This document is a Request for Proposals (RFP) for the repair of Quonset Hut Building S-1709 at Camp Casey, Korea. The RFP covers a wide scope of work including civil, architectural, mechanical, electrical, and structural repairs. The civil work includes replacing existing site elements like drainage, sidewalks, and landscaping. The architectural work involves floor, wall, ceiling, and roof replacements, as well as door, window, and accessory upgrades. The mechanical work focuses on repairing the HVAC, ventilation, and plumbing systems. The electrical work requires replacing the existing interior/exterior lighting, electrical distribution, fire alarm/mass notification, telecommunications, and CATV systems. The RFP also includes a small amount of new construction work for a pavilion and footpath. The solicitation is open only to contractors under a Multiple Award Task Order Contract (MATOC). Proposals are due by a specified date, and the Government intends to award a single contract for the required work.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 132491_STRC_DWG.pdf | ||
| 132491_ARCH_DWG.pdf | ||
| 132491_MECH_DWG.pdf | ||
| W90VN824R0061.pdf | ||
| 132491-CIVIL_DWG.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
A
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
ELECTRICAL
E-1
3S
L
L
GENERAL NOTES
1.
2.MOUNTING HEIGHTS ABOVE FLOOR SHALL BE AS FOLLOW UNLESS OTHERWISE
NOTED ON THE DRAWING.
LIGHTING FIXTURE SEE LIGHTING FIXTURE SCHEDULE
PANELBOARD SEE SPECIFICATION
SAFETY SWITCH 1524mm TO CENTER OF THE ENCL
RECEPTACLE,TELEPHONE OUTLET 305mm TO CENTER OF THE ENCL
MOTOR CONTROLLER 1524mm TO CENTER OF THE ENCL
1676mm TO CENTER OF THE ENCL
2286mm TO CENTER OF BELL
3.
4.
6.THE SOIL RESISTANCE TO GROUND FOR THE ELECTRICAL AND COMMMUNICATION
SYSTEMS SHALL BE 25 OHMS OR LESS. THE SOIL RESISTANCE TEST SHALL BE
7.
COORDINATED WITH THE CENTRAL FIRE DEPARTMENT SO THAT
THE EQUIPMENT SHOULD BE COMPATIBLE WITH THE MAIN EXISTING
ON CEILINGDETECTOR
1372mm TO CENTER OF STATIONMANUAL PULL STATION
5.
CONDUCTED BY THE CONTRACTOR TO OBTAIN THE REQUIRED SOIL RESISTANCE.
INDICATEDS 2 #12AWG IN 16C
INDICATEDS 3 #12AWG IN 16C
INDICATEDS 4 #12AWG IN 16C
A GREATER NUMBER OF WIRES ARE INDICATED AS FOLLOWS;
1219mm TO CENTER OF THE ENCLWALL SWTICH
CONDUIT UNLESS OTHERWISE INDICATED.
ALL EQUIPMENT CONTROL WIRING SHALL BE #14 AWG. "TW" IN 16C
AND LOCATION OF THE F/A ANTENNA WITH THE CENTRAL FIRE DEPARTMENT
THE CONTRACTOR SHALL SUBMIT THE SHOP DRAWING FOR THE MOUNTING
TO TRANSMIT THE ALARM RADIO SIGNAL WAVE WITHOUT ANY OBSTRUCTION.
DETAIL OF THE F/A ANTENNA, AND COORDINATE THE MOUNTING HEIGHT
F/A EQUIPMENT IN THE CENTRAL FIRE DEPARTMENT.
THE EQUIPMENT SHOULD BE COMPATIBLE WITH THE MAIN EXISTING
SCOPE OF WORK
F/A & MNS EQUIPMENT IN THE CENTRAL FIRE DEPARTMENT.
THE MANUFACTURER AND MODEL OF NEW F/A& MNS EQUIPMENT SHALL BE
F/A &MNS CONTROL
COMBO. SPEAKER & STROBE
12.
13.
14.
A. REPAIR/MAINTENANCE ( K )
10.
11.
8.
9.
L E G E N D
FLEXIBLE CONDUIT W/CONNECTORS
LIGHTING
WIRING
POWER
INTERIOR
S
SYMBOL DESCRIPTION
DESCRIPTION
DESCRIPTION
T
J
THERMOSTAT (UNDER MECH. ITEM)
JUNCTION BOX
SYMBOL
SYMBOL
SAFETY SWITCH
C CONTROL CIRCUIT
3-WAY SWITCH, 15A-125V
AND GOVERNMENT INSTALLED
GOVERNMENT FURNISHED
GFGI
WEATHERPROOFWP
LA LIGHTNING ARRESTER
EXPLOSIONPROOFEP
DISTRIBUTIONDIST
GROUND FAULT PROTECTIONGFP
A AMPERE
AC ALTERNATING CURRENT
AF/AT AMPERE FRAME/AMPERE TRIP
AWG AMERICAN WIRE GAUGE
BC BARE COPPER
BLDG BUILDING
BRKR BREAKER
C CONDUIT
CB CIRCUIT BREAKER
CKT CIRCUIT
CONN CONNECTION
CT CURRENT TRANSFORMER
DET(S) DETAIL(S)
DIAG DIAGRAM
DISC DISCONNECT
DWG(S) DRAWING(S)
EA EACH
EM EMERGENCY
ENCL ENCLOSURE
EXST EXISTING
F/A FIRE ALARM
FL FLOOR
FLUOR FLUORESCENT
FXTR FIXTURE
GEN GENERATOR
GND GROUND
HP HORSE POWER
HZ HERTZ
INCAND INCANDESCENT
INSTL INSTALLATION
J-BOX JUNCTION BOX
K KILO
KV KILO VOLT
KVA KILO VOLT AMPERE
LTG LIGHTING
MAG MAGNETIC
MAX MAXIMUM
MIN MINIMUM OR MINUTE
MTG MOUNTING
NO NUMBER
O/H OVER HEAD
PH PHASE
PNLBD PANELBOARD
PRIM PRIMARY
PWR POWER
Q'TY QUANTITY
RCPT RECEPTACLE
REQ'D REQUIRED
SCHED SCHEDULE
SEC SECONDARY
SPEC SPECIFICATION
STD STANDARD
SW SWITCH
TEL TELEPHONE
TYP TYPICAL
U/G UNDERGROUND
V VOLT
VA VOLT AMPERE
W WATT
W/ WITH
XFMR TRANSFORMER
CABNET TYPE, RATED WATT ON LTG SCHEDULE
LED LIGHTING FIXTURE, WALL MOUNTED OR UNDER
ON LTG SCHEDULE, WET LOCATION
LED LIGHTING FIXTURE, RATED WATT & TYPE OF MTG
PANELBOARD
HOMERUN CIRCUIT TO PANELBOARD
TYPE OF MTG ON LTG SCHEDULE
EXTERIOR LED LIGHTING FIXTURE, RATED WATT &
TYPE
DUPLEX RECEPTACLE, 2P-3W-20A-125V, GROUNDING
ABBREVIATION
THE COTNRACTOR SHALL SUBMIT A SHOP DRAWING OF HVAC SYSTEM
IN ACCORDANCE WITH SEQUENCE OF OPERATION INDICATED ON THE
MECHANICAL DRAWINGS.
ANY CIRCUIT WITHOUT FURTHER DESIGNATION INDICATES 2-#12AWG
WIRES IN 16C CONDUIT UNLESS OTHERWISE INDICATED.
THE GROUNDING CONDUCTORS SHALL BE SEPARATELY PROVIDED FOR
ELECTRICAL EQUIPMENT UNLESS OTHERWISE INDICATED ON THE DRAWING.
CEILING.
ALL WIRING SHALL BE CONCEALED ABOVE CEILING WHEN THE ROOM HAS
CATV BEFORE CONSTRUCTION.
CONTRACTOR SHALL COORDINATE WITH AREA MP, DO IMO, SIGNAL BRIGADE,
AND GOVERNMENT ACCEPTANCE.
PANELBOARD DOOR, REQUIRED BEFORE FINAL BUILDING INSPECTION
CONTRACTOR SHALL MAKE CIRCUIT CHARTS AND ATTACH THEM TO
FIRE CODE AND SPECIFICATIONS.
OF THE NATIONAL ELECTRICAL CODE, NATIONAL ELECTRICAL SAFETY CODE,
ALL ELECTRICAL WORK SHALL CONFORM TO THE LATEST REQUIREMENTS
OR RENOVATION.
CONDITION AND DIMENSIONS PRIOR TO COMMENCING ANY CONSTRUCTION
THE CONTRACTOR SHALL BE RESPONSIBLE IN VERIFING ALL EXISTING
FIXTURE A MINIMUM DISTANCE OF 458mm.
FIRE ALARM DETECTORS SHALL BE LOCATED TO CLEAR ANY LIGHTING
FMCP
FTR
ANTENNA
AUXILIARY
DESCRIPTION
F
TELEPHONE OUTLET
SYMBOL
CTC CATV SYSTEM CABINET
CATV OUTLET
ADDRESSABLE FA MANUAL PULL STATION
WP
F M
TTC
FIRE ALARM/MASS NOTIFICATION CONTROL PANEL
MOUNTED TYPE
F/A & MASS NOTIFICATION SPEAKER "WP" WALL
STROBES
WALL MOUNTED SPEAKER /COMBO. (FA+MNS)VISUAL
CONNECTION
BUILDING TRANSMITTER UNIT FOR FIRE ALARM
SYSTEM
F
WIRING FOR TELEPHONE LINET
BRANCH CIRCUIT, EXPOSED ON CEILING OR WALL
WIRING CONCEALED IN THE CEILING AND WALL
F/M
L
WP
TYPE WITH PLUG
SINGLE RECEPTACLE, 3P-4W-30A-125/250V, GROUNDING
TYPE WITH PLUG
SINGLE RECEPTACLE, 3P-4W-50A-125/250V, GROUNDING
ON LTG SCHEDULE
LED LIGHTING FIXTURE, RATED WATT & TYPE OF MTG
ON LTG SCHEDULE
LED LIGHTING FIXTURE, RATED WATT & TYPE OF MTG
W/EMERGENCY BATTERY UNIT
L
W/EMERGENCY UNIT
WIRING TO UPSTAIR OR DOWNSTAIR
ON LTG SCHEDULE
LED LIGHTING FIXTURE, RATED WATT & TYPE OF MTG
ON LTG SCHEDULE
LED LIGHTING FIXTURE, RATED WATT & TYPE OF MTG
L
L
CIRCUIT INTERRUPTER TYPE,WEATHER PROOF
DUPLEX RECEPTACLE, 2P-3W-20A-125V, GROUND FAULT
CIRCUIT INTERRUPTER TYPE
DUPLEX RECEPTACLE, 2P-3W-20A-125V, GROUND FAULT
EXIT LIGHT, SINGLE FACE, WALL MOUNTED TYPE
(CEILING MOUNTED TYPE W/ARROW)
L L
TELEPHONE TERMINAL CABINET
TV
TYPE
SINGLE RECEPTACLE, 2P-3W-20A-125V, GROUNDING
MAGNETIC MOTOR STARTER
FAN MOTOR (UNDER MECH. ITEM)
M MOTOR (UNDER MECH. ITEM)
UH
S
WHM
MANUAL MOTOR STARTER W/PILOT LAMP
UNIT HEATER (UNDER MECH. ITEM)
WATTHOUR METER
SAFETY SWITCH
S
TS TAMPER SWITCH (UNDER MECH. ITEM)
FS FLOW SWITCH (UNDER MECH. ITEM)
F
MANUAL MOTOR STARTER W/PILOT LAMP AND
3-POSITION SELECTOR SWITCH(H-O-A)
L
L
ON LTG SCHEDULE, DOWN LIGHT
LED LIGHTING FIXTURE, RATED WATT & TYPE OF MTG
TOGGLE SWITCH, 15A-125V
TYPE, RATED WATT ON LTG SCHEDULE
LED LIGHTING FIXTURE, CEILING PENDANT MOUNTED
15.
UNITS.
CERTIFICATE FROM MANUFACTURER FOR LED LIGHTING FIXTURES AND POWER
CONTRACTOR SHALL BE RESPONSIBLE TO PROVIDE 10 YEAR WARRANTY
16.
AND AFTER INSTALLATION OF ELECTRICAL SYSTEM.
TO THEIR ORIGINAL CONDITION AND OPERATION DURING
ALL DAMAGED AREA INCLUDING SODDING, UTILITIES, STRUCTURES
THE CONTRACTOR SHALL BE RESPONSIBLE FOR RESTORING
& AND
ON LTG SCHEDULE, EMERGENCY LIGHT
LED LIGHTING FIXTURE, RATED WATT & TYPE OF MTG
L
E
ON LTG SCHEDULE, EXTERIOR FLOOD LIGHT
LED LIGHTING FIXTURE, RATED WATT & TYPE OF MTG
ON LTG SCHEDULE
WALL MOUNTED RED ALARM, RATED WATT & TYPE OF MTG
ON LTG SCHEDULE
ROTATING WARNING LIGHT, RATED WATT & TYPE OF MTG
FIRE ALARM SYSTEM CIRCUIT, FACTORY PAINTED RED
STEEL CONDUIT
1.
2.
3.
OUTLETS & ASSOCIATED WIRING AND CONDUIT WITH NEW.
REPLACE EXISTING CATV DISTRIBUTION CANBINET, PULLBOXES, CATV
AND ASSOCIATED WIRE & CONDUIT WITH NEW.
OUTLETS W/COVER PLATES, TERMINAL BLOCKS, EQUIPMENT RACK
INCLUDING TELEPHONE TERMINAL BOARD, TELEPHONE/DATA
REPLACE EXISTING TELECOMMUNICATION SYSTEM
SYSTEMS WITH NEW.
BOXES, CONTROL/POWER WIRES AND CONDUITS FOR MECHANICAL
REPLACE EXISTING SAFETY SWTICHES, MOTOR CONTROLLERS, JUNCTION
7.
4.
5.
6.
8.
KIM, SY
132491
SCOPE OF WORKS
LEGEND, GENERAL NOTES AND
NTS
17.
CONTRACTING OFFICER.
THE CONTRACTOR SHALL COORDINATE ALL PHASES OF WORK WITH THE
WITH PHOTOCELL, WIRES AND CONDUITS WITH NEW.
TOGGLE SWITCHES, 3 WAY SWITCHES, LIGHTING CONTACTOR
REPLACE EXISTING INTERIOR/ EXTRIOR LIGHTING, FIXTURES, EXIT LIGHTS,
& ASSOCIATED ACCESSORIES AS SHOWN ON THE DRAWINGS.
REPLACE EXISTING EXTERIOR UNDERGROUND TELECOMMUNICATION LINE
WIRING & CONDUITS WITH NEW.
PANELBOARDS, RECEPTACLES W/COVER PLATES ASSOCIATED
REPLACE EXISTING WATTHOUR METER & CURRENT TRANSFORMER,
CP CASEY
REPAIR QUONSET HUT BUILDING S-1709,
CONDUIT AS SHOWN ON THE DRAWINGS.
PRIMARY, SECONDARY LINE & ASSOCIATED ACCESSORIES, WIRING AND
INCLUDING PAD MOUNTED TRANSFORMER, PRIMARY CON C POLE, MANHOLE,
REPLACE EXISTING EXTERIOR POWER DISTIBUTION SYSTEM WITH NEW
TRANSMITTER, LIGHTING ARRESTER AND ASSOCIATED WIRING AND CONDUIT.
(WATTAGE AS REQ'D) DEVICE, FIRE ALARM BUILDING
VISUAL/SIGNAL STROBES (15 OR 75 CANDELA), MICROPHONE, SPEAKER
MANUAL PULL STATION, SMOKE DETECTOR & RELAY MODULE, ANTENNA,
FIRE ALARM CONTROL AND MASS NOTIFICATION SYSTEM PANEL,
REPLACE EXISTING FIRE ALARM CONTROL SYSTEM WITH NEW ADDRESSABLE
SD DIMMING SWITCH
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
ELECTRICAL
1:100 E-2
132491
KIM, SY
L
L
L
L
L
L
L
L
L
L
L L
L L
L L
L
L L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L L
L
L
SS SS
S
S S S
SS
S S
S
S
S
S
3S
W.TOILET
FEC
MECH/ELEC
ROOM
ROOM
FEC
OFFICE-1 OFFICE-3
STORAGE
VEST
VEST
OFFICE-2
OFFICE-5 OFFICE-4
COMM
102 103 104
105106
JAN
M.TOILET
CORRIDOR
EWC
BB
BB
BREAK RM
RM
CONFERENCE
L L
LL
L
L
L
LL
L
L
L
S D
S D
S D
S
LIGHTING CONTRACTOR "LC"
W/PHOTOCELL, NEMA 1 ENCL.
1/100SCALE :
NEW GROUND FL LIGHTING PLAN
CP CASEY
REPAIR QUONSET HUT BUILDING S-1709,
M-1
P1-1
P1-3
P1-4
NEW GROUND FLOOR LIGHTING PLAN
"MDP"
"M"
"C
"P1" "P2"
P1-2
DIMMING CONTROL SWITCH (TYPICAL OF 3EA)
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
m m
308mm
NS-3a & 3b
WALL OR CEILING SURFACE MOUNTED LIGHT EMITTING
WITH BATTERY CHARGER, SINGLE FACE (NS-3a) OR
(MAX INPUT) OR 7.22W(MAX INPUT), BATTERY BACK-UP
DIODE(LED) EXIT LIGHT FIXTURE, 1PH, 120V, 4.99W
DOUBLE FACE (NS-3b) OR APPROVED EQUAL.
LIGHTING FIXTURE DETAILS
TYPE, UL LISTED
AND ACCESSORIES W/BUILT-IN PHOTOCELL, WET LOCATION
WALL OR CEILING SURFACE MOUNTED LIGHT EMITTING DIODE (LED)
LIGHTING FIXUTURE 1PH, 120V, 22W LED MODULES, WITH CONVERTER
NS-11
E-3
ELECTRICAL
FIXTURE, 1PH, 120V, 45W, WITH CONVERTER &
ACCESSORIES AS REQUIRED, (NS-4a) & WITH EM UNIT (NS-4b)
OR APPROVED EQUAL.
CEILING RECESSED MOUNTED LIGHT EMITTING DIODE (LED)
NS-4a & 4b m m
1220m m
0m m
FIXTURE, 1PH, 120V, 50W, WITH CONVERTER &
ACCESSORIES AS REQUIRED, (NS-6a) & WITH EM UNIT (NS-6b)
CEILING RECESSED MOUNTED LIGHT EMITTING DIODE (LED)
NS-6a & 6b
FIXTURE SCHEDULE)
(OPTION: DIMMING CONTROL (SEE REMARKS IN LIGHT
CEILING SURFACE/PENDANT MOUNTED LIGHT EMITTING DIODE (LED)
FIXTURE, 1PH, 120V, 45W, UL LISTED, WITH CONVERTER AND
ACCESSORIES AS REQUIRED, (NS-5a) & EM UNIT(NS-5b)
NS-5a & 5b
CEILING RECESSED MOUNTED LIGHT EMITTING DIODE (LED)
FIXTURE, 1PH, 120V, 25W, UL LISTED, PMMA LIGHT GUIDE PLATE,
WITH CONVERTER & ACCESSORIES AS REQUIRED,
(NS-10a) & WITH SELF TEST/DIAGNOSTIC EM UNIT (NS-13b)
NS-13a & 13bNS-12
CEILING SURFACE MOUNTED LED LIGHT FIXTURE, 1PH, 120V, 22W,
WET LOCATION TYPE, WITH CONVERTER & ACCESSORIES AS
REQUIRED, UL LISTED POWER UNIT
222mm m m
FIXTURE, 1PH, 120V, 18W, WITH CONVERTER & ACCESSORIES,
AS REQUIRED, OR APPROVED EQUAL.
WALL SURFACE MOUNTED LIGHT EMITTING DIODE (LED)
300 245mm
254mm
CEILING SURFACE MOUNTED LIGHT EMITTING DIODE (LED)
OR APPROVED EQUAL.
WET LOCATION SHOWER LIGHT TRIM, AS REQUIRED
FIXTURE, 1PH, 120V, 18W, WITH CONVERTER & ACCESSORIES,
WALL
FIXTURE, 1PH, 120V, 12W, WITH CONVERTER &
CEILING RECESSED LIGHT EMITTING DIODE (LED)
143.9mm
.3 m m
210mm
ACCESSORIES, AS REQUIRED AND UL LISTED
FIXTURE SCHEDULE)
(OPTION: DIMMING CONTROL (SEE REMARKS IN LIGHT
POWER UNIT (NS-9a) & EM UNIT (NS-9b)
NS-8 NS-9a & 9b NS-10
G N
C
OFF
AUTO
H
TO EXTERIOR LIGHTS (TYP)
EXTERIOR LIGHTING
WIRES
CONTROL
#14 AWG
NOT TO SCALE
FACING NORTH
2000W, 120V, ORIENTED
PHOTOELECTRIC CELL
P -5
CONTACTOR "LC" DIAGRAM
SW IN NEMA 1 ENCL
HAND-OFF-AUTO SEL.
120V, COIL
HELD CONTACTS,
N.O. MECHANICALLY
"LC" W/ 3EA-20A,12OV,
LIGHTING CONTRACTOR
KIM, SY
CP CASEY
REPAIR QUONSET HUT BUILDING S-1709,
132491
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
E-4
REMARKSQ'TY
WATTS
MOUNTING METHOD
TYPE
LAMP
NAMENO
ROOM OCE STD DET 40-06-04
LIGHT FIXTURE SCHEDULE
TYPE
LED
LIGHT FIXTURE SCHEDULE
ELECTRICAL
101 NS-4b 45 1
102 NS-6a
NS-6b 50
50 2
CEILING RECESSED
W/ "EM" UNIT
103 NS-6a
NS-6b 50
50 2
NS-8 18
WALL MOUNTED ABOVE THE MIRROR TOP107
NS-4b
NS-13a 25
45 1
W/ "EM" UNIT
NS-13b 25 4
NS-10 18 1
VEST W/ "EM" UNIT
OFFICE
OFFICE
W/ "EM" UNIT
104 NS-6a
NS-6b 50
50 2
OFFICE
W/ "EM" UNIT
105 NS-6a
NS-6b 50
50 2
OFFICE
W/ "EM" UNIT
106 NS-6a
NS-6b 50
50 2
OFFICE
W/ "EM" UNIT
NS-4b
108 JAN CEILING SURFACE
W.TOILET
M.TOILET
110 CORRIDOR
1NS-5a 45113 MECH/ELEC ROOM CEILING SURFACE
NS-5b 45 1 CEILING SURFACE W/ "EM" UNIT
EXIT SIGN
EXTERIOR LIGHT-
- NS-3
NS-12 22
4.99 WALL MOUNTED
2EXTERIOR LIGHT- NS-11 22 WALL MOUNTED
CEILING SURFACE
ABOVE THE DOOR TOP
ABOVE THE DOOR TOP
NS-4b 45 1114 COMM ROOM W/ "EM" UNIT
4NS-6a 50115
NS-6b 50 2 W/ "EM" UNIT
BREAK RM
CEILING RECESSED
NS-13b 25 1116 W/ "EM" UNITVEST
111 NS-6a
NS-6b 50
50 8
RM
CONFERENCE OPTION: DIMMING CONTROL
W/ "EM" UNIT & OPTION: DIMMING CONTROL
CEILING RECESSED
NS-8 WALL MOUNTED
CEILING RECESSED
W/ "EM" UNIT
KIM, SY
CP CASEY
REPAIR QUONSET HUT BUILDING S-1709,
W/ "EM" UNIT
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
ELECTRICAL
1:100 E-5
"WP"
"WP"
W.TOILET
FEC
MECH/ELEC
ROOM
ROOM
FEC
OFFICE-1 OFFICE-3
STORAGE
VEST
VEST
OFFICE-2
OFFICE-5 OFFICE-4
COMM
102 103 104
105106
JAN
M.TOILET
CORRIDOR
EWC
BB
BB
BREAK RM
RM
CONFERENCE
M R
J
PROJECTOR & 35C EMPTY CONDUIT
CEILING MOUNTED RECEPTACLE FOR
GROUNDING TYPE)
DUPLEX RECEPTACLE (2P-3W-20A-125VAC,
GROUND FAULT CIRCUIT INTERRUPTOR
M
CABINET WHERE MICROWAVE IS PLACED)
1PH-120V-1100W (LOCATED INSIDE
GROUNDING TYPE) W/PLUG FOR MICROWAVE,
SINGLE RECEPTACLE (2P-3W-20A-125V
R
SINGLE RECEPTACLE (2P-3W-20A-125V
GROUNDING TYPE) W/PLUG
REFRIGERATOR, 1PH-115V-1/4HP
(MH: +900mm TO CENTER OF RCPT)
(2P-3W-20A-125VAC, GROUNDING TYPE)
DUPLEX RECEPTACLE
* ADDITIONAL LEGEND(THIS SHEET ONLY)
1/100SCALE :
NEW GROUND FL POWER PLAN
P1-5
"P1"
"P2"
P1-6
P1-9
P1-8 P1-7
"C"
NEW GROUND FL POWER PLAN
KIM, SY
CP CASEY
REPAIR QUONSET HUT BUILDING S-1709,
132491
P1-10
P1-11
P1-12
"M"
M-2
P1-15 P1-16
P1-17
P1-18 P1-19
P1-20 P1-21
P1-13
P1-22
TV
DUPLEX RECEPTACLE (2P-3W-20A-125VAC,
GROUNDING TYPE) FOR NOTICE TV SET
(MH: +450mm BELOW CEILING)
TV
TV
TV TV
TVTVTV
TV
TV
P1-14
C CEILING MOUNTED DUPLEX RECEPTACLE
(2P-3W-20A-125VAC, GROUNDING TYPE) FOR
PROJECTOR
C
J
PROJECTOR CONTROLLER SWITCH LOCATION
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
FOR MECHANICAL SYSTEM
NEW GROUND FL POWER/CONTROL PLAN
SCALE :
NEW GROUND FL POWER/CONTROL PLAN FOR MECHANICAL SYSTEM
1/50
SINGLE RECEPTACLE (2P-3W-20A-240VAC,
* ADDITIONAL LEGEND(THIS SHEET ONLY)
HPU
70W, 208V, 1PH (MECH ITEM)
INDOOR SPLIT SYSTEM HEAT PUMP UNIT
HPU
70W, 208V, 1PH (MECH ITEM)
INDOOR SPLIT SYSTEM HEAT PUMP UNIT
HPU
B
C
FOR SAC
SAFETY SWITCH, DPST, 240V, 30A
SAFETY SWITCH, DPST, 240V, 30A
FOR ERV-1
NON-FUSIBLE, NEMA 3R ENCL
STRUCTURE SUPPORT
NON-FUSIBLE, NEMA 1 ENCL ABOUT CEILING W/ STEEL
HPU
79W, 208V, 1PH (MECH ITEM)
INDOOR SPLIT SYSTEM HEAT PUMP UNIT
EH
3KW, 208V, 1PH, (MECH ITEM)
ELEC. UNIT HEATER
3KW 208 V, 3 PH,
ELECTRIC HOT WATER HEATER
EWH
EUH
1,000W, 12.5AMP 120V, 1PH, (MECH ITEM)
ELECTRIC WALL HEATER
A
NON-FUSIBLE, NEMA 3R ENCL
SAFETY SWITCH, 3PST, 240V, 200A
FOR OHPU-1
GROUNDING TYPE) WITH PLUG FOR INDOOR HEAT PUMP UNIT
W.TOILET
COMM
EWC
RM
SAC
OFFICE-4
OFFICE-5
RM
CONFERENCE
CORRIDOR
JAN
OFFICE-3
OFFICE-2
OFFICE-1
STORAGE
BREAK RM
C
T
T
T
T
T
T T T
VEST-2
T
T T
HPU
HPU
HPU
HPU
HPU
HPU
HPU
SAC
HPU
VEST-1
OHPU
EH
EF
M
V
HPU
ERV
EH
EWH
EF
MECH/ELEC
RM
EUH
B
C
"M"
"C
"P1" "P2"
J
J
S
M.TOILET
EH
J J
S
J
HPU
A
J
J
HPU
EH
OHPU ENERGY RECOVERY VENTILATION HEAT PUMP UNIT
86.4 AMP MCA / 120 AMP MOP 208 VOLTS, 3 PH,(MECH ITEM)
199W, 208V, 1PH (MECH ITEM)
INDOOR SPLIT SYSTEM HEAT PUMP UNIT
ERV
420W, 208V, 1PH, (MECH ITEM)
ENERGY RECOVERY VENTILATION UNIT
SAC
30 AMP MOP 220V, 1PH, (MECH ITEM)
SPLIT AIR CONDITIONING
EF
1 / 4 HP, 115V, 1PH (MECH ITEM)
FANS
EF
1 / 4 HP, 115V, 1PH (MECH ITEM)
FANS
EH
2 2,000W, 12.5AMP 120V, 1PH, (MECH ITEM)
ELECTRIC WALL HEATER
S
SWITCH, W/PILOT LAMP 1P-120V, 1HP (MAX.)
MANUAL MOTOR STARTER "HAND-OFF-AUTO" KIM, SY
CP CASEY
REPAIR QUONSET HUT BUILDING S-1709,
132491
E-6
M-4 M-5
M-6
MDP-5
"MDP"
P2-1
P2-2
P2-3
P2-4
P2-5
J
P2-7
P2-8
J
P2-6
C-5
CONNECT TO
LIGHTING CIRCUIT "P1-4"
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
ELECTRICAL
E-7
SCALE: 1/100
NEW FL. FIRE ALARM AND MASS NOTIFICATION SYSTEM PLAN
F T R
F M
C P
F
W P
M F
W P
W.TOILET
FEC
ROOM
FEC
OFFICE-1 OFFICE-3
STORAGE
VEST
VEST
OFFICE-2
OFFICE-5 OFFICE-4
COMM
102 103 104
105106
JAN
M.TOILET
CORRIDOR
EWC
BB
BB
115BREAK RM
F
TO FMCP
TO FMCP ~
* ADDITIONAL LEGEND (THIS SHEET ONLY)
COMBINED ADDRESSABLE FIRE ALARM/
MASS NOTIFICATION CONTROL PANEL,
24VDC, BUILT-IN ADDRESSABLE POINTS
MODULES AS REQ'D, PROGRAMMABLE
MODULE & RELAYS LCD ANNUNCIATOR,
SYNCHRONIZATION CONTROL MODULE,
POWER SUPPLY, DIGITAL VOICE MODULE,
MICROPHONE, BATTERY, BATTERY CHAREGER,
POWER MODULES PANEL(AS REQ'D) AND
DIGITAL VOICE PANEL W/AMPLIFIER & BACK
UP AMPLIFIER (AS REQ'D) & MICROPHONE,
NEMA 1 ENCL
FMCP
ADDRESSABLE MANUAL PULL STATION
SPEAKER (WATTAGE AS REQ'D)
FIRE ALARM/MASS NOTIFICATION
WALL MOUNTED "WP" TYPE,
SHALL BE DE-RATED AS REQUIRED)
(15 CANDELA MINIMUM, AMBER STROBE
W/WORDS "ALERT") VISUAL SIGNAL STROBES
W/WORDS "FIRE" + MNS-AMBER STROBE
AS REQ'D)/COMBO. (FA-CLEAR STROBE
WALL MOUNTED SPEAKER (WATTAGE
WP
ADDRESSABLE SMOKE DETECTOR
FTR BUILDING TRANSMITTER
ADDRESSABLE FIRE ALARM
HEAT DETECTOR
HEAT DETECTOR
ADDRESSABLE FIRE ALARM
FIRE ALARM ANTENNA
OMNI-DIRECTION TYPE
W/MOUNTING BARCKET
F
F/M
F /M
F/M
F /M
F/M
F/M
F/M
F/M F/M
F/MF/MF/MF/M
F/M F/M
F /M
"P1" "P2"
NOTIFICATION SYSTEM PLAN
NEW GROUND FLOOR FIRE ALARM/MASS
ROOM
MECH/ELEC
RM
CONFERENCE
F
F F
F
F F
F F
FFF
FFF
F
KIM, SY
CP CASEY
REPAIR QUONSET HUT BUILDING S-1709,
F F
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
E-8
NOTES:
NFPA 72, 2013 EDITION.
PRERECORDED MESSAGES ARE IN ENGLISH AND HANGUL AT
CONTRACTOR SUBMITS SHOP DRAWINGS.
THE VOLTAGE DROP AND POWER SUPPLY CALCULATION
SHALL BE PROVIDED BY THE CONTRACTOR WHEN THE
4.
(3-FEET) FROM HVAC, HOT & COLD WATER PIPING.
ALSO CONDUITS SHALL BE RUN AWAY AT LEAST 900mmTHE FIRE ALARM SYSTEM IS CONCEPTUAL. THE
MANUFACTURER'S EQUIPMENT LISTING.
SHOP SUBMITTAL TO SHOW DETAILED INSTALLATION
MANUFACTURER'S LISTED INSTALLATION
2.
CONTRACTOR SHALL COMPLETE DESIGN AND INSTALL
13.
12.
11.
9.
SYSTEM SHALL BE DESIGNED IN ACCORDANCE WITH
AND THE MASS MESSAGE NEEDS TO HAVE PRE ALERT
PATTERN IS REQUIRED FOR FIRE ALARM EVACUATION
VOICE EVACUATION SYSTEM IN LIEU OF TEMPORAL
ALL DEVICES AND EQUIPMENT SHALL BE UL LISTED
ELECTRICAL AND MECHANICAL SYSTEM EQUIPMENT
COORDINATE THE EXACT DEVICE LOCATIONS WITH
SWITCHES AND NON-ADDRESSABLE INITIATION
ALL TAMPER SWITCHES, FLOW SWITCHES, PRESSURE
PROHIBITED FOR ALL IDC, NAC AND SLC.
ALL CLASS "B" EXCEPTIONS IN NFPA 72, 23.4.2.2 ARE8.
7. CLASS "B" RACEWAY OF FA SYSTEM SHALL BE
SEPARATED BY A MINIMUM OF 1220mm HORIZONTAL
10. COAXIAL CABLE SHALL BE ONE PIECE BETWEEN
3.
5.
6. THE POWER CIRCUIT NUMBER DEDICATED TO FIRE
ALARM CIRCUIT AND ROOM LOCATION OF PANEL
LETTER "FIRE ALARM CIRCUIT" ON THE DEDICATED
FIRE ALARM CIRCUIT SHALL BE IDENTIFIED BY A RED
THE FIRE ALARM/MASS NOTIFICATION SYSTEM
CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING
FIRE ALARM INTELLIGIBILITY/AUDIBILITY CALCULATION,
WIRE SIZE, CONDUIT SIZE, NO. OF WIRES FOR THE FIRE
POWER CIRCUIT BREAKER AND/OR DISCONNECT SWITCH.
SHALL BE INDICATED ON THE FIRE ALARM/MASS
BUILDING TRANSMITTER AND ANTENNA.
AND 305mm VERTICALLY.
DEVICES SHALL BE PROVIDED WITH CLASS "B"
THE SYSTEM FOR READY TO USE. THE NUMBER OF
DEVICES SHOWN IS THE MINIMUM REQUIRED AND THE
FINAL QUANTITY SHALL BE IN ACCORDANCE WITH THE
DEVICE LOCATIONS IN ACCORDANCE WITH THE
AND BUILDING ARCHITECTURAL FEATURES.
OR FM APPROVED.
SPECIFICATION SECTION 28.31.76.00.31 (FA) AND
HAVE PRE ALERT TEMPORAL PATTERN MIN 2 CYCLES
PROVIDE ADDITIONAL RELAYS AS REQUIRED.14.
18.
19.
20.
PER UFC 4-021-01.
17. THE MASS NOTIFICATION SYSTEM IS CONCEPTUAL. THE
NUMBER OF DEVICES SHOWN IS THE MINIMUM REQUIRED
AND THE FINAL QUANTITY SHALL BE IN ACCORDANCE
MANUFACTURER'S EQUIPMENT LISTING.
SHOP SUBMITTAL TO SHOW DETAILED INSTALLATION
THE MASS NOTIFICATION SYSTEM SHALL BE ENSURED THAT
LEAST FOR THE FOLLOWING ITEMS.
FOR ABBREVIATION, LEGEND, AND GENERAL NOTES
STROBES FOR MASS NOTIFICATION SHALL BE MARKED
STROBES FOR FIRE ALARM SHALL BE MARKED "FIRE"
"ALERT" IN RED LETTER AND W/AMBER LENS.
SYSTEM SHALL BE DESIGNED IN ACCORDANCE WITH
1.
AND W/CLEAR LENS.
15.
CONTINUOUS 3-10 SECOND TONE, NFPA 72, 24.4.1.2.2
& 24.4.1.8.2.
THE MASS SYSTEM ACTIVATION MUST OVERRIDE THE FIRE
ALARM NOTIFICATION APPLIANCES THE MASS SYSTEM
ON THE PANEL BY SWITCH.
THIS SEQUENCE IS REQUIRED FOR BOTH PRE-RECORDED
MASS MESSAGE IS REQUIRED TO BE ANNOUNCED
IMMEDIATELY UNTIL SHUTDOWN MANUALLY.
SPECIFICATION SECTION 28.31.76.00.31 (MNS)
THE CONTRACTOR SHALL PROVIDE THE REQUIRED
TESTING TO ACHIEVE A MINIMUM CIS SCORE 0.8 AS
16.
DEVICE LOCATIONS IN ACCORDANCE WITH THE
MANUFACTURER'S LISTED INSTALLATION
AND NFPA 72, 2013 EDITION.
APPLIANCES UNTIL MASS ALERT IS CANCELED MANUALLY
ACTIVATION MUST OVERRIDE THE FIRE ALARM NOTIFICATION
MESSAGES AND MANUAL MICROPHONE INITIATED MESSAGES.
ARE IDENTICAL TO FIRE ALARM VISUAL APPLIANCES.
23.
MASS VISUAL APPLIANCE LOCATION REQUIREMENTS
AS SHOP DRAWING SUBMITTALS.
CONTRACT DRAWINGS SHALL NOT BE SUBMITTED
ARMY AND AIR FORCE PROJECTS.
WITH ANY FIRE ALARM VISUAL APPLIANCES ON
MASS VISUAL APPLIANCES SHALL NOT BE COMBINED24.
25.
22. FIRE ALARM SYMBOLS FROM NEPA 170 SHALL BE
AND ALL VISUAL APPLIANCES WITHIN THE SAME ROOM
ALL AUDIBLE APPLIANCES WITHIN THE BUILDING21.
SHALL BE SYNCHRONIZED.
VOICE EVACUATION SPEAKERS, NEPA 72.
AUDIBLE APPLIANCES SHALL PROVIDE THE STANDARD
TEMPORAL PATTERN UNLESS NFPA 101 REQUIRES
USED.
26. SHOW WEATHERPROOF EXTERIOR SPEAKERS AT ALL
EXTERIOR DOORS OR EXTERIOR GATHERING AREAS.
SHALL BE UL LISTED OFF-THE-SHELF-EQUIPMENT AND
ALL BACK-UP AMPLIFIERS WIRING AND ARRANGEMENT27.
SHALL BE TESTED TO THE STANDARDS OF UL OR RM AS
REQUIRED BY UFC 4-21-01, PARAGRAPH 4-4.3.
BOTH KOREAN AND ENGLISH.
THE MAN SHALL HAVE PRERECORDED MASSAGES IN28.
APPLICABLE CODE, SPECIFICATIONS AND
REQUIREMENTS AND WIRE COUNT.
ALARM AND DETECTION SYSTEM.
NOTIFICATION CONTROL PANEL COVER.
MODULES.
SYSTEM. VOICE EVACUATION MESSAGE NEEDS TO
REQUIRED.
WITH THE APPLICABLE CODE, SPECIFICATIONS AND
REQUIREMENTS AND WIRE COUNT.
OF 20% SPARE ADDRESSES FOR FUTURE USE.
FIRE ALARM SYSTEM OF EACH SLC TO HAVE A MINIMUM29.
SEE SHEET NO. E-1.
2) INTRUDER/HOSTILE PERSON SIGHTED WITHIN/AROUND THE BUILDING
1) BOMB THREAT OR ACTUAL BOMB WITHIN/AROUND THE BUILDING
3) OCCUPANTS DIRECTED TO TAKE COVER WITHIN THE BUILDING
6) "ALL CLEAR" MESSAGE
TEST8)
THE BUILDING
CARBON MONOXIDE GAS DETECTION MESSAGE WITHIN/AROUND 7)
THE LOCAL AREA
5) EMERGENCY WEATHER CONDITIONS APPROPRIATE FOR
NORMAL MAIN ENTRANCE/EXIT
4) EVACUATION OF THE BUILDING USING EXITS OTHER THAN THE
FIRE ALARM/MASS NOTIFICATION
CONTROL PANEL (FMCP)
SG
G ~
G
CONTROL PANEL & BOOSTER PANEL)
(INSTALLED BESIDE FIRE ALARM
(RATED AS REQ'D) (TYPICAL)
SURGE PROTECTOR
2#12 & 1#12(G) IN 16C
GROUND ROD, COPPER CLAD
GROUNDING SYSTEM #6, "BC" IN 21C
CONN TO BLDG ELECTRODE
STEEL, 19mmdiax3000mmLG
WITH WELDING CONNECTION AND
WALL MOUNTED "WP" TYPE,
NOTIFICATION SPEAKER
FIRE ALARM/MASS
(WATTAGE AS REQ'D) (TYPICAL)
NOT TO SCALE
ELECTRICAL
102 104 116
BATTERY CHARGER, POWER MODULE PANEL(AS REQ'D)
SYNCHRONIZATION CONTROL MODULE, DIGITAL VOICE
FIRE ALARM/MASS NOTIFICATION CONTROL PANEL,
24VDC, BUILT-IN ADDRESSABLE POINTS MODULES
AS REQUIRED, PROGRAMMABLE MODULE & RELAYS,
POWER MODULE AS REQ.D LCD ANNUNCIATOR,
MODULE, POWER SUPPLY, MICROPHONE, BATTERY,
AND AMPLIFIER(AS REQ'D), NEMA 1 ENCL
SEMI FLUSH MOUNTED COMBINED ADDRESSABLE
NEW FIRE ALARM/MASS NOTIFICATION SYSTEM DIAGRAM
SYSTEM DIAGRAM
NEW FIRE ALARM/MASS NOTIFICATION
TO PANELBOARD P2-9 12#14 IN 21C(FOR SIGNAL)
2#12 IN 16C(FOR POWER)
(PROGRAM OF D-21 MONACO
BUILDING TRANSMITTER
BT-XM AT LEAST 16 ZONES)
#6 "BC" IN 21C
GROUND CONDUCTOR
COAXIAL CABLE
W/CONNECTORS IN 16C
W/MOUNTING BRACKET
GROUND ROD, COPPER CLAD
WITH WELDING CONNECTION
STEEL, 19mmdia x 3000mmLG
ENCLOSURE
LIGHTNING ARRESTER
W/WEATHER-PROOF
W/BATTERY & BATTERY
CHARGER, NEMA 1 ENCL
OMNI-DIRECTION TYPE
FIRE ALARM ANTENNA
FTR
(15 or 75 CANDELA MINIMUM, AMBER STROBE
W/WORDS "ALERT") VISUAL SIGNAL STROBES
W/WORDS "FIRE" + MNS-AMBER STROBE
WALL MOUNTED SPEAKER (WATTAGE
AS REQ'D)/COMBO. (FA-CLEAR STROBE
SHALL BE DE-RATED AS REQUIRED) (TYPICAL)
F
M
WP
EXT 105 106 107
110109111112111 F
M
WP
EXT113114115110
F
ADDRESSABLE SMOKE
DETECTOR
KIM, SY
CP CASEY
REPAIR QUONSET HUT BUILDING S-1709,
132491
110 110 102 104 116 F
109111111112 F
113113114
F
(TYPICAL)HEAT DETECTORADDRESSABLE
PULL STATION (TYPICAL)ADDRESSABLE MANUAL
HEAT DETECTOR
ADDRESSABLE FIRE ALARM
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
ELECTRICAL
E-9
* ADDITIONAL LEGEND (THIS SHEET ONLY)
LAN
NEW EQUIPMENT RACK FOR NIPR NETWORK
NEW TELEPHOE TERMINAL BOARD
SEE TELECOMMUNICATION SYSTEM DIAGRAM
SEE TELECOMMUNICATION SYSTEM DIAGRAM
DUAL MODULAR JACK, CAT-6
TTB
T
T
T
T
T
T
T
T
T T
T
T
SCALE:1/100
NEW FL LAN/TEL PLAN
"C
NEW GROUND FLOOR LAN/TEL PLAN
KIM, SY
CP CASEY
REPAIR QUONSET HUT BUILDING S-1709,
132491
W.TOILET
FEC
MECH/ELEC
ROOM
ROOM
FEC
OFFICE-1 OFFICE-3
STORAGE
VEST
VEST
OFFICE-2
OFFICE-5 OFFICE-4
COMM
102 103 104
105106
JAN
M.TOILET
CORRIDOR
EWC
BB
BB
BREAK RM
RM
CONFERENCE
EQUIPMENT RACK (2-DATA & 2-TEL) (TYPICAL)
TO BE TERMINATED AT PATCH PANELS IN
4-AWG#24, CAT6, LAN CABLE IN 27mm dia C.
TTB
LANOPTIC CABLE PATCH PANEL IN NEW EQUIPMENT RACK
NEW FIBER OPTIC CABLE (1-12CORE)TO NEW FIBER
EQUIPMENT RACK (3-DATA & 3-TEL) (TYPICAL)
TO BE TERMINATED AT PATCH PANELS IN
6-AWG#24, CAT6, LAN CABLE IN 27mm dia C.
EQUIPMENT RACK (1-DATA & 1-TEL) (TYPICAL)
TO BE TERMINATED AT PATCH PANELS IN
2-AWG#24, CAT6, LAN CABLE IN 27mm dia C.
NEW TELEPHONE TERMINAL BOARD
LENGTH AS REQUIRED (TYPICAL)
NEW CABLE TRAY 200mm(W)x100mm(H)
EXOTHERMIC WELDING, LISTED COMPRESSION TWO-
1. THE CONNECTIONS OF THE BONDING CONDUCTOR FOR
TELECOMMUNITIONS TO THE TMGB SHALL UTILIZE
HOLE LUGS, SUITABLE AND EQUIVALENT TWO-HOLE
1#6 "BC" IN 21C
CONN TO MAIN PANELBOARD
NOT TO SCALE
STAMP FACING OUT" TO ENSURE THAT THEY CAN BE
3. TEST RESULTS WILL BE PROVIDED IAW THE MOST RECENT
REVISION OF THE ANSI/TIA/EIA-568.
4. LABEL ALL DROPS IAW TIA/EIA-606-A.
5. LABEL ALL GROUNDS IAW I3A.
LUGS ARE PREFERRED.
FIELD VERIFIED.
TO TELEPHONE PATCH PANEL
TGB
CONN TO TMGB
1#6 "BC" IN 27C
(100mm x 450mmLG x 6.4mmTHK)
GROUND BUS BAR(TGB)
TMGB
G
(TYPICAL)
CABLE SUPPORT
G
110TYPE TERMINAL BLOCK
(TYPICAL)
CROSS CONNECTION CORD AS REQ'D
PLUS 25% SPARES TO BE FURNISHED BY THE
1#6 "BC" IN 16C
G
FOR TELEPHONE
1-48PORT PATCH PANEL
AS REQ'D
PROVIDE PATCH CORDS
HUB(N.I.C)
1-48PORT PATCH PANEL
W/ RACK MOUNTED 6-SINGLE
REAR RECEPTACLE, ON-OFF
SWITCH & CORD, 2P-3W-20A-125V
GROUND BUS BAR(TGB)
TELECOMMUNICATION
TELECOMMUNICATION MAIN
PTB
CONTRACTOR
RECEPTACLES
(1-25PAIR)
ENTRANCE TERMINAL BLOCK
110 TYPE PROTECTED
G
2. "PLYWOOD WILL BE INSTALLED WITH FIRE RATED
NOTE.
SHALL BE COORDINATED WITH BASE SIGNAL COMPANY.
SYSTEM AND WIRING FOR GOVERNMENT APPROVAL. TELECOMMUNCATION WORK
6. CONTRACTOR SHALL SUBMIT SHOP DRAWING FOR DETAILED TELECOMMUNICATION
1-24CORE, FIBER OPTIC CABLE IN 103C.
PATCH PANEL W/"SC" CONNECTOR
1-24 STRAND FIBER OPTIC
QUAD-PLEX RECEPTACLE
2P-3W-125V-20A GND TYPE
WITH DEDICATED CIRCUIT
(24"(W)x72"(H)x36"(D)
POWER SURGE PROTECTION
COMM RM
1-25PAIR, #24AWG TEL CABLE IN 103C.
TO EACH TEL OUTLET AS REQ'D VIA CABLE TRAY
3,200(W)x2,400(H) FIRE RATED PLYWOOD
TELEPHONE TERMINAL BOARD ("TTB"),
G
A
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
ELECTRICAL
(100PAIR) FOR TEL
(TYPICAL)
NEW LAN/TEL SYSTEM DIAGRAM
TO EACH DATA OUTLET AS REQ'D VIA CABLE TRAY
G
TO BE TERMINATED AT FIBER OPTIC PATCH PANEL
LENGTH AS REQUIRED
CABLE TRAY 300mm(W)x(150(H)
G
G
G
"MDP" GROUNDING BUS BAR
FOR DATA
(TYPICAL)
NEW LAN/TEL SYSTEM DIAGRAM
TO PNLBD C-1
EQUIPMENT CABINET
E-10
KIM, SY
CP CASEY
REPAIR QUONSET HUT BUILDING S-1709,
TO PNLBD C-2
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
ELECTRICAL
E-11
TV TV TV
TV TV
TV
TVCTC
SCALE:1/100
NEW FL CATV PLAN
TV
TV
WALL MOUNTED TYPE
TV OUTLET
TYPE CONNECTOR
W/"0.0"dB LOSS FACE
PLATE & F-81 BARREL
CEILING) (TYPICAL)
(MH:+450mm BELOW
COAXIAL CABLE
RG 6/U IN 16C
(TYPICAL)
RG 11/U IN 21C
COAXIAL CABLE
"C
NEW GROUND FL CATV PLAN
KIM, SY
CP CASEY
REPAIR QUONSET HUT BUILDING S-1709,
132491
W.TOILET
FEC
MECH/ELEC
ROOM
ROOM
FEC
OFFICE-1 OFFICE-3
STORAGE
VEST
VEST
OFFICE-2
OFFICE-5 OFFICE-4
COMM
102 103 104
105106
JAN
M.TOILET
CORRIDOR
EWC
BB
BB
BREAK RM
RM
CONFERENCE
CAPABILITIES, LOCKING DEVICE AND
INCLUDING NEW 3-WAY SPLITTER,
NEW CATV DISTRIBUTION CABINET
AIR VENTS SHALL BE INSTALLED
ON CATV CABINET TO ENSURE
ADEQUATE VENTILATION IN COMM RM
NEMA 1 ENCL
TRUNK BRIDGE AMPLIFIERS W/RETURN PATH
DEVICES BY COORDINATING WITH BASE CATV COMPANY.
CONNECTION POINT AND PROVIDE CATV CABLE, CONNECTION
CONTRACTOR SHALL VERIFY EXIST EXTERIOR CATV LINE
WITH ASSOCIATED ACCESSORIES
NEW O/H CATV CABLE, RG-11/U W/ MESSENGER WIRE,
TV WALL MOUNTED TYPE TV OUTLET
W/"0.0"dB LOSS FACE PLATE & F-81 BARREL
* ADDITIONAL LEGEND(THIS SHEET ONLY)
TYPE CONNECTOR (MH:+450mm BELOW CEILING)
G
C T
V
AMP
A
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
ELECTRICAL
TV
TV
TVTV
TV
TV
TV
TV
NOT TO SCALE
105104
9.
NOTES
1.
KORO, BASE CATV PERSONNEL PRIOR TO ORDERING.
ACCEPTANCE INSPECTION.
dbMV LEVELS.
CONTRACTOR PRIOR TO START OF WORK. ASSURANCE BRANCH PERSONNEL i.e. CORPS OF ENGINEERS, UPON BY BASE CATV PERSONNEL, CONTRACTOR, AND ANY QUALITY
MATERIAL AND PASSIVE DEVICES TO BE USED MUST BE AGREED
COORDINATION WITH BASE CATV PERSONNEL ON THE TYPE OF CABLE
THEN, BASE CATV PERSONNEL WILL INSPECT/TEST ALL PROJECTS
ON USFK INSTALLATIONS FOR QUALITY ASSURANCE.
RESULTS WILL BE RECORDED AND AVAILABLE AT THE FINAL
CONTRACTORS WILL COORDINATE WITH BASE CATV PERSONNEL
30 DAYS PRIOR TO PERFORMING FINAL ACCEPTANCE TESTING.
RANGE FROM 5 TO 860MHZ, RETURN PATH 5-42MHZ,
TO INCLUDE ALL ATTENUATION'S TO COMPENSATE FOR
C-COR LINE EXTENDER, DIRECTIONAL COUPLERS, SPLITTERS,
AND TAP-OFF'S ARE TO BE 2WAY AND OPERATE IN THE
COORDINATE LOCATION OF "NODE EQUIPMENT" WITH BASE
BASE CATV PERSONNEL.
TAP UNITS, SPLITTERS, AMPLIFIER, COAXIAL CABLE, etc.
THE SPECIFICATION OF MATERIALS SUCH AS CATV OUTLET
CATV SYSTEM. IT SHALL BE COORDINATED WITH
SHALL BE COMPATIBLE WITH THE EXISTING BASE
2. ALL CATV MATERIAL AND EQUIPMENT MUST HAVE RETURN
PATH(2-WAY) CAPABILITIES.
3. PROVIDE DIAGONAL VENTS ON OPPOSITE SIDE OF CATV PANEL;
ONE VENT HIGH AND ONE VENT LOW.
4.
5.
6.
7. INITIAL TESTING OF CATV SYSTEM SHALL BE PERFORMED BY THE
CONTRACTOR TO MEET THE REQUIREMENT OF CATV dB.
8.
THE LOCATION OF PULL BOX WITH COUPLERS WHICH IS INSTALLED
ABOVE THE CEILING SHALL BE MARKED ON THE CEILING FOR THE
MAINTENANCE.
NEW CATV SYSTEM DIAGRAM
NEW CATV SYSTEM DIAGRAM
INCLUDING NEW 3-WAY SPLITTER,
TRUNK BRIDGE AMPLIFIERS W/RETURN PATH
CAPABILITIES, LOCKING DEVICE AND
AIR VENTS SHALL BE INSTALLED
ON CATV CABINET TO ENSURE
ADEQUATE VENTILATION IN COMM RM
NEMA 1 ENCL
NEW ENTRANCE CAP
ON EXTERIOR WALL
& SECOND RACK
NEW GROUNDING WIRE
RG 11/U IN 21C
COAXIAL CABLE
NEW CATV DISTRIBUTION CABINET
E-12
TV
NTS
RG 11/U IN 21C
COAXIAL CABLE
(TYPICAL)
(2P-3W-20A-125VAC,
NEW DUPLEX RECEPTACLE
GROUNDING TYPE)
FOR CATV AMPLIFIER
TO PNLBD "C-4"
(2P-3W-20A-250VAC,
NEW SINGLE RECEPTACLE
GROUNDING TYPE)
FOR CATV AMPLIFIER
TO PNLBD "C-3"
EXTERIOR
NEW O/H CATV CABLE
RG 11/U IN 21C
COAXIAL CABLE
WALL MOUNTED TYPE
TV OUTLET
TYPE CONNECTOR
W/"0.0"dB LOSS FACE
PLATE & F-81 BARREL
CEILING) (TYPICAL)
(MH:+450mm BELOW
PULL BOX (300 x 300 x 200D)
W/ 8-WAY TAP-OFF AND LOCKING
DEVICE ABOVE CORRIDOR CEILING
(5-1000MHZ) (TYPICAL)
RG 6/U IN 16C
COAXIAL CABLE
(TYPICAL)
ROOM NO WHERE
DEVICE IS LOCATED
(TYPICAL)
KIM, SY
CP CASEY
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
E-13
ELECTRICAL
3 100 22000
TOTAL LOAD
LOAD
TOTAL
LOAD DESCRIPTION
NO.
CKT
GND
S/N
DIAGRAM
CONNECTION
CIRCUIT BREAKER
PHASE LOAD
A B PC AT
SIZE
AF AIC
B CA N G
REMARK
MTD TYPE, NEMA 1 ENCL.
3PHASE ,4WIRE, 120/208V,
107456
PANELBOARD "P1"
PANELBOARD "P2"
PANELBOARD "C"
60HZ, SN & GND, SURFACEPANELBOARD "MDP" LOAD SCHEDULE
36089 35817 35549
MAIN 3P-400AF-300AT CIRCUIT BREAKER 2SET OF 4#2/0 & 1#2(G)
PANELBOARD "M"
SPACE
SPACE
SPACE
4#4&1#8(G)20372 7490 62006682
15563 4781 53245457
250041259250 2625
10071 40002293 3778
43200
SPACE
SPACE
SPACE
4#6 & 1#8(G)
HEAT PUMP UNIT
OUTDOOR SPLIT SYSTEM
SPARE 3000
SPARE 3000
SPARE 3000 1000 1000 1000
1000 1000 1000
1000 1000 1000 20
20 -
SPACE
SPACE
SPACE - - - - ---
SPACE - - - - ---
- --- - - -SPACE - -
SPACE - - - - ---
TOTAL DEMAND LOAD ; 86,261(VA)
NEW PANELBOARD "MDP" LOAD SCHEDULE
NEW POWER ONE-LINE DIAGRAM &
KIM, SY
CP CASEY
REPAIR QUONSET HUT BUILDING S-1709,
132491
NOT TO SCALE
OUTDOOR
INDOOR
300AT
400AF
100AF
3P
3P
3P 3P
100AF
3P
CONDUCTOR, #3/0(G) IN 21C
NEW GROUNDING
CU BUS, 300A
22,000AIC SYM
G
S/NGND
100AF
321 5
FOR ABBREVIATION, LEGEND, GENERAL NOTES1.
& SCOPE OF WORK,
NOTES
PROVIDE A LABEL WITH THE FOLLOWING INSCRIPTION
"FIRE PROTECTION/LIFE SAFETY EQUIPMENT" CONSTRUCT
AND FASTEN THE LABEL IDENTICAL TO THE PANEL
NAMEPLATE, EXCEPT THE LABEL MUST BE RED LAMINATED
PLASTIC WITH THE WHITE CENTER CORE.
2.
"P1" "P2"
PVC CONDUIT
NEW U/G SEC LINE, 2WAY OF 103dia
EXT
CT BOX W/CT'S
300/5Ax3EA
WHM
7#12 IN 21C
W/NEW ADVANCED DIGITAL WATTHOUR
METER, TRANSFORMER TYPE
WITH 15 MINUTES DEMAND REGISTER
FOR 3PH, 4WIRE, 120/208V, 60Hz
NEMA 3R ENCL
REPLACE THE DETERIORATED EXISTING WHM
80AT
100AF
60AT 50AT
NEW CONDUIT COUPLING (TYPICAL)
CONNECTION (TYPICAL)
NEW GROUND ROD, COPPER CLAD
STEEL, 19diax3000LG WITH WELDING
NEW 1#3/0 "BC" IN 27C
OIL-FILLED, SELF-COOLED, LOAD BREAK SW,
NEW PAD MOUNTED,
3PH, 11.4KV-120/208V, 60HZ, 150KVA
REPLACE EXISTING PRIM LINE
IN 103dia PVC CONDUIT
W/BUILT-IN PROTECTIVE DEVICES (10A FUSE)
G
G
EXIST O/H PRIM LINE,
3PH, 4W, 11.4KW
RADIAL TYPE TRANSFORMER, METAL ENCL,
SEE SHEET NO. E-1.
EXIST/NEW POWER ONE-LINE DIAGRAM
"XLP" 25KV & 1-1/C, #2/0, "XLP" 600V
WITH NEW U/G PRIM LINE, 3-1/C, #2/0,
4#4 &
IN 41C
1#8(G)
4#6 &
IN 35C
1#8(G)
NEW
2SETS OF 4-2/0 & #2(G)IN 103C.
4#6 &
IN 35C
1#8(G)
"C"
60AT
SURGE SUPPRESSOR
TRANSIENT VOLTAGE
NEMA 1 ENCL
TVSS
"M"
3P
225AF
NEMA 3R ENCL
4#6 &
IN 35C
1#8(G)
WITH NEW MAIN PANELBOARD "MDP"
REPLACE EXISTING MAIN PANELBOARD
3P
100AF
3P
100AF
20AT
3P
100AF
3P
100AF
20AT
3P
100AF
3P
100AF
20AT150AT
A
1#4(G)
IN 53C
EXT
OHPU
SPARE SPARE SPARE
A
NON-FUSIBLE, NEMA 3R ENCL
SAFETY SWITCH, 3PST, 240V, 200A
FOR OHPU-1
14400 14400 14400 3#1/0&1#4(G)
3#1/0 &
NEW CONC POLE "E2"
NEW #4 "BC"
ARRESTER, 18KV-3EA
NEW LIGHTNING
NEW FUSE CUTOUT SWITCH
25KV, 100A W/25A FUSE-3EA
ADAPTER KIT FOR SINGLE
NEW TERMINATION AND
25KV-3EA & 600V-1EA
CONDUCTOR (#1, MAX)
OUTDOOR SPLIT SYSTEM HEAT PUMP UNIT
84 AMP MCA, 208 VOLTS, 3 PH,(MECH ITEM)
1WAY: 2SET OF 4#2/0 & 1#2(G)
1WAY: SPARE W/PULL WIRE & CAP
1 100 10000 2#12&1#12(G)
LOAD
TOTAL
PANELBOARD "P1" LOAD SCHEDULE
LOAD DESCRIPTION
NO.
CKT
GND
S/N
DIAGRAM
CONNECTION
CIRCUIT BREAKER
PHASE LOAD
A B PC AT
SIZE
AF AIC
B CA N G
REMARK
MTD TYPE, NEMA 1 ENCL.
3PHASE ,4WIRE, 120/208V,
435 20
9 10
60HZ, SN & GND, FLUSH
RCPTS 180VA x3EA
RCPTS 180VA x3EA
RCPTS 180VA x4EA
RCPTS 180VA x1EA
RCPTS 180VA x3EA
RCPTS 180VA x5EA
RCPTS 180VA x5EA
RCPTS 180VA x3EA
2 100 10000 2#12&1#12(G)
LOAD
TOTAL
PANELBOARD "P2" LOAD SCHEDULE
LOAD DESCRIPTION
NO.
CKT
GND
S/N
DIAGRAM
CONNECTION
CIRCUIT BREAKER
PHASE LOAD
A B PC AT
SIZE
AF AIC
B CA N G
REMARK
MTD TYPE, NEMA 1 ENCL.
3PHASE ,4WIRE, 120/208V,
608 20
60HZ, SN & GND, FLUSH
5001000
RCPT FOR CATV EQUIPMENT
TOTAL LOAD 25004125 2625
LOAD
TOTAL
PANELBOARD "C" LOAD SCHEDULE
LOAD DESCRIPTION
NO.
CKT
GND
S/N
DIAGRAM
CONNECTION
3PHASE ,4WIRE, 120/208V,
MTD TYPE, NEMA 1 ENCL.
CIRCUIT BREAKER
1000 1000 1
PHASE LOAD
A B PC
20100 10000
AT
SIZE
AF AIC
B CA N G
REMARK
2#12&1#12(G)
TVSS
11000
2250 1125
COMM RACK
RCPT FOR TTB
RCPT FOR CATV EQUIPMENT
SPARE
MAIN 3P-100AF-50AT CIRCUIT BREAKER
SPACE
SPACESPACE
SPACESPACE
SPARE
TVSS
SPACE - - - -
SPACE - - - - - - - -
SPACE - - - - - - - -
SPACE - - - - - - - -
3 30
1000 1000 -
TOTAL DEMAND LOAD ; 6150(VA)
& OUTDOOR UNIT (ACI & ACO)
SPLIT AIR CONDITIONING INDOOR
SPACE - - - -
10001000SPARE
1 20
20100
4#10&1#10(G)
SPACE - - - - - - - -
SPACE - - - - - - - -
SPACE - - - - - - - -
60HZ, SN & GND, FLUSH
4#6 & 1#8(G)
A
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
E-14
ELECTRICAL
LIGHTS LED 45W x1EA, 25W x7EA, RCPTS 180VA x4EA
RCPTS 180VA x3EA
RCPTS 180VA x5EA
MICROWAVE
RCPTS 180VA x4EA
21 22
HEAT PUMP-1x1EA & 3x2EA
VENTILATION UNIT
ENERGY RECOVERY
ELECTRIC WALL HEATER
ELECTRIC WALL HEATER
5 6
7 8
9 10
13 14
SPARE
SPARE
SPARE
SPARE
SPARE
SPACE
SPACE
304 304
153 153
210 210
SPACE SPACE
11 12
10002000
1000 1000
TOTAL LOAD 15563 4781 53245457
4#6 & 1#8(G)MAIN 3P-100AF-60AT CIRCUIT BREAKER
TOTAL DEMAND LOAD ; 11,563 (VA)
TOTAL LOAD 20372 7490 62006682
4#4 & 1#8(G)MAIN 3P-100AF-80AT CIRCUIT BREAKER
TOTAL DEMAND LOAD ; 12,565 (VA)
10000
TOTAL LOAD
LOAD
TOTAL
LOAD DESCRIPTION
NO.
CKT
GND
S/N
DIAGRAM
CONNECTION
CIRCUIT BREAKER
PHASE LOAD
A B PC AT
SIZE
AF AIC
B CA N G
REMARK
MTD TYPE, NEMA 1 ENCL.
3PHASE ,4WIRE, 120/208V,
10071
60HZ, SN & GND, SURFACE
SPACE --- - - - -
SPACE ---- - - - -
SPACE ---- - - -
SPACE
SPACESPACE
SPACE SPACE
SPACE
SPACE
PANELBOARD "M" LOAD SCHEDULE
2#12&1#12(G)
4#6 & 1#8(G)
7 SPARE 1000 1000
8 SPARE 1000 1000
10001000SPARE9
2293 3778
SPACE
SPACE ---- - - - -
MAIN 3P-100AF-60AT CIRCUIT BREAKER
LIGHTING CONTACTOR "LC",
ELECTRIC UNIT HEATER-1 21500 1500
ELECTRIC HOT WATER HEATER 1500
LOAD SCHEDULE
NEW PANELBOARD
KIM, SY
CP CASEY
REPAIR QUONSET HUT BUILDING S-1709,
132491
LIGHTS LED 50W x6EA, 45W x3EA
LIGHTS LED 50W x12EA, 45Wx3EA
25W x4EA, 18W x1EA, 4.99W x3EA
REF, RCPTS 180VA x2EA
RCPTS 180VA x3EA
RCPTS 180VA x5EA
RCPTS 180VA x5EA
22 RCPTS 180VA x2EA 360 360
HEAT PUMP-1x1EA, 3x3EA
& 2x1EA & 4x2EA
HEAT PUMP-1x2EA
ELECTRIC WALL HEATER
ELECTRIC WALL HEATER
EXTERIOR LIGHTS LED 22W x3EA 66 66
RCPTS 180VA x3EA 540 540
EXTERIOR LIGHTS LED 49W x2EA
RCPTS 180VA x1EA
WALL EXHAUST FAN-1 187 187
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPACE
SPACE
SPACE SPACE
114 114
SPACESPACE
SPACE
SPACE
1000 1000
18W x5EA, FAN 187W x1EA
LIGHTS LED 50W x6EA, 45W x2EA, 2#8&1#10(G)
9 SPACE
TOTAL DEMAND LOAD ; 8283(VA)
2#12&1#12(G)
FMCP
DEVICE
LOCKING
WITH
C
MH25
C
MHA1-11
C
MHA1-12
COMM RM
A
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
SCALE :1/400
EXIST/NEW EXTERIOR TELECOMMUNICATION LINE DISTRIBUITION PLAN
ELECTRICAL
MODE FIBER OPTIC CABLE
NEW SPLICE KIT FOR 1-12 CORE SINGLE
EXIST TELECOMMUNICATION MH-10 (TYPICAL) /IN EXIST U/G DUCT WAY
NEW 1-12 CORE SINGLE MODE FIBER OPTIC CABLE
IN EXIST U/G DUCT WAY
NEW 1-12 CORE SINGLE MODE FIBER OPTIC CABLE
EXIST MH (TYPICAL)
NOTES
FOR ABBREVIATION, LEGEND, AND GENERAL NOTES
SEE SHEET NO. E-1.
1.
2. CONTRACTOR SHALL PROVIDE ADEQUATE SUPPORTS
TO FIX NEW TELECOM CABLES.
3. NEW SINGLE MODE FIBER OPTIC CABLE
AND TELEPHONE CABLE SHALL BE INSTALLED
COORDINATED WITH BASE SIGNAL COMPANY.
AND TYPE OF SPLICE KITS SHALL BE
ON THE EXISTING MANHOLES,
THE CONTRACTOR SHALL VERIFY EXISTING
UNDERGROUND TELECOMM LINE'S ACTUAL
CONDITION PRIOR TO WORK.
4.
1-25PAIR AWG#24 TELEPHONE CABLE IN PATCH PANEL &TTB
TERMINATE 1-12 CORE SINGLE MODE FIBER OPTIC CABLE
NEW COMM RM /
IN FABRIC MESH 3x3" CELL INNER DUCT
1WAY: 1-25PAIR TELEPHONE CABLE
IN FABRIC MESH 3x3" CELL INNER DUCT
1WAY: 1-12 SINGLE MODE FIBER OPTIC CABLE
CONCRETE ENCASEMENT
NEW 2WAY OF 103mm PVC CONDUIT WITH
TELEPHONE CABLE IN EXIST MH 1-12
NEW SPLICE KIT FOR 1-25 PAIR /
EXIST TELECOMMUNICATION MH 1-12 /
T T
T T
T
T T U/G
U/G
U/G
U/G U/G
U /G
U /G
U/G
U/G
U/G T
T
T
T
LINE DISTRIBUITION PLAN
EXIST/NEW EXTERIOR TELECOMMUNICATION
132491
KIM, SY CP CASEY
E-15
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
SCALE:1/200SCALE:
REMOVAL/EXIST/NEW EXTERIOR ELECTRICAL DISTRIBUTION PLAN
ELECTRICAL
DISTRIBUTION PLAN
REMOVAL/EXIST/NEW EXTERIOR ELECTRICAL
E-16
E
E1
E
E
E
E
E~
E2
NEW PAD MOUNTED TRANSFORMER, METAL ENCL, RADIAL TYPE,
60HZ, 150KVA W/BUILT-IN PROTECTIVE DEVICES (10A FUSE)
OIL-FILLED, SELF-COOLED, LOAD BREAK SW, 3PH, 11.4KV-120/208V,
WHM
ROOM
ELEC
MECH/
U/G
U/G U/G
U /G
U /G
U /G
U /G
U /G
EXIST PAD MOUNTED TRANSFORMER
SEC LINE
REMOVE EXIST OVERHEAD
SEC LINE
REMOVE EXIST OVERHEAD
SEC LINE
REMOVE EXIST OVERHEAD
SEC LINE FOR BUILDING S-1710
REMOVE EXIST OVERHEAD
FOR BUILDING S-1710
FOR BUILDING S-1710SEC LINE
REMOVE EXIST OVERHEAD
FOR BUILDING S-1710
FOR BUILDING S-1710
EXIST OVERHEAD SEC LINE
NEW SMART WATT HOUR METER AND
CT'S NEMA 3R ENCL.
"M D
P
CONCRETE POLE (TYPICAL)
EXIST PRIMARY ELECTRIC
WOODEN POLE & SEC LINE
REMOVE EXIST
C T C
~DEVICES BY COORDINATING WITH BASE CATV COMPANY.
CONNECTION POINT AND PROVIDE CATV CABLE, CONNECTION
CONTRACTOR SHALL VERIFY EXIST EXTERIOR CATV LINE
NEW O/H CATV CABLE, RG-11/U W/ MESSENGER WIRE,
C tv
O /H
O /H
U /G
U /G
U /G
U /G
P
U /G
P
P
P
P
P
S
S
S
S
S
"XLP" 25KV & 1-1/C, #2/0, "XLP" 600V IN 103dia PVC CONDUIT
NEW U/G PRIM LINE, 3-1/C, #2/0,
"M
"W P
S
"W P
L
L
NS-14
CEILING SURFACE MOUNTED VAPOR TIGHT LED STRIP LIGHT
(NS-14) AS REQUIRED
120V, 49W, UL LISTED, WET LOCATION TYPE, WITH CONVERTER
FIXTURE, MODEL:CSVT - L48, LITHONIA LIGHTING, 5000K, 1PH,
& ACCESSORIES,
NEW LED LIGHTING FIXTURE
(TYPICAL OF 2EA)
TYPE: "NS-14",49W, SURFACE
CIRCUIT INTERRUPTER TYPE,WEATHER PROOF
DUPLEX RECEPTACLE, 2P-3W-20A-125V, GROUND FAULT
EXIST PAD MOUNTED TRANSFORMER, 300KVA
E
EXIST PAD MOUNTED TRANSFORMER, 500KVA
EXIST SEC LINE CON C POLE (TYPICAL)
EXIST PAD MOUNTED TRANSFORMER, 300KVA
15A-125V W/COVER PLATE
SINGLE POLE TOGGLE SWITCH, (WEATHER PROOF TYPE)
CP CASEY
REPAIR QUONSET HUT BUILDING S-1709,
KIM, SY
132491
NEW U/G CONCRETE ENCASED SEC LINE 2-AWG #8 & #10(G) IN 27C
TO "M-3" IN NEW PNLBD "M", BUILDING S-1709
2SET OF 4-AWG #2/0 & 1#1/0(G) 103C
FOR "MDP" PANEL IN S-1709
NEW U/G CONCRETE ENCASED
4- AWG #2 IN 53C FOR BUILDING S-1710
NEW U/G CONCRETE ENCASED SEC LINE
RECONNECT FROM EXISTING POLE "E1" TO NEW POLE "E2"
EXIST O/H PRIMARY LINE
REMOVE EXIST PRIMARY POLE "E1"
O /H
P
O /H
P
O /H
P
O /H
P
O /H
P
O /H
EXIST O/H PRIMARY LINE
RECONNECT FROM EXISTING POLE "E1" TO NEW POLE "E2"
4'(D)x4'(W)x4'(H)
NEW ELECTRIC MANHOLE,
4'(D)x4'(W)x4'(H)
NEW ELECTRIC MANHOLE,
O/H
O/H
O/H
O/H
P
P
P
REMOVE EXIST OVERHEAD PRIMARY LINE
103 dia, SEALING BUSHING, INSULATORS, TEMINATION KITS 24KV, CROSSARM, ENTRANCE CAP, INCUDING FUSE CUTOUT SWITCHS, INSTALL NEW PRIMARY "E2"CON C POLE(16M) / PROVIDE NEW MOUNTING ASSEMBLIES
LIGHTNING ARRESTER 24KV,
STEEL BAND, GUY WIRE & NECESSARY ACCESSORIES
"XLP" 25KV & 1-1/C, #2/0, "XLP" 600V IN 103dia PVC CONDUIT
NEW U/G PRIM LINE, 3-1/C, #2/0,
ARRESTERS, WITH ASSOCIATED ACCESSORIES ON EXIST PRIMARY POLE
TERMINATION KITS, FUSECUTOUT SWITCHES, LIGHTNING
PRIMARY LINE CABLE RISER SET INCLUDING
EXIST PRIMARY POLE/ PROVIDE NEW UNDERGROUND
| 1 |
| 2 |
| 3 |
| 4 |
| 5 |
| 6 |
| 7 |
| 8 |
| 9 |
| 10 |
| 11 |
| 12 |
| 13 |
| 14 |
| 15 |
| 16 |