Attachment VI - Modular Foundation.pdf
PDF 974 KB Posted
- Attached to
- Utility Site Preparation For Modular Unit Placement (Prosser, WA) Federal contract opportunity
- Solicitation number
- 12905B24Q0002
About this file
This document contains construction plans and specifications for a modular foundation to be installed at a USDA Agricultural Research Service facility in Prosser, WA. The plans provide dimensions and details for concrete footings, stem walls, crawlspace access and ventilation, and welded steel bearing plates to support the modular structure. Related federal contract opportunity 12905B24Q0002 issued by the USDA Agricultural Research Service seeks utility site preparation services for placement of a modular unit at the Prosser research location, including excavation, installation of the foundation according to the specifications, backfilling, and grading.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Site Visit Sign-In Sheet.pdf | ||
| Questions and Answers.pdf | ||
| SF30_12905B24Q0002_0002.pdf | ||
| Attachment VIII - Utility Rough In.pdf | ||
| Attachment X - Utilities.jpg | JPG image | |
| Attachment XI - Water Line Sizes.jpg | JPG image | |
| SF30_12905B24Q0002_0001.pdf | ||
| Attachment VII - Sewer.jpeg | JPEG file | |
| Attachment IX - Water.pdf | ||
| Attachment II Statement of Work.pdf | ||
| RFQ_12905B24Q0002 Terms and Conditions.pdf | ||
| Attachment I SF-18.pdf | ||
| Attachment IV ARS-371 - CONSTRUCTION PROGRESS AND PAYMENT SCHEDULE.pdf | ||
| Attachment III DOL WA20230064_082523.pdf | ||
| Attachment V ARS-372 - CONTRACTOR REQUEST FOR PAYMENT TRANSMITTAL.pdf |
Show all 15
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
M O
D 'A' M
O D 'B'
M O
D 'C'
B
C
C
C
C
C
C
C
C
C C
A
68'-8"
CONCRETE STEMWALL OUTSIDE EDGE DIMENSION
'-3
CO
N
CR
ET
E
ST
EM
W
AL
L O
U
TS
ID
E
ED
GE
D
IM
EN
SI
O N
IN
CL
U
DE
D W
/ 1 /2
" M
AT
EL
IN
E
GR
O W
TH
E
AC
H M
AT
EL
IN
E
14'-1"
5' -1
1" 5'
-1 1"
5' -1
1" 5'
-1 1"
5' -1
1" 6'
-0
14'-1"11'-8"14'-1"14'-1"
14'-1"14'-1"11'-8"14'-1"14'-1"
'-7
BU
IL
DI
N G
W
ID
TH
IN
CL
U
DE
D
W / 1
/2 " M
AT
EL
IN
E
GR
O
W
TH
E
AC
H
M
AT
EL
IN
E
5' -1
1" 5'
-1 1"
5' -1
1" 6'
-0
8"
TY
P.
S
TE
M
W
AL
L
24"x36" CRAWL SPACE ACCESS OPENING WITH
WINDOW WELL INSTALLED AT TOP OF STEM WALL.
1' -6
TY
P.
F
O O
TE
R
8"x16" CRAWL SPACE VENT OPENING WITH WINDOW
WELL INSTALLED AT TOP OF STEM WALL.
C
C
C
C
1/ 2"
1/ 2"
69'-6"
CONCRETE FOOTER OUTSIDE EDGE DIMENSION
'-0
CO
N
CR
ET
E
FO
O
TE
R
O U
TS
ID
E
ED
GE
D
IM
EN
SI
O
N
IN
CL
U
DE
D
W / 1
/2 " M
AT
EL
IN
E
GR
O
W
TH
E
AC
H
M
AT
EL
IN
E
11'-4" 11'-4"
C C C C C
C C C C C
5' -1
1" 5'
-1 1"
A
A
A
11'-4"11'-4"11'-4"11'-4"
B
B B
D
AT
E:
D R
AW
N
B Y:
SC
AL
E:
JO
B
N O
LO
C
AT
IO
N
R
EV
IS
IO
N
1. 2. 3. 4.
F-1
FOUNDATION PLAN
#7
- U
SD
A
- A
RS
PR
OS
SE
R, W
A
JH
P 4-1
9-2
3/8
1' -0"
PR
OS
SE
R, W A
LEGEND
DBL STACKED CMU BLOCK AND POURED
CONCRETE FOOTER BELOW
DESIGN LOADS:
ROOF LIVE LOAD: 30 PSF
ROOF DEAD LOAD: 20 PSF
GROUND SNOW LOAD: 35 PSF
FLOOR LIVE LOAD: 50 PSF (2000 LB CONCENTRATED)
STORAGE ROOM: 125 PSF
WIND LOAD: 110 MPH, EXP. C (VULT)
SEISMIC DESIGN CATEGORY: D
PER "SMOD3668PROSSER" DRAWING
GENERAL NOTES:
1. SEE DRAWING SHEET F-1.1 FOR FURTHER
INFORMATION AND DETAILS ON
FOUNDATION SUPPORT SYSTEM.
2. TOTAL AREA OF VENTILATION OPENINGS
REDUCED TO 1/1,500 OF THE
UNDER-FLOOR AREA AS ALLOWED PER
OBC SECTION 1203.4.2 WHEN GROUND
SURFACE IS COVERED WITH CLASS I VAPOR
RETARDER MATERIAL AND THE OPENINGS
ARE PLACED SO AS TO PROVIDE CROSS
VENTILATION OF THE SPACE.
SHEET KEYNOTES:
A 33"x33"x10" CONCRETE FOOTER WITH
DOUBLE 8"x16"x8" CMU BLOCK STACKED
ABOVE TO BOTTOM OF BUILDING FRAME.
C 8"x8"x1/4" STEEL PLATE w/ (2) 1/2" DIA.
'L' RODS 8" LONG WELDED TO BOTTOM
OF PLATE w/ 1/4" FILLET FOR ENTIRE
CIRCUMFERENCE AND ANCHORED INTO
TOP OF STEM WALL. SEE DETAILS ON
SHEET F-3 FOR MORE INFORMATION.
F-1.1 B1
F-1.1 B4
F-1.1 B1
F-1.1 B2
F-1.1 B3
B 54"x54"x16" CONCRETE FOOTER WITH DOUBLE 8"x16"x8" CMU BLOCK STACKED
ABOVE TO BOTTOM OF BUILDING FRAME.
http://www.sustainablemodular.com/ AutoCAD SHX Text www.sustainablemodular.com
PROVIDE POSITIVE DRAINAGE UNDER UNIT.
UNDERGROUND UTILITY LOCATIONS ARE THE RESPONSIBILITY OF OTHERS. ALL UNDER-
GROUND UTILITY LOCATIONS MUST BE VERIFIED PRIOR TO ANY EXCAVATION.
7.
8.
OF THE FOUNDATION TO DETERMINE THE AMOUNT OF INCREASED WIDTH TO BE ADDED TO THE
NOMINAL DIMENSIONS SHOWN ABOVE.
SOILS ONLY.
REQUIRED ALTERNATE FOUNDATION DESIGN. FOOTINGS SHALL BE PLACED ON NON-EXPANSIVE
CAPACITY IS LESS THAN 2,000 PSF, THE ARCHITECT/ENGINEER MUST BE CONSULTED FOR
SOIL BEARING CAPACITY SHOWN ON THIS PLAN IS ASSUMED. IF THE ACTUAL SOIL BEARING
MINIMUM SOIL BEARING CAPACITY IS 2,000 PSF. TO BE VERIFIED BY BUILDING'S OWNER.
THE FOUNDATION DIMENSIONS SHOWN ARE NOMINAL. AN INCREASE IN MODULE WIDTH SHOULD
BE EXPECTED DUE TO MODULE EXPANSION, SETTING TOLERANCES, ETC. THE FOUNDATION CON- TRACTOR SHOULD CONSULT WITH THE MANUFACTURER OF THE MODULES PROIR TO CONSTRUCTION
NOTE: ALL REQUIRED BUILDING AND/OR CONSTRUCTION PERMITS MUST BE APPLIED
FOR AND OBTAINED FROM THE LOCAL AUTHORITIES HAVING JURISDICTION PRIOR TO
ANY WORKED BEING DONE ON THE ABOVE SHOWN FOUNDATION DESIGN.
FOUNDATION NOTES:
6.
OF THIS FOUNDATION IS SUBJECT TO THE LOCAL JURISDICTION HAVING AUTHORITY.
THE WIND LOAD AND SOIL BEARING REQUIREMENTS OF THESE CODES. THE APPROVAL
ALTERNATIVE DESIGN OR METHOD OF CONSTRUCTION. THIS DESIGN MEETS OR EXCEEDS
THE FOUNDATION IS DESIGNED AS PER SECTION 104.11 OF THE 2018 IBC USING2.
5.
UNITS & 1/2" GROWTH. ACTUAL OVERALL WIDTH MAY INCREASE DUE TO SITE CONDITIONS,
OVERALL WIDTH DIMENSION IS NOMINAL AND IS BASED ON UNIT WIDTH x NUMBER OF
BEYOND THE CONTROL OF THE BUILDING MANUFACTURER.
MATERIAL, TOLERANCES. FAILURE TO REMOVE CLOSE-UP MATERIAL AND/OR OTHER FACTORS
4.
3.
IS REMOVED FROM UNDER THE BUILDING AND THAT THE GROUND IS LEVELED AND
IT WILL BE THE BUILDING OWNER'S RESPONSIBILITY TO INSURE THAT ALL LOOSE DEBRIS
FIRMLY COMPACTED.
WITH ALL APPLICABLE STATE AND LOCAL CODES.
ALL FOUNDATION CONSTRUCTION, MATERIALS, AND INSTALLATION SHALL BE IN ACCORDANCE1.
9. FOUNDATION SITE PREP IS TO BE COMPLETED BY OTHERS PRIOR TO ANY FOUNDATION WORK
TO BE DONE.
10. SMM IS NOT RESPONSIBLE FOR ANY FOUNDATION OR SETTLING ISSUES DUE TO NO GEOTECH
REPORT PROVIDED. ASSUMING MINIMUM 2,000 PSF SOIL BEARING CAPACITY
1'-6"
2' -4
GRADE @ CRAWL SPACE
EXTERIOR 'SMART' PANEL SIDING
5"
CONCRETE
STEMWALL
CONCRETE
SPREAD FOOTING
12" C-CHANNEL
8"
DAMPPROOFING
6 MIL. CLASS I
VAPOR BARRIER
5"(2) #4 HORIZONTAL
REBAR (3" CLEAR)
#4 VERTICAL REBAR
@ 36" O.C.
2"x4" KEY
1/4" BEARING PLATE W/ 1/2" DIA. 'L' RODS
8" LONG WELDED TO PLATE w/ 1/4" FILLET
FOR ENTIRE CIRCUMFERENCE
(3) #4 HORIZONTAL REBAR
SILL SEAL
2' -0
1'
-0
2x8 FLOOR JOISTS
1'-6"
2' -4
GRADE @ CRAWL SPACE
5" 5"
CONCRETE SPREAD FOOTING
SILL SEAL
8"
GRAVEL FILL
24"x36" VENT OPENING w/ COVERING
6 MIL. CLASS I
VAPOR BARRIER
GALVANIZED WINDOW
WELL w/ GRATED COVER
#4 VERTICAL REBAR
@ 36" O.C.
EXTERIOR HARDI PANEL SIDING
(2) #4 HORIZONTAL
REBAR (3" CLEAR)
1' -0
12" C-CHANNEL
2' -0
2x8 FLOOR JOISTS
2'-9"
2' -4
GRADE @ CRAWL SPACE
8"x8"x16" CMU
BLOCKED PIER
CONCRETE SQUARE FOOTING
M O
DU
LE
M
AT
E
LI
N E
1/2" TOLERANCE
1/2" THREADED ROD w/ WASHER
8'-0" O.C. FIRST ROD TO BE WITHIN
24" OF FRONT AND REAR BEAMS
4"x8"x16" SOLID
CMU CAP BLOCK
6 MIL. CLASS I
VAPOR BARRIER
SELF-ADHERED MEMBRANE AROUND
PIER. SECURE TO VAPOR BARRIER TO
PROVIDE COMPLETE SEAL
2x8 FLOOR JOISTS
12" C-CHANNEL
2x8 FLOOR JOISTS
FOOTING 'A'
NOTES:
1. WELD PLATES TO BE PLACED PER THE LOCATIONS AND
SPACING SHOWN ON THE FOUNDATION PLAN SHEET F-2.
8"
8"
4"
TYP.
1/
2"
TY
P.
6"
2"
1/4" STEEL PLATE
1/2" 'L' RODS 8" LONG WELDED TO PLATES w/
1/4" FILLET FOR ENTIRE CIRCUMFERENCE
PRESPECTIVE VIEWPLAN VIEW
4'-6"
2' -4
GRADE @ CRAWL SPACE
8"x8"x16" CMU
BLOCKED PIER
CONCRETE SQUARE FOOTING
M O
DU
LE
M
AT
E
LI
N E
1/2" TOLERANCE
1/2" THREADED ROD w/ WASHER
8'-0" O.C. FIRST ROD TO BE WITHIN
24" OF FRONT AND REAR BEAMS
4"x8"x16" SOLID
CMU CAP BLOCK
6 MIL. CLASS I
VAPOR BARRIER
SELF-ADHERED MEMBRANE AROUND
PIER. SECURE TO VAPOR BARRIER TO
PROVIDE COMPLETE SEAL
2x8 FLOOR JOISTS
12" C-CHANNEL
2x8 FLOOR JOISTS
FOOTING 'B'
CMU BLOCKS TO BE
CONCRETE FILLED
D
AT
E:
D R
AW
N
B Y:
SC
AL
E:
JO
B
N O
LO
C
AT
IO
N
R
EV
IS
IO
N
1. 2. 3. 4.
F-1.1
FOUNDATION NOTES &
DETAILS
#7
- U
SD
A
- A
RS
PR
OS
SE
R, W
A
MC
4-1 9-2
N.
T.S
PR
OS
SE
R, W A
B1
B2
B3
C3
SECTION DETAIL @ BUILDING ENTRANCES
SCALE: 1" = 1'-0"
SECTION DETAIL @ CRAWL SPACE VENT OPENING
SCALE: 1" = 1'-0"
SECTION DETAIL @ MATE LINE FOOTINGS
SCALE: 1" = 1'-0"
STEEL BEARING WELD PLATE DETAIL
SCALE: 3" = 1'-0"
B4 SECTION DETAIL @ MATE LINE FOOTINGS
SCALE: 1" = 1'-0"
http://www.sustainablemodular.com/ AutoCAD SHX Text www.sustainablemodular.com
| 717 - PROSSER, WA - USDA ARS - F-1 FOUNDATION PLAN |
| Sheets and Views |
| F-1 FOUNDATION PLAN |
| 717 - PROSSER, WA - USDA ARS - F-1.1 FOUNDATION NOTES & DETAILS |
| Sheets and Views |
| F-1.1 FOUNDATION NOTES & DETAILS |