This is a set of electrical drawings detailing upgrades to internal building transformers and disconnect switches at the USDA Agricultural Research Service Northwest Irrigation & Soils Research Laboratory in Kimberly, ID. The drawings include a project cover page, electrical site plan, and electrical single line diagrams showing both removal work and new work to be performed.

The drawings specify replacement of multiple transformers ranging from 9KVA to 75KVA across several buildings including the Main Building, Head House, Irrigation Lab, Vehicle Storage, and Greenhouse facilities. Key work includes removing existing floor and wall-mounted transformers while retaining primary/secondary conductors, installing new transformers with proper wall brackets and disconnect switches, replacing aluminum wiring with copper, and providing new bonding cables sized appropriately for each transformer capacity (#8AWG for 30KVA, #4AWG for 45KVA, #2AWG for 75KVA transformers). The drawings include detailed general notes about wire replacement requirements, grounding specifications, and working clearance requirements per NEC 110.26(A)(1).

View the file

Other files

Show all 15

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

REAL PROPERTY

USDA

SAFETY & HEALTH

AREA ENGINEER

DRAWN BY

CHECKED BY

DESIGNER

PROJECT MANAGER

EPM

PROJECT NO.

DATE

REV. DATE BY

SHEET

DESCRIPTION

Service Research Agricultural

USDA AGRICULTURAL RESEARCH

SERVICE

ELECTRICAL UPGRADE

3793 E 3600 N, KIMBERLY, ID

83341, USA

USDA AGRICULTURAL RESEARCH SERVICE

PROJECT II: INTERNAL BUILDING TRANSFORMERS AND DISCONNECT

SWITCHES

U S D A

OF

SEAL

4112 APR 2024

1555-00

J.ARMSTRONG

O.TRUJILLO

S.RASTKAR

B.SANTANA

E-000-B

SR04/12/24 ISSUED FOR CONSTRUCTION0

PROJECT COVER PAGE

PROJECT II: INTERNAL BUILDING TRANSFORMERS AND DISCONNECT SWITCHES

USDA-ARS NORTHWEST IRRIGATION & SOILS RESEARCH LAB

3793 EAST 3600 NORTH KIMBERLY, ID 83341-5076

DRAWING LIST

E-000-B PROJECT COVER PAGE

E-005 ELECTRICAL SITE PLAN

E-006 ELECTRICAL SINGLE LINE DIAGRAM - REMOVAL WORK

E-007 ELECTRICAL SINGLE LINE DIAGRAM - NEW WORK

N 3800 E

N

E

ID-50

W . F

LS

A

VE

E

85.7710"MAIN BUILDING (B1)

HEAD HOUSE (B2)

IR

RI

G

AT

IO

N

LA

B

(B 3)

VE

HI

CL

E

ST

O

RA

G

E (B

4)

SH

O

P

RE

PA

IR

A

ND

SE

RV

IC

ES

(B 5)

STORAGE BARN (B6)

O

LD

G

RE

EN

HO

US

E

NE

W

G

RE

EN

HO

US

E

AN

NE

X

12 April, 2024

ELECTRICAL SITE PLAN

E E

E

T

2 2

30KVA

45KVA

30KVA

45KVA9KVA

30KVA

75KVA

SCALE 1" = 400'

MAIN BUILDING (B1)

HEAD HOUSE (B2)

IR

RI

G

AT

IO

N

LA

B

(B 3)

VE

HI

CL

E

ST

O

RA

G

E (B

4)

SH

O

P

RE

PA

IR

A

ND

S

ER

VI

CE

S (B

5)

45KVA

STORAGE BARN (B6)

FUTURE

EXPANSION PROJECT

FUTURE AREA OF RENOVATION

NE

W

G

RE

EN

HO

US

E

O

LD

G

RE

EN

HO

US

E

AN

NE

X

45KVA

RM 122A

RM 136

RM 114

RM 113B

RM 124A

RM 210

RM 302

RM 401

30KVA 30KVA

75KVA

RM 501

T

T

T

TT

T

T

TTT

T

F

F

F

FF

F

F

RM 230 RM 210

GENERAL NOTES

F FUSED DISCONNECT

TRANSFORMER

REMOVAL WORK LINE WEIGHT

KEY NOTES

LEGEND

T

EXISTING TO REMAIN LINE WEIGHT

NEW WORK LINE WEIGHT

FUTURE WORK LINE WEIGHT

REMOVE EXISTING FLOOR MOUNTED TRANSFORMER

AND DISCONNECT SWITCH. RETAIN PRIMARY AND

SECONDARY CONDUCTORS. REPLACE

WITH A FLOOR MOUNTED TRANSFORMER AND

DISCONNECT SWITCH AND RECONNECT TO EXISTING

CONDUCTORS TO MATCH EXISTING.

TRANSFORMER TO BE PROVIDED UNDER FUTURE

SCOPE OF WORK. LOCATION SHOWN IS

APPROXIMATE.

FUSED DISCONNECT TO BE PROVIDED UNDER

FUTURE SCOPE OF WORK. LOCATION SHOWN IS

APPROXIMATE.

PROVIDE AND INSTALL NEW FUSED DISCONNECT.

T75KVA

REAL PROPERTY

USDA

SAFETY & HEALTH

AREA ENGINEER

DRAWN BY

CHECKED BY

DESIGNER

PROJECT MANAGER

EPM

PROJECT NO.

DATE

REV. DATE BY

SHEET

DESCRIPTION

Service Research Agricultural

USDA AGRICULTURAL RESEARCH

SERVICE

ELECTRICAL UPGRADE

3793 E 3600 N, KIMBERLY, ID

83341, USA

USDA AGRICULTURAL RESEARCH SERVICE

PROJECT II: INTERNAL BUILDING TRANSFORMERS AND DISCONNECT

SWITCHES

U S D A

OF

SEAL

4212 APR 2024

1555-00

J.ARMSTRONG

O.TRUJILLO

S.RASTKAR

B.SANTANA

E-005

SR04/12/24 ISSUED FOR CONSTRUCTION0

ELECTRICAL SITE PLAN

DISCONNECT SWITCH

REMOVE THE EXISTING WALL MOUNTED

TRANSFORMER ALONG WITH ASSOCIATED WALL

BRACKET/SUPPORT AND DISCONNECT SWITCH.

RETAIN PRIMARY AND SECONDARY CONDUCTORS.

REPLACE THE TRANSFORMER USING NEW FACTORY

PROVIDED WALL MOUNT BRACKET. REPLACE THE

DISCONNECT SWITCH AND RECONNECT THE WIRING.

F F F

1. WIRES TO BE REPLACED BETWEEN THE NEW

DISCONNECT AND THE NEW TRANSFORMER PRIMARY.

CONTRACTOR SHALL PROVIDE NEW WIRING BETWEEN

ANY REPLACED TRANSFORMER AND RESPECTIVE

LOCAL DISCONNECT SWITCHES.

2. CONTRACTOR SHALL PROVIDE GREEN JACKETED

BONDING CABLE TO CONNECT BETWEEN THE

SECONDARY OF THE TRANSFORMER AND BUILDING

GROUND AS FOLLOWS:

-30KVA TRANSFORMER: #8AWG

-45KVA TRANSFORMER: #4AWG

-75KVA TRANSFORMER: #2AWG

3. THE TRANSITION LOG BETWEEN COPPER CABLE AND

ALUMINUM BAR SHALL BE UTILIZED IF THE SECONDARY

OF THE TRANSFORMER COPPER CABLES TERMINATES

INTO THE ALUMINUM BUS PANELS.

4. ALL NEW WIRING, DISCONNECT SWITCH, AND

TRANSFORMER CORES SHALL BE COPPER TYPE.

5. ALL WIRES COMING FROM AND LEAVING DEMOLISHED

EQUIPMENT SHALL BE CAPPED FOR RECONNECTION

TO NEW EQUIPMENT WHERE WIRES ARE TO BE

REUSED. ALUMINUM WIRES SHALL BE REPLACED WITH

COPPER TYPE.

6. AREA AROUND TRANSFORMERS TO BE CHECKED FOR

ANY OBSTRUCTIONS. REFER TO NEC 110.26(A)(1) FOR

WORKING CLEARANCE REQUIREMENTS THAT ARE

WITHIN CLEARANCE AREA OF TRANSFORMER.

60AF

45AT

60AF

45AT

GENERAL NOTES

FEEDER ROUTING LOCATION HAS NOT BEEN

IDENTIFIED. CONTRACTOR SHALL CONDUCT FIELD

INSPECTION.

SHOP REPAIR AND SERVICESSTORAGE BARN

IRRIGATION LAB VEHICLE STORAGE

KEY NOTES

LEGEND

ELECTRICAL SINGLE LINE DIAGRAM - REMOVAL WORK

1 1

REAL PROPERTY

USDA

SAFETY & HEALTH

AREA ENGINEER

DRAWN BY

CHECKED BY

DESIGNER

PROJECT MANAGER

EPM

PROJECT NO.

DATE

REV. DATE BY

SHEET

DESCRIPTION

Service Research Agricultural

USDA AGRICULTURAL RESEARCH

SERVICE

ELECTRICAL UPGRADE

3793 E 3600 N, KIMBERLY, ID

83341, USA

USDA AGRICULTURAL RESEARCH SERVICE

PROJECT II: INTERNAL BUILDING TRANSFORMERS AND DISCONNECT

SWITCHES

U S D A

OF

SEAL

4312 APR 2024

1555-00

J.ARMSTRONG

O.TRUJILLO

S.RASTKAR

B.SANTANA

E-006

SR04/12/24 ISSUED FOR CONSTRUCTION1

ELECTRICAL SINGLE LINE

DIAGRAM - REMOVAL WORK

7200/12740V:

480/277V

300KVA

MAIN OUTDOOR SWITCHBOARD 480/277V

600A 3P

200A 3P

200A 3P

300A 3P

100A 3P

MAIN BUILDING:B1 HEAD HOUSE & NEW

GREENHOUSE:B2

IRRIGATION

LAB:B3

VEHICLE

STORAGE/SHOP:B4/B5

200A 3P

MAIN BUILDING

HVAC:B1

200A 3P

ANNEX/

OLD GREENHOUSE:B2

BURIED

CONCRETE ENCASED DUCTBANK

(x2) 4" CONDUITS

2 SETS 4#4/0AWG+#1GRD-3 1/2"C 4#1/0AWG+#6GRD-2"C 4#4/0AWG+#6GRD-3"C

SPARE

4#3/0AWG+#6GRD-2"C 4#2/0AWG+#6GRD-3"C 4#350MCM+#3GRD-3 1/2"C

100A 3P

SPARE

200A 3P

SPARE

480V 225A 3P

480V 225A 3P

150A 3P

1HC

1LC

1PB

1PC

1HB

1PD2 1LB 1LE

1LA

30A,3P

1/2HP

1HA

RM 113

RM 124B

208V

225AF

48 POLE

MLO

3P, 3W

120/208V

225AF

42 POLE

MLO

3P, 4W

RM 122A

RM 145

RM 122A RM 122A

480/277V

225AF

32 POLE

MLO

3P,4W

480/277V

225AF

16 POLE

MLO

3P,4W

RM 122A

RM 119A RM 119A

120/208V

30 POLE

MLO

3P,4W

120/208V

225AF

30 POLE

MLO

3P, 4W

120/208V

225AF

42 POLE

MLO

3P, 4W

120/208V

225AF

42 POLE

MLO

3P, 4W

RM 136

RM 136 RM 136

480/277V

225AF

42 POLE

MCB

3P, 4W

RM 136

120/208V

225AF

48 POLE

MLO

3P, 4W

RM 136

NORTH/EAST HALL

NORTH/EAST

HALL

RM 135

RM 135

RM 135

WIREWAY GUTTER

WIREWAY GUTTER

1PE1

1PE2

RM 119A

120/208V

30 POLE

MLO

3P, 4W

120/208V

225AF

42 POLE

MLO

3P, 4W

WEST

HALL

WEST

HALL

RM 121

4#4/0AWG+GRD-3"C 4#3/0AWG

+GRD-2"C

4#3/0AWG+

GRD-2"C

3#6AWG

+GRD-3/4"C

3#1/0AWG+GRD-2"C

3#1/0AWG+GRD-2"C 3#1/0AWG+GRD-2"C

3#4AWG+GRD-1 1/4"C

3#4AWG+GRD,1-1/4"C

4#4AWG+

GRD,1-1/2"C

3#1/0AWG+GRD-2"C

3#8AWG+

GRD,3/4"C

3#12AWG+

GRD,1/2"C

PENT-

HOUSE

PANEL

480/277V 3P,4W

480V:

120/208V

30KVA

120/208V 3P,4W

WIREWAY GUTTER

3#12AWG+

GRD,1/2"C

M

1/2HP

RM 135

RM 135

M

3HP

RM 135

RM 135

M

3HP

RM 135

RM 135

M

1-1/2HP

RM 135

RM 135

M

PENT-

HOUSE

PANEL

T

3#4AWG+GRD,1-1/4"C

4#4AWG+

GRD,1-1/2"C

FEED THROUGH

LUGS

480V:

120/208V

30KVA

RM 113B

RM 124A

RM 114

480V:

120/208V

30KVA 480V:

120/208V

45KVA

60AF

45AT F

100AF

70AT F

F

480V:

120/208V

45KVA

480V:

120/208V

9KVA

RM 122A

RM 122A

RM 122A

100AF

70AT

30AF

15AT

T

T

480V:

120/208V

30KVA

RM 136

RM 136

60AF

45AT

T

100A 3P

2LB

70A 3P

2PA

150A 3P

100A 3P

480V:

120/208V

45KVA

RM 230

480/277V

225AF

28 POLE

MLO

3P, 4W

120/208V

150AF

42 POLE

MCB

3P, 4W

2LA

120/208V

100AF

36 POLE

MCB

3P, 4W

PANEL

A

120/208V

200AF

42 POLE

MCB

3P, 4W

2B

480/277V

125AF

18 POLE

MCB

3P, 4W

CORR TO

ANNEX

CORR TO

ANNEX

RM 230

RM 230

WIREWAY GUTTER

2PB

120/208V

225AF

66 POLE

MCB

3P, 4W

2LD

120/208V 3P, 4W

OLD GREEN

HOUSE

2A

CORR TO

ANNEX

CORR TO

ANNEX

CORR TO

ANNEX

120/208V

42 POLE

MCB

3P, 4W

4#4/0AWG+

GRD,1-1/2"C

4#4AWG+

GRD,1-1/2"C

4#1/0AWG

+GRD,2"C 3#1/0AWG+

GRD,2"C

3#1AWG+#6GRD-1 1/4"C

3#1/0AWG+GRD-2"C

4#1AWG+

GRD,1"C

2[4#1/0AWG+

#6GRD,2-1/2"C]

F200AF

125AT

70A 3P

CORR TO

OLD GREEN

HOUSE

PANEL B

120/208V 3P, 4W

RM 230

480V:

120/208V

75KVA

RM 210

T

RM 210

T 480V:

120/208V

75KVA

RM 210

MAIN BUILDING

45A 3P

RM 302

RM 302

120/208V

100AF

48 POLE

MLO

3P, 4W

5LA

5HA480/277V

100AF

48 POLE

MCB

3P, 4W

RM 302

480V:

120/208V

30KVA

T

4LA

120/208V

225AF

42 POLE

MLO

3P, 4WRM 401

480V:

120/208V

30KVA

T

RM 401

RM 401

RM 401

J-BOX

480V:

120/208V

75KVA

6LA

120/208V

100AF

38 POLE

MCB

3P, 4W

6A 480/277V

150AF

6 POLE

MCB

3P, 4W

4#2/0AWG+

GRD,1-1/2"C

3#6AWG+

GRD,1"C

4#2AWG+

GRD,1"C

150A 3P

RM 601

RM 601

RM 601

T

480V BUS

BUS

DISCONNECT

F F

3PA1

200A

3P3LA

WIREWAY GUTTER

60A

120/208V

225AF

42 POLE

MCB

3P, 4W

3PA2

120/208V

200AF

18 POLE

MCB

3P, 4W

120/208V

200AF

42 POLE

MLO

3P, 4W

3LB

RM 504

120/208V

42 POLE

MLO

3P, 4W

RM 501

RM 501

RM 501RM 501

RM 501

4#4/0AWG+

GRD,1-1/2"C

4#6AWG+GRD-3/4"C

4#6AWG+

GRD-3/4"C

FEED THROUGH

LUGS

480V:

120/208V

75KVA

RM 501

RM 501200AF

125AT F

T

F

T

T

T

RM 113B

RM 124A

RM 114

J

RM 113B

RM 122A

J

F

F

F

HEADHOUSE, NEW GREENHOUSE

OLD GREENHOUSE, AND ANNEX

RM 136

F

800AF

500AT

T

CORR TO

ANNEX

T

REMOVE EXISTING TRANSFORMER AND

DISCONNECT SWITCH. RETAIN PRIMARY AND

SECONDARY CONDUCTORS. REPLACE

TRANSFORMER AND DISCONNECT SWITCH AND

RECONNECT TO EXISTING CONDUCTORS TO MATCH

EXISTING. RETAIN THE METHOD OF INSTALLATION

TO MATCH EXISTING. ANY WALL MOUNTED

INSTALLATION SHALL BE EQUIPPED WITH NEW

FACTORY PROVIDED WALL BRACKET.

RETAIN JUNCTION BOX. INSTALL TERMINATION LUGS

AND ROUTE CONDUCTORS TO FUSIBLE SWITCHES

MOUNTED TO ADJACENT WALL.

1. WIRES TO BE REPLACED BETWEEN THE NEW

DISCONNECT AND THE NEW TRANSFORMER PRIMARY.

CONTRACTOR SHALL PROVIDE NEW WIRING BETWEEN

ANY REPLACED TRANSFORMER AND RESPECTIVE

LOCAL DISCONNECT SWITCHES.

2. CONTRACTOR SHALL PROVIDE GREEN JACKETED

BONDING CABLE TO CONNECT BETWEEN THE

SECONDARY OF THE TRANSFORMER AND BUILDING

GROUND AS FOLLOWS:

-30KVA TRANSFORMER: #8AWG

-45KVA TRANSFORMER: #4AWG

-75KVA TRANSFORMER: #2AWG

3. THE TRANSITION LOG BETWEEN COPPER CABLE AND

ALUMINUM BAR SHALL BE UTILIZED IF THE SECONDARY

OF THE TRANSFORMER COPPER CABLES TERMINATES

INTO THE ALUMINUM BUS PANELS.

4. ALL NEW WIRING, DISCONNECT SWITCH, AND

TRANSFORMER CORES SHALL BE COPPER TYPE.

5. ALL WIRES COMING FROM AND LEAVING DEMOLISHED

EQUIPMENT SHALL BE CAPPED FOR RECONNECTION

TO NEW EQUIPMENT WHERE WIRES ARE TO BE

REUSED. ALUMINUM WIRES SHALL BE REPLACED WITH

COPPER TYPE.

6. AREA AROUND TRANSFORMERS TO BE CHECKED FOR

ANY OBSTRUCTIONS. REFER TO NEC 110.26(A)(1) FOR

WORKING CLEARANCE REQUIREMENTS THAT ARE

WITHIN CLEARANCE AREA OF TRANSFORMER.

F

MOTOR

PULL BOX

FUSED DISCONNECT

TRANSFORMER

ENCLOSED CIRCUIT BREAKER,

CIRCUIT BREAKER

JUNCTION BOX

REMOVAL WORK LINE WEIGHT

T

PB

M

EXISTING TO REMAIN LINE WEIGHT

NEW WORK LINE WEIGHT

FUTURE WORK LINE WEIGHT

DISCONNECT SWITCH

J

100A 3P

27 Nov, 2024

Sheets and Views
DEMOLITION SINGLE LINE DIAGRAM JA-NEW E0
DEMOLITION SINGLE LINE DIAGRAM JA-NEW E5
DEMOLITION SINGLE LINE DIAGRAM JA-NEW E6
DEMOLITION SINGLE LINE DIAGRAM JA-NEW E7