This document is a Request for Proposal (RFP) for the GLERL, LMFS, Building 3 Addition Project issued by the U.S. Department of Commerce, National Oceanic and Atmospheric Administration (NOAA). The Government intends to award a single Firm-Fixed-Price (FFP) contract for the contractor to provide all effort, work, planning, labor, materials, equipment, permits, transportation and performance of all operations necessary for the Building 3 Addition. Key details include: the solicitation number is 1305M324R0067, the site visit is scheduled for July 12, 2024, proposals are due by August 5, 2024, and the anticipated award date is August or September 2024. The solicitation includes multiple attachments such as the Statement of Work, architectural drawings, specifications, furniture plan, environmental assessment, and geotechnical report.
View the file
Other files
Show all 18
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
TYPE OF EXISTING CONSTRUCTION:
USE GROUP:
B BUSINESS (Section 304)
TYPE IIB (Section 602)
ALLOWABLE AREAS (Table 506.2) AREA of Tenant Space:
FIRST FLOOR 906 SF
OCCUPANT LOAD (Table 1004.5): [Gross Area / SF per Person = # Persons]
TOTAL Occupant Load (By Calculation) = 9 Persons
NUMBER OF EXITS - TABLE 1006.2.1
Minimum No. of Exits
Based on Occupant Load:
Required Provided
B (BUSINESS) = 906 SF 100 SF/Person = 9 Persons
APPLICABLE CODES (MICHIGAN BUILDING CODE BASED ON IBC 2015)
KEY PLAN
LOCATION MAP
PROJECT TEAM
SYMBOLS LEGEND
RM NAME
ELEVATION/DWG. OR
BLDG. SECTION/DWG.
OR WALL SECTION/DWG.
REVISION -
CONSTRUCTION
BULLETIN
C.J. CONTROL JOINT
CLG. CEILING
CLKG. CAULKING
CLR. CLEAR
C.O. CASED OPENING
COL. COLUMN
CONC. CONCRETE
CONN. CONNECTION
CONST. CONSTRUCTION
CONT. CONTINUOUS
CORR. CORRIDOR
CTSK. COUNTERSUNK
CNTR. COUNTER
C.T. CERAMIC TILE
CTR. CENTER
DBL. DOUBLE
DEPT. DEPARTMENT
D.F. DRINKING FOUNTAIN
DET. DETAIL
DIA. DIAMETER
DIM. DIMENSION
DISP. DISPENSER
DN. DOWN
HDWE HARDWARE
H.M. HOLLOW METAL
HORIZ. HORIZONTAL
HR. HOUR
I.D. INSIDE DIMENSION
INSUL. INSULATION
INT. INTERIOR
O.A. OVERALL
OBS. OBSCURE
O.C. ON CENTER
O.D. OUTSIDE DIMENSION
OPNG. OPENING
OPP. OPPOSITE
PRCST. PRE-CAST
PL. PLATE
P.LAM. PLASTIC LAMINATE
PLAS. PLASTER
PLYWD. PLYWOOD
HDWD HARDWOOD
D.O. DOOR OPENING
DR. DOOR
DWR. DRAWER
DS. DOWNSPOUT
DWG. DRAWING
E. EAST
E.J. EXPANSION JOINT
EL. ELEVATION
ELEC. ELECTRICAL
EMER. EMERGENCY
ENCL. ENCLOSURE
EQ. EQUAL
EQPT. EQUIPMENT
E.W.C. ELECTRIC WATER COOLER
EXIST. EXISTING
EXPO. EXPOSED
EXP. EXPANSION
EXT. EXTERIOR
F.D. FLOOR DRAIN
FDN. FOUNDATION
F.E. FIRE EXTINGUISHER
F.E.C. FIRE EXTINGUISHER CABINET
FIN. FINISH
FIXT. FIXTURE
FL. FLOOR
FLASH. FLASHING
FLUOR. FLUORESCENT
F.O.C. FACE OF CONCRETE
F.O.F. FACE OF FINISH
F.O.S. FACE OF STUDS
FT. FOOT OR FEET
FTG. FOOTING
FURR. FURRING
GALV. GALVANIZED
GL. GLASS
GR. GRADE
GYP. GYPSUM
GYP.BD. GYPSUM WALLBOARD
H.B. HOSE BIBB
H.C. HOLLOW CORE
PR. PAIR
PSF POUNDS PER SQUARE FOOT
Q.T. QUARRY TILE
R. RISER
RAD. RADIUS
R.D. ROOF DRAIN
REF. REFERENCE
REFR. REFRIGERATOR
REINF REINFORCED
REQD REQUIRED
RESIL. RESILIENT
RM. ROOM
R.O. ROUGH OPENING
RWC RAINWATER CONDUCTOR
S. SOUTH
S.C. SOLID CORE
SCHED. SCHEDULED
SHT. SHEET
S.J. SAWCUT JOINT
SIM. SIMILAR
SPEC. SPECIFICATION
SPECD. SPECIFIED (SECTION)
S.ST. STAINLESS STEEL
STD. STANDARD
STL. STEEL
STOR. STORAGE
STRUC. STRUCTURAL
SUSP. SUSPENDED
T.C. TOP OF CURB
TEL. TELEPHONE
T&G TONGUE AND GROOVE
THK. THICK
T.O. TOP OF
T.P. TOP OF PAVEMENT
TV TELEVISION
T.W. TOP OF WALL
TYP. TYPICAL
UNF. UNFINISHED
U.O.N. UNLESS OTHERWISE NOTED
UR. URINAL
VCT VINYL COMPOSITION TILE
VERT. VERTICAL
VEST. VESTIBULE
W. WEST
W/ WITH
WD WOOD
W/O WITHOUT
WP WATERPROOF
WSCT. WAINSCOT
WT. WEIGHT
EA. EACH
CMU CONCRETE MASONRY UNIT
D DEPTH
H.D. HEAVY DUTY
HGT. HEIGHT
PSI POUNDS PER SQUARE INCH
RET. RETAINING
TS TUBE STEEL
FR.TR. FIRE-RETARDANT TREATED
I.G. INSULATING GLASS
PR.TR. PRESSURE TREATED
T.G. TEMPERED GLASS
U.G. UNDERGROUND
HSS HOLLOW STEEL SECTION
P.O.C. POINT OF CONNECTION
E.I.F.S. EXT. INSUL. & FINISH SYSTEM
O.H. OVERHANG
R.T.U. HVAC UNIT
P.S.F.F. PREFAB. STRUC. STL. FABR.
FABR. FABRICATOR/ FABRICATED
F.C. FURRING CHANNEL
F.O.M. FACE OF MASONRY
WDT. WIDTH
VENT THRU ROOF
V.I.F. VERIFY IN FIELD
V.T.R.
THR. THRESHOLD
SF STOREFRONT
SECT. SECTION
INFO. INFORMATION
PLMB. PLUMBING
QTR. QUARTER
RND. ROUND
F.O.(XX) FACE OF (XX)
GA. GAUGE
PRTN. PARTITION
T.I.G. TEMPERED INSULATING GLASS
VWC VINYL WALL COVERING
PT. POINT
PTD. PAINTED
S.F. SQUARE FEET
CER. CERAMIC
C.I. CAST IRON
C.G. CORNER GUARD
NO. NUMBER
NOM. NOMINAL
N.T.S. NOT TO SCALE
C.F. COLD FORMED
ARCH. DRAWING ABBREVIATIONS
& AND
L ANGLE
@ AT
L CENTERLINE
# POUND or NUMBER
ACCES. ACCESSIBLE
AL. ALUMINUM
APPROX. APPROXIMATE
ARCH. ARCHITECTURAL
ASPH. ASPHALT
BD. BOARD
BITUM. BITUMINOUS
BLDG. BUILDING
BLK. BLOCK
BM. BEAM
B.O. BOTTOM OF
CAB. CABINET
CEM. CEMENT
JAN. JANITOR
JT. JOINT
KIT. KITCHEN
LAM. LAMINATE
LAV. LAVATORY
LLH LONG LEG HORIZONTAL
MAX. MAXIMUM
MECH. MECHANICAL
MEMB. MEMBRANE
MET. METAL
MFR. MANUFACTURER
MIN. MINIMUM
MISC. MISCELLANEOUS
M.O. MASONRY OPENING
M.R. MOISTURE RESISTANT
MTD. MOUNTED
N. NORTH
N.I.C. NOT IN CONTRACT
C
B.C. BACK OF CURB
L. LENGTH
MED. MEDIUM
MAS. MASONRY
BRG.
BTWN.
BEARING
BETWEEN
ADJ. ADJUSTABLE
A.F.F. ABOVE FINISH FLOOR
ACT. ACOUSTICAL CEILING TILE
BUR BUILT-UP ROOFING MTG. MOUNTING
LLV LONG LEG VERTICAL
LT. LIGHT
GREAT LAKES
ENVIRONMENTAL RESEARCH LAB
LAKE MICHIGAN FIELD STATION
BUILDING 3 ADDITION
CODE DATA
NOAA GLERL-LMFS
1431 BEACH STREET
MUSKEGON, MI 49441
CONTACT: SCOTT BURNHAM
PHONE: (609) 379-2827
EMAIL: SCOTT.BURNHAM@NOAA.GOV
G-001
COVER SHEET
CPT CARPET
EF EXHAUST FAN
DRAWING TITLE:
NO
AA
G
RE
AT
LA
KE
S
EN
VI
RO
NM
EN
TA
L R
ES
EA
RC
H
LA
B
LA
KE
M
IC
HI
GA
N
FIE
LD
S
TA
TIO
N
- B
UI
LD
IN
G 3 A
DD
ITI
ON
B
EA
CH
S
TR
EE
T, MU
SK
EG
ON
, M I 4
1431 BEACH STREET, MUSKEGON, MI 49441
NOAA GLERL-LMFS
1431 BEACH STREET
MUSKEGON, MI 49441
NOAA GLERL-LMFS
1431 BEACH STREET
MUSKEGON, MI 49441
WINDOW TAG
DOOR TAG
WINDOW TAG
G-001 COVER SHEET
A-101 FLOOR PLAN - NEW WORK
A-102 REFLECTED CEILING PLAN - NEW WORK
A-103 ROOF PLAN - NEW WORK
A-104 BUILDING ELEVATIONS
S-101 FOUNDATION PLAN - NEW WORK
A-401 DETAILS
A-601 SCHEDULES
E-001 GENERAL ELECTRICAL NOTES
E-101 POWER PLAN - NEW WORK
E-102 LIGHTING PLAN - NEW WORK
A-105 BUILDING SECTION
BUILDING CODE MBC 2015
ELECTRIC CODE NEC 2017
PLUMBING CODE MPC 2018
MECHANICAL CODE IFC 2015
ENERGY CODE MEC 2015
FUEL GAS CODE MFGC 2015
E-002 GENERAL ELECTRICAL NOTES AND SCHEDULES
AutoCAD SHX Text W1
OFFICE
OFFICE
1.3 2.5 3.2 4.1
OPEN
OFFICE
A-101
FLOOR PLAN
NEW WORK
FLOOR PLAN - NEW WORK 1
1/4" = 1'-0"
PARTITION TYPES 4
N.T.S.
P1
P2
P3
P4
GENERAL NOTES 3
N.T.S.
KEYED NOTES 2
N.T.S.
DRAWING TITLE:
NO
AA
G
RE
AT
LA
KE
S
EN
VI
RO
NM
EN
TA
L R
ES
EA
RC
H
LA
B
LA
KE
M
IC
HI
GA
N
FIE
LD
S
TA
TIO
N
- B
UI
LD
IN
G 3 A
DD
ITI
ON
B
EA
CH
S
TR
EE
T, MU
SK
EG
ON
, M I 4
P1
P1
P4 P4 P4
P4 P4 P4
P4
P4
A-401
AutoCAD SHX Text 16'-2 "12"
AutoCAD SHX Text 16'-2 "12"
AutoCAD SHX Text 16'-2 "12"
AutoCAD SHX Text 50'-4"
AutoCAD SHX Text 8'-2
AutoCAD SHX Text 8'-2"
AutoCAD SHX Text 5'-4"
AutoCAD SHX Text 9'-7"
AutoCAD SHX Text 20'-1"
AutoCAD SHX Text
EQ
AutoCAD SHX Text
EQ
AutoCAD SHX Text
EQ
AutoCAD SHX Text
EQ
AutoCAD SHX Text 8"
AutoCAD SHX Text 6'-0"
AutoCAD SHX Text 1 PROVIDE VCT AND WALL BASE, TYP. THIS ROOM/AREA. 2 PAINT ALL WALLS, TYP. THIS ROOM/AREA. 3 NEW DOOR AND HOLLOW METAL FRAME, TYP. 4 PROVIDE NEW METAL STUD AND GYPSUM BOARD PARTITION, TYP. PARTITION TYPE AS INDICATED. 5 CUT NEW OPENING IN WALL. CUT THROUGH AND REMOVE EXTERIOR CUT NEW OPENING IN WALL. CUT THROUGH AND REMOVE EXTERIOR NSULATED METAL WALL PANEL, INTERIOR METAL STUD FRAMING AND GYPSUM BOARD. PROVIDE NEW METAL STUD FRAMING AND METAL STUD BOX HEADER FOR NEW OPENING. PROVIDE FINISHED DRYWALL OPENING WITH BOTTOM OF HEADER AT 8-FEET AFF. 6 BOX OUT COLUMN WITH PARTITION TYPE P2, TYP. ALL COLUMNS. BOX OUT COLUMN WITH PARTITION TYPE P2, TYP. ALL COLUMNS. 7 PROVIDE PAINTED WOOD WINDOW SILL AND FINISHED DRYWALL PROVIDE PAINTED WOOD WINDOW SILL AND FINISHED DRYWALL OPENING AROUND WINDOW ON THREE SIDES, TYP. FOR ALL WINDOWS.
AutoCAD SHX Text
KEYED NOTES THIS SHEET:
AutoCAD SHX Text
AREA NOT IN SCOPE
AutoCAD SHX Text
NEW WORK LEGEND:
AutoCAD SHX Text 3-5/8" X 20 GA. METAL STUDS @ 16" O.C. TO UNDERSIDE OF STRUCTURE, W/ 5/8" GYP. BD. ON BOTH SIDES AND R-13 BATT INSULATION FULL HEIGHT. 3-5/8" X 20 GA. METAL STUDS @ 16" O.C. TO UNDERSIDE OF STRUCTURE, W/ 5/8" GYP. BD. ON ONE SIDE AND R-13 BATT INSULATION FULL HEIGHT. 6" X 20 GA. METAL STUDS @ 16" O.C. TO UNDERSIDE OF STRUCTURE, W/ 5/8" GYP. BD. ON BOTH SIDES AND R-13 BATT INSULATION FULL HEIGHT. 6" X 20 GA. METAL STUDS @ 16" O.C. TO UNDERSIDE OF STRUCTURE, W/ 5/8" GYP. BD. ON ONE SIDE AND R-13 BATT INSULATION FULL HEIGHT.
AutoCAD SHX Text PARTITION NOTES: 1. ALL PARTITIONS TO BE TAPED, MUDDED, AND SANDED. READY FOR SCHEDULED FINISH.ALL PARTITIONS TO BE TAPED, MUDDED, AND SANDED. READY FOR SCHEDULED FINISH.
AutoCAD SHX Text
1. DEMOLITION PLANS SHOW THE APPROXIMATE LAYOUT OF THE EXISTING DEMOLITION PLANS SHOW THE APPROXIMATE LAYOUT OF THE EXISTING BUILDING AND ARE NOT INTENDED TO DOCUMENT "AS-BUILT" CONDITIONS. THE CONTRACTOR SHALL VISIT THE SITE AND BECOME FAMILIAR WITH ACTUAL CONDITIONS WHEN BIDDING THE WORK, PRIOR TO THE START OF CONSTRUCTION. 2. WALLS, PARTITIONS, DOORS, FRAMES, AND OTHER ITEMS TO BE REMOVED WALLS, PARTITIONS, DOORS, FRAMES, AND OTHER ITEMS TO BE REMOVED ARE SHOWN DASHED. SERVICES WITHIN THE WALLS AND PARTITIONS SHALL BE REMOVED. EDGES OF WALLS SHOWN TO REMAIN SHALL BE SAW CUT OR CLEANLY TOOTHED TO ACCEPT NEW CONSTRUCTION. REPAIR AND PATCH OF EXISTING WALLS SHOWN TO REMAIN WHERE INTERSECTING WALLS, DOORS, FRAMES, ETC. ARE SHOWN TO BE REMOVED WHERE EXISTING CONSTRUCTION WILL NOW BE EXPOSED IN THE NEW CONSTRUCTION. 3. AFTER OR DURING DEMOLITION ACTIVITIES, THE CONTRACTOR SHALL NOTIFY AFTER OR DURING DEMOLITION ACTIVITIES, THE CONTRACTOR SHALL NOTIFY THE GOVERNMENT OF ANY CONDITIONS THAT ARE MADE EVIDENT THAT WILL ALTER OR CONFLICT WITH THE COMPLETION OF THE WORK OR REQUIRE ADDITIONAL DEMOLITION TO MEET PROJECT REQUIREMENTS. 4. EXISTING CONSTRUCTION SHOWN TO REMAIN, INCLUDING WALLS, PARTITIONS, EXISTING CONSTRUCTION SHOWN TO REMAIN, INCLUDING WALLS, PARTITIONS, DOORS, FRAMES, ETC. SHALL BE PROTECTED DURING EXECUTION OF THE WORK. DAMAGE TO EXISTING CONSTRUCTION SHOWN TO REMAIN SHALL BE RESTORED TO MATCH PRE-DAMAGED CONDITION AT NO COST TO THE GOVERNMENT. 5. THE CONTRACTOR SHALL REMOVE, STORE, AND PROTECT MATERIALS TO BE THE CONTRACTOR SHALL REMOVE, STORE, AND PROTECT MATERIALS TO BE REINSTALLED OR RETAINED TO PREVENT DAMAGE. COORDINATE STORAGE LOCATION WITH THE GOVERNMENT. 6. BEFORE SAWCUTTING, CORING, OR PENETRATING THE EXISTING FLOOR SLAB, BEFORE SAWCUTTING, CORING, OR PENETRATING THE EXISTING FLOOR SLAB, THE CONTRACTOR SHALL TAKE DELIBERATE STEPS TO DETERMINE IF THE STRUCTURAL INTEGRITY OF THE SLAB WILL BE COMPROMISED. IF THE STRUCTURAL INTEGRITY WILL BE COMPROMISED BY THE WORK, THE CONTRACTOR SHALL NOTIFY THE GOVERNMENT AND RECEIVE DIRECTION BEFORE PROCEEDING.
AutoCAD SHX Text
GENERAL NOTES THIS SHEET:
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text F.0.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AREA NOT IN SCOPE
AutoCAD SHX Text
EXISTING 1-STORY PRE-ENGINEERED
AutoCAD SHX Text
METAL BUILDING
AutoCAD SHX Text W1
AutoCAD SHX Text W1
AutoCAD SHX Text W1
W1
1.3 2.5 3.2 4.1
OFFICE
OPEN
OFFICE
A-102
REFLECTED CEILING PLAN
NEW WORK
REFLECTED CEILING PLAN - NEW WORK 1
1/4" = 1'-0"
LEGEND 2
N.T.S.
DRAWING TITLE:
NO
AA
G
RE
AT
LA
KE
S
EN
VI
RO
NM
EN
TA
L R
ES
EA
RC
H
LA
B
LA
KE
M
IC
HI
GA
N
FIE
LD
S
TA
TIO
N
- B
UI
LD
IN
G 3 A
DD
ITI
ON
B
EA
CH
S
TR
EE
T, MU
SK
EG
ON
, M I 4
GENERAL NOTES 3
N.T.S.
A-401
AutoCAD SHX Text
LEGEND
AutoCAD SHX Text 2X4 LAY-IN LED TROFFER FIXTURE LED DIRECTIONAL EXIT FIXTURE CEILING MOUNTED LED EXIT FIXTURE CEILING MOUNTED COMBINATION LED EXIT/EMERGENCY FIXTURE 24"X24" SUPPLY AIR REGISTER 24"X24" RETURN AIR GRILLE EMERGENCY WALLPACK FIXTURE WALL-MOUNTED LIGHT FIXTURE
AutoCAD SHX Text +9'-0"
AutoCAD SHX Text
AREA NOT IN SCOPE
AutoCAD SHX Text
NEW WORK LEGEND:
AutoCAD SHX Text
AREA NOT IN SCOPE
AutoCAD SHX Text
EXISTING 1-STORY PRE-ENGINEERED
AutoCAD SHX Text
METAL BUILDING
AutoCAD SHX Text +9'-0"
AutoCAD SHX Text +9'-0"
AutoCAD SHX Text
1. INSTALL ACT CEILINGS CENTERED IN THE ROOM/AREA WITH EQUAL BORDERS, INSTALL ACT CEILINGS CENTERED IN THE ROOM/AREA WITH EQUAL BORDERS, UNLESS OTHERWISE INDICATED.
GENERAL NOTES THIS SHEET:
A-103
ROOF PLAN
NEW WORK
ROOF PLAN - NEW WORK 1
1/4" = 1'-0"
DRAWING TITLE:
NO
AA
G
RE
AT
LA
KE
S
EN
VI
RO
NM
EN
TA
L R
ES
EA
RC
H
LA
B
LA
KE
M
IC
HI
GA
N
FIE
LD
S
TA
TIO
N
- B
UI
LD
IN
G 3 A
DD
ITI
ON
B
EA
CH
S
TR
EE
T, MU
SK
EG
ON
, M I 4
AutoCAD SHX Text
AREA NOT IN SCOPE
AutoCAD SHX Text
NEW WORK LEGEND:
AutoCAD SHX Text
AREA NOT IN SCOPE
AutoCAD SHX Text
EXISTING 1-STORY PRE-ENGINEERED
AutoCAD SHX Text
METAL BUILDING
AutoCAD SHX Text
SLOPE DN
AutoCAD SHX Text STANDING SEAM METAL ROOF. MATCH PROFILE AND SLOPE OF THE ROOF ON THE EXISTING BUILDING. ALIGN RIBS, TYP.
AutoCAD SHX Text
GUTTER, MATCH GUTTER PROFILE ON THE EXISTING BUILDING.
AutoCAD SHX Text
DOWNSPOUT AND SPLASHBLOCK AT GRADE
AutoCAD SHX Text
ROOF STRUCTURE BY METAL BUILDING MANUFACTURER
AutoCAD SHX Text
REMOVE GUTTER AND FASCIA, TYP. AT INTERFACE WITH NEW ADDITION
AutoCAD SHX Text
CAP OPEN END OF GUTTER AFTER REMOVAL OF EXISTING GUTTER FOR THE ADDITION
AutoCAD SHX Text
SLOPE DN
AutoCAD SHX Text
SLOPE DN
EXISTING GUTTER TO REMAIN
A-401
DETAILS
DRAWING TITLE:
NO
AA
G
RE
AT
LA
KE
S
EN
VI
RO
NM
EN
TA
L R
ES
EA
RC
H
LA
B
LA
KE
M
IC
HI
GA
N
FIE
LD
S
TA
TIO
N
- B
UI
LD
IN
G 3 A
DD
ITI
ON
B
EA
CH
S
TR
EE
T, MU
SK
EG
ON
, M I 4
HEADER DETAIL 1
1" = 1'-0"
P4
OPEN
OFFICE
STAGING
HEADER DETAIL 2
1" = 1'-0"
P4
JAMB DETAIL 3
1" = 1'-0"
P4
HEADER DETAIL 4
1" = 1'-0"
P1
AutoCAD SHX Text METAL STUD BOX FRAME HEADER, 6" METAL STUDS AND METAL TRACK RUNNER TOP AND BOTTOM, TYP.
AutoCAD SHX Text
EXISTING BUILDING
AutoCAD SHX Text
NEW ADDITION
AutoCAD SHX Text 8'-0"
AutoCAD SHX Text
TO FLOOR
AutoCAD SHX Text
EL. 8'-0"
AutoCAD SHX Text
OPENING
AutoCAD SHX Text
6" METAL STUDS W/ 5/8" GYP. BOARD, TYP. FURRING ON INTERIOR OF EXIST. BUILDING
AutoCAD SHX Text
INSULATED METAL PANEL, TYP. ON EXTERIOR OF EXIST. BUILDING
AutoCAD SHX Text WOOD BLOCKING AS NEEDED TO CLOSE IN THE BOTTOM OF METAL STUD FRAMING AFTER CUTTING OFF STUDS FOR NEW OPENING, TYP. WIDTH OF THE OPENING
AutoCAD SHX Text
B.O. FINISHED
AutoCAD SHX Text
H.M. DOOR AND FRAME AS DOOR AND FRAME AS SCHEDULED
AutoCAD SHX Text
DRIP EDGE PER SCHEDULED DOOR HARDWARE SET
AutoCAD SHX Text
FLASHING BY PEMB MANUFACTURER
AutoCAD SHX Text
INSULATED METAL PANEL
AutoCAD SHX Text METAL STUD BOX FRAME HEADER, 6" METAL STUDS AND METAL TRACK RUNNER TOP AND BOTTOM, TYP.
AutoCAD SHX Text
WOOD BLOCK, AS REQUIRED
AutoCAD SHX Text
RETURN GYP. BOARD TO DOOR FRAME, TYP.
AutoCAD SHX Text
INSULATED METAL PANEL
AutoCAD SHX Text
FLASHING BY PEMB MANUFACTURER
AutoCAD SHX Text
WOOD BLOCK, AS REQUIRED
AutoCAD SHX Text
RETURN GYP. BOARD TO DOOR FRAME, TYP.
AutoCAD SHX Text
DOUBLE STUDS, TYP. AT DOOR JAMB, BOTH SIDES
AutoCAD SHX Text
FLASHING PER PEMB MANUFACTURER
AutoCAD SHX Text 9'-0"
AutoCAD SHX Text
TO FLOOR
AutoCAD SHX Text
EL. 9'-0"
AutoCAD SHX Text
ACT CEILING
AutoCAD SHX Text
ACT CEILING AS SCHEDULED
AutoCAD SHX Text
WOOD DOOR AND H.M. FRAME AS SCHEDULED
METAL STUD BOX FRAME HEADER, 3 5/8" METAL STUDS AND METAL TRACK RUNNER TOP AND BOTTOM, TYP.
A-601
SCHEDULES
ROOM FINISH SCHEDULE 1
N.T.S.
DOOR AND FRAME SCHEDULE 2
N.T.S.
DOOR HARDWARE SETS 4
N.T.S.
ADA DETAILS 7
N.T.S.
WINDOW SCHEDULE 12
N.T.S.
ADA SIGNAGE 13
N.T.S.
ADA DOOR CLEARANCE DETAILS 16
N.T.S.
FINISHES SCHEDULE 11
N.T.S.
DOOR AND FRAME TYPES 3
N.T.S.
A-401
DRAWING TITLE:
NO
AA
G
RE
AT
LA
KE
S
EN
VI
RO
NM
EN
TA
L R
ES
EA
RC
H
LA
B
LA
KE
M
IC
HI
GA
N
FIE
LD
S
TA
TIO
N
- B
UI
LD
IN
G 3 A
DD
ITI
ON
B
EA
CH
S
TR
EE
T, MU
SK
EG
ON
, M I 4
A-401
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text
OPEN OFFICE
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text
TYPE "WD-1"
AutoCAD SHX Text 3'-0"
AutoCAD SHX Text 7'-0"
AutoCAD SHX Text
WD-1
AutoCAD SHX Text
HM-1
AutoCAD SHX Text
WD
AutoCAD SHX Text
METAL
AutoCAD SHX Text
WD
AutoCAD SHX Text 3'-0"
AutoCAD SHX Text 3'-0"
AutoCAD SHX Text 3'-0"
AutoCAD SHX Text 7'-0"
AutoCAD SHX Text 1-3/4"
AutoCAD SHX Text 1-3/4"
AutoCAD SHX Text 7'-0"
AutoCAD SHX Text 7'-0"
AutoCAD SHX Text
PAINTED
AutoCAD SHX Text
HM
AutoCAD SHX Text
HM
AutoCAD SHX Text
PAINTED
AutoCAD SHX Text
PAINTED
AutoCAD SHX Text
NONE
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
OPEN OFFICE
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text P-1
AutoCAD SHX Text P-2
AutoCAD SHX Text P-1
AutoCAD SHX Text P-2
AutoCAD SHX Text
CPT-1
AutoCAD SHX Text
VCT-1
AutoCAD SHX Text
VB-1
AutoCAD SHX Text
ACT-1
AutoCAD SHX Text NOTES: 1. REVIEW AND CONFIRM COLOR SELECTIONS AND LOCATIONS WITH OWNER PRIOR REVIEW AND CONFIRM COLOR SELECTIONS AND LOCATIONS WITH OWNER PRIOR TO ACQUISITION.
AutoCAD SHX Text
PRODUCT NO.
AutoCAD SHX Text
COLOR
AutoCAD SHX Text
REMARKS
AutoCAD SHX Text
MANUFACTURER
AutoCAD SHX Text
MATERIAL
AutoCAD SHX Text
SYMBOL
AutoCAD SHX Text
PAINT
AutoCAD SHX Text
PAINT
AutoCAD SHX Text
CARPET
AutoCAD SHX Text
VINYL COMPOSITION TILE
AutoCAD SHX Text
VINYL BASE
AutoCAD SHX Text
ACOUSTICAL CEILING
AutoCAD SHX Text
SHERWIN WILLIAMS
AutoCAD SHX Text
SHERWIN WILLIAMS
AutoCAD SHX Text
ARMSTRONG
AutoCAD SHX Text HW SET #1 3 HINGES, FULL MORTISE STANLEY F179 4.5"X4.5" US26D STANLEY F179 4.5"X4.5" US26D 4.5"X4.5" US26D US26D 1 LOCKSET, LEVER HANDLE FALCON T521D ENTRANCE 626 FALCON T521D ENTRANCE 626 ENTRANCE 626 626 1 RIM EXIT DEVICE VON DUPRIN 99EO 36" 626 VON DUPRIN 99EO 36" 626 36" 626 626 1 CLOSER NORTON 7500 689 NORTON 7500 689 689 1 THRESHOLD, SADDLE TYPE NATIONAL GUARD 36"X5" 627 NATIONAL GUARD 36"X5" 627 36"X5" 627 627 1 DRIP EDGE NATIONAL GUARD 36"X1/2" 627 NATIONAL GUARD 36"X1/2" 627 36"X1/2" 627 627 HW SET #2 3 HINGES, FULL MORTISE STANLEY F179 4.5"X4.5 US26D STANLEY F179 4.5"X4.5 US26D 4.5"X4.5 US26D US26D 1 LOCKSET, LEVER HANDLE FALCON T571D DORMITORY 626 FALCON T571D DORMITORY 626 DORMITORY 626 626 1 DOOR STOP, FLOOR MTD IVES 438 DOME US26D IVES 438 DOME US26D DOME US26D US26D 3 SILENCERS IVES SR64 GRAY IVES SR64 GRAY GRAY
AutoCAD SHX Text
HW SET #1
AutoCAD SHX Text NOTES: 1. WOOD DOORS: VT INDUSTRIES, ARCHITECTURAL WOOD DOORS, HERITAGE SERIES PC-5, 5-PLY PARTICLE CORE, WOOD DOORS: VT INDUSTRIES, ARCHITECTURAL WOOD DOORS, HERITAGE SERIES PC-5, 5-PLY PARTICLE CORE, PAINTED FINISH. 2. HOLLOW METAL DOORS: STEELCRAFT SL SERIES, SQUARE EDGE FLUSH DOOR, FL-16-UL-4-5.75-70-SJ-LHRB-RPD, HOLLOW METAL DOORS: STEELCRAFT SL SERIES, SQUARE EDGE FLUSH DOOR, FL-16-UL-4-5.75-70-SJ-LHRB-RPD, PAINTED FINISH. 3. PROVIDE 20"X30" LITE KIT WITH CLEAR TEMPERED GLASS. PROVIDE 20"X30" LITE KIT WITH CLEAR TEMPERED GLASS.
AutoCAD SHX Text
NONE
AutoCAD SHX Text
NONE
AutoCAD SHX Text
NOTE #2
AutoCAD SHX Text
NOTES #1, 3
AutoCAD SHX Text
CPT-1
AutoCAD SHX Text
ROOM NO.
AutoCAD SHX Text
ROOM NAME
AutoCAD SHX Text
FLOOR
AutoCAD SHX Text
WALL BASE
AutoCAD SHX Text
CEILING
AutoCAD SHX Text
CEILING HGT.
AutoCAD SHX Text
ELEVATION 1
AutoCAD SHX Text
ELEVATION 2
AutoCAD SHX Text
ELEVATION 3
AutoCAD SHX Text
ELEVATION 4
AutoCAD SHX Text
REMARKS
AutoCAD SHX Text
VB-1
AutoCAD SHX Text
ACT-1
AutoCAD SHX Text 8'-0"
AutoCAD SHX Text
PT-1
AutoCAD SHX Text
PT-1
AutoCAD SHX Text
PT-1
AutoCAD SHX Text
PT-1
AutoCAD SHX Text
VB-1
AutoCAD SHX Text
ACT-1
AutoCAD SHX Text 8'-0"
AutoCAD SHX Text
PT-1
AutoCAD SHX Text
PT-1
AutoCAD SHX Text
PT-1
AutoCAD SHX Text
PT-1
AutoCAD SHX Text
VB-1
AutoCAD SHX Text
ACT-1
AutoCAD SHX Text 8'-0"
AutoCAD SHX Text
PT-1
AutoCAD SHX Text
PT-1
AutoCAD SHX Text
PT-1
AutoCAD SHX Text
PT-1
AutoCAD SHX Text
AutoCAD SHX Text
WHITE
AutoCAD SHX Text
OPTIMA SQUARE LAY-IN, 24"X24" WITH PRELUDE XL 15/16" EXPOSED GRID
AutoCAD SHX Text
4" COVE
AutoCAD SHX Text 2/A-401
AutoCAD SHX Text 4/A-401
AutoCAD SHX Text
TBD
AutoCAD SHX Text
TBD
AutoCAD SHX Text
TARKETT
AutoCAD SHX Text
TBD
AutoCAD SHX Text
TBD
AutoCAD SHX Text
TBD
AutoCAD SHX Text
TBD
AutoCAD SHX Text
TBD
AutoCAD SHX Text
TBD
AutoCAD SHX Text
TBD
AutoCAD SHX Text
TBD
AutoCAD SHX Text
TBD
AutoCAD SHX Text
TBD
AutoCAD SHX Text
TYPE "HM-1"
AutoCAD SHX Text 3'-0"
AutoCAD SHX Text 7'-0"
AutoCAD SHX Text
WD-1
AutoCAD SHX Text 1-3/4"
AutoCAD SHX Text
PAINTED
AutoCAD SHX Text
PAINTED
AutoCAD SHX Text
HM
AutoCAD SHX Text 4/A-401
AutoCAD SHX Text
PAINTED
AutoCAD SHX Text
NOTES #1, 3
AutoCAD SHX Text W1
AutoCAD SHX Text GENERAL WINDOW NOTES: 1. WINDOW TYPE W-1: BASIS-OF-DESIGN PLY GEM 1500 SERIES, WINDOW TYPE W-1: BASIS-OF-DESIGN PLY GEM 1500 SERIES, SINGLE HUNG, DOUBLE PANE INSULATED GLASS UNIT, LOW E WITH ARGON, NO GRILLS, MANUFACTURER'S STANDARD LOCK, TILT SASH AND BEVELED FRAME.
AutoCAD SHX Text 4'-0"
AutoCAD SHX Text
4'-5" VIF
AutoCAD SHX Text
MATCH EXIST.
AutoCAD SHX Text
CPT-1
AutoCAD SHX Text
CPT-1
AutoCAD SHX Text
HW SET #2
HW SET #2
E-001
GENERAL
ELECTRICAL NOTES
GENERAL ELECTRICAL NOTES 1
N.T.S.
DRAWING TITLE:
NO
AA
G
RE
AT
LA
KE
S
EN
VI
RO
NM
EN
TA
L R
ES
EA
RC
H
LA
B
LA
KE
M
IC
HI
GA
N
FIE
LD
S
TA
TIO
N
- B
UI
LD
IN
G 3 A
DD
ITI
ON
B
EA
CH
S
TR
EE
T, MU
SK
EG
ON
, M I 4
AutoCAD SHX Text GENERAL ELECTRICAL NOTES 1. ALL WORK SHALL COMPLY WITH ALL PROVISIONS OF THE DRAWINGS AND ALL WORK SHALL COMPLY WITH ALL PROVISIONS OF THE DRAWINGS AND APPLICABLE CODES, STANDARDS, AND ORDINANCES OF THE PROJECT LOCATION. 2. ALL WORK DETAILED ON THESE ELECTRICAL DRAWINGS SHALL BE THE ALL WORK DETAILED ON THESE ELECTRICAL DRAWINGS SHALL BE THE RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR UNLESS OTHERWISE INDICATED. THE ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR ALL WORK MATERIAL AND LABOR TO SATISFY A COMPLETE AND WORKING SYSTEM WHETHER IMPLIED OR SPECIFIED. 3. ALL DRAWINGS SHALL BE REVIEWED BY THE ELECTRICAL CONTRACTOR TO ALL DRAWINGS SHALL BE REVIEWED BY THE ELECTRICAL CONTRACTOR TO BECOME FAMILIAR WITH THE REQUIREMENTS OF THE PROJECT. THE ELECTRICAL CONTRACTOR IS REQUIRED TO ALERT THE GOVERNMENT OF ANY DISCREPANCIES ON THE DRAWINGS IMMEDIATELY. THE ELECTRICAL CONTRACTOR SHALL VISIT THE SITE AND BECOME FAMILIAR WITH THE SCOPE OF WORK. 5. ALL WIRING AND CONDUIT SIZING SHALL BE IN COMPLIANCE WITH ARTICLE 310 ALL WIRING AND CONDUIT SIZING SHALL BE IN COMPLIANCE WITH ARTICLE 310 AND APPENDIX C OF THE LATEST VERSION OF THE NATIONAL ELECTRIC CODE. 6. THE ELECTRICAL CONTRACTOR IS REQUIRED TO OBTAIN AND PAY FOR ALL THE ELECTRICAL CONTRACTOR IS REQUIRED TO OBTAIN AND PAY FOR ALL NECESSARY ELECTRICAL PERMITS AND FEES. 7. THE ELECTRICAL CONTRACTOR IS REQUIRED TO CHECK ALL EQUIPMENT THE ELECTRICAL CONTRACTOR IS REQUIRED TO CHECK ALL EQUIPMENT DIMENSIONS PRIOR TO PURCHASE OF ANY EQUIPMENT. IF THERE IS A DISCREPANCY BETWEEN THESE DRAWINGS AND THE EQUIPMENT PURCHASED, THE ELECTRICAL CONTRACTOR SHALL NOTIFY THE GOVERNMENT IMMEDIATELY FOR RESOLUTION. 8. ALL MATERIAL AND EQUIPMENT SHALL BE INSTALLED IN ACCORDANCE WITH ALL MATERIAL AND EQUIPMENT SHALL BE INSTALLED IN ACCORDANCE WITH MANUFACTURERS' INSTRUCTIONS. 9. ALL WORK SHALL COMPLY WITH STARTUP PROCEDURES AS DEFINED BY THE ALL WORK SHALL COMPLY WITH STARTUP PROCEDURES AS DEFINED BY THE GOVERNMENT. ANY SHUTDOWNS TO ELECTRICAL SYSTEMS SHALL BE COORDINATED WITH THE GOVERNMENT. 10. ANY OPENINGS MADE THROUGH MASONRY AND CONCRETE BY CORE DRILLING ANY OPENINGS MADE THROUGH MASONRY AND CONCRETE BY CORE DRILLING SHALL BE PERFORMED IN AGREED LOCATIONS WITH THE GOVERNMENT. ALL OPENINGS SHALL BE RESTORED TO THEIR ORIGINAL CONDITION TO MATCH ADJACENT CONSTRUCTION AND MATERIALS. 11. THE ELECTRICAL CONTRACTOR SHALL ARRANGE FOR THE COORDINATION OF ALL THE ELECTRICAL CONTRACTOR SHALL ARRANGE FOR THE COORDINATION OF ALL TRADES AND THE PROCUREMENT OF ALL INSPECTION CERTIFICATES AND FEES FOR THE COMPLETE ELECTRICAL INSTALLATION. INSPECTIONS ARE REQUIRED ON ALL WORK AND NO WORK SHALL BE CLOSED OR CONCEALED UNTIL INSPECTED AND APPROVED. 12. NO CONDUIT SHALL BE SMALLER THAN 3/4" ELECTRICAL TRADE SIZE. HOME NO CONDUIT SHALL BE SMALLER THAN 3/4" ELECTRICAL TRADE SIZE. HOME RUN CIRCUITS MORE THAN 100 FEET FROM THE PANEL BOARD SHALL BE MADE WITH THE NEXT LARGER SIZE AS REQUIRED TO LIMIT VOLTAGE DROP TO 2% MAXIMUM. VOLTAGE DROP CALCULATIONS MUST BE PERFORMED BY THE ELECTRICAL CONTRACTOR AND SUBMITTED TO PROFESSIONAL ENGINEER IF REQUESTED. 13. THE ELECTRICAL CONTRACTOR SHALL PROVIDE A TYPED DIRECTORY OF THE ELECTRICAL CONTRACTOR SHALL PROVIDE A TYPED DIRECTORY OF EQUIPMENT THAT EACH CIRCUIT CONTROLS. A COPY SHALL BE LEFT IN A SLEEVE LOCATED INSIDE THE FRONT COVER OF THE PANEL BOARD. 14. THE ELECTRICAL CONTRACTOR SHALL CONFIRM EXACT LOCATIONS OF ALL NEW THE ELECTRICAL CONTRACTOR SHALL CONFIRM EXACT LOCATIONS OF ALL NEW EQUIPMENT SELECTED WITH THE GOVERNMENT. REQUIRED NEC CLEARANCES SHALL BE OBSERVED. BEFORE ORDERING ANY MATERIAL OR DOING ANY WORK, THE ELECTRICAL CONTRACTOR SHALL CHECK AND VERIFY ALL MEASUREMENTS. 15. A COPY OF THE CONTRACT DRAWINGS SHALL BE MAINTAINED ON THE JOB SITE A COPY OF THE CONTRACT DRAWINGS SHALL BE MAINTAINED ON THE JOB SITE AT ALL TIMES UNTIL PROJECT COMPLETION.
AutoCAD SHX Text
16. THE ELECTRICAL CONTRACTOR SHALL PROVIDE THE MANUFACTURER'S OPERATION MANUALS WITH DETAILED OPERATING AND MAINTENANCE INSTRUCTIONS FOR EACH PIECE OF EQUIPMENT FURNISHED BY THE PROJECT. 17. THE ELECTRICAL CONTRACTOR SHALL REMOVE ALL RUBBISH AND DEBRIS CAUSED WHILE PERFORMING THE WORK. 18. ELECTRICAL SHUTDOWNS REQUIRED FOR DISCONNECTING EXISTING ELECTRICAL ITEMS AND THE CONNECTION OF NEW ELECTRICAL ITEMS MUST BE COORDINATED AND SCHEDULED WITH THE GOVERNMENT. 19. ALL CONDUCTORS SHALL BE COPPER THHN/THWN CONDUCTORS IN RACEWAY UNLESS OTHERWISE NOTED. 20. NON-METALLIC CONDUIT ONLY SHALL BE USED FOR UNDERGROUND FEEDS. 21. THE ELECTRICAL CONTRACTOR SHALL FOLLOW PROPER GROUNDING TECHNIQUES PER ARTICLE 250 OF THE LATEST VERSION OF THE NATIONAL ELECTRIC CODE. 22. ALL EQUIPMENT SHALL BE RATED FOR PROPER ENVIRONMENTAL CONDITIONS. ALL OUTDOOR EQUIPMENT SHALL BE RATED NEMA-3R FOR WEATHERPROOF LOCATIONS. 23. UPON COMPLETION OF THE WORK, THE ENTIRE WIRING SYSTEM SHALL BE ENTIRELY FREE FROM GROUNDS, SHORT CIRCUITS, OPENS, OVERLOADS AND IMPROPER VOLTAGES. THE ELECTRICAL CONTRACTOR SHALL FURNISH ALL LABOR, MATERIALS AND TESTING EQUIPMENT NECESSARY TO CONDUCT THE REQUIRED TESTS AND SUBMIT A WRITTEN RECORD OF THE TEST RESULTS FOR GOVERNMENT'S RECORD. 24. ALL EQUIPMENT AND SYSTEMS SHALL BE GUARANTEED AGAINST DEFECTIVE MATERIALS AND WORKMANSHIP FOR ONE (1) YEAR FROM DATE OF ACCEPTANCE. UPON WRITTEN NOTICE, AND AT NO ADDITIONAL EXPENSE TO THE GOVERNMENT, THE ELECTRICAL CONTRACTOR SHALL PROMPTLY REPAIR ALL DEFECTIVE MATERIALS. 25. THE ELECTRICAL CONTRACTOR SHALL PROVIDE IDENTIFICATION ON THE INSIDE OF JUNCTION BOXES WITH BLANK COVERS. 26. IN GENERAL, THE ELECTRICAL CONTRACTOR SHALL ARRANGE WORK SO THAT NO ACCESS PANELS WILL BE REQUIRED. JUNCTION BOXES AND SIMILAR EQUIPMENT THAT REQUIRE ACCESS SHALL BE LOCATED ABOVE REMOVABLE TILE CEILING OR IN UNFINISHED SPACES. 27. THE ELECTRICAL CONTRACTOR SHALL PROVIDE ADEQUATE PROTECTION AGAINST DAMAGE TO ALL MATERIAL AND EQUIPMENT DURING SHIPPING AND STORAGE AT THE SITE. ALL STORED EQUIPMENT SHALL BE COVERED TO AVOID DUST AND MOISTURE. AFTER EQUIPMENT IS INSTALLED, THE ELECTRICAL CONTRACTOR SHALL COVER ALL OPENINGS TO PREVENT ENTRANCE OF WATER AND OTHER MATERIALS. ALL CONDUIT OPENINGS SHALL BE CLOSED WITH TEMPORARY METAL OR PLASTIC CAPS, INCLUDING THOSE TERMINATED IN ELECTRICAL EQUIPMENT. 28. ALL ELECTRICAL PENETRATIONS THROUGH FIRE-RATED CONSTRUCTION SHALL BE FIRESTOPPED USING AN APPROVED SYSTEM BY A RECOGNIZED THIRD PARTY ENTITY. 29. ALL EQUIPMENT AND MATERIALS SHALL BE NEW AND UL APPROVED. 30. THE ELECTRICAL CONTRACTOR IS REQUIRED TO SUBMIT EQUIPMENT CUT-SHEETS AND SHOP DRAWINGS, AND OBTAIN APPROVAL BEFORE PURCHASE
AND/OR INSTALLATION OF MATERIALS. APPROVAL WILL BE GIVEN ONLY TO INDICATE GENERAL COMPLIANCE WITH PROJECT REQUIREMENTS. THE ELECTRICAL CONTRACTOR SHALL CHECK ALL DRAWINGS AND SPECIFICATIONS FOR COMPLIANCE BEFORE SUBMISSION. 31. THE ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR COORDINATING ALL LUG SIZES OF EQUIPMENT WITH WIRE SIZES USED AND OR SPECIFIED. 32. FASTENING SHALL BE PERFORMED BY THE ELECTRICAL CONTRACTOR AS FOLLOWS: a) IN HOLLOW MASONRY OR DRYWALL CONSTRUCTION SHALL BE IN HOLLOW MASONRY OR DRYWALL CONSTRUCTION SHALL BE PERFORMED WITH TOGGLE BOLTS b) IN STRUCTURAL IRON MACHINE BOLTS SHALL BE UTILIZED IN STRUCTURAL IRON MACHINE BOLTS SHALL BE UTILIZED c) IN WOOD OR OTHER FIBROUS MATERIALS, LAG SCREW OR BOLTS SHALL IN WOOD OR OTHER FIBROUS MATERIALS, LAG SCREW OR BOLTS SHALL BE UTILIZED d) IN SOLID MASONRY, METALLIC EXPANSION SHIELDS AND MACHINE BOLTS IN SOLID MASONRY, METALLIC EXPANSION SHIELDS AND MACHINE BOLTS SHALL BE UTILIZED e) IN POURED CONCRETE, CONCRETE BOX INSERTS WITH ADDITIONAL IN POURED CONCRETE, CONCRETE BOX INSERTS WITH ADDITIONAL REINFORCING STEEL INSTALLED WHERE DIRECTED SHALL BE USED. f) GROUPS OF EQUIPMENT AND DEVICES SHALL BE SUPPORTED ON RACKS GROUPS OF EQUIPMENT AND DEVICES SHALL BE SUPPORTED ON RACKS AND FRAMES CONSTRUCTED OF POWER-STRUT OR SIMILAR STRUCTURAL MEMBERS. 33. ALL CONDUITS SHALL BE RIGIDLY AND FIRMLY INSTALLED BY MALLEABLE OR ALL CONDUITS SHALL BE RIGIDLY AND FIRMLY INSTALLED BY MALLEABLE OR WROUGHT STEEL HANGERS OF STANDARD DESIGN, PIPE CLAMPS, OR FABRICATED STEEL SUPPORTS OF APPROVED DESIGN. 34. USE ONLY UL-APPROVED RACEWAYS, WITH UL LABEL AND MANUFACTURER'S USE ONLY UL-APPROVED RACEWAYS, WITH UL LABEL AND MANUFACTURER'S NAME CLEARLY IDENTIFIED. THE MINIMUM SIZE CONDUIT SHALL BE 3/4". 35. RIGID STEEL CONDUIT (HEAVYWALL) SHALL BE GALVANIZED. CONDUIT FITTINGS RIGID STEEL CONDUIT (HEAVYWALL) SHALL BE GALVANIZED. CONDUIT FITTINGS SHALL BE CAST, MALLEABLE IRON, SMOOTH FINISH, FULL THREADED HUBS (IMC ACCEPTABLE). 36. ELECTRICAL METALLIC TUBING (EMT) (THINWALL) SHALL BE GALVANIZED. EMT ELECTRICAL METALLIC TUBING (EMT) (THINWALL) SHALL BE GALVANIZED. EMT FITTINGS SHALL BE SET SCREW TYPE. 37. WIREWAYS AND TROUGHS SHALL BE GALVANIZED STEEL, PROPERLY SIZED, WITH WIREWAYS AND TROUGHS SHALL BE GALVANIZED STEEL, PROPERLY SIZED, WITH SCREWED COVERS. THE ELECTRICAL CONTRACTOR SHALL PROVIDE INTERIOR PARTITIONS WHERE REQUIRED. 38. FLEXIBLE CONDUIT SHALL BE STEEL, GALVANIZED AND UL-APPROVED FOR FLEXIBLE CONDUIT SHALL BE STEEL, GALVANIZED AND UL-APPROVED FOR GROUNDING. THE ELECTRICAL CONTRACTOR SHALL PROVIDE SEPARATE GROUND WIRE. 39. LIQUID-TIGHT CONDUIT SHALL BE PVC JACKETED FLEXIBLE STEEL TYPE. LIQUID-TIGHT CONDUIT SHALL BE PVC JACKETED FLEXIBLE STEEL TYPE. 40. UNDERGROUND RACEWAYS SHALL BE PLASTIC (PVC) MINIMUM TYPE I, SUITABLE UNDERGROUND RACEWAYS SHALL BE PLASTIC (PVC) MINIMUM TYPE I, SUITABLE FOR ENCASEMENT IN CONCRETE. PROVIDE CONDUIT TO DUCT FITTINGS WHERE CHANGE OR RACEWAY OCCURS. 41. THROUGH-WALL OUTLET BOXES SHALL NOT BE PERMITTED. THROUGH-WALL OUTLET BOXES SHALL NOT BE PERMITTED. 42. SLIP JOINT FITTINGS SHALL BE USED FOR CONDUITS PASSING THROUGH SLIP JOINT FITTINGS SHALL BE USED FOR CONDUITS PASSING THROUGH STRUCTURAL EXPANSION JOINTS. FITTINGS SHALL BE UL-APPROVED FOR GROUNDING. 43. JUNCTION AND PULL BOXES SHALL BE CODE GAUGE GALVANIZED SHEET STEEL, JUNCTION AND PULL BOXES SHALL BE CODE GAUGE GALVANIZED SHEET STEEL, WITH SCREWED COVERS, SIZED AS ACCORDING TO THE NEC. RECESSED BOXES IN FINISHED AREAS WILL NOT BE ACCEPTED UNLESS SPECIFICALLY INDICATED ON THE DRAWINGS.
ELECTRICAL CONDUIT SCHEDULE PVC = UNDERGROUND/OUTDOOR, EMT= INTERIOR ABOVE GRADE
CONDUIT I.D. CONDUIT SIZE/TYPE CONDUIT WIRE SIZE & GROUND
EC-00 2" PVC (4) 3/0 THHN /THWN COPPER
EC-01 1 1/4" EMT (3) #3 THHN /THWN COPPER & (1) #8 THHN/THWN COPPER GND
EC-02 1 1/4" EMT (3) #4 THHN /THWN COPPER & (1) #8 THHN/THWN COPPER GND
EC-03 2" EMT (4) 1/0 THHN /THWN COPPER & (1) #6 THHN/THWN COPPER GND
EC-04 3/4" EMT (3) #12 THHN /THWN COPPER & (1) #12 THHN/THWN COPPER GND
EC-05 3/4" EMT (3) #10 THHN /THWN COPPER & (1) #10 THHN/THWN COPPER GND
EC-06 2" EMT (4) 3/0 THHN /THWN COPPER & (1) #4 THHN/TWHN COPPER GROUND
E-002
GENERAL NOTES
AND SCHEDULES
CONDUIT SCHEDULE 1
N.T.S.
GENERAL ELECTRICAL NOTES (CONT.) 3
N.T.S.
DRAWING TITLE:
NO
AA
G
RE
AT
LA
KE
S
EN
VI
RO
NM
EN
TA
L R
ES
EA
RC
H
LA
B
LA
KE
M
IC
HI
GA
N
FIE
LD
S
TA
TIO
N
- B
UI
LD
IN
G 3 A
DD
ITI
ON
B
EA
CH
S
TR
EE
T, MU
SK
EG
ON
, M I 4
PANEL "PP1"
PANEL DESCRIPTION: 120/208V 3Ø, 150A MAIN CIRCUIT BREAKER
CB SIZE CIRCUIT DESCRIPTION VA VA CIRCUIT DESCRIPTION SIZE CB
40A
15A 2 3 15A 4 5 15A 6 7 15A 8 9 15A 10
11 20A 12 13 20A 20A 14 15 20A 20A 16 17 20A 20A 18
19 20A 20 21 20A 22 23 20A 24 25 20A 26 27 20A 28 29 20A 30
PANEL SCHEDULE 2
N.T.S.
ELECTRIC ROOM 106
HVAC UNIT "CU-1"
GAS FURNACE "GF-1"
GAS FURNACE "GF-2"
EXHAUST FAN "EF-4"
EXHAUST FAN "EF-5"
EXHAUST FAN "EF-6"
NOTES:
1. E.C. SHALL PROVIDE NEW BREAKERS IN PANEL, UNLESS OTHERWISE DIRECTED.
PANEL IS SUPPOSED TO BE NEW AND RELOCATED UNDER THE ELECTRICAL
UPGRADES PROJECT.
SPARE
SPARE
SPARE
20A 20A 20A 20A 20A 20A
SPARE
SPARE
EXTERIOR LIGHTS
OPEN OFFICE WORKSTATIONS
HVAC UNIT "CU-2"40A
WATER HEATER "WH-1"25A
SPARE
SPARE
SPARE
SPARE
SPARE
OPEN OFFICE WORKSTATIONS
OPEN OFFICE 110 OUTLETS
OPEN OFFICE 110 OUTLETS
OFFICE 111 OUTLETS
OFFICE 112 OUTLETS
OFFICES 111 & 112 LIGHTS
OPEN OFFICE 110 LIGHTS
AutoCAD SHX Text GENERAL ELECTRICAL NOTES (CONT.) 44. RACEWAY INSTALLATIONS SHALL BE MECHANICALLY SECURED FOR A RACEWAY INSTALLATIONS SHALL BE MECHANICALLY SECURED FOR A CONTINUOUS EFFECTIVE GROUND. 45. RIGID STEEL CONDUIT SHALL BE USED WHERE EXPOSED TO MOISTURE, BELOW RIGID STEEL CONDUIT SHALL BE USED WHERE EXPOSED TO MOISTURE, BELOW GRADE OR IN FLOOR FILLS, FOR EXPOSED RUNS OUTDOORS AND IN OTHER WET LOCATIONS, INCLUDING WEATHER PROTECTED AREAS. 46. THINWALL TUBING (EMT) MAY BE USED FOR EXPOSED AND CONCEALED WIRING THINWALL TUBING (EMT) MAY BE USED FOR EXPOSED AND CONCEALED WIRING IN DRY LOCATIONS, NOT SPECIFICALLY MENTIONED ABOVE. 47. WIRING IN CONCRETE SLABS (ON GRADE), WHERE EXPOSED TO MOISTURE OR WIRING IN CONCRETE SLABS (ON GRADE), WHERE EXPOSED TO MOISTURE OR BELOW GRADE SHALL BE INSTALLED IN GALVANIZED STEEL CONDUIT. PVC RACEWAYS MAY BE INSTALLED UNDER SLAB ON GRADE. THE ELECTRICAL CONTRACTOR SHALL PROVIDE SEPARATE GROUND CABLE IN ALL PVC RACEWAYS. 48. LIQUID-TIGHT FLEXIBLE CONDUIT SHALL BE USED FOR FINAL CONNECTIONS TO LIQUID-TIGHT FLEXIBLE CONDUIT SHALL BE USED FOR FINAL CONNECTIONS TO EQUIPMENT, MOTORS, AND SIMILAR EQUIPMENT IN WET/DAMP AREAS. 49. THE ELECTRICAL CONTRACTOR SHALL INSTALL EXPOSED CONDUIT IN A NEAT THE ELECTRICAL CONTRACTOR SHALL INSTALL EXPOSED CONDUIT IN A NEAT SYMMETRICAL MANNER. CONDUITS SHALL FOLLOW BUILDING LINES, SECURELY SUPPORTED FROM THE BUILDING STRUCTURE ON 10-FOOT INTERVALS BY CONDUIT STRAPS OR PIPE HANGERS ON SUPPORTING ASSEMBLIES AND SUPPORTED WITHIN 3 FEET OF OUTLET BOX OR FITTING. 50. THE ELECTRICAL CONTRACTOR SHALL RUN EXPOSED CONDUIT IN UNFINISHED THE ELECTRICAL CONTRACTOR SHALL RUN EXPOSED CONDUIT IN UNFINISHED SPACES AFTER DUCTWORK AND PIPING HAVE BEEN INSTALLED, AND PROVIDE SUSPENSION MATERIALS AS REQUIRED. THE ELECTRICAL CONTRACTOR SHALL PROVIDE ALL REQUIRED OFFSETS, BENDS, BOXES AND FITTINGS NECESSARY. 51. THE ELECTRICAL CONTRACTOR SHALL NOT PENETRATE THROUGH STRUCTURAL THE ELECTRICAL CONTRACTOR SHALL NOT PENETRATE THROUGH STRUCTURAL MEMBERS WITHOUT PERMISSION. 52. WHERE CONDUIT PASSES THROUGH EXTERIOR WALLS, FLOOR OR ROOF, THE WHERE CONDUIT PASSES THROUGH EXTERIOR WALLS, FLOOR OR ROOF, THE ELECTRICAL CONTRACTOR SHALL INSTALL APPROPRIATE FITTINGS AND MATERIALS TO ENSURE OPENINGS ARE WATERTIGHT. 53. THE ELECTRICAL CONTRACTOR SHALL PROVIDE A NYLON LINE PULL STRING IN THE ELECTRICAL CONTRACTOR SHALL PROVIDE A NYLON LINE PULL STRING IN ALL EMPTY CONDUITS. 54. THE ELECTRICAL CONTRACTOR SHALL MAKE PANELBOARD CONNECTIONS SO THE ELECTRICAL CONTRACTOR SHALL MAKE PANELBOARD CONNECTIONS SO THAT CIRCUIT PROTECTORS ARE IN LOGICAL OPERATING SEQUENCE, AND SO THAT LOADS ARE BALANCED ACROSS ALL PHASES. 55. WHERE CONDUIT ENTERS BUILDING FROM BELOW GRADE, THE ELECTRICAL WHERE CONDUIT ENTERS BUILDING FROM BELOW GRADE, THE ELECTRICAL CONTRACTOR SHALL SEAL END OF RACEWAY WITH APPROVED WATERPROOFING COMPOUND AFTER WIRES HAVE BEEN INSTALLED. 56. THE ELECTRICAL CONTRACTOR SHALL SUPPORT CONDUCTORS IN VERTICAL THE ELECTRICAL CONTRACTOR SHALL SUPPORT CONDUCTORS IN VERTICAL RACEWAYS IN ACCORDANCE WITH THE LATEST VERSION OF THE NATIONAL ELECTRIC CODE. 57. THE ELECTRICAL CONTRACTOR SHALL PROVIDE ALL WIRING, CONNECTIONS AND THE ELECTRICAL CONTRACTOR SHALL PROVIDE ALL WIRING, CONNECTIONS AND DEVICES, ETC. NECESSARY TO COMPLY WITH THE GROUNDING REQUIREMENTS OF THE LATEST VERSION OF THE NATIONAL ELECTRIC CODE AND AS SHOWN ON THE DRAWINGS. EXCEPT WHERE SPECIFICALLY INDICATED OTHERWISE, ALL EXPOSED NON-CURRENT CARRYING METALLIC PARTS OF ELECTRICAL EQUIPMENT, RACEWAY SYSTEMS, GROUNDING CONDUCTORS OF NON-METALLIC COVERED CABLE AND NEUTRAL CONDUCTORS OF THE WIRING SYSTEM, SHALL BE GROUNDED.
58. THE ELECTRICAL CONTRACTOR SHALL VERIFY ALL SERVICE EQUIPMENT HAS BEEN APPROVED BY THE LOCAL UTILITY COMPANY BEFORE PURCHASE OF SUCH EQUIPMENT. THIS INCLUDES VERIFYING THAT THE AIC RATINGS OF ALL DISTRIBUTION EQUIPMENT ARE ACCEPTABLE. THE ELECTRICAL CONTRACTOR SHALL SUBMIT AIC CALCULATIONS IF REQUESTED BY PROFESSIONAL ENGINEER.
OFFICE
OPEN
OFFICE
ELEC
POWER PLAN - NEW WORK 1
1/4" = 1'-0"
E-101
POWER PLAN
NEW WORK
GENERAL NOTES 2
N.T.S.
LEGEND 3
N.T.S.
KEYED NOTES 3
N.T.S.
DRAWING TITLE:
NO
AA
G
RE
AT
LA
KE
S
EN
VI
RO
NM
EN
TA
L R
ES
EA
RC
H
LA
B
LA
KE
M
IC
HI
GA
N
FIE
LD
S
TA
TIO
N
- B
UI
LD
IN
G 3 A
DD
ITI
ON
B
EA
CH
S
TR
EE
T, MU
SK
EG
ON
, M I 4
AutoCAD SHX Text
LEGEND
AutoCAD SHX Text DUPLEX OUTLET QUADRAPLEX OUTLET DATA OUTLET - BLANK 2-GANG BOX WITH 3/4 IN. EMT STUBBED OUT ABOVE THE CEILING DEVICE INSTALLED 48 IN. AFF DEVICE INSTALLED 64 IN. AFF RECESSED TV/DATA BOX FOR MONITOR - ARLINGTON #TVBS507, PROVIDE BLANK COVER PLATE #TVFR3C FOR LOCATIONS WHERE MONITORS WILL NOT BE INSTALLED FIRE ALARM HORN/STROBE DEVICE FIRE ALARM PULL STATION FIRE ALARM HORN DEVICE
AutoCAD SHX Text
1. ELECTRICAL CONTRACTOR SHALL INSTALL NEW SWITCHES AND OTHER ELECTRICAL CONTRACTOR SHALL INSTALL NEW SWITCHES AND OTHER LIGHTING DEVICES AS SPECIFIED. 2. ELECTRICAL CONTRACTOR SHALL REFERENCE ARCHITECTURAL DRAWINGS ELECTRICAL CONTRACTOR SHALL REFERENCE ARCHITECTURAL DRAWINGS FOR ALL LIGHTING LOCATIONS. ALL LOCATIONS SHALL BE COORDINATED WITH THE OWNER. 3. ALL ELECTRICAL COMPONENTS INCLUDING: FIRE/SMOKE DETECTION AND ALL ELECTRICAL COMPONENTS INCLUDING: FIRE/SMOKE DETECTION AND ALARM SYSTEMS SHALL BE INSTALLED, WIRED, AND MODIFIED IN ACCORDANCE WITH ALL LOCAL, STATE, AND NATIONAL CODES AND ORDINANCES (INCLUDING ADA) AS REQUIRED BY THE NEW WORK PLANS. 4. SWITCHING INDICATES LOCATION ONLY. IT DOES NOT DENOTE WIRING OR SWITCHING INDICATES LOCATION ONLY. IT DOES NOT DENOTE WIRING OR CIRCUITRY. 5. ALL SWITCHES, OCCUPANCY SENSORS, AND FAN CONTROLS SHALL BE ALL SWITCHES, OCCUPANCY SENSORS, AND FAN CONTROLS SHALL BE MOUNTED AT 48-INCHES AFF AND MIN. 4-INCHES FROM DOOR FRAMES, CORNERS, ETC. UNLESS OTHERWISE NOTED. SWITCHES INDICATED AS ADJ. SHALL BE GANGED. SWITCH PLATES THROUGHOUT SHALL MATCH THE BUILDING STANDARD. 6. EMERGENCY LIGHTING AND EXIT SIGNAGE SHALL BE BATTERY BACKUP EMERGENCY LIGHTING AND EXIT SIGNAGE SHALL BE BATTERY BACKUP TYPE. THESE ITEMS SHALL BE CIRCUITED THE SAME AS THE GENERAL LIGHTING IN THE AREA SWERVED, CONNECTED AHEAD OF ANY LOCAL SWITCHES/CONTROLS. 7. LIGHTING CONTROLS SHALL BE INSTALLED PER THE DRAWINGS. LIGHTING CONTROLS SHALL BE INSTALLED PER THE DRAWINGS. OCCUPANCY SENSORS SHALL BE EQUIPPED WITH MANUAL OVERRIDE AND BE INSTALLED OR BE INTEGRAL TO THE SENSOR DEVICE. 8. ELECTRICAL CONTRACTOR SHALL FOLLOW EXISTING EMERGENCY LIGHTING ELECTRICAL CONTRACTOR SHALL FOLLOW EXISTING EMERGENCY LIGHTING LAYOUT FOR CONNECTION OF NEW FIXTURES.
AutoCAD SHX Text
GENERAL NOTES THIS SHEET:
AutoCAD SHX Text +48
AutoCAD SHX Text +64
AutoCAD SHX Text 1 INTERCEPT THE WIRING FOR THE 2 FLOOR B0X OUTLETS IN THIS ROOM INTERCEPT THE WIRING FOR THE 2 FLOOR B0X OUTLETS IN THIS ROOM AND RECONNECT THEM TO PANEL 5L/10. 2 INTERCEPT THE WIRING FOR THE 1 FLOOR BOX OUTLET IN THIS ROOM AND INTERCEPT THE WIRING FOR THE 1 FLOOR BOX OUTLET IN THIS ROOM AND RECONNECT IT TO PANEL 5L/12. 3 INTERCEPT THE WIRING FOR THE 1 FLOOR BOX OUTLET IN THIS ROOM AND INTERCEPT THE WIRING FOR THE 1 FLOOR BOX OUTLET IN THIS ROOM AND RECONNECT IT TO PANEL 5L/12. 4 INTERCEPT THE WIRING FOR THE 2 FLOOR BOX OUTLETS IN THIS ROOM INTERCEPT THE WIRING FOR THE 2 FLOOR BOX OUTLETS IN THIS ROOM AND RECONNECT THEM TO PANEL 5L/16.
AutoCAD SHX Text
KEYED NOTES THIS SHEET:
AutoCAD SHX Text
PP1/12
AutoCAD SHX Text
PS
AutoCAD SHX Text
AREA NOT IN SCOPE
AutoCAD SHX Text
NEW WORK LEGEND:
AutoCAD SHX Text
AREA NOT IN SCOPE
AutoCAD SHX Text
EXISTING 1-STORY PRE-ENGINEERED
AutoCAD SHX Text
METAL BUILDING
AutoCAD SHX Text J
AutoCAD SHX Text J
AutoCAD SHX Text
PANEL "PP1"
AutoCAD SHX Text
PP1/14
AutoCAD SHX Text
PP1/16
AutoCAD SHX Text
PP1/18
AutoCAD SHX Text
PP1/13
PP1/15
OFFICE
OPEN
OFFICE
ELEC
O
SD
S O
SD
S
S
S 3D
3D
POWER PLAN - NEW WORK 1
1/4" = 1'-0"
E-102
LIGHTING PLAN
NEW WORK
DRAWING TITLE:
NO
AA
G
RE
AT
LA
KE
S
EN
VI
RO
NM
EN
TA
L R
ES
EA
RC
H
LA
B
LA
KE
M
IC
HI
GA
N
FIE
LD
S
TA
TIO
N
- B
UI
LD
IN
G 3 A
DD
ITI
ON
B
EA
CH
S
TR
EE
T, MU
SK
EG
ON
, M I 4
LIGHTING FIXTURE SCHEDULE 2
N.T.S.
GENERAL NOTES 3
N.T.S.
LEGEND 4
N.T.S.
S
S
S
S
OSD
3D
D
OS
OS
OS
AutoCAD SHX Text
AREA NOT IN SCOPE
AutoCAD SHX Text
NEW WORK LEGEND:
AutoCAD SHX Text
AREA NOT IN SCOPE
AutoCAD SHX Text
EXISTING 1-STORY PRE-ENGINEERED
AutoCAD SHX Text
METAL BUILDING
AutoCAD SHX Text
PANEL "PP1"
AutoCAD SHX Text
LEGEND
AutoCAD SHX Text 2'X4' LAY-IN LED TROFFER FIXTURE, UNSWITCHED 2'X4' LAY-IN LED TROFFER FIXTURE LED DIRECTIONAL EXIT FIXTURE CEILING MOUNTED LED EXIT FIXTURE CEILING MOUNTED COMBINATION LED EXIT/EMERGENCY FIXTURE EMERGENCY WALL PACK FIXTURE WITH BATTERY BACKUP SINGLE POLE SWITCH 3-WAY SWITCH WITH DIMMER SINGLE POLE SWITCH WITH OCCUPANCY SENSOR AND DIMMER SINGLE POLE SWITCH WITH DIMMER CEILING-MOUNTED OCCUPANCY SENSOR EXTERIOR LED WALL PACK FIXTURE ON PHOTOCELL
AutoCAD SHX Text
1. ELECTRICAL CONTRACTOR SHALL INSTALL NEW SWITCHES AND OTHER ELECTRICAL CONTRACTOR SHALL INSTALL NEW SWITCHES AND OTHER LIGHTING DEVICES AS SPECIFIED. 2. ELECTRICAL CONTRACTOR SHALL REFERENCE ARCHITECTURAL DRAWINGS ELECTRICAL CONTRACTOR SHALL REFERENCE ARCHITECTURAL DRAWINGS FOR ALL LIGHTING LOCATIONS. 3. ALL ELECTRICAL COMPONENTS INCLUDING: FIRE/SMOKE DETECTION AND ALL ELECTRICAL COMPONENTS INCLUDING: FIRE/SMOKE DETECTION AND ALARM SYSTEMS SHALL BE INSTALLED, WIRED, AND MODIFIED IN ACCORDANCE WITH ALL LOCAL, STATE, AND NATIONAL CODES AND ORDINANCES (INCLUDING ADA) AS REQUIRED BY THE NEW WORK PLANS. 4. SWITCHING INDICATES LOCATION ONLY. IT DOES NOT DENOTE WIRING OR SWITCHING INDICATES LOCATION ONLY. IT DOES NOT DENOTE WIRING OR CIRCUITRY. 5. ALL SWITCHES, OCCUPANCY SENSORS, AND FAN CONTROLS SHALL BE ALL SWITCHES, OCCUPANCY SENSORS, AND FAN CONTROLS SHALL BE MOUNTED AT 48-INCHES AFF AND MIN. 4-INCHES FROM DOOR FRAMES, CORNERS, ETC. UNLESS OTHERWISE NOTED. SWITCHES INDICATED AS ADJ. SHALL BE GANGED. SWITCH PLATES THROUGHOUT SHALL MATCH THE BUILDING STANDARD. 6. EMERGENCY LIGHTING AND EXIT SIGNAGE SHALL BE BATTERY BACKUP EMERGENCY LIGHTING AND EXIT SIGNAGE SHALL BE BATTERY BACKUP TYPE. THESE ITEMS SHALL BE CIRCUITED THE SAME AS THE GENERAL LIGHTING IN THE AREA SERVED, CONNECTED AHEAD OF ANY LOCAL SWITCHES/CONTROLS. 7. LIGHTING CONTROLS SHALL BE INSTALLED PER THE DRAWINGS. LIGHTING CONTROLS SHALL BE INSTALLED PER THE DRAWINGS. OCCUPANCY SENSORS SHALL BE EQUIPPED WITH MANUAL OVERRIDE AND BE INSTALLED OR BE INTEGRAL TO THE SENSOR DEVICE. 8. ELECTRICAL CONTRACTOR SHALL FOLLOW EXISTING EMERGENCY LIGHTING ELECTRICAL CONTRACTOR SHALL FOLLOW EXISTING EMERGENCY LIGHTING LAYOUT FOR CONNECTION OF NEW FIXTURES. 9. EMERGENCY FIXTURES (E.G., EXIT LIGHTS, EMERGENCY WALL PACK EMERGENCY FIXTURES (E.G., EXIT LIGHTS, EMERGENCY WALL PACK FIXTURES, NIGHTLIGHT FIXTURES, ETC.) SHALL BE UNSWITCHED.
AutoCAD SHX Text
GENERAL NOTES THIS SHEET:
AutoCAD SHX Text
LIGHTING FIXTURE SCHEDULE:
AutoCAD SHX Text A 2'X4' LED LAY-IN TYPE TROFFER FIXTURE 2'X4' LED LAY-IN TYPE TROFFER FIXTURE LITHONIA LIGHTING # 2BLT4-40L-ADP-EZ1-LP840 2BLT4-40L-ADP-EZ1-LP840 B COMPASS CEILING-MOUNTED LED COMBINATION EXIT/EMERGENCY COMPASS CEILING-MOUNTED LED COMBINATION EXIT/EMERGENCY LIGHT FIXTURE #CCRG C COMPASS WALL-MOUNTED LED EMERGENCY LIGHT FIXTURE #CU2 COMPASS WALL-MOUNTED LED EMERGENCY LIGHT FIXTURE #CU2 D EXTERIOR LED WALL PACK FIXTURE, LITHONIA #TWX2 WITH EXTERIOR LED WALL PACK FIXTURE, LITHONIA #TWX2 WITH PHOTOCELL OPTION
AutoCAD SHX Text J
AutoCAD SHX Text
PP1/17
AutoCAD SHX Text J
AutoCAD SHX Text
PP1/17
AutoCAD SHX Text J
AutoCAD SHX Text
PP1/19
AutoCAD SHX Text J
AutoCAD SHX Text
PP1/20
AutoCAD SHX Text P
AutoCAD SHX Text P
AutoCAD SHX Text P
AutoCAD SHX Text P
AutoCAD SHX Text A
AutoCAD SHX Text A
AutoCAD SHX Text A
AutoCAD SHX Text A
AutoCAD SHX Text A
AutoCAD SHX Text A
AutoCAD SHX Text A
AutoCAD SHX Text A
AutoCAD SHX Text A
AutoCAD SHX Text A
AutoCAD SHX Text B
AutoCAD SHX Text B
AutoCAD SHX Text C
AutoCAD SHX Text C
AutoCAD SHX Text C
AutoCAD SHX Text J
AutoCAD SHX Text J
AutoCAD SHX Text D
AutoCAD SHX Text D
D
| 20240417_BLDG 3 ADD_FINAL |
| 20240416_TEST |
| Sheets and Views |
| BLDG3ADD_A-101-Work |
| BLDG3ADD_A-102-Work |
| BLDG3ADD_A-103-Work |
| BLDG3ADD_A-401-Work |
| BLDG3ADD_A-601-Work |
| BLDG3ADD_E-001-Work |
| BLDG3ADD_E-002-Work |
| BLDG3ADD_E-101-Work |
| BLDG3ADD_E-102-Work |
| BLDG3ADD_G-001-Work |
| BLDG3ADD_A-104 Work (1) |
| BLDG3ADD_A-105 Work (1) |
| BLDG3ADD_S-101 Work (1) |