Yakima Job Corps Main.xls

XLS spreadsheet 103 KB Posted

Attached to
USDA US Forest Service, Fort Simcoe Job Corps Center, Annual Fire Suppression Inspections
Solicitation number
1282A724Q0033
Issued by

About this file

This document is a service report for the annual inspection and maintenance of the fire suppression system at the Fort Simcoe Job Corps Center. The report details the inspection of the Ansul R-102 range hood system, including the locations of the system components, checks performed, and any discrepancies noted. The report indicates the system was inspected and tested in accordance with NFPA 17, 17A, and 96 standards, and the manufacturer's requirements.

The related federal contract opportunity is a combined synopsis/solicitation for the USDA Forest Service's requirement for annual fire suppression system inspections at the Fort Simcoe Job Corps Center. The solicitation number is 1282A724Q0033, and the contract will be for commercial items. The solicitation includes a Statement of Work and maps of the facilities. No other details about the procurement, such as response dates, award dates, pricing terms, or set asides, are provided in the given information.

View the file

Other files

File Type Posted
Amendment 001_1282A724Q0033.docx DOCX document
20240606_142253.jpg JPG image
Yakima Job Corps Lounge.xls XLS spreadsheet
20240606_135242.jpg JPG image
Yakima Job Corps Pizza Oven.xls XLS spreadsheet
Statement of Work - Fort Simcoe.pdf PDF
WageDeterminationYakimaWA_SAM.pdf PDF
ForestService_FireInspectionServicesJobCorps_Combined SS_ RFQ.pdf PDF
MapsFromSOW.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Rells Fire Service Sheet

Range Hood Systems Report
Service CompanyDate of ServiceTimeA.M.P.M.
3/28/24xx
AnnualSemi-AnnualRechargeInstallationRenovation
xx
Location Of System Cylinders
Inside to right of hood
ManufacturerModel NumberWetDry Chemical
AnsulR-102xx
CustomerCylinder Size MasterCylinder Size SlaveCylinder Size Slave
Fort Simcoe Job Corps3 gal3 gal
NameFuse Links 360 FFuse Links 450 FFuse Links 500 FOther
40 Abella Lnxx114oz
AddressFuel Shut-offElectricGasSize
White SwanWa.98952xxxx
CityStateZipSerial NumberLast Hydro Test DateLast Recharge Date
509-874-8908no coverJan-11Jan-11
TelephoneStore No.Manufacturer's Manual Reference
Miranda OlsonDisk 20
Owner or ManagerPage Number:Drawing Number:
COOKING APPLIANCE LOCATIONS: LEFT TO RIGHT
SteamerOven
3- 36" Fryers4' SkilletStove/4 Burners
1All appliances properly covered w/correct nozzlesx20Replaced fuse linksx
2Duct and plenum covered w/correct nozzlesx21Check travel of cable nuts/S-hooksx
3Check positioning of all nozzlesx22Piping & conduit securely bracketedx
4System installed in accordance w/MFG UL listingx23Proper separation between fryers & flamen/a
5Hood/duct penetrations sealed w/weld or UL devicex24Proper clearance-flame to filtersn/a
6Check if seals intact, evidence of tamperingx25Exhaust fan in operating orderx
7If system has been discharged, report samen/a26All filters replacedx
8Pressure gauge in proper range (If gauged)n/a27Fuel shut-off in on positionn/a
9Check cartridge weight (If applicable)x28Manual & remote set/seals in placex
10Hydrostatic test datex29Replace systems coversx
116 year maintenance daten/a30System operational & seals in placex
12Inspect cylinder and mountx31Slave system operationalx
13Operate system from terminal linkx32Clean cylinder & mountx
14Test for proper operation from remotex33Fan warning sign on hoodx
15Check operation of micro switchx34Personnel instructed in manual operation of systemx
16Check operation of gas valven/a35Proper hand portable extinguishersx
17Clean nozzlesx36Portable extinguishers properly servicedx
18Proper nozzle covers in placex37Service & Certification tag on systemx
19Check fuse links and cleann/aNOTE DISCREPANCIES OR DEFICIENCIES BELOW
COMMENTS:
System is serviced, both tanks due for hydro, wire connections should be moved to a junction box.
On this date, the above system was tested and inspected in accordance with procedures of the presently adopted editions of NFPA 17, 17A, 96 and the manufacturer's manual and was operated according to these procedures with results indicated above.
T. Smith
Service TechnicianPermit No.Date:Time:AMPMCustomers Authorized Agent
The above service technician certifies that the system was personally inspected and found conditions to be as indicated on this report

File details come from the government source that posted it. Updated .