This is a set of electrical drawings detailing upgrades to internal building transformers and disconnect switches at the USDA Agricultural Research Service Northwest Irrigation & Soils Research Laboratory in Kimberly, ID. The drawings include a project cover page, electrical site plan, and electrical single line diagrams showing both removal work and new work to be performed.
The drawings specify replacement of multiple transformers ranging from 9KVA to 75KVA across several buildings including the Main Building, Head House, Irrigation Lab, Vehicle Storage, and Greenhouse facilities. Key work includes removing existing floor and wall-mounted transformers while retaining primary/secondary conductors, installing new transformers with proper wall brackets and disconnect switches, replacing aluminum wiring with copper, and providing new bonding cables sized appropriately for each transformer capacity (#8AWG for 30KVA, #4AWG for 45KVA, #2AWG for 75KVA transformers). The drawings include detailed general notes about wire replacement requirements, grounding specifications, and working clearance requirements per NEC 110.26(A)(1).
View the file
Other files
Show all 15
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
REAL PROPERTY
USDA
SAFETY & HEALTH
AREA ENGINEER
DRAWN BY
CHECKED BY
DESIGNER
PROJECT MANAGER
EPM
PROJECT NO.
DATE
REV. DATE BY
SHEET
DESCRIPTION
Service Research Agricultural
USDA AGRICULTURAL RESEARCH
SERVICE
ELECTRICAL UPGRADE
3793 E 3600 N, KIMBERLY, ID
83341, USA
USDA AGRICULTURAL RESEARCH SERVICE
PROJECT II: INTERNAL BUILDING TRANSFORMERS AND DISCONNECT
SWITCHES
U S D A
OF
SEAL
4112 APR 2024
1555-00
J.ARMSTRONG
O.TRUJILLO
S.RASTKAR
B.SANTANA
E-000-B
SR04/12/24 ISSUED FOR CONSTRUCTION0
PROJECT COVER PAGE
PROJECT II: INTERNAL BUILDING TRANSFORMERS AND DISCONNECT SWITCHES
USDA-ARS NORTHWEST IRRIGATION & SOILS RESEARCH LAB
3793 EAST 3600 NORTH KIMBERLY, ID 83341-5076
DRAWING LIST
E-000-B PROJECT COVER PAGE
E-005 ELECTRICAL SITE PLAN
E-006 ELECTRICAL SINGLE LINE DIAGRAM - REMOVAL WORK
E-007 ELECTRICAL SINGLE LINE DIAGRAM - NEW WORK
N 3800 E
N
E
ID-50
W . F
LS
A
VE
E
85.7710"MAIN BUILDING (B1)
HEAD HOUSE (B2)
IR
RI
G
AT
IO
N
LA
B
(B 3)
VE
HI
CL
E
ST
O
RA
G
E (B
4)
SH
O
P
RE
PA
IR
A
ND
SE
RV
IC
ES
(B 5)
STORAGE BARN (B6)
O
LD
G
RE
EN
HO
US
E
NE
W
G
RE
EN
HO
US
E
AN
NE
X
12 April, 2024
ELECTRICAL SITE PLAN
E E
E
T
2 2
30KVA
45KVA
30KVA
45KVA9KVA
30KVA
75KVA
SCALE 1" = 400'
MAIN BUILDING (B1)
HEAD HOUSE (B2)
IR
RI
G
AT
IO
N
LA
B
(B 3)
VE
HI
CL
E
ST
O
RA
G
E (B
4)
SH
O
P
RE
PA
IR
A
ND
S
ER
VI
CE
S (B
5)
45KVA
STORAGE BARN (B6)
FUTURE
EXPANSION PROJECT
FUTURE AREA OF RENOVATION
NE
W
G
RE
EN
HO
US
E
O
LD
G
RE
EN
HO
US
E
AN
NE
X
45KVA
RM 122A
RM 136
RM 114
RM 113B
RM 124A
RM 210
RM 302
RM 401
30KVA 30KVA
75KVA
RM 501
T
T
T
TT
T
T
TTT
T
F
F
F
FF
F
F
RM 230 RM 210
GENERAL NOTES
F FUSED DISCONNECT
TRANSFORMER
REMOVAL WORK LINE WEIGHT
KEY NOTES
LEGEND
T
EXISTING TO REMAIN LINE WEIGHT
NEW WORK LINE WEIGHT
FUTURE WORK LINE WEIGHT
REMOVE EXISTING FLOOR MOUNTED TRANSFORMER
AND DISCONNECT SWITCH. RETAIN PRIMARY AND
SECONDARY CONDUCTORS. REPLACE
WITH A FLOOR MOUNTED TRANSFORMER AND
DISCONNECT SWITCH AND RECONNECT TO EXISTING
CONDUCTORS TO MATCH EXISTING.
TRANSFORMER TO BE PROVIDED UNDER FUTURE
SCOPE OF WORK. LOCATION SHOWN IS
APPROXIMATE.
FUSED DISCONNECT TO BE PROVIDED UNDER
FUTURE SCOPE OF WORK. LOCATION SHOWN IS
APPROXIMATE.
PROVIDE AND INSTALL NEW FUSED DISCONNECT.
T75KVA
REAL PROPERTY
USDA
SAFETY & HEALTH
AREA ENGINEER
DRAWN BY
CHECKED BY
DESIGNER
PROJECT MANAGER
EPM
PROJECT NO.
DATE
REV. DATE BY
SHEET
DESCRIPTION
Service Research Agricultural
USDA AGRICULTURAL RESEARCH
SERVICE
ELECTRICAL UPGRADE
3793 E 3600 N, KIMBERLY, ID
83341, USA
USDA AGRICULTURAL RESEARCH SERVICE
PROJECT II: INTERNAL BUILDING TRANSFORMERS AND DISCONNECT
SWITCHES
U S D A
OF
SEAL
4212 APR 2024
1555-00
J.ARMSTRONG
O.TRUJILLO
S.RASTKAR
B.SANTANA
E-005
SR04/12/24 ISSUED FOR CONSTRUCTION0
ELECTRICAL SITE PLAN
DISCONNECT SWITCH
REMOVE THE EXISTING WALL MOUNTED
TRANSFORMER ALONG WITH ASSOCIATED WALL
BRACKET/SUPPORT AND DISCONNECT SWITCH.
RETAIN PRIMARY AND SECONDARY CONDUCTORS.
REPLACE THE TRANSFORMER USING NEW FACTORY
PROVIDED WALL MOUNT BRACKET. REPLACE THE
DISCONNECT SWITCH AND RECONNECT THE WIRING.
F F F
1. WIRES TO BE REPLACED BETWEEN THE NEW
DISCONNECT AND THE NEW TRANSFORMER PRIMARY.
CONTRACTOR SHALL PROVIDE NEW WIRING BETWEEN
ANY REPLACED TRANSFORMER AND RESPECTIVE
LOCAL DISCONNECT SWITCHES.
2. CONTRACTOR SHALL PROVIDE GREEN JACKETED
BONDING CABLE TO CONNECT BETWEEN THE
SECONDARY OF THE TRANSFORMER AND BUILDING
GROUND AS FOLLOWS:
-30KVA TRANSFORMER: #8AWG
-45KVA TRANSFORMER: #4AWG
-75KVA TRANSFORMER: #2AWG
3. THE TRANSITION LOG BETWEEN COPPER CABLE AND
ALUMINUM BAR SHALL BE UTILIZED IF THE SECONDARY
OF THE TRANSFORMER COPPER CABLES TERMINATES
INTO THE ALUMINUM BUS PANELS.
4. ALL NEW WIRING, DISCONNECT SWITCH, AND
TRANSFORMER CORES SHALL BE COPPER TYPE.
5. ALL WIRES COMING FROM AND LEAVING DEMOLISHED
EQUIPMENT SHALL BE CAPPED FOR RECONNECTION
TO NEW EQUIPMENT WHERE WIRES ARE TO BE
REUSED. ALUMINUM WIRES SHALL BE REPLACED WITH
COPPER TYPE.
6. AREA AROUND TRANSFORMERS TO BE CHECKED FOR
ANY OBSTRUCTIONS. REFER TO NEC 110.26(A)(1) FOR
WORKING CLEARANCE REQUIREMENTS THAT ARE
WITHIN CLEARANCE AREA OF TRANSFORMER.
60AF
45AT
60AF
45AT
GENERAL NOTES
FEEDER ROUTING LOCATION HAS NOT BEEN
IDENTIFIED. CONTRACTOR SHALL CONDUCT FIELD
INSPECTION.
SHOP REPAIR AND SERVICESSTORAGE BARN
IRRIGATION LAB VEHICLE STORAGE
KEY NOTES
LEGEND
ELECTRICAL SINGLE LINE DIAGRAM - REMOVAL WORK
1 1
REAL PROPERTY
USDA
SAFETY & HEALTH
AREA ENGINEER
DRAWN BY
CHECKED BY
DESIGNER
PROJECT MANAGER
EPM
PROJECT NO.
DATE
REV. DATE BY
SHEET
DESCRIPTION
Service Research Agricultural
USDA AGRICULTURAL RESEARCH
SERVICE
ELECTRICAL UPGRADE
3793 E 3600 N, KIMBERLY, ID
83341, USA
USDA AGRICULTURAL RESEARCH SERVICE
PROJECT II: INTERNAL BUILDING TRANSFORMERS AND DISCONNECT
SWITCHES
U S D A
OF
SEAL
4312 APR 2024
1555-00
J.ARMSTRONG
O.TRUJILLO
S.RASTKAR
B.SANTANA
E-006
SR04/12/24 ISSUED FOR CONSTRUCTION1
ELECTRICAL SINGLE LINE
DIAGRAM - REMOVAL WORK
7200/12740V:
480/277V
300KVA
MAIN OUTDOOR SWITCHBOARD 480/277V
600A 3P
200A 3P
200A 3P
300A 3P
100A 3P
MAIN BUILDING:B1 HEAD HOUSE & NEW
GREENHOUSE:B2
IRRIGATION
LAB:B3
VEHICLE
STORAGE/SHOP:B4/B5
200A 3P
MAIN BUILDING
HVAC:B1
200A 3P
ANNEX/
OLD GREENHOUSE:B2
BURIED
CONCRETE ENCASED DUCTBANK
(x2) 4" CONDUITS
2 SETS 4#4/0AWG+#1GRD-3 1/2"C 4#1/0AWG+#6GRD-2"C 4#4/0AWG+#6GRD-3"C
SPARE
4#3/0AWG+#6GRD-2"C 4#2/0AWG+#6GRD-3"C 4#350MCM+#3GRD-3 1/2"C
100A 3P
SPARE
200A 3P
SPARE
480V 225A 3P
480V 225A 3P
150A 3P
1HC
1LC
1PB
1PC
1HB
1PD2 1LB 1LE
1LA
30A,3P
1/2HP
1HA
RM 113
RM 124B
208V
225AF
48 POLE
MLO
3P, 3W
120/208V
225AF
42 POLE
MLO
3P, 4W
RM 122A
RM 145
RM 122A RM 122A
480/277V
225AF
32 POLE
MLO
3P,4W
480/277V
225AF
16 POLE
MLO
3P,4W
RM 122A
RM 119A RM 119A
120/208V
30 POLE
MLO
3P,4W
120/208V
225AF
30 POLE
MLO
3P, 4W
120/208V
225AF
42 POLE
MLO
3P, 4W
120/208V
225AF
42 POLE
MLO
3P, 4W
RM 136
RM 136 RM 136
480/277V
225AF
42 POLE
MCB
3P, 4W
RM 136
120/208V
225AF
48 POLE
MLO
3P, 4W
RM 136
NORTH/EAST HALL
NORTH/EAST
HALL
RM 135
RM 135
RM 135
WIREWAY GUTTER
WIREWAY GUTTER
1PE1
1PE2
RM 119A
120/208V
30 POLE
MLO
3P, 4W
120/208V
225AF
42 POLE
MLO
3P, 4W
WEST
HALL
WEST
HALL
RM 121
4#4/0AWG+GRD-3"C 4#3/0AWG
+GRD-2"C
4#3/0AWG+
GRD-2"C
3#6AWG
+GRD-3/4"C
3#1/0AWG+GRD-2"C
3#1/0AWG+GRD-2"C 3#1/0AWG+GRD-2"C
3#4AWG+GRD-1 1/4"C
3#4AWG+GRD,1-1/4"C
4#4AWG+
GRD,1-1/2"C
3#1/0AWG+GRD-2"C
3#8AWG+
GRD,3/4"C
3#12AWG+
GRD,1/2"C
PENT-
HOUSE
PANEL
480/277V 3P,4W
480V:
120/208V
30KVA
120/208V 3P,4W
WIREWAY GUTTER
3#12AWG+
GRD,1/2"C
M
1/2HP
RM 135
RM 135
M
3HP
RM 135
RM 135
M
3HP
RM 135
RM 135
M
1-1/2HP
RM 135
RM 135
M
PENT-
HOUSE
PANEL
T
3#4AWG+GRD,1-1/4"C
4#4AWG+
GRD,1-1/2"C
FEED THROUGH
LUGS
480V:
120/208V
30KVA
RM 113B
RM 124A
RM 114
480V:
120/208V
30KVA 480V:
120/208V
45KVA
60AF
45AT F
100AF
70AT F
F
480V:
120/208V
45KVA
480V:
120/208V
9KVA
RM 122A
RM 122A
RM 122A
100AF
70AT
30AF
15AT
T
T
480V:
120/208V
30KVA
RM 136
RM 136
60AF
45AT
T
100A 3P
2LB
70A 3P
2PA
150A 3P
100A 3P
480V:
120/208V
45KVA
RM 230
480/277V
225AF
28 POLE
MLO
3P, 4W
120/208V
150AF
42 POLE
MCB
3P, 4W
2LA
120/208V
100AF
36 POLE
MCB
3P, 4W
PANEL
A
120/208V
200AF
42 POLE
MCB
3P, 4W
2B
480/277V
125AF
18 POLE
MCB
3P, 4W
CORR TO
ANNEX
CORR TO
ANNEX
RM 230
RM 230
WIREWAY GUTTER
2PB
120/208V
225AF
66 POLE
MCB
3P, 4W
2LD
120/208V 3P, 4W
OLD GREEN
HOUSE
2A
CORR TO
ANNEX
CORR TO
ANNEX
CORR TO
ANNEX
120/208V
42 POLE
MCB
3P, 4W
4#4/0AWG+
GRD,1-1/2"C
4#4AWG+
GRD,1-1/2"C
4#1/0AWG
+GRD,2"C 3#1/0AWG+
GRD,2"C
3#1AWG+#6GRD-1 1/4"C
3#1/0AWG+GRD-2"C
4#1AWG+
GRD,1"C
2[4#1/0AWG+
#6GRD,2-1/2"C]
F200AF
125AT
70A 3P
CORR TO
OLD GREEN
HOUSE
PANEL B
120/208V 3P, 4W
RM 230
480V:
120/208V
75KVA
RM 210
T
RM 210
T 480V:
120/208V
75KVA
RM 210
MAIN BUILDING
45A 3P
RM 302
RM 302
120/208V
100AF
48 POLE
MLO
3P, 4W
5LA
5HA480/277V
100AF
48 POLE
MCB
3P, 4W
RM 302
480V:
120/208V
30KVA
T
4LA
120/208V
225AF
42 POLE
MLO
3P, 4WRM 401
480V:
120/208V
30KVA
T
RM 401
RM 401
RM 401
J-BOX
480V:
120/208V
75KVA
6LA
120/208V
100AF
38 POLE
MCB
3P, 4W
6A 480/277V
150AF
6 POLE
MCB
3P, 4W
4#2/0AWG+
GRD,1-1/2"C
3#6AWG+
GRD,1"C
4#2AWG+
GRD,1"C
150A 3P
RM 601
RM 601
RM 601
T
480V BUS
BUS
DISCONNECT
F F
3PA1
200A
3P3LA
WIREWAY GUTTER
60A
120/208V
225AF
42 POLE
MCB
3P, 4W
3PA2
120/208V
200AF
18 POLE
MCB
3P, 4W
120/208V
200AF
42 POLE
MLO
3P, 4W
3LB
RM 504
120/208V
42 POLE
MLO
3P, 4W
RM 501
RM 501
RM 501RM 501
RM 501
4#4/0AWG+
GRD,1-1/2"C
4#6AWG+GRD-3/4"C
4#6AWG+
GRD-3/4"C
FEED THROUGH
LUGS
480V:
120/208V
75KVA
RM 501
RM 501200AF
125AT F
T
F
T
T
T
RM 113B
RM 124A
RM 114
J
RM 113B
RM 122A
J
F
F
F
HEADHOUSE, NEW GREENHOUSE
OLD GREENHOUSE, AND ANNEX
RM 136
F
800AF
500AT
T
CORR TO
ANNEX
T
REMOVE EXISTING TRANSFORMER AND
DISCONNECT SWITCH. RETAIN PRIMARY AND
SECONDARY CONDUCTORS. REPLACE
TRANSFORMER AND DISCONNECT SWITCH AND
RECONNECT TO EXISTING CONDUCTORS TO MATCH
EXISTING. RETAIN THE METHOD OF INSTALLATION
TO MATCH EXISTING. ANY WALL MOUNTED
INSTALLATION SHALL BE EQUIPPED WITH NEW
FACTORY PROVIDED WALL BRACKET.
RETAIN JUNCTION BOX. INSTALL TERMINATION LUGS
AND ROUTE CONDUCTORS TO FUSIBLE SWITCHES
MOUNTED TO ADJACENT WALL.
1. WIRES TO BE REPLACED BETWEEN THE NEW
DISCONNECT AND THE NEW TRANSFORMER PRIMARY.
CONTRACTOR SHALL PROVIDE NEW WIRING BETWEEN
ANY REPLACED TRANSFORMER AND RESPECTIVE
LOCAL DISCONNECT SWITCHES.
2. CONTRACTOR SHALL PROVIDE GREEN JACKETED
BONDING CABLE TO CONNECT BETWEEN THE
SECONDARY OF THE TRANSFORMER AND BUILDING
GROUND AS FOLLOWS:
-30KVA TRANSFORMER: #8AWG
-45KVA TRANSFORMER: #4AWG
-75KVA TRANSFORMER: #2AWG
3. THE TRANSITION LOG BETWEEN COPPER CABLE AND
ALUMINUM BAR SHALL BE UTILIZED IF THE SECONDARY
OF THE TRANSFORMER COPPER CABLES TERMINATES
INTO THE ALUMINUM BUS PANELS.
4. ALL NEW WIRING, DISCONNECT SWITCH, AND
TRANSFORMER CORES SHALL BE COPPER TYPE.
5. ALL WIRES COMING FROM AND LEAVING DEMOLISHED
EQUIPMENT SHALL BE CAPPED FOR RECONNECTION
TO NEW EQUIPMENT WHERE WIRES ARE TO BE
REUSED. ALUMINUM WIRES SHALL BE REPLACED WITH
COPPER TYPE.
6. AREA AROUND TRANSFORMERS TO BE CHECKED FOR
ANY OBSTRUCTIONS. REFER TO NEC 110.26(A)(1) FOR
WORKING CLEARANCE REQUIREMENTS THAT ARE
WITHIN CLEARANCE AREA OF TRANSFORMER.
F
MOTOR
PULL BOX
FUSED DISCONNECT
TRANSFORMER
ENCLOSED CIRCUIT BREAKER,
CIRCUIT BREAKER
JUNCTION BOX
REMOVAL WORK LINE WEIGHT
T
PB
M
EXISTING TO REMAIN LINE WEIGHT
NEW WORK LINE WEIGHT
FUTURE WORK LINE WEIGHT