12a_P21776733DWGS.pdf
PDF 20 MB Posted
- Attached to
- USCG Sector Field Office Southwest Harbor - Major Maintenance and Repair Galley and Housing
- Solicitation number
- 70Z0G126BSNNESW01
About this file
This is a set of construction design drawings for a Major Maintenance and Repair (M&R) project at the U.S. Coast Guard Sector Field Office (SFO) Southwest Harbor in Southwest Harbor, Maine (Project No. 21776733). The project is issued for bid as of February 9, 2026.
The work includes one base bid item (BBI) and two optional bid items (OBIs). The base bid scope encompasses: replacement of windows with hurricane-rated units featuring extruded aluminum exterior cladding and wood interiors, including double-hung configuration, new mini-blinds, and new interior sills and trim; replacement of exterior doors with new hardware, frames, and thresholds; removal of existing EPDM roofing system and installation of a new fully TPO roofing system; and removal of existing gutters with installation of new heavy-duty box gutters and downspouts with concrete splash blocks at grade. OBI Alternate #1A requires removal of vinyl siding and replacement with new vinyl siding in-kind, while OBI Alternate #1B requires replacement with fiber-cement board siding and cellular composite PVC trim components. The building must remain occupied during construction. The project is designed by Oak Point Associates (Biddeford, Maine) and managed by the USCG Civil Engineering Unit Providence. The drawings include detailed site plans, floor plans, elevations, and construction details referencing applicable codes including the 2024 International Building Code, 2024 International Existing Building Code, 2023 National Electrical Code, and 2020 Unified Facilities Criteria standards.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
M
AJ
OR
M
&R B
AR
RA
CK
S/
GA
LL
EY
B
UI
LD
IN
G
SF
O
SO
UT
HW
ES
T
HA
RB
OR
SO
UT
HW
ES
T
HA
RB
OR
M E
GE
NE
RA
L
CO
VE
R
SH
EE
T
BARRACKS/
GALLEY
BUILDING
G-001
P2
P2
3G -0
.D
W G
US
CG
C
IV
IL
E
NG
IN
EE
RI
NG
U
NI
T
PR
OV
ID
EN
CE
KI
LV
ER
T
ST
, S
UI
TE
W
AR
W
IC
K, R I 0
DA
VI
D M
IL
ES
JM
c
CR
R
CR
R
KP
MICHAEL P. CAROSOTTO, PE
DAVID GLASS, PE
OA
K
PO
IN
T
AS
SO
CI
AT
ES
M
AI
N
ST
RE
ET
, B
ID
DE
FO
RD
, M
E
(2
) 2
-0
0.
IS
SU
E
FO
R
BI
D
FE
B
9, U.S. COAST GUARD
CIVIL ENGINEERING
DE
SI
GN
ED
B Y:
DE
SC
RI
PT
IO
N
M
AR
K
ED
IT
ED
B Y:
DA
TE
CH
EC
KE
D
BY
DR
AW
N
BY
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A
TECHNICAL DIRECTOR
BRANCH CHIEF
APPROVING OFFICIAL DATE
SH
EE
T
OF
US
CG
P
RO
JE
CT
N
UM
BE
R
US
CG
F
IL
EN
AM
E
A/ E
CO
M
PA
NY
CO
NS
UL
TI
NG
A
/E
US
CG
P
RO
JE
CT
M
AN
AG
ER
A/
E
PR
OJ
EC
T
NO
SHEET ID
M
EA
SU
RE
M
EN
T
BA
R:
1"
HA
LF
S
IZ
E
1/ 2"
US
CG
D
RA
W
IN
G
SE
RI
ES
N
UM
BE
R
U.S. COAST GUARD
CIVIL ENGINEERING UNIT
PROVIDENCE
VICINITY MAP
SCALE: NTS
LOCATION MAP
SCALE: NTS
SECTOR FIELD OFFICE (SFO) SOUTHWEST HARBOR
SOUTHWEST HARBOR, MAINE
21776733, MAJOR M&R BARRACKS/GALLEY BUILDING
SFO SOUTHWEST HARBOR
EXCEL
LE
N C E
I N E N G I N E E R I N G
U . S . C O A S T G U
A R
D
CIVIL
ENGINEERING UNIT
PROVIDENCE
AREA MAP
SCALE: NTS
PORTSMOUTH
JACKMAN
PORTLAND
MOOSEHEAD
VERMONT
HAMPSHIRE
CONCORD
NEW WASHINGTON
MT.
QUEBEC
LAKE
LIMESTONE
ACADIA NATIONAL
BANGOR
AUGUSTA
BRUNSWICK
MAINE
GULF OF
MACHIAS
PARK
PRESQUE ISLE
MAINE
CARIBOU
HOULTON
LOCATION
PROJECT
NEW
BRUNSWICK
WEST GOULD
BAR HARBOR
OTTER CREEEK
FRENCHBOROMINTURN
SWANS ISLAND
PRETTY MARSH
SEAL COVE
NASKEAG
ATLANTIC
WEST TREMONT
BALDWIN CORNERS
HALL QUARRY
ASTICOU
NORTHEAST HARBOR
TREMONT
ISLESFORD
SOUTH SURRY
INDIAN POINT
EAST BLUE HILL
BLUE HILL FALLS
SOUTH BLUE HILL
TRENTON
BAYSIDE EAST LAMOINE
SALSBURY COVE
TOWN HILL
HULLS COVE GERNISHVILLE
BIRCH HARBOR
3 186
BLUEDBERRY LN FEMALD POINT RD
SEAL COVE RD
E RIDGE RD
RIDGE AORES LN
M
ITCHELL LN
MAIN ST
CAUSEWAY CLUB
PARK VIEW RD
HERRICK RD
FOREST AVE
KINFOLK RD
WESLEY RD SOUTHWEST HARBOR
LAWLER LN
MA
IN
S
T SOUTHWEST
HARBOR
CLARK POINT RD
BULLERMILK BROOK
ROBINSON LN
BASS HARBOR RD
GOTTS LN
AL
EX
AN
DR
A
RD
BE
NN
ET
T L
N
AL
DE
R
LN
SL
UI
CE
LN
MANSET SHORE RD
SEAWALL RD
HARBOR
PROJECT
LOCATION
MAIN ST
SOUTHWEST
HARBOR
PROJECT
LOCATION
SOUTHWEST
DRAWING INDEX
SHEET ID SHEET# SHEET TITLE
G-001 01 COVER SHEET
G-002 02 GENERAL NOTES, ABBREVIATIONS, AND LEGEND
CS101 03 SITE PLAN
AD101 04 REMOVALS FIRST FLOOR PLAN
AD102 05 REMOVALS SECOND FLOOR PLAN
AD120 06 REMOVALS ROOF PLAN
AD201 07 REMOVALS ELEVATIONS
AD202 08 REMOVALS ELEVATIONS - OPTION BID ITEM
A-101 09 FIRST FLOOR PLAN
A-102 10 SECOND FLOOR PLAN
A-120 11 ROOF PLAN AND DETAILS
A-201 12 ELEVATIONS
A-202 13 ELEVATIONS - OPTION BID ITEM
A-501 14 WALL DETAILS - OPTION BID ITEM
A-502 15 DOOR DETAILS (BASE BID)
A-503 16 DOOR DETAILS (OBI #1A)
A-504 17 DOOR DETAILS (OBI #1B)
A-505 18 WINDOW DETAILS (BASE BID)
A-506 19 WINDOW DETAILS (OBI #1A)
A-507 20 WINDOW DETAILS (OBI #1B)
A-601 21 DOOR SCHEDULE, DOOR & FRAME TYPES, AND WINDOW TYPES
PROJECT DESCRIPTION
UNLESS OTHERWISE NOTED, CONTRACTOR SHALL PROVIDE SUPERVISION, LABOR, EQUIPMENT AND MATERIAL NECESSARY TO
PERFORM THE FOLLOWING WORK:
1. THE PROJECT INCLUDES ONE (1) BASE BID ITEM (BBI) AND TWO (2) OPTIONAL BID ITEMS (OBIS) AS SUMMARIZED BELOW. ANY WORK THAT IS NOT SPECIFIED AS BEING PART OF AN OBI SHALL BE INCLUDED AS PART OF THE BASE BID SCOPE.
BASE BID ITEMS
· REPLACE WINDOWS WITH HURRICANE RATED UNIT WITH EXTRUDED ALUMINUM EXTERIOR CLADDING AND WOOD INTERIORS.
WINDOWS MUST BE DOUBLE HUNG, HAVE NEW MINI-BLINDS, AND NEW INTERIOR SILLS AND TRIM.
· REPLACE EXTERIOR DOORS INCLUDING ALUMINUM ENTRY DOOR. EXTERIOR DOORS MUST RECEIVE NEW HARDWARE, FRAMES AND THRESHOLDS.
· REMOVE EXISTING EPDM SYSTEM DOWN TO ROOF SUBSTRATE AND INSTALL NEW FULLY TPO ROOFING SYSTEM. REMOVE EXISTING GUTTERS AND PROVIDE NEW HEAVY DUTY BOX GUTTERS AND DOWNSPOUTS WITH NEW CONCRETE SPLASH
BLOCKS AT GRADE.
OBI ALTERNATE #1A
· REMOVE EXISTING VINYL SIDING, SOFFITS, VINYL TRIM COMPONENTS. PROVIDE NEW WEATHER RESISTIVE AIR BARRIER AND
REPLACE SIDING AND TRIM COMPONENTS WITH NEW VINYL SIDING IN-KIND.
OBI ALTERNATE #1B
· REMOVE EXISTING VINYL SIDING, SOFFITS, VINYL TRIM COMPONENTS. PROVIDE NEW WEATHER RESISTIVE AIR BARRIER AND REPLACE SIDING WITH FIBER-CEMENT BOARD. REPLACE TRIM COMPONENTS WITH CELLULAR COMPOSITE PVC (POLYVINYL
CHLORIDE) MATERIAL.
USCG ANNOTATION SYMBOLS LEGEND
GRID IDENTIFIER
RPUID: ######
NAME
BUILDING
## SQ. FT.
NAME
ROOM
## SQ. FT.
SL 1:##
#XX
W.L. AT '##
FLOOR X#
XX## XXX### XXXXX
FLOW
XXX
XXX XXXXXXXX
XX ##### XX
XXXXXXXX XX##
CFM#####
KEYNOTE SYMBOL
BUILDING/ASSET IDENTIFIER ROOM NAME IDENTIFIER
SPOT ELEVATION INDICATORVERTICAL ELEVATION INDICATOR
SLOPE ARROW FLOW ARROW
EQUIPMENT IDENTIFIERS DUCT CLASS IDENTIFIERS
OPENING IDENTIFIERS WALL TYPE IDENTIFIER
DUCT BANK IDENTIFIER CIRCUIT IDENTIFIER
CFM IDENTIFIER CEILING GRILLE IDENTIFIER
WATER LEVEL IDENTIFIER FASTENER TYPE IDENTIFIER
MECH & ELECTYPICAL VERTICAL HORIZONTAL
WINDOWS & LOUVERS DOORS & GATES
PREFIX
X/#
CG X/Y
USCG DRAWING VIEW SYMBOLS LEGEND
NORTH
PLAN
TRUE N
X# TITLE
SCALE: X=1'-0"
XX###
X#
X#
X#
X#
X#
XX###
X#
XX###
0 1" 2"1/2"
XX###
X#
X#
XX###
X#
XX###
XX###
X#
XX###
X#
REVISION #
DRAWING VIEW TITLES REVISION CLOUDS AND DELTAS
GRAPHIC SCALES NORTH ARROWS
DRAWING VIEW INDICATOR EXTERIOR ELEVATION INDICATOR
ENLARGED DETAIL INDICATORS INTERIOR ELEVATION INDICATOR
BUILDING SECTION INDICATOR SECTIONAL VIEW INDICATOR
REV CLOUD
PLAN NORTH
TRUE NORTH
ELEVATION
NUMBER/ID
ELEVATION
DRAWING
SHEET
DRAWING
SHEET
NUMBER/ID
DRAWING
VIEW
NUMBER/ID
DRAWING
VIEW
NUMBER/ID
DRAWING
VIEW
TITLE
DRAWING
SCALE
APPLICABLE CODES
SOLICITATION NO.: CONTRACT NO.:
C
I
UN
TE
D
1 07 9
ST
EAT S
T
RD
GUA
OAS
M
AJ
OR
M
&R B
AR
RA
CK
S/
GA
LL
EY
B
UI
LD
IN
G
SF
O
SO
UT
HW
ES
T
HA
RB
OR
SO
UT
HW
ES
T
HA
RB
OR
M E
GE
NE
RA
L
GE
NE
RA
L N
OT
ES
, A
BB
RE
VIA
TIO
NS
, A
ND
LE
GE
ND
BARRACKS/
GALLEY
BUILDING
G-002
P2
P2
3G -0
.D
W G
US
CG
C
IV
IL
E
NG
IN
EE
RI
NG
U
NI
T
PR
OV
ID
EN
CE
KI
LV
ER
T
ST
, S
UI
TE
W
AR
W
IC
K, R I 0
DA
VI
D M
IL
ES
JM
c
CR
R
CR
R
KP
OA
K
PO
IN
T
AS
SO
CI
AT
ES
M
AI
N
ST
RE
ET
, B
ID
DE
FO
RD
, M
E
(2
) 2
-0
0.
IS
SU
E
FO
R
BI
D
FE
B
9, US COAST GUARD
CIVIL ENGINEERING
N/A N/A
DE
SI
GN
ED
B Y:
DE
SC
RI
PT
IO
N
M
AR
K
ED
IT
ED
B Y:
DA
TE
CH
EC
KE
D
BY
DR
AW
N
BY
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A
US
CG
D
RA
W
IN
G
NU
M
BE
R
SH
EE
T
OF
US
CG
P
RO
JE
CT
N
UM
BE
R
US
CG
F
IL
EN
AM
E
A/ E
CO
M
PA
NY
CO
NS
UL
TI
NG
A
/E
US
CG
P
RO
JE
CT
M
AN
AG
ER
A/
E
PR
OJ
EC
T
NO
SHEET ID
M
EA
SU
RE
M
EN
T
BA
R:
1"
HA
LF
S
IZ
E
1/ 2"
SOLICITATION NO.: CONTRACT NO.:
CORRIDORCORR
NIC NOT IN CONTRACT
OCCUPATIONAL SAFETY ANDOSCA
U.S. UNITED STATES
UNITED STATES COAST GUARDUSCG
REPRESENTATIVE
COR CONTRACTING OFFICER'S
TESTING AND MATERIALS
AMERICAN SOCIETY FORASTM
INSUL INSULATION
HM HOLLOW METAL
ELEV ELEVATION
DN DOWN
CONC CONCRETE
CMU CONCRETE MASONRY UNIT
AFF ABOVE FINISH FLOOR
MFR MANUFACTURER
MAX MAXIMUM
DS DOWNSPOUT
CONT CONTINUOUS
ALUM ALUMINUM
@ AT
AND
DIA DIAMETER
APPROX APPROXIMATELY
± PLUS OR MINUS
# POUND
EXIST EXISTING
ABBREVIATIONS
BLDG BUILDING
COORDINATECOORD
CEILINGCLG
ELECTRICALELEC
EQUIPMENTEQUIP
DRAWINGSDWGS
REINF REINFORCED
MECH MECHANICAL
MASONRY OPENINGMO
STRUCT STRUCTURAL
METALMTL
VIF VERIFY IN FIELD
ON CENTEROC
W/ WITH
MINIMUMMIN
PAINTPNT
WOODWD
PRESSURE TREATEDPT
STAINLESS STEELSS
SQUARE FEET
SIMILARSIM
SF
ROUGH OPENINGRO
TYPICALTYP
VINYL COMPOSITION TILEVCT
SYSTEMSYS
ADJ ADJACENT
PLYWD PLYWOOD
GALVANIZEDGALV
HEATH ADMINISTRATION
GENERAL PROJECT NOTES
1. WORK MUST BE COMPLETED IN ACCORDANCE WITH AND BETTER THAN INDUSTRY STANDARDS AND PERFORMED IN A WORKMANLIKE PROFESSIONAL MANNER TO PROVIDE COMPLETE AND OPERATIONAL
SYSTEMS.
2. WHERE CONFLICTS EXIST WITHIN THE DOCUMENTS OR BETWEEN THE DOCUMENTS AND APPLICABLE CODES, ORDINANCES, UFC OR INDUSTRY STANDARDS, THE MORE STRINGENT REQUIREMENT, AS
DETERMINED BY THE CONTRACTING OFFICER, WILL APPLY.
3. MAINTAIN THE CONSTRUCTION SITE IN A SECURE, WEATHERTIGHT, NEAT, CLEAN, AND SAFE MANNER.
4. ITEMS AND COMPONENTS SHOWN ON THE DRAWINGS MUST BE PROVIDED BY THE CONTRACTOR UNLESS NOTED AS EXISTING/(EXIST). ITEMS NOTED AS EXISTING ARE TO REMAIN UNLESS NOTED
OTHERWISE.
5. WORK FROM GIVEN DIMENSIONS AND LARGE-SCALE DETAILS. DO NOT SCALE DRAWINGS.
6. DIMENSIONING SYSTEM: PLAN DIMENSIONS, UNLESS NOTED OTHERWISE (UNO), ARE TO FINISHED FACE OF EXISTING WALLS, TO FACE OF FRAMING, AND TO FINISH FACE OF MASONRY FOR MASONRY WALLS. DIMENSIONS INDICATED AS "CLEAR" (CLR) MUST BE MAINTAINED IN CASE OF DISCREPANCY AND ARE MEASURED FROM THE FACE OF FINISH. CENTERLINE DIMENSIONS ARE INDICATED BY
CENTERLINE SYMBOL ( ℄ ).
7. VERIFY EXISTING CONDITIONS AND DIMENSIONS AND REPORT DISCREPANCIES TO THE CONTRACTING OFFICER. PROCEED WITH THE WORK ONLY AFTER THE DISCREPANCIES HAVE BEEN RESOLVED BY
THE GOVERNMENT.
8. DO NOT PENETRATE JOISTS, BEAMS OR OTHER STRUCTURAL MEMBERS. OBTAIN WRITTEN APPROVAL FROM THE ENGINEER OF RECORD FOR ANY PENETRATIONS OF STRUCTURAL MEMBERS.
9. UTILITY INTERRUPTIONS ARE NOT ANTICIPATED IN THE COURSE OF THE WORK. IF NECESSARY, COORDINATE WITH CONTRACTING OFFICERS REPRESENTATIVE (COR) 72 HOURS PRIOR TO INTERRUPTING
UTILITY SERVICES WITHIN THE BUILDING.
10. THE CONTRACTOR MUST PROVIDE TEMPORARY PROTECTION DURING REMOVALS UNTIL A WEATHERTIGHT ENCLOSURE HAS BEEN COMPLETED TO PROTECT THE BUILDING INTERIORS AND IS
RESPONSIBLE FOR REPAIRS OF DAMAGED SURFACES AT NO COST TO THE GOVERNMENT.
11. DISPOSE OF AND/OR RECYCLE CONSTRUCTION DEBRIS FROM THE PROJECT SITE AS REQUIRED BY THE STATE OF MAINE AND AS REQUIRED BY THE CONTRACT. OBTAIN DISPOSAL PERMITS AS REQUIRED.
12. PROTECT EXISTING SYSTEMS AND SURFACES TO REMAIN. DAMAGE RESULTING FROM THE CONTRACTOR'S OPERATIONS MUST BE REPAIRED OR REPLACED AS APPROVED BY THE CONTRACTING OFFICER AT NO ADDITIONAL COST TO THE GOVERNMENT. REMOVE ITEMS IN SUCH A MANNER THAT THE ADJACENT ORIGINAL STRUCTURE (E.G. MORTAR JOINTS, MASONRY, SHEATHING, INTERIOR FINISHES) IS NOT DAMAGED DURING REMOVAL AND CONSTRUCTION ACTIVITIES. REPAIR ITEMS TO REMAIN THAT ARE DAMAGED DURING WORK TO THEIR ORIGINAL CONDITION AT NO ADDITIONAL COST TO THE
GOVERNMENT.
13. PRIOR TO BEGINNING WORK, THE CONTRACTOR MUST PROVIDE THEIR PROJECT SCHEDULE AND PHASING PLAN TO THE UNITED STATES COAST GUARD CONTRACTING OFFICER FOR APPROVAL. WORK WILL NOT BE ALLOWED TO BEGIN UNTIL THE CONTRACTOR HAS RECEIVED WRITTEN APPROVAL OF THE PROJECT SCHEDULE.
14. PRIOR TO BEGINNING ANY WORK, THE CONTRACTOR MUST PROVIDE A STAGING/SCAFFOLDING PLAN AND A SAFETY PLAN FOR APPROVAL.
15. BUILDING MUST REMAIN OCCUPIED DURING CONSTRUCTION.
LF LINEAR FEET
ACM ASBESTOS CONTAINING
INT INTERIOR
GYP BD GYPSUM BOARD
EXT EXTERIOR
STYRENE-BUTADIENE-STYRENESBS
ETHYLENE PROPYLENEEPDM
MDO MEDIUM DENSITY OVERLAY
POUNDS PER SQUARE INCHPSI
MATERIAL
DIENE MONOMER
2024 INTERNATIONAL BUIILDING CODE (IBC)
2024 INTERNATIONAL EXISTING BUILDING CODE (IEBC)
2024 INTERNATIONAL PLUMBING CODE (IPC)
2024 INTERNATIONAL MECHANICAL CODE (IMC)
2023 NATIONAL ELECTRICAL CODE (NFPA 70) WITH LOCAL AMENDMENTS
2024 LIFE SAFETY CODE (NFPA 101)
29 CFR 1910 OCCUPATIONAL SAFETY AND HEALTH (OSHA)
2017 ICC/ANSI A-117.1 ACCESSIBLE AND USABLE BUILDINGS AND FACILITIES
2022 ASHRAE 90.1
2020 UNIFIED FACILITIES CRITERIA (UFC) 3-101-01 ARCHITECTURE
2020 UNIFIED FACILITIES CRITERIA (UFC) 3-110-01 ROOFING
2025 UNIFIED FACILITIES CRITERIA (UFC) 3-301-01 STRUCTURAL ENGINEERING
2021 UNIFIED FACILITIES CRITERIA (UFC) 3-600-01 FIRE PROTECTION ENGINEERING FOR FACILITIES
THERMOPLASTIC POLYOLEFIN ROOFINGTPO
EX
IS
TI
NG
M
UL
TI
M
IS
SO
N
BU
IL
DI
NG
M
AJ
OR
M
&R U
PH
/G
AL
LE
Y
BU
IL
DI
NG
SF
O
SO
UT
HW
ES
T
HA
RB
OR
SO
UT
HW
ES
T
HA
RB
OR
M
E
CI
VI
L
SI
TE
P
LA
N
BARRACKS
/ GALLEY
BUILDING
CS101
P2
P2
3C S1
.D
W G
US
CG
C
IV
IL
E
NG
IN
EE
RI
NG
U
NI
T
PR
OV
ID
EN
CE
KI
LV
ER
T
ST
, S
UI
TE
W
AR
W
IC
K, R I 0
DA
VI
D M
IL
ES
PJ
M
IJR
ED
IT
ED
B
Y
PJ
M
OA
K
PO
IN
T
AS
SO
CI
AT
ES
M
AI
N
ST
RE
ET
, B
ID
DE
FO
RD
, M
E
(2
) 2
-0
0.
IS
SU
E
FO
R
BI
D
FE
B
9, US COAST GUARD
CIVIL ENGINEERING
N/A N/A
DE
SI
GN
ED
B Y:
DE
SC
RI
PT
IO
N
M
AR
K
ED
IT
ED
B Y:
DA
TE
CH
EC
KE
D
BY
DR
AW
N
BY
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A
SH
EE
T
OF
US
CG
P
RO
JE
CT
N
UM
BE
R
US
CG
F
IL
EN
AM
E
A/ E
CO
M
PA
NY
CO
NS
UL
TI
NG
A
/E
US
CG
P
RO
JE
CT
M
AN
AG
ER
A/
E
PR
OJ
EC
T
NO
SHEET ID
M
EA
SU
RE
M
EN
T
BA
R:
1"
HA
LF
S
IZ
E
1/ 2"
US
CG
D
RA
W
IN
G
SE
RI
ES
N
UM
BE
R
SOLICITATION NO.: CONTRACT NO.:
EXIST BARRACKS/GALLEY BUILDING
FINISH FLOOR ELEV: 26.50'
FINISH FLOOR
ELEV: 24.00'
T
CLARK POINT ROAD
B4 SITE PLAN
SCALE: 1"=10' 0 10' 20'
1. THE PROJECT BENCHMARK IS THE TILE FINISH FLOOR OF THE BARRACKS
BUILDING JUST INSIDE THE EXISTING DOUBLE DOORS. TILE ELEVATION IS 26.50'
BASED ON MEAN LOW WATER DATUM.
2. EXISTING UNDERGROUND UTILITIES ARE SHOWN IN THEIR APPROXIMATE
LOCATIONS ONLY. PRIOR TO COMMENCING EXCAVATION OPERATIONS OR GROUND
PENETRATING WORK ON THE SITE, THE CONTRACTOR MUST:
a). CONTACT "DIGSAFE" (1-888-344-7233) AND OBTAIN A "DIGSAFE" PERMIT;
b.) VERIFY AND MARK THE LOCATION OF ALL UNDERGROUND UTILITIES
WITHIN THE PROJECT LIMITS AND;
c.) OBTAIN APPROVAL FROM THE CONTRACTING OFFICER.
GENERAL SHEET NOTES
SHEET KEYNOTES
2 EXISTING ASPHALT PAVEMENT.
EXISTING CONCRETE WALK.3
4 EXISTING CONCRETE RAMP.
5 EXISTING CONCRETE STAIRS.
EXISTING WOOD DECK.
EXIST
DUMPSTER
EXIST GREASE
DUMPSTER
EXIST
INTERCOM
EXISTING TIMBER CURBING.
EXIST OUT FALL
INV: ±17.0'
EXISTING TURF.
EXIST ELECTRIC
TRANSFORMER ON
CONCRETE PADEXIST PROPANE
TANKS
EXIST FUEL
OIL TANKS
EXIST 10'± DOUBLE
SWING GATE
21 REMOVE EXISTING CONCRETE SPLASH BLOCK AND ± 3" OF EXISTING
TOPSOIL BENEATH FOOTPRINT OF NEW SPLASH BLOCK. PROVIDE 3"
LAYER OF 3/4" CRUSHED STONE AND NEW PRECAST CONCRETE SPLASH
BLOCK, ± 30" LONG x ± 12" WIDE x ± 3" THICK. PRECAST CONCRETE
SPLASH BLOCKS MUST BE MINIMUM 5,000 PSI CONCRETE AND A
PRODUCT OF A QUALIFIED PRECAST CONCRETE MANUFACTURER.
SUBMIT SPLASH BLOCK PRODUCT DATA FOR REVIEW BY THE
CONTRACTING OFFICER. OBTAIN CONTRACTING OFFICERS' APPROVAL
PRIOR TO ORDERING.
EXIST
USCG SIGN
PROJECT BENCHMARK,
(ELEV 26.50') SEE NOTE 1
EXIST SHED
EXIST USCG
MONUMENT
PROPERTY LINE
EXISTING CONCRETE STOOP.
20 NOT USED-
EXISTING CONCRETE PAVERS.
EXISTING CONCRETE RETAINING WALL.
EXISTING METAL STAIRS.
TO
W
N W
HA
RF
W
AY
EXISTING SHRUB TO REMAIN (TYP).
CIVIL LEGEND
CIVIL ABBREVIATIONS
EXIST EXISTING
, EXISTING CATCH BASIN
EXISTING SEWER MANHOLE
EXISTING HYDRANT
EXISTING WATER VALVE
EXISTING CLEANOUT
EXISTING ELECTRIC HANDHOLE
EXISTING COMMUNCIATIONS HANDHOLE
EXISTING SHRUB
ELEV ELEVATION
USCG UNITED STATES COAST GUARD
± PLUS OR MINUS
EXISTING UTILITY POLE
INV INVERT
EXISTING BENCHMARK
EXISTING CONCRETE
EXISTING IRON PIPE
EXISTING CONTOUR LINE
EXISTING UNDERGROUND WATER LINE (SIZE AS NOTED)
EXISTING UNDERGROUND SEWER LINE (SIZE AS NOTED)
EXISTING UNDERGROUND TELEPHONE LINE
EXISTING STORM DRAIN LINE (SIZE AS NOTED)
EXISTING PROPERTY LINE
EXISTING CHAINLINK FENCE WITH 3 STRANDS OF BARBED WIRE.
EXISTING UNDERGROUND ELECTRIC LINE (SIZE AS NOTED)
EXISTING OVERHEAD ELECTRIC AND TELEPHONE LINE
EXISTING UNKNOWN UTILITY LINE (SIZE AS NOTED)
13 EXISTING FLAGPOLE.
14 EXISTING CONCRETE CURB.
EXIST
STOCKADE
FENCE
(UNDER
STAIRS)
EXIST GRAVEL
DRIVEWAY
EXISTING FIRE DEPT.
CONNECTION
LINE OF CANOPY (ABOVE)
EXIST CATCH
BASIN NOT FOUND
EXISTING PRECAST CONCRETE SPLASH BLOCK
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text H
AutoCAD SHX Text Y
AutoCAD SHX Text D
AutoCAD SHX Text
EOE/T
AutoCAD SHX Text
EOE/T
AutoCAD SHX Text
EOE/T
AutoCAD SHX Text
EOE/T
AutoCAD SHX Text
EW(3/4"CU)
AutoCAD SHX Text
EW(3/4"CU)
AutoCAD SHX Text
EW
AutoCAD SHX Text E
AutoCAD SHX Text
ECO
AutoCAD SHX Text
EUE
AutoCAD SHX Text
EUE
AutoCAD SHX Text
EUE
AutoCAD SHX Text
EUE (2-4")
AutoCAD SHX Text
EUE(2-4")
AutoCAD SHX Text
EW(2-1/2"CU)
AutoCAD SHX Text
EW
AutoCAD SHX Text
EW
AutoCAD SHX Text
EW
AutoCAD SHX Text
EUT
AutoCAD SHX Text
EUT
AutoCAD SHX Text
EUT
AutoCAD SHX Text
EUC
AutoCAD SHX Text
EUC
AutoCAD SHX Text
EUC
AutoCAD SHX Text
EUU(3-2")
AutoCAD SHX Text
ESS(ABANDONED)
AutoCAD SHX Text
ESS(4"AC)
AutoCAD SHX Text
ESS(6"AC)
AutoCAD SHX Text
ESS(4")
AutoCAD SHX Text
ESS(4")
AutoCAD SHX Text
ESS(4")
AutoCAD SHX Text
ECO
AutoCAD SHX Text
ESS
AutoCAD SHX Text
ECO
AutoCAD SHX Text
ECO
AutoCAD SHX Text
ESS(4")
AutoCAD SHX Text
ECO
AutoCAD SHX Text
ESS(4")
AutoCAD SHX Text
ESD(8")
AutoCAD SHX Text
EW(3/4"CU)
AutoCAD SHX Text
ESS(4")
AutoCAD SHX Text
ESD(8")
AutoCAD SHX Text
EUD(8")
AutoCAD SHX Text
ESD(12")
AutoCAD SHX Text
ESS(ABAN)
AutoCAD SHX Text
ESD(8")
AutoCAD SHX Text
ESD(6")
AutoCAD SHX Text S
AutoCAD SHX Text W
AutoCAD SHX Text S
AutoCAD SHX Text O
AutoCAD SHX Text W
AutoCAD SHX Text S
AutoCAD SHX Text O
AutoCAD SHX Text
EW(1")
AutoCAD SHX Text
EW(3/4")
AutoCAD SHX Text
EW(3/4")
AutoCAD SHX Text
EW(1")
AutoCAD SHX Text
EW(1")
AutoCAD SHX Text
EW(3/4")
AutoCAD SHX Text
ESS(8"AC)
AutoCAD SHX Text
ESS(8"AC)
AutoCAD SHX Text
ESS(8"AC)
AutoCAD SHX Text
ESS(8"AC)
AutoCAD SHX Text W
AutoCAD SHX Text S
AutoCAD SHX Text O
AutoCAD SHX Text S
AutoCAD SHX Text C
AutoCAD SHX Text E
AutoCAD SHX Text C
AutoCAD SHX Text
ESD(6")
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
MEAN HIGH TIDE LINE
AutoCAD SHX Text
ELEVATION 10.2
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
ECO
AutoCAD SHX Text W
AutoCAD SHX Text S
AutoCAD SHX Text O
AutoCAD SHX Text S
AutoCAD SHX Text C
AutoCAD SHX Text H
AutoCAD SHX Text Y
AutoCAD SHX Text D
AutoCAD SHX Text E
AutoCAD SHX Text
AutoCAD SHX Text
EW
AutoCAD SHX Text
ESS
AutoCAD SHX Text
EUT
AutoCAD SHX Text
ESD
AutoCAD SHX Text
EUE
AutoCAD SHX Text
EOE/T
AutoCAD SHX Text
EUU
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text S
AutoCAD SHX Text E
AutoCAD SHX Text T
AutoCAD SHX Text A
AutoCAD SHX Text T
AutoCAD SHX Text S
AutoCAD SHX Text D
AutoCAD SHX Text E
AutoCAD SHX Text T
AutoCAD SHX Text I
AutoCAD SHX Text N
AutoCAD SHX Text U
AutoCAD SHX Text D
AutoCAD SHX Text R
AutoCAD SHX Text A
AutoCAD SHX Text U
AutoCAD SHX Text G
AutoCAD SHX Text T
AutoCAD SHX Text S
AutoCAD SHX Text A
AutoCAD SHX Text O
AutoCAD SHX Text C
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text N
AutoCAD SHX Text
MAGNETIC
AutoCAD SHX Text
NORTH
C4 REMOVALS FIRST FLOOR PLAN
SCALE: 1/8"=1'-0"
'-4
172'-4"±
50'-11 5/8"± 97'-0 3/8"± 24'-4"±
8'-0 3/8"± 7'-11"± 15'-0"± 15'-6"± 15'-0"± 35'-7"±
'-8
'-4
'-0
'-4
50'-0"± 93'-4"± 29'-0"±
22'-4 3/8"± 15'-0"± 14'-6"± 15'-0"± 8'-6"± 8'-0"±8'-4"±
1'-7 5/8"±
19'-8"±30'-4"±
8'- 8"
8'- 8"
6'- 0"
'-0
7'- 6"
3'- 0"
'-4
'-0
2'- 6"
3'-0"±
F5
AD201
C5
AD201
A2
AD201 D2
AD201
1A
2 12
117 122
A5
AD201
A5
AD201
A8
AD201
A8
AD201
D5
AD201
D5
AD201
OFFICE
MEDICAL
ROOM
EXERCISE
TOILET
STORAGE
TOILET
STORAGE
STAIR
HALL/
CORR
TOILET
ROOM
SERVER
BEDROOM
BEDROOM
STORAGE
CLOSET
121A
TOILET
STORAGE
LAUNDRY
ROOM
BOILER
FURNACE
TOILET
LOUNGE
CORRIDOR
BEDROOM
BEDROOM
TOILET
TOILET
LOCKER RM
MORALE
TOILET
TOILET
BEDROOM
BEDROOM
STAIR 2
CLOSET
139A
STAIR 1
CLOSET
TOILET
SPRINKLER
FIRE
LOBBY
VESTIBULE
OFFICE
STORAGE
DRY
STORAGE
GALLEY
DINING AREA
ENTRY
11 111 1
1 1 1
1 1 1
2 3 2 3 2 3 2 3 2 3
2 3
2 3
2 3
2 3
2 3
2 32 32 3
2 3
7 3
7 3
7 3 7 3
2 3
2 3
2 3
2 3 2 3
2 3
100100 100
NORTH
PLAN
TRUE N
REFRIGERATOR
FREEZER
106A
EXIST MTL FENCE
EXIST MECH UNIT
A1 SILL DETAIL (BASE BID)
REMOVALS WINDOW
SCALE: 1-1/2"=1'-0" A3 SILL DETAIL (BASE BID)
REMOVALS WINDOW
SCALE: 1-1/2"=1'-0"
B1 HEAD DETAIL (BASE BID)
REMOVALS WINDOW
SCALE: 1-1/2"=1'-0" B3 HEAD DETAIL (BASE BID)
REMOVALS WINDOW
SCALE: 1-1/2"=1'-0"
1'-4 1/4"± 9 5/8"±
REMOVE MINI-BLIND
REMOVE WD TRIM
EXIST MTL LINTEL
EXIST BOND BEAM
REMOVE VINYL WINDOW TRIM
REMOVE ALUM WINDOW
FLASHING
EXIST WD BLOCKING
REMOVE WINDOW
REMOVE MINI-BLIND
EXIST BOND BEAM
REMOVE VINYL WINDOW TRIM
REMOVE ALUM WINDOW RETURN
EXIST WD BLOCKING5
1/
2"
3/ 4"
7/
5/
A4 SILL DETAIL (OBI #1A & OBI #1B)
REMOVALS WINDOW
SCALE: 1-1/2"=1'-0" A6 SILL DETAIL (OBI #1A & OBI #1B)
REMOVALS WINDOW
SCALE: 1-1/2"=1'-0"
B4 HEAD DETAIL (OBI #1A & OBI #1B)
REMOVALS WINDOW
SCALE: 1-1/2"=1'-0" B6 HEAD DETAIL (OBI #1A & OBI #1B)
REMOVALS WINDOW
SCALE: 1-1/2"=1'-0"
1'-4 1/4"± 9 5/8"±
EXIST MASONRY WALL, RIGID
INSUL, & SHEATHING
REMOVE MINI-BLIND
REMOVE WD TRIM
EXIST MTL LINTEL
EXIST BOND BEAM
REMOVE VINYL WINDOW TRIM
REMOVE ALUM WINDOW RETURN
EXIST WD BLOCKING
REMOVE MINI-BLIND
REMOVE WD TRIM
EXIST BOND BEAM
REMOVE VINYL WINDOW TRIM
REMOVE ALUM WINDOW RETURN
1/
2"
3/ 4"
7/
5/
NOTE
REMOVALS WINDOW JAMB DETAIL SIMILAR.
NOTE
REMOVALS WINDOW JAMB DETAIL SIMILAR.
NOTES
1. REMOVALS WINDOW JAMB DETAIL SIMILAR.
2. REMOVAL OF VINYL WINDOW TRIM AND ALUMINUM
RETURN COVERED UNDER BASE BID.
REMOVE WINDOW
REMOVE WD TRIM
REMOVE WINDOW
REMOVE WINDOW
EXIST MASONRY WALL, RIGID
INSUL, & SHEATHINGEXIST MASONRY WALL, RIGID
INSUL, & SHEATHING
EXIST MASONRY WALL, RIGID
INSUL, & SHEATHING
REMOVE VINYL SIDING & AIR
BARRIERREMOVE VINYL SIDING & AIR
BARRIER
NOTES
1. REMOVALS WINDOW JAMB DETAIL SIMILAR.
2. REMOVAL OF VINYL WINDOW TRIM AND
ALUMINUM RETURN COVERED UNDER BASE BID.
REMOVE WOOD TRIM
REMOVE WOOD STOOL
EXIST MASONRY WALL, RIGID
INSUL, & SHEATHING
REMOVE ALUM WINDOW
FLASHING
EXIST WD BLOCKING
REMOVE WINDOW
REMOVE WOOD TRIM
REMOVE WOOD STOOL
EXIST MASONRY WALL, RIGID
INSUL, & SHEATHING
REMOVE ALUM WINDOW
FLASHING
EXIST WD BLOCKING
REMOVE WINDOW
EXIST CERAMIC TILE SILL/TRIM
EXIST MASONRY WALL, RIGID
INSUL, & SHEATHING
REMOVE ALUM WINDOW
FLASHING
EXIST WD BLOCKING
REMOVE WINDOW
EXIST CERAMIC TILE SILL/TRIM
EXIST MASONRY WALL, RIGID
INSUL, & SHEATHING
REMOVE VINYL SIDING & AIR
BARRIERREMOVE VINYL SIDING & AIR
BARRIER
REMOVE INSECT SCREEN
REMOVE INSECT SCREEN
REMOVE ALUM WINDOW RETURN
REMOVE WINDOW
REMOVE INSECT SCREEN
EXIST WD BLOCKING
EXIST WD BLOCKING
REMOVE INSECT SCREEN
REMOVE INSECT SCREENREMOVE INSECT SCREEN
REMOVE INSECT
SCREEN
REMOVE INSECT SCREEN
M
AJ
OR
M
&R B
AR
RA
CK
S/
GA
LL
EY
B
UI
LD
IN
G
SF
O
SO
UT
HW
ES
T
HA
RB
OR
SO
UT
HW
ES
T
HA
RB
OR
M E
AR
CH
IT
EC
TU
RA
L
RE
M
OV
AL
S
FI
RS
T
FL
OO
R
PL
AN
BARRACKS/
GALLEY
BUILDING
AD101
P2
P2
3A D1
.D
W G
US
CG
C
IV
IL
E
NG
IN
EE
RI
NG
U
NI
T
PR
OV
ID
EN
CE
KI
LV
ER
T
ST
, S
UI
TE
W
AR
W
IC
K, R I 0
DA
VI
D M
IL
ES
JM
c
CR
R
CR
R
KP
OA
K
PO
IN
T
AS
SO
CI
AT
ES
M
AI
N
ST
RE
ET
, B
ID
DE
FO
RD
, M
E
(2
) 2
-0
0.
IS
SU
E
FO
R
BI
D
FE
B
9, US COAST GUARD
CIVIL ENGINEERING
N/A N/A
DE
SI
GN
ED
B Y:
DE
SC
RI
PT
IO
N
M
AR
K
ED
IT
ED
B Y:
DA
TE
CH
EC
KE
D
BY
DR
AW
N
BY
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A
SH
EE
T
OF
US
CG
P
RO
JE
CT
N
UM
BE
R
US
CG
F
IL
EN
AM
E
A/ E
CO
M
PA
NY
CO
NS
UL
TI
NG
A
/E
US
CG
P
RO
JE
CT
M
AN
AG
ER
A/
E
PR
OJ
EC
T
NO
SHEET ID
M
EA
SU
RE
M
EN
T
BA
R:
1"
HA
LF
S
IZ
E
1/ 2"
US
CG
D
RA
W
IN
G
SE
RI
ES
N
UM
BE
R
GENERAL SHEET NOTES
SOLICITATION NO.: CONTRACT NO.:
1. ITEMS ON THIS SHEET ARE EXISTING UNLESS NOTED OTHERWISE.
2. REFER TO SHEET G-002 FOR ADDITIONAL GENERAL REMOVALS NOTES.
3. THE CONTRACTOR MUST MAINTAIN BUILDING SECURITY, ACCESS, AND INTERIOR INTEGRITY
THROUGHOUT THE PROJECT.
4. SEE SHEETS AD202 FOR WALL MOUNTED ITEMS THAT WILL BE REMOVED AND REINSTALLED.
SHEET KEYNOTES
BASE BID KEYNOTES
REMOVE WINDOW, EXTERIOR VINYL WINDOW TRIM AND METAL FLASHING RETURN.
REMOVE INTERIOR WOOD WINDOW TRIM AND WINDOW STOOL.
REMOVE WINDOW BLIND.
REMOVE HOLLOW METAL DOOR, FRAME, HARDWARE, AND EXTERIOR VINYL TRIM.
REMOVE ALUMINUM STOREFRONT ENTRY SYSTEM, ALUMINUM DOOR, AND HARDWARE.
REMOVE HOLLOW METAL DOOR AND DOOR HARDWARE. EXISTING HOLLOW METAL DOOR
FRAME TO REMAIN.
REMOVE AND STORE EXISTING STAINED WOOD WINDOW TRIM/WIDOW OPENING INFILL FOR
REINSTALLATION.
OPTION BID ITEMS #1A & #1B
REMOVE EXTERIOR VINYL SHINGLE SIDING, CORNER BOARDS, TRIM, AND WEATHER
BARRIER.
GRAPHIC SCALES
0 8'4' 16'
CHECK GRAPHIC SCALES BEFORE USING
1/8" = 1'-0"
1' 2'0 6" 1-1/2" = 1'-0"
C4 REMOVALS SECOND FLOOR PLAN
C5
AD201
A2
AD201 49
'-6
122'-4"±
98'-0"± 24'-4"±
9'-0"± 7'-11"± 15'-0"± 15'-6"± 15'-0"± 35'-7"±
'-8
'-4
'-0
'-4
93'-4"± 29'-0"±
22'-4 3/8"± 15'-0"± 14'-6"± 15'-0"± 8'-6"± 8'-0"±8'-4"±
1'-7 5/8"±
F5
AD201
D2
AD201
'-4
8'- 8"
'-1 0"
'-0
3'- 0"
'-1 0"
A5
AD201
A5
AD201
A8
AD201
A8
AD201
KITCHENETTE
TOILET
TOILET
TOILET
TOILET
TOILET
TOILET
TOILET
TOILET
TOILET
BEDROOM
BEDROOM
BEDROOM
BEDROOM
BEDROOM
BEDROOM
BEDROOM
BEDROOM
BEDROOM
LOUNGE
UPH
ROOM
EQUIPMENT
STAIR 1
STAIR 2
STORAGE
TOILET
CORR
ROOM
EXERCISE
TOILET
228 TOILET
OFFICE
CORRIDOR
11 111 1
1 1 1
2 3 2 3 2 3 2 3 2 3
2 3
2 3
2 3
2 3
2 3
2 32 32 3
2 3
2 32 3
12 3
2 3 2 3
1 1
1 1
2 32 3
2 3
2 3
100 100
NORTH
PLAN
TRUE N
SOLICITATION NO.: CONTRACT NO.:
M
AJ
OR
M
&R B
AR
RA
CK
S/
GA
LL
EY
B
UI
LD
IN
G
SF
O
SO
UT
HW
ES
T
HA
RB
OR
SO
UT
HW
ES
T
HA
RB
OR
M E
AR
CH
IT
EC
TU
RA
L
RE
M
OV
AL
S
SE
CO
ND
F
LO
OR
P
LA
N
BARRACKS/
GALLEY
BUILDING
AD102
P2
P2
3A D1
.D
W G
US
CG
C
IV
IL
E
NG
IN
EE
RI
NG
U
NI
T
PR
OV
ID
EN
CE
KI
LV
ER
T
ST
, S
UI
TE
W
AR
W
IC
K, R I 0
DA
VI
D M
IL
ES
JM
c
CR
R
CR
R
KP
OA
K
PO
IN
T
AS
SO
CI
AT
ES
M
AI
N
ST
RE
ET
, B
ID
DE
FO
RD
, M
E
(2
) 2
-0
0.
IS
SU
E
FO
R
BI
D
FE
B
9, US COAST GUARD
CIVIL ENGINEERING
N/A N/A
DE
SI
GN
ED
B Y:
DE
SC
RI
PT
IO
N
M
AR
K
ED
IT
ED
B Y:
DA
TE
CH
EC
KE
D
BY
DR
AW
N
BY
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A
SH
EE
T
OF
US
CG
P
RO
JE
CT
N
UM
BE
R
US
CG
F
IL
EN
AM
E
A/ E
CO
M
PA
NY
CO
NS
UL
TI
NG
A
/E
US
CG
P
RO
JE
CT
M
AN
AG
ER
A/
E
PR
OJ
EC
T
NO
SHEET ID
M
EA
SU
RE
M
EN
T
BA
R:
1"
HA
LF
S
IZ
E
1/ 2"
US
CG
D
RA
W
IN
G
SE
RI
ES
N
UM
BE
R
GRAPHIC SCALE
0 8'4' 16'
CHECK GRAPHIC SCALE BEFORE USING
1/8" = 1'-0"
GENERAL SHEET NOTES
SHEET KEYNOTES
BASE BID KEYNOTES
REMOVE WINDOW, EXTERIOR VINYL WINDOW TRIM AND METAL FLASHING RETURN.
REMOVE INTERIOR WOOD WINDOW TRIM AND WINDOW STOOL.
REMOVE WINDOW BLIND.
REMOVE HOLLOW METAL DOOR, FRAME, HARDWARE, AND EXTERIOR VINYL TRIM.
OPTION BID ITEMS #1A & #1B
REMOVE EXTERIOR VINYL SHINGLE SIDING, CORNER BOARDS, TRIM, AND WEATHER
BARRIER.
1. ITEMS ON THIS SHEET ARE EXISTING UNLESS NOTED OTHERWISE.
2. REFER TO SHEET G-002 FOR ADDITIONAL GENERAL REMOVALS NOTES.
3. THE CONTRACTOR MUST MAINTAIN BUILDING SECURITY, ACCESS, AND INTERIOR INTEGRITY
THROUGHOUT THE PROJECT.
4. SEE SHEETS AD202 FOR WALL MOUNTED ITEMS THAT WILL BE REMOVED AND REINSTALLED.
C4 REMOVALS ROOF PLAN
'-4
172'-4"±
50'-11 5/8"± 97'-0 3/8"± 24'-4"±
8'-2 3/8"± 7'-9"± 15'-0"± 15'-6"± 15'-0"± 35'-7"±
'-8
'-4
'-0
'-4
50'-0"± 93'-4"± 29'-0"±
22'-4 3/8"± 15'-0"± 14'-6"± 15'-0"± 8'-4"± 8'-2"±8'-4"±
1'-7 5/8"±
19'-8"±30'-4"±
8'- 8"
8'- 8"
'-0
7'- 6"
3'- 0"
'-4
'-0
2'- 6"
3'-0"±
'-1
0"
1 1
3 3
4 6
4 7
8 (TYP)
8 (TYP)
NORTH
PLAN
TRUE N
M
AJ
OR
M
&R B
AR
RA
CK
S/
GA
LL
EY
B
UI
LD
IN
G
SF
O
SO
UT
HW
ES
T
HA
RB
OR
SO
UT
HW
ES
T
HA
RB
OR
M E
AR
CH
IT
EC
TU
RA
L
RE
M
OV
AL
S
RO
OF
P
LA
N
BARRACKS/
GALLEY
BUILDING
AD120
P2
P2
3A D1
.D
W G
US
CG
C
IV
IL
E
NG
IN
EE
RI
NG
U
NI
T
PR
OV
ID
EN
CE
KI
LV
ER
T
ST
, S
UI
TE
W
AR
W
IC
K, R I 0
DA
VI
D M
IL
ES
JM
c
CR
R
CR
R
KP
OA
K
PO
IN
T
AS
SO
CI
AT
ES
M
AI
N
ST
RE
ET
, B
ID
DE
FO
RD
, M
E
(2
) 2
-0
0.
IS
SU
E
FO
R
BI
D
FE
B
9, US COAST GUARD
CIVIL ENGINEERING
N/A N/A
DE
SI
GN
ED
B Y:
DE
SC
RI
PT
IO
N
M
AR
K
ED
IT
ED
B Y:
DA
TE
CH
EC
KE
D
BY
DR
AW
N
BY
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A
SH
EE
T
OF
US
CG
P
RO
JE
CT
N
UM
BE
R
US
CG
F
IL
EN
AM
E
A/ E
CO
M
PA
NY
CO
NS
UL
TI
NG
A
/E
US
CG
P
RO
JE
CT
M
AN
AG
ER
A/
E
PR
OJ
EC
T
NO
SHEET ID
M
EA
SU
RE
M
EN
T
BA
R:
1"
HA
LF
S
IZ
E
1/ 2"
US
CG
D
RA
W
IN
G
SE
RI
ES
N
UM
BE
R
SOLICITATION NO.: CONTRACT NO.:
GRAPHIC SCALE
0 8'4' 16'
CHECK GRAPHIC SCALE BEFORE USING
1/8" = 1'-0"
GENERAL SHEET NOTES
1. ITEMS ON THIS SHEET ARE EXISTING UNLESS NOTED OTHERWISE.
2. REFER TO SHEET G-002 FOR ADDITIONAL GENERAL REMOVALS NOTES.
3. THE CONTRACTOR MUST MAINTAIN BUILDING SECURITY, ACCESS AND INTERIOR INTEGRITY
THROUGHOUT THE PROJECT.
4. MAINTAIN AND PROTECT UTILITY CONDUITS AND ROOF TOP EQUIPMENT DURING
CONSTRUCTION.
5. THE ROOF ELEVATION OVER THE BEDROOM PORTION OF THE BUILDING IS APPROXIMATELY 24'-0"
ABOVE GRADE. THE ROOF ELEVATION OVER THE GALLEY AND DINING ROOM ROOF IS
APPROXIMATELY15'-0"ABOVE GRADE.
SHEET KEYNOTES
BASE BID KEYNOTES
REMOVE EPDM ROOF MEMBRANE, 2"± THICK COMPOSITE INSULATION BOARD (1/2"± OSB
COVERBOARD AND 1-1/2"± RIGID INSULATION) AND TAPERED RIGID BASE LAYER ROOF
INSULATION OVER EXISTING METAL ROOF DECK/STRUCTURE TO REMAIN.
REMOVE EPDM ROOF MEMBRANE, 2"± THICK COMPOSITE INSULATION BOARD (1/2"± OSB
COVERBOARD AND 1-1/2"± RIGID INSULATION) AND 2"± RIGID BASE LAYER ROOF INSULATION
OVER EXISTING SLOPED METAL ROOF DECK/STRUCTURE TO REMAIN.
REMOVE GUTTER AND DOWNSPOUT.
REMOVE METAL ROOF FASCIA/DRIP EDGE.
REMOVE ROOF DRAIN.
REMOVE EPDM WALL FLASHING.
REMOVE SCUPPER FLASHING.
REMOVE MEMBRANE WALKWAY PADS.
EXISTING EXHAUST FAN CURB TO REMAIN. REMOVE MEMBRANE FLASHING FROM CURB.
F5 REMOVALS SOUTH ELEVATION
SCALE: 1/8"=1'-0"
D5 REMOVALS PARTIAL EAST ELEVATION
SCALE: 1/8"=1'-0"D2 REMOVALS EAST ELEVATION
SCALE: 1/8"=1'-0"
C5 REMOVALS NORTH ELEVATION
SCALE: 1/8"=1'-0"
A2 REMOVALS WEST ELEVATION
SCALE: 1/8"=1'-0" A5 REMOVALS PARTIAL WEST ELEVATION
SCALE: 1/8"=1'-0" A8 REMOVALS PARTIAL WEST ELEVATION
SCALE: 1/8"=1'-0"
'-4
'-0
'-4
'-4
8'-
0"
'-4
'-4
'-0
'-4
2'- 5"
'-4
'-4
'-0
'-4
'-4
'-4
'-4
8'-
0"
'-4
'-4
'-4
'-0
'-4
'-4
8'-
0"
'-4
120 112
FIRST FLOOR
ELEV = 24.00'±
SECOND FLOOR
ELEV = 34.00'±
FIRST FLOOR
ELEV = 26.50'±
SECOND FLOOR
ELEV = 36.50'±
FIRST FLOOR
ELEV = 24.00'±
SECOND FLOOR
ELEV = 34.00'±
FIRST FLOOR
ELEV = 26.50'±
FIRST FLOOR
ELEV = 24.00'±
SECOND FLOOR
ELEV = 34.00'±
FIRST FLOOR
ELEV = 26.50'±
SECOND FLOOR
ELEV = 36.50'±
FIRST FLOOR
ELEV = 26.50'±
SECOND FLOOR
ELEV = 36.50'±
FIRST FLOOR
ELEV = 26.50'±
SECOND FLOOR
ELEV = 36.50'±
EXIST MTL WALL
PANEL WINDOW INFILL
EXIST MTL WALL
PANEL WINDOW INFILL
EXIST MTL LOUVER EXIST MTL LOUVER
EXIST MTL LOUVER
EXIST ROOF TOP
MECH EQUIP
EXIST ROOF TOP
MECH EQUIP
EXIST ROOF TOP
MECH EQUIP
EXIST ROOF TOP
MECH EQUIP
EXIST ROOF TOP
MECH EQUIP
EXIST ROOF TOP
MECH EQUIP
EXIST ROOF TOP
MECH EQUIP
EXIST ROOF TOP
MECH EQUIP
EXIST ROOF TOP
MECH EQUIP
EXIST ROOF TOP
MECH EQUIP
EXIST PLUMB
VENT (TYP)
EXIST PLUMB
VENT (TYP)
EXIST PLUMB
VENT (TYP)
EXIST WALL MOUNTED
SIGNAGE (TYP)
EXIST WALL MOUNTED
SIGNAGE (TYP)
1111 1 1 1
1 1 311
1 1 1 1 1 1 2
55 5 5
2 4 554
4 5 5 4 4 4
6 121
111 11 1 1
14 2
45 5 45
1 11 1 1 4554
M
AJ
OR
M
&R B
AR
RA
CK
S/
GA
LL
EY
B
UI
LD
IN
G
SF
O
SO
UT
HW
ES
T
HA
RB
OR
SO
UT
HW
ES
T
HA
RB
OR
M E
AR
CH
IT
EC
TU
RA
L
RE
M
OV
AL
S
EL
EV
AT
IO
NS
BARRACKS/
GALLEY
BUILDING
AD201
P2
P2
3A D2
.D
W G
US
CG
C
IV
IL
E
NG
IN
EE
RI
NG
U
NI
T
PR
OV
ID
EN
CE
KI
LV
ER
T
ST
, S
UI
TE
W
AR
W
IC
K, R I 0
DA
VI
D M
IL
ES
JM
c
CR
R
CR
R
KP
OA
K
PO
IN
T
AS
SO
CI
AT
ES
M
AI
N
ST
RE
ET
, B
ID
DE
FO
RD
, M
E
(2
) 2
-0
0.
IS
SU
E
FO
R
BI
D
FE
B
9, US COAST GUARD
CIVIL ENGINEERING
N/A N/A
DE
SI
GN
ED
B Y:
DE
SC
RI
PT
IO
N
M
AR
K
ED
IT
ED
B Y:
DA
TE
CH
EC
KE
D
BY
DR
AW
N
BY
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A
SH
EE
T
OF
US
CG
P
RO
JE
CT
N
UM
BE
R
US
CG
F
IL
EN
AM
E
A/ E
CO
M
PA
NY
CO
NS
UL
TI
NG
A
/E
US
CG
P
RO
JE
CT
M
AN
AG
ER
A/
E
PR
OJ
EC
T
NO
SHEET ID
M
EA
SU
RE
M
EN
T
BA
R:
1"
HA
LF
S
IZ
E
1/ 2"
US
CG
D
RA
W
IN
G
SE
RI
ES
N
UM
BE
R
SOLICITATION NO.: CONTRACT NO.:
GRAPHIC SCALE
0 8'4' 16'
CHECK GRAPHIC SCALE BEFORE USING
1/8" = 1'-0"
GENERAL SHEET NOTES
1. ITEMS ON THIS SHEET ARE EXISTING UNLESS NOTED OTHERWISE.
2. REFER TO SHEET G-002 FOR ADDITIONAL GENERAL REMOVALS NOTES.
3. THE CONTRACTOR MUST MAINTAIN BUILDING SECURITY, ACCESS AND INTERIOR INTEGRITY
THROUGHOUT THE PROJECT.
4. EXISTING FENCE AND MECHANICAL UNIT AT EAST ELEVATION NOT SHOWN FOR CLARITY.
SHEET KEYNOTES
BASE BID KEYNOTES
REMOVE WINDOW AND VINYL/PVC WINDOW TRIM.
REMOVE HOLLOW METAL DOOR, FRAME, AND HARDWARE.
REMOVE ALUMINUM STOREFRONT ENTRY SYSTEM, ALUMINUM DOOR, AND HARDWARE.
REMOVE METAL ROOF FASCIA/DRIP EDGE.
REMOVE GUTTER AND DOWNSPOUT.
REMOVE HOLLOW METAL DOOR AND DOOR HARDWARE. EXISTING HOLLOW METAL DOOR
FRAME TO REMAIN.
REMOVE SCUPPER FLASHING AND TRIM.
F5 REMOVALS SOUTH ELEVATION - OPTION BID ITEM (OBI #1A & #1B)
SCALE: 1/8"=1'-0"
D5 OPTION BID ITEM (OBI #1A & #1B)
REMOVALS PARTIAL EAST ELEVATION -
SCALE: 1/8"=1'-0"D2 REMOVALS EAST ELEVATION - OPTION BID ITEM (OBI #1A & #1B)
SCALE: 1/8"=1'-0"
C5 REMOVALS NORTH ELEVATION - OPTION BID ITEM (OBI #1A & #1B)
SCALE: 1/8"=1'-0"
A2 REMOVALS WEST ELEVATION - OPTION BID ITEM (OBI #1A & #1B)
SCALE: 1/8"=1'-0" A5 OPTION BID ITEM (OBI #1A & #1B)
REMOVALS PARTIAL WEST ELEVATION -
SCALE: 1/8"=1'-0" A8 OPTION BID ITEM (OBI #1A & #1B)
REMOVALS PARTIAL WEST ELEVATION -
SCALE: 1/8"=1'-0"
'-4
'-0
'-4
'-4
8'-
0"
'-4
'-4
'-0
'-4
2'- 5"
'-4
'-4
'-0
'-4
'-4
'-4
'-4
8'-
0"
'-4
'-4
'-0
'-4
'-4
'-0
'-4
'-4
8'-
0"
'-4
120 112
FIRST FLOOR
ELEV = 24.00'±
SECOND FLOOR
ELEV = 34.00'±
FIRST FLOOR
ELEV = 26.50'±
SECOND FLOOR
ELEV = 36.50'±
FIRST FLOOR
ELEV = 24.00'±
SECOND FLOOR
ELEV = 34.00'±
FIRST FLOOR
ELEV = 26.50'±
FIRST FLOOR
ELEV = 24.00'±
SECOND FLOOR
ELEV = 34.00'±
FIRST FLOOR
ELEV = 26.50'±
SECOND FLOOR
ELEV = 36.50'±
FIRST FLOOR
ELEV = 26.50'±
SECOND FLOOR
ELEV = 36.50'±
FIRST FLOOR
ELEV = 26.50'±
SECOND FLOOR
ELEV = 36.50'±
EXIST MTL WALL
PANEL WINDOW INFILL
EXIST MTL WALL
PANEL WINDOW INFILL
EXIST MTL LOUVER EXIST MTL LOUVER
EXIST MTL LOUVER
EXIST ROOF TOP
MECH EQUIP
EXIST ROOF TOP
MECH EQUIP
EXIST ROOF TOP
MECH EQUIP
EXIST ROOF TOP
MECH EQUIP
EXIST ROOF TOP
MECH EQUIP
EXIST ROOF TOP
MECH EQUIP
EXIST ROOF TOP
MECH EQUIP
EXIST ROOF TOP
MECH EQUIP
EXIST ROOF TOP
MECH EQUIP
EXIST ROOF TOP
MECH EQUIP
EXIST PLUMB
VENT (TYP)
EXIST PLUMB
VENT (TYP)
EXIST PLUMB
VENT (TYP)
1 22
3 3
32 3
5 5
5 5
6 6 6
77 7
8 88
M
AJ
OR
M
&R B
AR
RA
CK
S/
GA
LL
EY
B
UI
LD
IN
G
SF
O
SO
UT
HW
ES
T
HA
RB
OR
SO
UT
HW
ES
T
HA
RB
OR
M E
AR
CH
IT
EC
TU
RA
L
RE
MO
VA
LS
EL
EV
AT
IO
NS
- O
PT
IO
N
BID
IT
EM
BARRACKS/
GALLEY
BUILDING
AD202
P2
P2
3A D2
.D
W G
US
CG
C
IV
IL
E
NG
IN
EE
RI
NG
U
NI
T
PR
OV
ID
EN
CE
KI
LV
ER
T
ST
, S
UI
TE
W
AR
W
IC
K, R I 0
DA
VI
D M
IL
ES
JM
c
CR
R
CR
R
KP
OA
K
PO
IN
T
AS
SO
CI
AT
ES
M
AI
N
ST
RE
ET
, B
ID
DE
FO
RD
, M
E
(2
) 2
-0
0.
IS
SU
E
FO
R
BI
D
FE
B
9, US COAST GUARD
CIVIL ENGINEERING
N/A N/A
DE
SI
GN
ED
B Y:
DE
SC
RI
PT
IO
N
M
AR
K
ED
IT
ED
B Y:
DA
TE
CH
EC
KE
D
BY
DR
AW
N
BY
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A
SH
EE
T
OF
US
CG
P
RO
JE
CT
N
UM
BE
R
US
CG
F
IL
EN
AM
E
A/ E
CO
M
PA
NY
CO
NS
UL
TI
NG
A
/E
US
CG
P
RO
JE
CT
M
AN
AG
ER
A/
E
PR
OJ
EC
T
NO
SHEET ID
M
EA
SU
RE
M
EN
T
BA
R:
1"
HA
LF
S
IZ
E
1/ 2"
US
CG
D
RA
W
IN
G
SE
RI
ES
N
UM
BE
R
SOLICITATION NO.: CONTRACT NO.:
GRAPHIC SCALE
0 8'4' 16'
CHECK GRAPHIC SCALE BEFORE USING
1/8" = 1'-0"
1. ITEMS ON THIS SHEET ARE EXISTING UNLESS NOTED OTHERWISE.
2. REFER TO REMOVALS ELEVATIONS ON SHEET AD201 FOR REMOVALS PERFORMED UNDER
BASE BID.
3. REFER TO SHEET G-002 FOR ADDITIONAL GENERAL REMOVALS NOTES.
4. THE CONTRACTOR MUST MAINTAIN BUILDING SECURITY, ACCESS AND INTERIOR INTEGRITY
THROUGHOUT THE PROJECT.
5. EXISTING FENCE AND MECHANICAL UNIT AT EAST ELEVATION NOT SHOWN FOR CLARITY.
SHEET KEYNOTES
OPTION BID ITEMS (OBI #1A AND OBI #1B) KEYNOTES
TEMPORARILY SUPPORT EXISTING SECURITY CAMERA, CONDUIT, AND JUNCTION BOX.
DISCONNECT, REMOVE, AND STORE FOR REINSTALLATION EXISTING WALL MOUNTED LIGHT
FIXTURE.
REMOVE AND STORE FOR REINSTALLATION EXISTING WALL MOUNTED SIGNAGE.
REMOVE AND STORE FOR REINSTALLATION EXISTING METAL ROOF ACCESS LADDER.
REMOVE VINYL SHINGLE SIDING AND 2"± COMPOSITE INSULATION BOARD (1/2" OSB SHEATHING
AND 1-1/2" RIGID INSULATION) MECHANICALLY FASTENED TO EXISTING MASONRY WALL.
REMOVE VINYL CORNER TRIM BOARD.
REMOVE VINYL WINDOW AND DOOR CASING/TRIM.
REMOVE PVC SKIRT BOARD.
GENERAL SHEET NOTES
C4 FIRST FLOOR PLAN
'-4
172'-4"±
50'-11 5/8"± 97'-0 3/8"± 24'-4"±
8'-0 3/8"± 7'-11"± 15'-0"± 15'-6"± 15'-0"± 35'-7"±
'-8
'-4
'-0
'-4
50'-0"± 93'-4"± 29'-0"±
22'-4 3/8"± 15'-0"± 14'-6"± 15'-0"± 8'-6"± 8'-0"±8'-4"±
1'-7 5/8"±
19'-8"±30'-4"±
8'- 8"
8'- 8"
6'- 0"
'-0
7'- 6"
3'- 0"
'-4
'-0
2'- 6"
3'-0"±
F5 A-201
C5 A-201
A2 A-201 D2
A-201
111111222
4 444
1 1 1 1
1A
2 12
117 122
A5 A-201
A5 A-201
A8 A-201
A8 A-201
D5 A-201
D5 A-201
OFFICE
MEDICAL
ROOM
EXERCISE
TOILET
STORAGE
TOILET
STORAGE
STAIR
HALL/
CORR
TOILET
BEDROOM
BEDROOM
STORAGE
CLOSET
121A
TOILET
STORAGE
LAUNDRY
ROOM
BOILER
FURNACE
TOILET
LOUNGE
CORRIDOR
BEDROOM
BEDROOM
TOILET
TOILET
TOILET
TOILET
STAIR 2
CLOSET
139A
STAIR 1
CLOSET
TOILET
LOBBY
VESTIBULE
OFFICE
STORAGE
DRY
STORAGE
GALLEY
DINING AREA
ENTRY
1 1
1 1 11
2 3 2 3 2 3 2 3 2 3
2 3
2 3
2 3
2 3
2 3
2 32 32 3
2 3
7 3
7 3
7 3 7 3
2 3
2 3
2 3
2 3 2 3
2 3
100100 100200 200200
NORTH
PLAN
TRUE N
ROOM
SERVER
LOCKER RM
MORALE
BEDROOM
BEDROOM
SPRINKLER
FIRE
REFRIGERATOR
FREEZER
106A
EXIST MTL FENCE
EXIST MECH UNIT
M
AJ
OR
M
&R B
AR
RA
CK
S/
GA
LL
EY
B
UI
LD
IN
G
SF
O
SO
UT
HW
ES
T
HA
RB
OR
SO
UT
HW
ES
T
HA
RB
OR
M E
AR
CH
IT
EC
TU
RA
L
FI
RS
T
FL
OO
R
PL
AN
BARRACKS/
GALLEY
BUILDING
A-101
P2
P2
3A -1
.D
W G
US
CG
C
IV
IL
E
NG
IN
EE
RI
NG
U
NI
T
PR
OV
ID
EN
CE
KI
LV
ER
T
ST
, S
UI
TE
W
AR
W
IC
K, R I 0
DA
VI
D M
IL
ES
JM
c
CR
R
CR
R
KP
OA
K
PO
IN
T
AS
SO
CI
AT
ES
M
AI
N
ST
RE
ET
, B
ID
DE
FO
RD
, M
E
(2
) 2
-0
0.
IS
SU
E
FO
R
BI
D
FE
B
9, US COAST GUARD
CIVIL ENGINEERING
N/A N/A
DE
SI
GN
ED
B Y:
DE
SC
RI
PT
IO
N
M
AR
K
ED
IT
ED
B Y:
DA
TE
CH
EC
KE
D
BY
DR
AW
N
BY
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A
SH
EE
T
OF
US
CG
P
RO
JE
CT
N
UM
BE
R
US
CG
F
IL
EN
AM
E
A/ E
CO
M
PA
NY
CO
NS
UL
TI
NG
A
/E
US
CG
P
RO
JE
CT
M
AN
AG
ER
A/
E
PR
OJ
EC
T
NO
SHEET ID
M
EA
SU
RE
M
EN
T
BA
R:
1"
HA
LF
S
IZ
E
1/ 2"
US
CG
D
RA
W
IN
G
SE
RI
ES
N
UM
BE
R
SOLICITATION NO.: CONTRACT NO.:
GRAPHIC SCALE
0 8'4' 16'
CHECK GRAPHIC SCALE BEFORE USING
1/8" = 1'-0"
GENERAL SHEET NOTES
1. VERIFY IN FIELD EXISTING CONDITIONS.
2. REFER TO SHEET G-002 FOR ADDITIONAL GENERAL REMOVALS NOTES.
3. THE CONTRACTOR MUST MAINTAIN BUILDING SECURITY, ACCESS AND INTERIOR INTEGRITY
THROUGHOUT THE PROJECT.
4. SEE SHEETS A-201 AND A-202 FOR WALL MOUNTED ITEMS THAT WILL BE REMOVED AND
REINSTALLED.
5. REFER TO SHEET A-601 FOR DOOR SCHEDULE, DOOR TYPES, DOOR FRAME TYPES, AND
DETAILS.
6. REFER TO SHEET A-601 FOR WINDOW TYPES.
SHEET KEYNOTES
BASE BID KEYNOTES
DOUBLE-HUNG, HURRICANE RATED, ALUMINUM CLAD, WOOD WINDOW. VERIFY ROUGH
OPENING SIZE IN FIELD.
INTERIOR WOOD WINDOW TRIM AND WINDOW STOOL. PAINT TO MATCH EXISTING.
WINDOW MINI BLIND. VERIFY WINDOW OPENING IN FIELD.
INSULATED HOLLOW METAL DOOR, HOLLOW METAL FRAME, AND HARDWARE.
ALUMINUM STOREFRONT ENTRANCE SYSTEM, ALUMINUM DOOR, AND HARDWARE.
INSULATED HOLLOW METAL DOOR AND DOOR HARDWARE IN EXISTING HOLLOW METAL DOOR
FRAME. PREP AND PAINT EXISTING DOOR FRAME.
REINSTALL EXISTING STAINED, WOOD TRIM/WINDOW OPENING INFILL TO MATCH EXISTING.
REFINISH AS REQUIRED TO MATCH EXISTING FINISH.
OPTION BID ITEMS #1A
SELF-ADHERED WEATHER BARRIER, EXTERIOR VINYL SHINGLE SIDING, VINYL CORNER
BOARDS, VINYL WINDOW TRIM, AND PVC SKIRT BOARD. REFER TO SHEET A-501 FOR WALL
DETAILS.
OPTION BID ITEMS #1B
SELF-ADHERED WEATHER BARRIER, EXTERIOR FIBER-CEMENT SHINGLE SIDING, PVC
CORNER BOARDS, PVC WINDOW AND DOOR CASING/TRIM, AND PVC SKIRT BOARD. REFER TO
SHEET A-501 FOR WALL DETAILS.
C4 SECOND FLOOR PLAN
C5 A-201
A2 A-201 49
'-6
11111
111111
4 4
444 4
122'-4"±
98'-0"± 24'-4"±
9'-0"± 7'-11"± 15'-0"± 15'-6"± 15'-0"± 35'-7"±
'-8
'-4
'-0
'-4
93'-4"± 29'-0"±
22'-4 3/8"± 15'-0"± 14'-6"± 15'-0"± 8'-6"± 8'-0"±8'-4"±
1'-7 5/8"±
F5 A-201
D2 A-201
'-4
8'- 8"
'-1 0"
'-0
3'- 0"
'-1 0"
A5 A-201
A5 A-201
A8 A-201
A8 A-201
TOILET
TOILET
TOILET
TOILET
TOILET
TOILET
TOILET
TOILET
TOILET
BEDROOM
BEDROOM
BEDROOM
BEDROOM
BEDROOM
BEDROOM
BEDROOM
BEDROOM
BEDROOM
ROOM
EQUIPMENT
STAIR 1
STAIR 2
STORAGE
TOILET
CORR
ROOM
EXERCISE
TOILET
228 TOILET
OFFICE
CORRIDOR
11 111 1
1 1 11
2 3 2 3 2 3 2 3 2 3
2 3
2 3
2 3
2 3
2 3
2 32 32 3
2 3
2 32 3
12 3
2 3 2 3
1 1
1 1
2 32 3
2 3
2 3
100 100
200200
NORTH
PLAN
TRUE N
KITCHENETTE
LOUNGE
UPH
SOLICITATION NO.: CONTRACT NO.:
M
AJ
OR
M
&R B
AR
RA
CK
S/
GA
LL
EY
B
UI
LD
IN
G
SF
O
SO
UT
HW
ES
T
HA
RB
OR
SO
UT
HW
ES
T
HA
RB
OR
M E
AR
CH
IT
EC
TU
RA
L
SE
CO
ND
F
LO
OR
P
LA
N
BARRACKS/
GALLEY
BUILDING
A-102
P2
P2
3A -1
.D
W G
US
CG
C
IV
IL
E
NG
IN
EE
RI
NG
U
NI
T
PR
OV
ID
EN
CE
KI
LV
ER
T
ST
, S
UI
TE
W
AR
W
IC
K, R I 0
DA
VI
D M
IL
ES
JM
c
CR
R
CR
R
KP
OA
K
PO
IN
T
AS
SO
CI
AT
ES
M
AI
N
ST
RE
ET
, B
ID
DE
FO
RD
, M
E
(2
) 2
-0
0.
IS
SU
E
FO
R
BI
D
FE
B
9, US COAST GUARD
CIVIL ENGINEERING
N/A N/A
DE
SI
GN
ED
B Y:
DE
SC
RI
PT
IO
N
M
AR
K
ED
IT
ED
B Y:
DA
TE
CH
EC
KE
D
BY
DR
AW
N
BY
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A
SH
EE
T
OF
US
CG
P
RO
JE
CT
N
UM
BE
R
US
CG
F
IL
EN
AM
E
A/ E
CO
M
PA
NY
CO
NS
UL
TI
NG
A
/E
US
CG
P
RO
JE
CT
M
AN
AG
ER
A/
E
PR
OJ
EC
T
NO
SHEET ID
M
EA
SU
RE
M
EN
T
BA
R:
1"
HA
LF
S
IZ
E
1/ 2"
US
CG
D
RA
W
IN
G
SE
RI
ES
N
UM
BE
R
GRAPHIC SCALE
0 8'4' 16'
CHECK GRAPHIC SCALE BEFORE USING
1/8" = 1'-0"
GENERAL SHEET NOTES
SHEET KEYNOTES##
1. VERIFY IN FIELD EXISTING CONDITIONS.
2. REFER TO SHEET G-002 FOR ADDITIONAL GENERAL REMOVALS NOTES.
3. THE CONTRACTOR MUST MAINTAIN BUILDING SECURITY, ACCESS AND INTERIOR INTEGRITY
THROUGHOUT THE PROJECT.
4. SEE SHEETS A-200 AND A-202 FOR WALL MOUNTED ITEMS THAT WILL BE REMOVED AND
REINSTALLED.
5. REFER TO SHEET A-601 FOR DOOR SCHEDULE, DOOR TYPES, DOOR FRAME TYPES, AND
DETAILS.
6. REFER TO SHEET A-601 FOR WINDOW TYPES.
BASE BID KEYNOTES
DOUBLE-HUNG, HURRICANE RATED, ALUMINUM CLAD, WOOD WINDOW. VERIFY ROUGH
OPENING SIZE IN FIELD.
INTERIOR WOOD WINDOW TRIM AND WINDOW STOOL. PAINT TO MATCH EXISTING.
WINDOW MINI BLIND. VERIFY WINDOW OPENING IN FIELD.
INSULATED HOLLOW METAL DOOR, HOLLOW METAL FRAME, AND HARDWARE.
REATTACH EXISTING VINYL SIDING BELOW SECOND FLOOR WINDOW.
OPTION BID ITEMS #1A
SELF-ADHERED WEATHER BARRIER, EXTERIOR VINYL SHINGLE SIDING, VINYL CORNER
BOARDS, VINYL WINDOW TRIM, AND PVC SKIRT BOARD. REFER TO SHEET A-501 FOR WALL
DETAILS.
OPTION BID ITEMS #1B
SELF-ADHERED WEATHER BARRIER, EXTERIOR FIBER-CEMENT SHINGLE SIDING, PVC
CORNER BOARDS, PVC WINDOW AND DOOR CASING/TRIM, AND PVC SKIRT BOARD. REFER TO
SHEET A-501 FOR WALL DETAILS.
D4 ROOF PLAN
'-4
172'-4"±
50'-11 5/8"± 97'-0 3/8"± 24'-4"±
8'-2 3/8"± 7'-9"± 15'-0"± 15'-6"± 15'-0"± 35'-7"±
'-8
'-4
'-0
'-4
50'-0"± 93'-4"± 29'-0"±
22'-4 3/8"± 15'-0"± 14'-6"± 15'-0"± 8'-4"± 8'-2"±8'-4"±
1'-7 5/8"±
19'-8"±30'-4"±
8'- 8"
8'- 8"
'-0
7'- 6"
3'- 0"
'-4
'-0
2'- 6"
3'-0"±
'-1
0"
3 3
4 6
4 7
(TYP)
(TYP)
9 9
NORTH
PLAN
TRUE N
B1 A-501
(SIM)
B1 A-501
(SIM)
F1 A-501
(TYP)
F1 A-501
(TYP)
B1 A-501
(SIM)
B1
A-501(SIM)
B1 A-501
(TYP)
B1 A-501
(TYP)
B1 A-501
(TYP)
F1,D1 A-501
(TYP)
F1,D1 A-501
(TYP)
B1 TYPICAL ROOF SYSTEM DETAIL
SCALE: 1-1/2"=1'-0"
FULLY ADHERED TPO
ROOF MEMBRANE
1/2" HIGH-DENSITY POLY
ISO COVER BOARD
BASE LAYER, 1" RIGID
ROOF INSUL
VAPOR BARRIER
EXIST MTL ROOF
DECK
1/4" GLASS-MAT GYPSUM
SUBSTRATE BOARD
TAPERED RIGID ROOF
INSUL
SLOPE
1/4"/1'-0"
A1 TYP MECH EQUIPMENT CURB DETAIL
SCALE: 1-1/2"=1'-0"
B2 TYPICAL VENT PIPE FLASHING DETAIL
SCALE: 1-1/2"=1'-0"
A2 TYPICAL ROOF DRAIN DETAIL
SCALE: 1-1/2"=1'-0"
TYP ROOF SYS, SEE
DETAIL B1/A-120
CONT SEALANT
PRE-MOLDED
MEMBRANE FLASHING
BOOT
EXIST 3-1/2"± DIA PLUMB
VENT PIPE
WATER CUTOFF
MASTIC
CLAMPING RING
TYP ROOF SYS, SEE
DETAIL B1/A-120
CONT SEALANT
EXIST EQUIP CURB
FASTENER & PLATE PER
ROOFING MFR'S
RECOMMENDATION
TPO MEMBRANE
FLASHING
REINSTALL EXIST MECH
EXHAUST FAN
EXIST MTL SUPPORT
ANGLE
2'-0" 2'-0"
CL
EXIST ROOF DRAIN
PROVIDE 1'-0"± DIA ROOF
DRAIN COVER TO MATCH
EXIST
EXIST CLAP RING &
MTL ANGLE
2x WD BLOCKING
EXIST 4"± DIA ROOF
DRAIN LEADER
TYP ROOF SYS, SEE
DETAIL B1/A-120
EXIST MTL ANGLE
RIGID INSUL CANT B5 TYPICAL ROOF EDGE DETAIL
SCALE: 3"=1'-0"
TYP ROOF SYS, SEE
DETAIL B1/A-120
WOOD BLOCKING
W/ PLYWD FILLER
CONT SEALANT
EXIST CONC
2x12 PT WD
MTL FASCIA &
MTL CLEAT
1'- 0"
8" 4"
SLOPE
1/4"/1'-0"
B7 TYPICAL PARAPET ROOF EDGE DETAIL
SCALE: 3"=1'-0"
SLOPE
1/4"/1'-0"
1'- 0"
8" 4"
TYP ROOF SYS, SEE
DETAIL B1/A-120
WOOD BLOCKING
W/ PLYWD FILLER
CONT SEALANT
EXIST CMU
MTL FASCIA &
MTL CLEAT
TPO FLASHING
& LAP SEALANT
(2) 2x12 PT WD
MTL FASCIA &
MTL CLEAT
EXIST VINYL
BLOCKING
SIDING
EXIST VINYL
SIDING
BLOCKING
BEAM
MTL FASCIA &
MTL CLEAT
TPO FLASHING
& LAP SEALANT
TPO MEMBRANE
M
AJ
OR
M
&R B
AR
RA
CK
S/
GA
LL
EY
B
UI
LD
IN
G
SF
O
SO
UT
HW
ES
T
HA
RB
OR
SO
UT
HW
ES
T
HA
RB
OR
M E
AR
CH
IT
EC
TU
RA
L
RO
OF
P
LA
N
AN
D
DE
TA
IL
S
BARRACKS/
GALLEY
BUILDING
A-120
P2
P2
3A -1
.D
W G
US
CG
C
IV
IL
E
NG
IN
EE
RI
NG
U
NI
T
PR
OV
ID
EN
CE
KI
LV
ER
T
ST
, S
UI
TE
W
AR
W
IC
K, R I 0
DA
VI
D M
IL
ES
JM
c
CR
R
CR
R
KP
OA
K
PO
IN
T
AS
SO
CI
AT
ES
M
AI
N
ST
RE
ET
, B
ID
DE
FO
RD
, M
E
(2
) 2
-0
0.
IS
SU
E
FO
R
BI
D
FE
B
9, US COAST GUARD
CIVIL ENGINEERING
N/A N/A
DE
SI
GN
ED
B Y:
DE
SC
RI
PT
IO
N
M
AR
K
ED
IT
ED
B Y:
DA
TE
CH
EC
KE
D
BY
DR
AW
N
BY
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A
SH
EE
T
OF
US
CG
P
RO
JE
CT
N
UM
BE
R
US
CG
F
IL
EN
AM
E
A/ E
CO
M
PA
NY
CO
NS
UL
TI
NG
A
/E
US
CG
P
RO
JE
CT
M
AN
AG
ER
A/
E
PR
OJ
EC
T
NO
SHEET ID
M
EA
SU
RE
M
EN
T
BA
R:
1"
HA
LF
S
IZ
E
1/ 2"
US
CG
D
RA
W
IN
G
SE
RI
ES
N
UM
BE
R
SOLICITATION NO.: CONTRACT NO.:
GRAPHIC SCALES
0 8'4' 16'
CHECK GRAPHIC SCALES BEFORE USING
1/8" = 1'-0"
GENERAL SHEET NOTES
SHEET KEYNOTES
BASE BID KEYNOTES
FULLY ADHERED TPO ROOF MEMBRANE WITH 1/2" HIGH-DENSITY POLYISO FOAM COVER
BOARD, TAPERED RIGID POLYISO ROOF INSULATION (1/4" PER FOOT), POLYISO RIGID ROOF
BASE INSULATION, VAPOR BARRIER, AND 1/4" GLASS-MAT GYPSUM SUBSTRATE BOARD OVER
EXISTING METAL ROOF DECK/STRUCTURE. SEE DETAIL B1/A-120.
FULLY ADHERED TPO ROOF MEMBRANE WITH 1/2" HIGH-DENSITY POLYISO FOAM COVER
BOARD, RIGID POLYISO ROOF INSULATION, VAPOR BARRIER, AND 1/4" GLASS-MAT GYPSUM
SUBSTRATE BOARD OVER EXISTING SLOPED METAL ROOF DECK/STRUCTURE. SEE DETAIL
B1/AE120 (SIMILAR).
6" WIDE x 5" DEEP, METAL (K-STYLE PROFILE) GUTTER WITH CONTINUOUS LEAF SCREEN AND 2"x 3" RECTANGULAR METAL DOWNSPOUT WITH FASTENER STRAPS AT 8'-0" ON-CENTER. SEE
DETAIL F1/A-501.
METAL ROOF EDGE FASCIA SYSTEM. SEE DETAILS B5/A-120 AND B7/A-120.
TPO ROOF DRAIN FLASHING AND ROOF DRAIN INSERT AT EXISTING ROOF DRAIN LEADER. SEE
DETAIL A2/A-120.
TPO WALL FLASHING AND CONTINUOUS STAINLESS STEEL TERMINATION BAR. SEE DETAIL
D1/A-501.
TPO ROOF SCUPPER FLASHING AND METAL DRIP EDGE. SEE DETAIL A1/A-501.
MEMBRANE WALKWAY PADS.
TPO FLASHING AT EXISTING PLUMBING VENT PIPE. SEE DETAIL B2/A-120.
TPO MEMBRANE FLASHING AT EXISTING MECHANICAL EQUIPMENT CURB. SEE DETAIL
A1/A-120.
1' 2'0 6" 1-1/2" = 1'-0"
1. ITEMS ON THIS SHEET ARE EXISTING UNLESS NOTED OTHERWISE.
2. REFER TO SHEET G-002 FOR ADDITIONAL GENERAL REMOVALS NOTES.
3. THE CONTRACTOR MUST MAINTAIN BUILDING SECURITY, ACCESS AND INTERIOR INTEGRITY
THROUGHOUT THE PROJECT.
4. MAINTAIN AND PROTECT UTILITY CONDUITS AND ROOF TOP EQUIPMENT DURING
CONSTRUCTION.
5. THE ROOF ELEVATION OVER THE BEDROOM PORTION OF THE BUILDING IS APPROXIMATELY 24'-0"
ABOVE GRADE. THE ROOF ELEVATION OVER THE GALLEY AND DINING ROOM ROOF IS
APPROXIMATELY15'-0"ABOVE GRADE.
6"0 3" 1' 3" = 1'-0"
F5 SOUTH ELEVATION
D5 PARTIAL EAST ELEVATION
SCALE: 1/8"=1'-0"D2 EAST ELEVATION
SCALE: 1/8"=1'-0"
C5 NORTH ELEVATION
SCALE: 1/8"=1'-0"
A2 WEST ELEVATION
SCALE: 1/8"=1'-0" A5 PARTIAL WEST ELEVATION
SCALE: 1/8"=1'-0" A8 PARTIAL WEST ELEVATION
SCALE: 1/8"=1'-0"
'-4
'-0
'-4
'-4
8'-
0"
'-4
'-4
'-0
'-4
2'- 5"
'-4
'-4
'-0
'-4
'-4
'-4
'-4
8'-
0"
'-4
'-4
'-4
'-0
'-4
'-4
8'-
0"
'-4
111 139
120 112
1111 1 1 1
1 1 311
1 1 1 1 1 1 2
57 5 5
2 4 554
4 5 5 4 4 4
6 121
111 11 1 1
14 2
45 5 45
1 11 1 1 4554
1 1 1
111 1 1
1 1
5 6 7
1 1 1
1 1 1 1
1 3
2 2
4 4 4
FIRST FLOOR
ELEV = 24.00'±
SECOND FLOOR
ELEV = 34.00'±
FIRST FLOOR
ELEV = 26.50'±
SECOND FLOOR
ELEV = 36.50'±
FIRST FLOOR
ELEV = 24.00'±
SECOND FLOOR
ELEV = 34.00'±
FIRST FLOOR
ELEV = 26.50'±
FIRST FLOOR
ELEV = 24.00'±
SECOND FLOOR
ELEV = 34.00'±
FIRST FLOOR
ELEV = 26.50'±
SECOND FLOOR
ELEV = 36.50'±
FIRST FLOOR
ELEV = 26.50'±
SECOND FLOOR
ELEV = 36.50'±
FIRST FLOOR
ELEV = 26.50'±
SECOND FLOOR
ELEV = 36.50'±
EXIST MTL WALL
PANEL WINDOW INFILL
EXIST MTL WALL
PANEL WINDOW INFILL
EXIST MTL LOUVER EXIST MTL LOUVER
EXIST MTL LOUVER
EXIST ROOF TOP
MECH EQUIP
EXIST ROOF TOP
MECH EQUIP
EXIST ROOF TOP
MECH EQUIP
EXIST ROOF TOP
MECH EQUIP
EXIST ROOF TOP
MECH EQUIP
EXIST ROOF TOP
MECH EQUIP
EXIST ROOF TOP
MECH EQUIP
EXIST ROOF TOP
MECH EQUIP
EXIST ROOF TOP
MECH EQUIP
EXIST ROOF TOP
MECH EQUIP
EXIST PLUMB
VENT (TYP)
EXIST PLUMB
VENT (TYP)
EXIST PLUMB
VENT (TYP)
EXIST WALL MOUNTED
SIGNAGE (TYP)
EXIST WALL MOUNTED
SIGNAGE (TYP)
M
AJ
OR
M
&R B
AR
RA
CK
S/
GA
LL
EY
B
UI
LD
IN
G
SF
O
SO
UT
HW
ES
T
HA
RB
OR
SO
UT
HW
ES
T
HA
RB
OR
M E
AR
CH
IT
EC
TU
RA
L
EL
EV
AT
IO
NS
BARRACKS/
GALLEY
BUILDING
A-201
P2
P2
3A -2
.D
W G
US
CG
C
IV
IL
E
NG
IN
EE
RI
NG
U
NI
T
PR
OV
ID
EN
CE
KI
LV
ER
T
ST
, S
UI
TE
W
AR
W
IC
K, R I 0
DA
VI
D M
IL
ES
JM
c
CR
R
CR
R
KP
OA
K
PO
IN
T
AS
SO
CI
AT
ES
M
AI
N
ST
RE
ET
, B
ID
DE
FO
RD
, M
E
(2
) 2
-0
0.
IS
SU
E
FO
R
BI
D
FE
B
9, US COAST GUARD
CIVIL ENGINEERING
N/A N/A
DE
SI
GN
ED
B Y:
DE
SC
RI
PT
IO
N
M
AR
K
ED
IT
ED
B Y:
DA
TE
CH
EC
KE
D
BY
DR
AW
N
BY
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A
SH
EE
T
OF
US
CG
P
RO
JE
CT
N
UM
BE
R
US
CG
F
IL
EN
AM
E
A/ E
CO
M
PA
NY
CO
NS
UL
TI
NG
A
/E
US
CG
P
RO
JE
CT
M
AN
AG
ER
A/
E
PR
OJ
EC
T
NO
SHEET ID
M
EA
SU
RE
M
EN
T
BA
R:
1"
HA
LF
S
IZ
E
1/ 2"
US
CG
D
RA
W
IN
G
SE
RI
ES
N
UM
BE
R
SOLICITATION NO.: CONTRACT NO.:
GRAPHIC SCALE
0 8'4' 16'
CHECK GRAPHIC SCALE BEFORE USING
1/8" = 1'-0"
GENERAL SHEET NOTES
SHEET KEYNOTES
BASE BID KEYNOTES
DOUBLE-HUNG, HURRICANE RATED, ALUMINUM CLAD, WOOD WINDOW. VERIFY IN FIELD ROUGH
OPENING SIZE.
INSULATED HOLLOW METAL DOOR, HOLLOW METAL FRAME, AND HARDWARE.
ALUMINUM STOREFRONT ENTRY SYSTEM, ALUMINUM DOOR, AND HARDWARE.
METAL ROOF EDGE FASCIA SYSTEM WITH WOOD BLOCKING AS REQUIRED.
6" WIDE x 5" DEEP, METAL (K-STYLE PROFILE) GUTTER WITH CONTINUOUS LEAF SCREEN AND 2"x 3"
RECTANGULAR METAL DOWNSPOUT WITH FASTENER STRAPS AT 8'-0" ON-CENTER.
INSULATED HOLLOW METAL DOOR AND DOOR HARDWARE IN EXISTING HOLLOW METAL DOOR FRAME.
PREP AND PAINT EXISTING DOOR FRAME.
REATTACH EXISTING VINYL SIDING BELOW SECOND FLOOR WINDOW AT PARTIAL EAST ELEVATION.
SCUPPER FLASHING AND SCUPPER BOX.
1. VERIFY IN FIELD EXISTING CONDITIONS.
2. REFER TO SHEET G-002 FOR ADDITIONAL GENERAL REMOVALS NOTES.
3. THE CONTRACTOR MUST MAINTAIN BUILDING SECURITY, ACCESS AND INTERIOR INTEGRITY
THROUGHOUT THE PROJECT.
4. REFER TO SHEET A-601 FOR DOOR SCHEDULE, DOOR TYPES, DOOR FRAME TYPES, AND DETAILS.
5. REFER TO SHEET A-601 FOR WINDOW TYPES.
6. EXISTING FENCE AND MECHANICAL UNIT AT EAST ELEVATION NOT SHOWN FOR CLARITY.
F5 SOUTH ELEVATION - OPTION BID ITEM (OBI #1A & #1B)
D5 PARTIAL EAST ELEVATION - OPTION BID ITEM (OBI #1A & #1B)
SCALE: 1/8"=1'-0"D2 EAST ELEVATION - OPTION BID ITEM (OBI #1A & #1B)
SCALE: 1/8"=1'-0"
C5 NORTH ELEVATION - OPTION BID ITEM (OBI #1A & #1B)
SCALE: 1/8"=1'-0"
A2 WEST ELEVATION - OPTION BID ITEM (OBI #1A & #1B)
SCALE: 1/8"=1'-0" A5 OPTION BID ITEM (OBI #1A & #1B)
PARTIAL WEST ELEVATION -
SCALE: 1/8"=1'-0" A8 OPTION BID ITEM (OBI #1A & #1B)
PARTIAL WEST ELEVATION -
SCALE: 1/8"=1'-0"
(TYP)
(TYP)
EXIST MTL LOUVER EXIST MTL LOUVER
EXIST MTL LOUVER
EXIST ROOF TOP
MECH EQUIP
EXIST ROOF TOP
MECH EQUIP
EXIST ROOF TOP
MECH EQUIP
EXIST ROOF TOP
MECH EQUIP
EXIST ROOF TOP
MECH EQUIP EXIST ROOF TOP
MECH EQUIP
EXIST ROOF TOP
MECH EQUIP
EXIST ROOF TOP
MECH EQUIP
EXIST ROOF TOP
MECH EQUIP
EXIST PLUMB
VENT (TYP)
EXIST PLUMB
VENT (TYP)
EXIST PLUMB
VENT (TYP)
(TYP)
(TYP)
(TYP)
(TYP) (TYP)
1 2
1 2
1 2
2 1 2
1 2
1 2 1 2
1 21 2
1 2
1 2
1 2
5 5
FIRST FLOOR
ELEV = 24.00'±
SECOND FLOOR
ELEV = 34.00'±
FIRST FLOOR
ELEV = 26.50'±
SECOND FLOOR
ELEV = 36.50'±
FIRST FLOOR
ELEV = 24.00'±
SECOND FLOOR
ELEV = 34.00'±
FIRST FLOOR
ELEV = 26.50'±
FIRST FLOOR
ELEV = 24.00'±
SECOND FLOOR
ELEV = 34.00'±
FIRST FLOOR
ELEV = 26.50'±
SECOND FLOOR
ELEV = 36.50'±
FIRST FLOOR
ELEV = 26.50'±
SECOND FLOOR
ELEV = 36.50'±
FIRST FLOOR
ELEV = 26.50'±
SECOND FLOOR
ELEV = 36.50'±
'-4
'-0
'-4
'-4
8'-
0"
'-4
'-9
'-0
'-4
'-4
'-4
'-0
'-4
'-4
'-4
'-4
8'-
0"
'-4
'-4
'-0
'-4
'-4
'-0
'-4
'-4
8'-
0"
'-4
120 112
222 1
1 1
11 1
6 7
2 2
4 4 4
172'-6"±
53'-2"±
6'-1"± 7'-7"±
'-4
53'-10"±
8'-10"± 8'-10"± 10'-0"±10'-4"±
53'-4"±
40'-6"±
172'-6"±
1 1
1 1
M
AJ
OR
M
&R B
AR
RA
CK
S/
GA
LL
EY
B
UI
LD
IN
G
SF
O
SO
UT
HW
ES
T
HA
RB
OR
SO
UT
HW
ES
T
HA
RB
OR
M E
AR
CH
IT
EC
TU
RA
L
EL
EV
AT
IO
NS
OP
TI
ON
B
ID
IT
EM
BARRACKS/
GALLEY
BUILDING
A-202
P2
P2
3A -2
.D
W G
US
CG
C
IV
IL
E
NG
IN
EE
RI
NG
U
NI
T
PR
OV
ID
EN
CE
KI
LV
ER
T
ST
, S
UI
TE
W
AR
W
IC
K, R I 0
DA
VI
D M
IL
ES
JM
c
CR
R
CR
R
KP
OA
K
PO
IN
T
AS
SO
CI
AT
ES
M
AI
N
ST
RE
ET
, B
ID
DE
FO
RD
, M
E
(2
) 2
-0
0.
IS
SU
E
FO
R
BI
D
FE
B
9, US COAST GUARD
CIVIL ENGINEERING
N/A N/A
DE
SI
GN
ED
B Y:
DE
SC
RI
PT
IO
N
M
AR
K
ED
IT
ED
B Y:
DA
TE
CH
EC
KE
D
BY
DR
AW
N
BY
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A
SH
EE
T
OF
US
CG
P
RO
JE
CT
N
UM
BE
R
US
CG
F
IL
EN
AM
E
A/ E
CO
M
PA
NY
CO
NS
UL
TI
NG
A
/E
US
CG
P
RO
JE
CT
M
AN
AG
ER
A/
E
PR
OJ
EC
T
NO
SHEET ID
M
EA
SU
RE
M
EN
T
BA
R:
1"
HA
LF
S
IZ
E
1/ 2"
US
CG
D
RA
W
IN
G
SE
RI
ES
N
UM
BE
R
SOLICITATION NO.: CONTRACT NO.:
GRAPHIC SCALE
0 8'4' 16'
CHECK GRAPHIC SCALE BEFORE USING
1/8" = 1'-0"
GENERAL SHEET NOTES
SHEET KEYNOTES
OPTION BID ITEMS KEYNOTES
OPTION BID ITEM #1A SELF-ADHERED WEATHER BARRIER, EXTERIOR VINYL SHINGLE SIDING, VINYL CORNER BOARDS, VINYL WINDOW TRIM, AND CELLULAR PVC SKIRT BOARD. REFER TO SHEET A-501
FOR WALL DETAILS.
OPTION BID ITEM #1B SELF-ADHERED WEATHER BARRIER, EXTERIOR FIBER-CEMENT SHINGLE SIDING, CELLULAR PVC CORNER BOARDS, CELLULAR PVC WINDOW AND DOOR CASING/TRIM, AND CELLULAR
PVC SKIRT BOARD. REFER TO SHEET A-501 FOR WALL DETAILS.
RECONNECT EXISTING SECURITY CAMERA, CONDUIT, AND JUNCTION BOX.
RECONNECT AND REINSTALL EXISTING WALL MOUNTED LIGHT FIXTURE.
REINSTALL EXISTING WALL MOUNTED SIGNAGE.
PREP, PAINT AND REINSTALL EXISTING METAL ROOF ACCESS LADDER.
1. VERIFY IN FIELD EXISTING CONDITIONS.
2. REFER TO ELEVATIONS ON SHEET A-201 FOR WORK PERFORMED UNDER BASE BID.
3. REFER TO SHEET G-002 FOR ADDITIONAL GENERAL REMOVALS NOTES.
4. THE CONTRACTOR MUST MAINTAIN BUILDING SECURITY, ACCESS AND INTERIOR INTEGRITY
THROUGHOUT THE PROJECT.
5. REFER TO SHEET A-601 FOR DOOR SCHEDULE, DOOR TYPES, DOOR FRAME TYPES, AND DETAILS.
6. REFER TO SHEET A-601 FOR WINDOW TYPES.
7. EXISTING FENCE AND MECHANICAL UNIT AT EAST ELEVATION NOT SHOWN FOR CLARITY.
F1 TYP ROOF EDGE DETAIL - BASE BID
SCALE: 1-1/2"=1'-0"
D1 TYP WALL FLASHING DETAIL - BASE BID
SCALE: 1-1/2"=1'-0"
8" (M
IN
EXIST BRICK & CMU WALL
EXIST CONC BEAM
EXIST VINYL SIDING
EXIST RIGID INSUL &
OSB SHEATHING
EXIST VINYL "J" CHANNEL
PNT EXPOSED BLOCKING
TO MATCH FLASHING
SLOPE
1/4"/1'-0"
TYP ROOF SYS, SEE
DETAIL B1/A-120
TYP ROOF SYS, SEE
DETAIL B1/A-120
EXIST BRICK & CMU WALL
EXIST RIGID INSUL &
OSB SHEATHING
EXIST VINYL SIDING
CONT MTL TERMINATION
BAR & FASTNERS
TPO MEMBRANE FLASHING
CONT SEALANT
FASTENER & PLATE PER ROOFING
MFR'S RECOMMENDATION
1/4" HIGH-DENSITY FOAM COVER BOARD
SLOPE
1/4"/1'-0"
TYP ROOF SYS, SEE
DETAIL B1/A-120SLOPE
1/4"/1'-0"
TYP ROOF SYS, SEE
DETAIL B1/A-120
F6 TYP ROOF EDGE DETAIL - OBI #1B
SCALE: 1-1/2"=1'-0"
EXIST BRICK & CMU WALL
EXIST CONC BEAM
CONT SEALANT
EXIST RIGID INSUL &
OSB SHEATHING
5/4 x 6 CELLULAR PVC TRIM BOARD
PNT EXPOSED BLOCKING
TO MATCH FLASHING
FIBER-CEMENT SIDING
SELF-ADHERED WEATHER BARRIER
E6 TYP WALL SECTION DETAIL - OBI #1B
SCALE: 1-1/2"=1'-0"
FIBER-CEMENT SHINGLE SIDING
TO MATCH…
This is the start of the file's text. The full file is on GovTribe.