEAT PUMP1
OHPU
HSS DC SCROLL 3 PROPELLER 4208/ 3/ 60 40+80 28.5+57.9 4
HEAT PUMP UNIT
SAC
SPLIT AIR CONDITIONING
QTY.ITEM NO SERVICE T Y P E COOLING CAP
(W)
31 2 4
REMARKSREFRIGERANT
TYPE
VOLT/PH/HZPOWER INPUT
(W)
1 COMM ROOM(114)
PACKAGED SPLIT AIR CONDITIONING TYPE
WALL MOUNTED
6,500 2,250 220/1/60 R-410A
CAPACITY SHALL BE BASED ON 35DEG C
1 2
4ALL AC UNIT REFRIGERANT PIPING SHALL BE INSTALLED PERMANUFACTURER RECOMMENDATIONS.
WALL MOUNTED DUCT FREE SPLIT COOLING SYSTEM WITH REMOTE ELECTRONIC CONTROLLER.
LG ELECTRINICES MODEL "NO. SW16BDKWMS OR APPROVED EQUAL.
NOTES :
MOP
(A)
30A
HPU
61 231,50028,000 199 208/ 1/ 60855/771/687 R-410A 2.09 15
ERV
T Y P EQTY.ITEM NO
ENERGY RECOVERY VENTILATION UNIT
HORIZONTAL
AIR FLOW RATE
(CFM)
POWER INPUT
(W)
SOUND
PRESSURE
dB(A)
ELECTRIC RATING REMARKS
REFERED TO "LG"MODEL NO. LZ-H080GXN0 OR APPROVED EQUAL470/470/376 420 41/38/36 208V/60Hz/1PH
(H/H/L)
HEATING CAP.
(BTU/H)(BTU/H)
COOLING CAP.
25,470 30,000
HPU
2.09
2-WAY CEILING CASSETTE TYPE1 BREAK RM(115) 41 227,30024,200 70 208/ 1/ 60512/438/364 R-410A 15 7
HPU
0.84
6 SIMILAR TO LG MULTIV MODEL ARNU283TAA4 OR APPROVED EQUAL.
CHONG, ST
REPAIR QUONSET HUT BUILDING S-1709
M-4
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
MECHANICAL
MECHANICAL EQUIPMENT SCHEDULE - 2
NOTE :
REQUIRMENTS.
ACTUAL QUANTITIES BASED ON THE CONTRACT DOCUMENT
THE CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING
QUANTITIES ARE SHOWN FOR ESTIMATING PURPOSE ONLY,
M E C H A N I C A L E Q U I P M E N T S C H E D U L E - 2
PROVIDE UNIT MTD. DISCONNECT
(AMPS)
WALL MTD TYPE
HEAVY DUTY, RECESSED
WALL MTD TYPE
2,0002 120/ 1/ 60
EH
12.5
12.5
AMPERAGE
(WATTS)
EH
REMARKS
VOLT/PH/HZ
TOTAL
1,000 120/ 1/ 60
ELEMENT CAPACITY
HEAVY DUTY, RECESSED
T Y P ESERVICEQTYITEM NO
ELECTRIC WALL HEATER
SWITCH.
PROVIDE UNIT MTD. DISCONNECT
SWITCH.
VEST-1 (101 & 116)
W & M TOILET (107 & 109)
AIR CAP.(LPS) VOLT/PH/HZHPRPM
1,600 208/1/601/100165.2
FAN CAPACITYITEM
DISCHARGE
T Y P E
HORIZONTAL
ELECTRIC UNIT HEATER
NO
QTY SERVICE
TYPE
REMARKS
208/1/60
VOLT/PH/HZ
HEATING ELEMENT CAP
POWER(KW)
EUH PROVIDE UNIT MTD. DISCONNECT SWITCH.
W/ BUILT-IN THERMOSATAT
HORIZONTAL
MECH & ELEC
RM (113)
ITEM NO Q'TY
EWC
DESCRIPTION
ELECTRIC WATER COOLER
CAPACITY : 8.0GPH, 50 DEG F DRINKING WATER
POWER : 370WATTS, 115 V, 1 PH, 60 HZ.
MODEL : ELKAY LZSTL8WSLK OR APPROVED EQUAL.
UL LISTED, NSF61 APPROVAL, BI-LEVEL, WALL MOUNT TYPE,
SENSOR-ACTIVATED BOTTLE FILLING STATION, VISUAL FILTER MONITOR,
FRONT AND SIDE BUBBLER PUSH BAR, REFRIGERATION SYSTEM,
NSF 42 & 53 CERTIFIED FILTER, 1-1/2"DRAIN
ITEM NO Q'TY
FANS
SERVICE TYPE
AIR CAP
(LPS) N O T E
FAN MOTORESP
(Pa) RPM
HP VOLT/PH/HZ
R E M A R K S
EF
115/1/60 NOTES : 1
2 DISCONNECT SWITCH
BIRDSCREEN3
BACKDRAFT DAMPER
PREFABRICATED ROOF CURB.
ROOF MOUNTED BELT DRIVE
CENTRIFUGAL FAN
431 2
431 2
ROOF MOUNTED BELT DRIVE
CENTRIFUGAL FAN
1 1,02793.3 1/4
EF
115/1/60275W. TOILET(107)/M. TOILET(109)/J/C(108)
234 1/462.3 948
ELECTRIC TYPE
WATER SYSTEM
DOMESTIC HOT
ELEMENT CAPACITY
REMARKSTYPEITEM NO SERVICE
Q'TY
VOLT/PH/HZ
3.0
KW
220/1/60 21.1 43.3
ELECTRIC HOT WATER HEATER
TEMP. RISE
(DEG C) TEMP. (DEG C)
SUPPLY WATER
(LITS)
113.6
STORAGE
CAPACITY
EWH
MECH & ELEC RM(113)
CHONG, ST
REPAIR QUONSET HUT BUILDING S-1709
M-5
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
MECHANICAL
M5 SCALE : 1 / 100-
EXIST/REMOVAL GROUND FLOOR PLAN
EXIST/REMOVAL GROUND FLOOR PLAN
ACCESSORIES.
EXHAUST FANS, INSULATIONS, CONTROLS, EQUIPMENT SUPPORT (CONC. PAD), AND ALL ASSOCIATED
ALL HVAC DUCTS, AIR CONDITIONS, PLUMBING PIPING. VALVES, DIFFUSERS, GRILLES, LOUVERS, REMOVE EXISTING DETERIORATED GAS TYPE WARM AIR FURANCES, GAS PIPING SYSTEM, HEAT PUMP SYSTEM, TURN-IN TO SUPPLY DIVISION
AND ALL ASSOCIATED ACCESSORIES.
REMOVE EXISTING DETERIORATED GAS PIPING SYSTEM,
CHONG, ST
REPAIR QUONSET HUT BUILDING S-1709
M-6
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
MECHANICAL
NEW GROUND FL HVAC PIPING PLAN
1. CONTRACTOR SHALL VERIFY EXACT LOCATION, SIZE AND
2. CONTRACTOR SHALL SUBMIT SHOP DRAWING FOR HVAC PIPING
PRIOR TO HVAC PIPING INSTALLATION.
3. PROVIDE CEILING/WALL ACCESS PANEL FOR VALVES.
NOTES :
M6-
NEW GROUND FL HVAC PIPING PLAN,
AND NOTES
DIRECTION OF HVAC PIPING AND DRAIN PIPING IN FIELD (TYP.).
GWB CEILING
ACST OR
TO CEILING)
(FINISH MATCH
16 GA STEEL FRAME
PIANO HINGE
CONTINUOUS
(LIGHT WEIGHT METAL)
FINISH MATCH TO CEILING
14 GA STL ACCESS PANEL
AS REQUIRED
CAM LATCH
STL PLATE FRAME
75 Wx6 THK
@ EACH CORNER
WIRE HANGER
10 GA.
& NUT
6 DIA BOLT
CEILING ACCESS DOOR DETAIL
W.TOILET
MECH/ELEC
COMM
M.TOILET
EWC
RM
RM
SCALE : 1 / 50
PIPE CHASE
METAL PIPE TRAY
NEW CONC.PAD
PIPE CHASE
METAL PIPE TRAY
SAC
.A .A
.A
O.A
E S
R
OFFICE-4
OFFICE-5
RM
CONFERENCE
CORRIDOR
JAN
OFFICE-3
OFFICE-2
OFFICE-1
STORAGE
BREAK RM
C
T
T
T
T
T
T T T
ACCESS DOOR(TYP)
VEST-2
T
T T
ERV
HPU
HPU
HPU
HPU
HPU
HPU
HPU
HPU
HPU
SAC
NEW CONC.PAD
HPU
VEST-1
HPU
OHPU
EH
EH
EH
EUH
CHONG, ST
REPAIR QUONSET HUT BUILDING S-1709
M-7
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
MECHANICAL
1. CONTRACTOR SHALL VERIFY EXACT LOCATION, SIZE AND
M7 SCALE : 1 / 100-
NOTES :
SUSPENDED LAY-IN OR GYPSUM BOARD CEILING.
AIR DEVICE SCHEDULE
MATCH TO CEILING COLOR INDICATED ARCH. DWG.
SUSPENDED LAY-IN OR GYPSUM BOARD CEILING.
4-WAY THROW UNLESS OTHERWISE INDICATED
USE FOR 150 DIA NECK DIA AND SMALLER.
OPPOSED BLADE DAMPER
NOMINAL FULL FACE 300x300 3-CONE
DIFFUSER FOR SURFACE MOUNTING IN
EQUALIZING DEFLECTOR OR GYPSUM BOARD.
NOMINAL FULL FACE 600x600 3-CONE
DIFFUSER FOR MOUNTING IN
USE FOR 200 DIA NECK DIA AND LARGER.
b) a)
SUPPLY
RETURN
EXHAUST
FUNCTION TYPE
E-1
R-1
UNIT NO.
S-1
REGISTER
REGISTER
TYPE ACCESSORIES
ALUMINUM
MATERIAL
FINISH
2 4 3 5
REMARKS
TRANSFERG-1 EXHAUST OR TRANSFER GRILLE
REGISTERSUPPLYS-2 1 4 2ALUMINUM
ALUMINUM
ALUMINUM
ALUMINUM 1 6-
DIRECTION OF HVAC DUCT IN FIELD (TYP.).
2. CONTRACTOR SHALL SUBMIT SHOP DRAWING FOR HVAC DUCT
PRIOR TO HVAC DUCT INSTALLATION.
AIR DEVICE SCHEDULE AND NOTES
NEW GROUND FL HVAC DUCT PLAN-1
NEW GROUND FL HVAC DUCT PLAN-1,
ROUND DIFFUSER
W.TOILET
FEC
MECH/ELEC
OFFICE-1 OFFICE-3
STORAGE
OFFICE-2
OFFICE-5
OFFICE-4
COMM
102 103 104
CORRIDOR
EWC
BREAK RM
VEST-1
RM
RM
O.A
E.A S.A
R.A
O .A
E .A
VD VD
37.7 LPS
20 LPS
20 LPS
ERV
20 LPS
20 LPS
O100
O150
O150
O100
O150
O200
O150 O150
O200
O150
O200
O200 O200
O150
O150
RM
CONFERENCE
M.TOILET
JAN
O200
O250
O200
O200
O200
O250
O150
O100
O100 O100
O150
O100
O100
O100
O150
O200
O100 O125
O150
O150 O150
O150
O100
O100
O125
O100
O100
O100
O100
O125
O100
VD
VD
VD
VD
VD
VD
VD
VD
VD
VD VD
VD
VD
VD
VD
VD
VD
VD
VD
VD
S-1: 150ONCD
12.2 LPS
S-1: 150ONCD
20 LPS
S-1: 150ONCD
13.2 LPS
x 2
S-1: 150ONCD
20 LPS
S-1: 150ONCD
37.7 LPS
S-1: 150ONCD
13.2 LPS
x 3
E-1: 150ONCD
12.2 LPS
BDD
MD
20 LPS
E-1: 150ONCD
E-1: 150ONCD
13.2 LPS
x 2
E-1: 150ONCD
13.2 LPS
x 3
E-1: 150ONCD
2 x
11 LPS
S-1: 150ONCD
2 x
11 LPS
EF
EXHAUST FAN
E-1: 200x200
37.8 LPSE-1: 250x250
2 x
118.6 LPS
VD
EF
EXHAUST FAN
M
V
MOTORIZED DAMPER
w/BIRDSCREEN AND
300x300 O.A INTAK LOUVER
VENTILATION
THERMOSTAT
BIRD SCREEN(TYP OF 2)
HOODED WALL CAP W/STS METAL
STAINLESS STEEL SQUARE SHAPE
VEST-2
CHONG, ST
REPAIR QUONSET HUT BUILDING S-1709
M-8
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
MECHANICAL
HVAC CONTROL FLOW DIAGRAM
M8-
HVAC PIPE FLOW DIAGRAM
HVAC CONTROL FLOW DIAGRAM
NOT TO SCALE
M8- NOT TO SCALE
ENERGY RECOVERY
VENTILATOR UNIT
HVAC SYSTEM
S.A
RA
T
SA
SUPPLY AIR
RETURN AIR
DX THERMOSTAT
TO/FROM
TO/FROM
HVAC SYSTEM
SHUT-DOWN
EMERGENCY
EA
OA
CONTROL BOX
TO/FROM
OUTDOOR UNIT
MOTOR DAMPER
BACKDRAFT DAMPER
MD
BDD
M8- NOT TO SCALE
ERV CONTROL DIAGRAM
HVAC PIPE FLOW DIAGRAM,
AND ERV CONTROL DIAGRAM
ERV
1ST
OHPU
HPU
ERV
HPU
HPU
HPU
HPU
HPU
HPU
HPU
HPU
OFFCIE-6
(106)
OFFICE--5
(104)
OFFICE-2
(103)
OFFICE-1
(102)
CORRIDOR
(110)
CONFERENCE RM
(111)
STORAGE
(112)
HPU
OFFICE-3
(105)
CORRIDOR
(110)
HPU
BREAK RM
(115)
1ST
OHPU
HPU
ERV
HPU
HPU
DARIN
HPU
HPU
HPU
HPU
PBL-1601H2
HPU
HPU
OFFCIE-6
(106)
OFFICE--5
(104)
OFFICE-2
(103)
OFFICE-1
(102)
CORRIDOR
(110)
STORAGE
(112)
PBL-1601H2PBL-3501H2PBL-3501H2PBL-3501H2PBL-7001H2PBL-7001H2PBL-7001H2PBL-8701H2
HPU
OFFICE-3
(105)
PBL-1601H2
CORRIDOR
(110)
HPU
PBL-3501H2
CONFERENCE RM
(111)
BREAK RM
(115)
CHONG, ST
REPAIR QUONSET HUT BUILDING S-1709
M-9
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
MECHANICAL
(OUTDOOR UNIT)
(INDOOR UNIT)
CONTROLLER
SPACE COOLING REMOTE
T
ACU
ACU
AIR CONDITIONING UNIT
BUILT-IN CONTROL
RS
RL
SEQUENCE OF OPERATION
AIR CONDITIONING UNIT
OUTDOOR UNIT SHALL CYCLE "ON-OFF"BY BUILT-IN-HEAD PRESSURE CONTROL.
SET "FAN-OFF-COOL"SWITCH TO"COOL"POSITION, SPACE THERMOSTAT CONTROLS
SOLENOID VALVE "ON-OFF"TO MAINTAIN IT'S SETPOINT OF 25.5 DEG C.
THE THERMOSTAT SHALL HAVE A TEMPERATURE RANGE OF 12.7 DEC. C
INCLUDE WALL MOUNTED THERMOSTAT AND ON-OFF SWITCH.
MANUFACTURER SHALL FURNISH THE CONTROL SYSTEM TO
SEQUENCE OF OPERATION
THE THERMOSTAT SHALL CYCLE WALL HEATER TO MAINTAIN THERMOSTAT
SETPOINT. SET THE THERMOSTAT AT 12.7 DEG.C.
TO 29.4 DEC. C.
GENERAL:
MELECTRIC UNIT HEATER
ELEC. UNIT HEATER CONTROL
THERMOSTAT &
WALL MOUNTED
ON-OFF SWITCH
SWT
(EH-1 THRU EH-5)
INTEGRAL THERMOSTAT
WALL HEATER W/
ELECTRIC WALL HEATER CONTROL
THERMOSTAT SETPOINT. SET THE THERMOSTAT AY 20 DEG. C.
THE THERMOSTAT SHALL CYCLE WALL HEATER TO MAINTAIN
SEQUENCE OF OPERATION
12.7 DEC. C TO 29.4 DEC. C.
THE THERMOSTAT SHALL HVAC A TEMPERATURE RANGE OF
INTEGRAL THERMOSTAT.
MANUFACTURER SHALL FURNISH THE SYSTEM TO INCLUDE
GENERAL
MECH RM VENT SYS CONTROL DIAGRAM
VENTILATION THERMOSTAT(T-1)
BACKDRAFT DAMPER VENTILATION TO MAINTAIN T-1 SETPOINT.
SHALL OPERATE AND OPEN O.A. INTAKE DAMPER AND MOTORIZED
WHEN SPACE TEMP. RISES ABOVE 37.7 DEG.C, ROOF EXHAUST FAN
SEQUENCE OF OPERATION
T
T-1
SET AT 37.7 DEG. C.
DM
VENT THERMOSTAT
H
OFF
H
A
OL'S
1PH 120VAC
T
DAMPER MOTOR
O.A.
C
N
W/A.O.H. SEL. SW
MAGNETIC MOTOR STARTER
G
LOUVER W/BIRDSCREEN
OUTSIDE AIR INTAKE
FOR MECH.RM.
DAMPER
MOTORIZED O.A.
O.A.
M
COMM CLO
EF
E.A.
NOT TO SCALE
NOT TO SCALE
NOT TO SCALE
NOT TO SCALE
ACU UNIT CONTROL DIAGRAM
O/L
HAND
PUMP CONTROL
DOMESTIC HOT WATER HEATER CONTROL DIAGRAM
P
G
C1
GREEN PILOT
HOLDING COIL
LIGHT
FOR P-2
MOTOR STARTER
T-1
OFF
AUTO AQUASTAT SHALL CONTROL PUMP TO MAINTAIN ITS SET POINT.
DIFFERENTIAL. AND SUITABLE FOR 8 FLA AT 120 VAC.
ITS SETPOINT. T-1 SHALL BE PROVIDED WITH A COPPER CAPILLARY.
REMOTE BULB THERMOSTAT T-1 SHALL CONTROL PUMP P-2 TO MAINTAIN
P
GROUND
AS FOLLOWS ;
SEQUENCE OF OPERATION
120V, 1PH, 60HZ
T-1 SHALL BE A REMOTE BULB
FUSE
WELL
(TYPICAL)
SEE ELECTRICAL DWGS
MOUNT IN DOMESTIC
HOT WATER RETURN PIPING
EWH
T
T-1 AQUASTAT
DOMESTIC HW
RECIRC. PUMP
SENSOR STRAP ON
P
ELECTRIC HOT WATER HEATER
NOT TO SCALE
CONTROLS
M9
M9 M9
M9
M9
CHONG, ST
REPAIR QUONSET HUT BUILDING S-1709
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
MECHANICAL
M-10
1. CONTRACTOR SHALL VERIFY EXACT LOCATION, SIZE AND
3. PROVIDE CEILING/WALL ACCESS PANEL FOR VALVES.
- M10 SCALE : 1 / 100
2. CONTRACTOR SHALL SUBMIT SHOP DRAWING FOR PLUMBING PIPING
PRIOR TO PLUMBING PIPING INSTALLATION.
DIRECTION OF HOT/COLD WATER, SEWER AND VENT PIPING IN FIELD (TYP.).
NOTES :
P.D.I
SYMBOL
WATER HAMMER ARRESTER SCHEDULE
Q' TY
FIXTURE
UNIT RATING
1 - 11
12 - 32 20 mm
15 mm
SIZE
CONN.
REMARK
COMPRESSION CHAMBER WITH EXPANSION
STAINLESS STEEL CONSTRUCTION PRESSURIZED
B
A
( TYPICAL )
W.TOILET
MECH/ELEC
OFFICE-1 OFFICE-3
STORAGE
OFFICE-2
OFFICE-5 OFFICE-4
COMM
102 103 104
105106
JAN
BREAK RM
RM
CONFERENCE
PM
VEST-1
VEST-2
RM
RM
P-1 x 4
P-3 x 3
P-5 x 4P-8
P-8
P-750
SEE CIVIL DWG
FOR CONT.
EWH
ELEC. WATER HEATER
NEW CONC. PAD
PRESSURE RELIEF VALVE
HOSE BIBB
M.TOILET
CORRIDOR
WATER HAMMER ARRESTOR
(P.D.I:"A" TYPE)(TYP OF 2)
WATER HAMMER ARRESTOR
(P.D.I:"A" TYPE)(TYP OF 2)
WATER HAMMER ARRESTOR
(P.D.I:"A" TYPE)(TYP OF 2)
50 32 40 32
40 25
EWC
WASTE
PIPE CONNECTION
H.W. VENT
BACK
R E M A R K S
PLUMBING FIXTURE SCHEDULE
C.W.
NOTES :
QTY.
P-1
SYMBOL
F I X T U R E
LAVATORY
WATER CLOSET4
3P-3 URINAL 504020 -
RESPONSIBLE FOR VERIFYING ACTUAL QUANTITIES BASED ON THE CONTRACT DOCUMENTS
1. QUANTITIES ARE SHOWN FOR ESTIMATION PURPOSE ONLY, THE CONTRACTOR SHALL BE
REQUIREMENTS.
7515 40SERVICE SINK1 15
2. ALL PLUMBING DEVICES FOR POTABLE SERVICE HAS TO CONFIRM TO NSF 61, CHAPTER 8&9
WALL MOUNTED STAINLESS STEEL TYPE.
SINGLE BOWL
KITCHEN SINK STAINLESS STEEL TYPE4015 50P-7 1
P-5
P-8
FLUSH TANK TYPE, AMERICAN STANDARD
WALL HUNG TYPE/AMERICAN STANDARD
COUNTER TOP TYPE./AMERICAN STANDARD
PLUMBING FIXTURE SCH.,
WATER HAMMER ARRESTER SCH. AND NOTES
NEW GROUND FL PLUMBING PIPING PLAN - 1
NEW GROUND FL PLUMBING PIPING PLAN-1,
CHONG, ST
REPAIR QUONSET HUT BUILDING S-1709
CAMP CASEY
CW & HW PIPING
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
MECHANICAL
M-11
- M11 SCALE : 1 / 50
NEW MECH RM & TOILET PLUMBING PIPING
1. CONTRACTOR SHALL VERIFY EXACT LOCATION, SIZE AND
3. PROVIDE CEILING/WALL ACCESS PANEL FOR VALVES.
2. CONTRACTOR SHALL SUBMIT SHOP DRAWING FOR PLUMBING PIPING
PRIOR TO PLUMBING PIPING INSTALLATION.
DIRECTION OF HOT/COLD WATER, SEWER AND VENT PIPING IN FIELD (TYP.).
NOTES :
WATER HAMMER ARRESTER SCH. AND NOTES
NEW MECH RM & TOILET PLUMBING PIPING PARTIAL PLAN-2
PARTIAL PLAN-2, PLUMBING FIXTURE SCH.,
W.TOILET
FEC
MECH/ELEC
OFFICE-1 OFFICE-3
STORAGE
OFFICE-2
OFFICE-5
OFFICE-4
COMM
102 103 104
JAN
CORRIDOR
EWC
BREAK RM
RM
CONFERENCE
VEST-1
VEST-2
RM
RM
SEE CIVIL DWG
FOR CONT.
S
100 FCO
V
V
M.TOILET
S
OPEN DRAIN
V
50 FD
50 FD
75 FD
80 VTR
V
V
V
V
V
V
V
CHONG, ST
REPAIR QUONSET HUT BUILDING S-1709
CAMP CASEY
SEWER & VENT PIPING
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
MECHANICAL
M-12
FD ECA BG HF
HOT PIPE LINE
HGD FECBG H A
CG
MF
EXPOSED
CLINCHING STAPLE @ 100 O.C.
CG OR
MF
EXPOSED
WEATHER
A
C
D
B
CLASS II ADHESIVE
OVERLAP (40)
VAPOR-BARRIER JACKET
2. HOT WATER HEATING
3. HEATED OIL PIPE LINE
1. STEAM & CONDENSATE
5. REFRIGERATION SUCTION
4. A/C CONDENSATE DRAIN
LONGITUDINAL JOINTS
COLD WATER PIPE LINE
3. DUAL TEMP. WATER
2. CHILLED WATER
1. MAKE-UP WATER
DOWN TO SHED WATER
SHALL BE OVERLAPPED
ALUMINUM JACKET
H
G
NOTE :
BAPIPING
COLD PIPE LINE
HOT PIPE LINE
D EC
INSULATION
PIPE
AREA
ITEM
80 JACKET STRIPE
F
CONCEALED
VAPOR-BARRIER JACKET
(MIN. 40 JACKET OVERLAP)
VAPOR-BARRIER COATING
10 W x 0.5 THK @300 O.C.
ALUMINUM LOCK-TYPE BANDS
80 JACKET STRIP OR
MF - MINERAL FIBER SHALL BE USED FOR HOT PIPES
CG - CELLULAR GLASS SHALL BE USED FOR COLD PIPES
SEE SPECIFICATION FOR INSULATION THICKNESS
PIPE INSULATION DETAIL3
REFRIGERANT PIPE SLEEVE DETAILS2
"B"
"A"
"A"
"B"
DRAIN PIPE
S=1/100
PIPE
REFRIGERANT
1M
ROD
HANGER
CONNECT TO MAIN PIPE
POWER WIRE
WIRE
COMMUNICATION2
HANGER BRACKET
3/8" HANGER ROD
NUT
WASHER
HANGER ROD(3/8")
STRONG ANCHOR X 4
CELING HEAT PUMP UNIT DETAILS1
OUTER TAPE
FROM HEAT PUMP
INSULATION
COVER
REFRIGERANT GAS PIPE
TO INDOOR UNIT
FROM HEAT PUMP
A
B
TO INDOOR UNIT
EXIT SIDE
(X) VERTICAL LEVEL
:IMPOSSIBLE
(O) HORIZONTAL LEVEL
:POSSIBLE
E
(X) HORIZONTAL LEVEL
:POSSIBLE BRANDH TAKE OFF LEVEL
1.MAINTAIN HORIZATAL ELVEL BETWEED
REFRIGERANT PIPES PRIOR TO /AFTER
BRANCH TAKE OFF FITTINGS.
NOTE
1,240
1,260
Mount:4ea
,6
1,240
,8
4 OUTDOORUNIT PAD DETAIL
DETAILS - 1
CHONG, ST
REPAIR QUONSET HUT BUILDING S-1709
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
MECHANICAL
M-13
DUCT INSULATIONDUCTWORK DETAILS 64 5
C cmh x Y=X
SD
A cmh B cmh
X
NOTE; ABOVE APPLY TO SUPPLY AND RETURN
W
SD
YX
W
Y
D
90° RADIUS ELBOWS
FOR D OF 300 OR MORE
USE VANED ELBOW
D LESS THAN 300
R=D Y
R1=(X+Y)/2
R2=X+Y
X OR W LESS THAN 300
Y
R1
Y
R
D
R2=X+Y
90° TEES
R1=(X+Y)/2
SD
W2
R2=W1+W2
X
R
TURNING VANES (TYP.)
RETURN ONLY
Y
BRANCH TAKEOFFS
C 300 OR MORE
MANUAL DAMPER
X OR Y LESS THAN 300
R1=(W1+W2)/2
SPLITTER DAMPER(TYP.)
PROVIDE VE WHEN COIL OR DIFFUSER IS
1,500 OR LESS FROM BRANCH TAKEOFF.
A cmhC c h m x Y=X C cmh
SD
A cmh B cmh
W
W
20° MAX.
X
W
R=W
W
NOTE; SEE SMACNA DUCT MANUAL
C LESS THAN 300
(1985) FIGS. 2-7
C c m h
A cmh
PREFERED OFFSET
FULL RADIUS WHERE POSSIBLE
OFFSETS
FROM RECTANGULAR MAIN
ROUND DUCT TAKEOFF
ALL FOUR SIDE OF DUCT 300 APART
THE 100 OVERLAP.
RIGID TYPE
CLASS II ADHESIVE UNDER
APPLY VAPOR-BARRIER JACKET)
EMBEDDED BETWEEN COATS.(WHEN FIELD
BARRIER COATING WITH GLASS CLOTH
APPLYING TWO COATS OF VAPOR-
EDGES OF THE INSULATION JOINT.
AND NOT MORE THAN 80 FROM THE
VAPOR-BARRIER JACKET
D
F
E
EXPOSED
STAPLE
OVERLAP
A ADHESIVE
B
C
FASTENER
INSULATION
VAPOR-BARRIER JACKET
F
CLASS II ADHESIVE UNDER
A
600 LARGE DUCT
D
C
E
THE 50 OVERLAP.
FLEXIBLE TYPE
B
CONCEALED
DUCT IN
AREA
ITEM
DUCT
CLASS II ADHESIVE (LESS THAN 600 DUCT) AROUND ENTIRE PERIMETER OF THE
100 O.C. WITH TYPE II VAPOR-BARRIER COATING
DUCT IN 150 WIDTH STRIPS ON 300 ON CENTER
MORE THAN 80 FROM DUCT CORNER.
BOTTOM/SIDES 450 O.C. AND NOT
ALL TRANSVERSE EDGES
DIMENSIONS
TO BE COATED WITH ADHESIVE
CB
E
FOLDED CORNER
PIN AND WASHER
ALTERNATE
(FASTENER)
12.71 TO 30.5 MPS
DUCT SECTION
UP TO 12.7 MPS
VELOCITY
(TYPICAL 1,200 OR 1,500mm)
A
E
B
LINING
C
B
C
B
C
A
E
1.NOTE :
DUCT LINING DETAIL
MAXIMUM SPACING FOR
INTERVALS ARE
LAPPED AND BUTTED CORNER
FRONT
WALL
CONSIDERING SERVICE, SUCTION AND DISCHARGE.
CONSIDER AT LEAST A SPACE AS SHOWN IN THE DRAWING,
WHEN INSTALLING THE PRODUCT,NOTE :
OUTDOORUNIT INSTALL2
FASTENERS ACTUAL
APPROXIMATE.
FIN. GRADE
150 150
SECTION
PLAN
N F S M
150150ACTUAL EQUIPMENT SIZE
AT EXPOSED EDGES
20mm CHAMFERS #4 @300 O.C.
50 CLR
CONC. PAD
150 150 150150ACTUAL EQUIPMENT SIZE
A C
T U
A L
E
Q U
IP
M E
N T
S
IZ
E
EQUIPMENT UNIT
GRAVEL BASE
150mm THK.
WITH MANUFACTURER.
FINAL PAD SIZE SHALL BE CORDINATED
6" (150mm) LARGER THAN UNIT SIZE AND
ALL EQUIPMENT CONC PAD SIZE SHALL BE
NOTE :
OHPU CONCRETE PAD DETAIL
DETAILS - 2
CHONG, ST
REPAIR QUONSET HUT BUILDING S-1709
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
MECHANICAL
M-14
PLAN
SUB EXHAUST
TYPICAL AIR HANDLING UNIT CONDENSATE
D1 = UNIT FAN OPERATING NEGATIVE PRESSURE PLUS 2"
SIDE VIEW
RISER
EXHAUST DUCT
BATH ROOM MAIN
AIR DUCT (150x100)
BATH ROOM MAIN
SUB EXHAUST
EXHAUST DUCT
RISER
DEVICE SHOWN ON
D2 = EQUAL TO "D1".
THE PLUMBING
DRAIN PIPING DETAIL
DRAWINGS
(BUT NO LESS THAN 40)
DRAIN LINE SIZE
OF AHU CONNECTION
(BUT NO LESS THAN 40)
CLEAN OUT PLUG
THREADED
TOWARDS DRAINAGE
PITCH DOWN
OF AHU CONNECTION
DRAIN LINE SIZE
D2
D1
FROM EXHAUST
GRILLE
FROM EXHAUST
GRILLE
PIPE SLEEVE-THRU FLOOR WITH
WATERPROOFING
SEALANT #2
PIPE SLEEVE - THRU INTERIOR WALL
INTERIOR WALL
CEILING
RUBBER OR
MATERIAL
PLASTIC)
METAL BAND
BACK UP
SEALANT #2
(CLOSED CELL
FLEXIBLE FOAM
AHU DRAIN PAN
(TYP)
SLEEVE
PIPE
ALL AROUND
BACK UP MATERIAL
SEALANT #2
PIPE WITHOUT INSULATION
WATERPROOFING
PIPE WITH
L
MIN 7 CLEARANCE
INSULATION
PIPE WITHOUT
INSULATION7
C
INSULATION
METAL JACKET
SLEEVE
4 LBS/SF LEAD OR
16 OUNCE COPPEER
FLASHING
FLEXIBLE FOAM
(CLOSED CELL
RUBBER OR
PLASTIC)
BACK UP
MATERIAL
PIPE WITH INSULATION
LC
METAL JACKER
FLOOR
P
IP
E
METAL BAND
AIR DUCT (150x100)
BATH ROOM EXHAUST DUCT RISER DETAIL
ANCHOR
BOLT & NUT
ISOLATOR
VIBRATION
SEE DETAIL "A"
WATER CHILLER
150150
PAD SIZE(INCH)
LENGTH
3350 -80
50 CLR
FOR
CHILLER UNIT
4# @ 1300 OC
80 CLR
2" CLR
2400 - 150
WIDTH
REMARKS
GRAVEL FILL
WATER CHILLER
FIN GRADE
25 CHAMFER
SEE DETAIL "A"
300 THK COMPACTED
NOTE ; 1. THE PAD SHOULD BE AT LEAST 6 INCHES LARGER
ALL AROUND THAN THE UNIT.
NOTE ; SUPPORT PIPE BOTH SIDE OF WALL SO THAT NO
WALL FAN
POWER ROOF FAN
RECOMMENDED BY MFG.
SCREWS SIZE & Q'TY AS
OUT SIDE
DAMPER
BACK DRAFT
WALL VENTILATOR
CONC. WALL
B Y
M F
G
CURB HT.
300 MIN.
MIN. 2 EACH SIDE
BY FAN MFR.,
RECOMMENDED
LAGBOLTS AS
POWER ROOF VENTILATOR
INSTALLATION OF GRAVITY ROOF FANS(VENTILATORS)
NOTE;
DIVISION 7 WORK
INSULATED ROOF CURVE,
EXHAUST DUCT WORK
WHERE SCHEDULED.
BACKDRAFT DAMPER
SEE ARCH. DWGS.
WOOD BLOCKING,
SEE ARCH. DWGS.
ROOF CONSTR.
SEE ARCH. DWGS.
(SPECIFIED IN DIVISION 7)
FLASHING
WOOD NAILER
ALL AROUND
GASKET SEAL
WEIGHT RESTS AT POINT OF SLEEVE
2. ACTUAL SIZE OF PAD SHALL BE COORDINATED WITH MFR
SHALL BE SIMILAR.
"D
"D 1"
PAD DETAIL
1 2 3 4
5 6 7
DETAILS - 3
CHONG, ST
REPAIR QUONSET HUT BUILDING S-1709
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
MECHANICAL
M-15
JUTE PACKING
SUPPLY
FROM BRANCH
FOR LOCATION AND
STAINLESS STEEL FLUSH TYPE ACCESS COVER PLATE
FLOOR CLEANOUT
2.CHROMIUM-PLATED BRONZE, NICKEL BRONZE,NICKEL BRASS OR
NOTES : 1.WATER-PROOF MEMBRANE IS NOT REQUIRED IN SLAB ON GRADE.
Y-BRANCH
CAST IRON
PIPE
WATER-PROOF MEMBRANE
FINISH/TILE FLOOR
WHEN NOT THRE RUN
PLUG Y-BRANCH
1/8 BEND
AREA/PIT DRAIN
DRAINS
DRAIN AND BACKWATER VALVE
SEE NOTE-2
SEE NOTE-2
FILL/BED
SEE NOTE-1
SLAB
STRUCTURAL
SEE NOTE-1
CEMENT
THREADED PLUG
TYPE
SEE NOTE-1
OUTLET SIZE
FLOOR/SHOWER DRAIN
SEE NOTE-2
A
MEMBRANE
TO LAST
FIXTURE
WATER HAMMER ARRESTOR
HEIGHT
B
C
A
DIMENSION SHALL BE
DIAMETER
12-32
33-60
CAPACITY(FU)
FIXTURE UNIT
1-11
SIZE
DISPLACEMENT
HYDRAULIC DISPLACEMENT
PRESSURE PNEMATIC
COPPER ADAPTOR
20 OR 25 SEE DWGS
SCORIATED COVER
SEE NOTE-2
WATER-PROOF MEMBRANE
ADJUSTABLE HOUSING
TWO PIECE THREADED
WATER SERVICE MAIN
4. DRAINS SHALL HAVE A CAST IRON BODY AND SEEPAGE PAN AND
1. WATER-PROOF MEMBERANE ARE NOT REQUIRED IN SLAB ON GRADE.
WATER-PROOF MEMBRANE
A CHROMIUM PLATED BRONZE, NICKEL BRONZE OR NICKEL BRASS STRAINER.
EXTERIOR THRUST BLOCK
PROVIDE STEEL HARNESS THRUST
RESTRAINT RODS FROM ELL TO
NEOPRENE GASKET
LEAD CAULKING
FINISH FLOOR
DRAINS SHALL BE CONNECTED TO CAST IRON P-TRAP.
2. NEOPRENE RUBBER GASKET COMPRESSION TYPE JOINT.
3.
CEMENT
FILL/BED
SLAB
STRUCTURAL
FINISH/TILE FLOOR
WALL SLEEVE
BELOW FROST LINE
NON FREEZE TYPE WALL
POLISHED BRONZE BOX
20 HOSE CONNECTION
HYDRANT
GRADE
WALL CLAMP
KEY HANDLE
OUTSIDE WALL
FLOW CONTROL
COPPER SHELL
FLOOR
FINISH/TILE
CEMENT
SLAB
WATER-PROOF
STRUCTURAL
FILL/BED
ORIFICE
PIPE SLEEVE THRU FLOOR
CAULK
H E
IG
H T
DIAMETER
FLUID
BELLOWS
CUSHION
AS CLOSE TO FLOOR AS
POSSIBLE
GATE VALVE
UNION
15 HOSE BIBB W20
HOSE THREAD
BRASS CASING
PIPE SOCKET
61-113D
VARIED DEPEND UPON
MFR
1 2
4 5
FILL/BED
CEMENT
SLAB
STRUCTURAL
SEE NOTE 2
SEE NOTE 1
MEMBRANE
WATERPROOF
FLOOR
FINISH/TILE A
P-TRAP
ADAPTOR
WASTE LINE
CLEANOUT PLUG
3 FLOOR DRAIN
DETAILS - 4
CHONG, ST
REPAIR QUONSET HUT BUILDING S-1709
| 000000-Repair Quonset Hut building S-1709, Cp Casey(FINAL)-M1 |
| 000000-Repair Quonset Hut building S-1709, Cp Casey(FINAL)-M2 |
| 000000-Repair Quonset Hut building S-1709, Cp Casey(FINAL)-M3 |
| 000000-Repair Quonset Hut building S-1709, Cp Casey(FINAL)-M4 |
| 000000-Repair Quonset Hut building S-1709, Cp Casey(FINAL)-M5 |
| 000000-Repair Quonset Hut building S-1709, Cp Casey(FINAL)-M6 |
| 000000-Repair Quonset Hut building S-1709, Cp Casey(FINAL)-M7 |
| 000000-Repair Quonset Hut building S-1709, Cp Casey(FINAL)-M8 |
| 000000-Repair Quonset Hut building S-1709, Cp Casey(FINAL)-M9 |
| 000000-Repair Quonset Hut building S-1709, Cp Casey(FINAL)-M10 |
| 000000-Repair Quonset Hut building S-1709, Cp Casey(FINAL)-M11 |
| 000000-Repair Quonset Hut building S-1709, Cp Casey(FINAL)-M12 |
| 000000-Repair Quonset Hut building S-1709, Cp Casey(FINAL)-M13 |
| 000000-Repair Quonset Hut building S-1709, Cp Casey(FINAL)-M14 |
| 000000-Repair Quonset Hut building S-1709, Cp Casey(FINAL)-M15 |
File details come from the government source that posted it. Updated .