Yakima Job Corps Lounge.xls
XLS spreadsheet 103 KB Posted
- Attached to
- USDA US Forest Service, Fort Simcoe Job Corps Center, Annual Fire Suppression Inspections
- Solicitation number
- 1282A724Q0033
- Issued by
-
Department of Agriculture Forest Service
About this file
This document is a fire system service report for the Yakima Job Corps Lounge, which appears to be related to a federal contract opportunity for the USDA Forest Service's Fort Simcoe Job Corps Center.
The report details the annual inspection and service performed on the fire suppression system, including the range hood, cylinders, fuse links, and related components. It indicates the system was serviced and is due for a hydrostatic test. The report also provides information on the cooking appliance locations and certifies the system was inspected and operated according to NFPA and manufacturer's procedures.
The related federal contract opportunity is for annual fire suppression inspections at the Fort Simcoe Job Corps Center, issued by the USDA Forest Service. The solicitation number is 1282A724Q0033, and the contract type is for commercial items. The procurement includes a Statement of Work and facility maps.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Amendment 001_1282A724Q0033.docx | DOCX document | |
| 20240606_142253.jpg | JPG image | |
| 20240606_135242.jpg | JPG image | |
| Yakima Job Corps Main.xls | XLS spreadsheet | |
| Yakima Job Corps Pizza Oven.xls | XLS spreadsheet | |
| Statement of Work - Fort Simcoe.pdf | ||
| WageDeterminationYakimaWA_SAM.pdf | ||
| ForestService_FireInspectionServicesJobCorps_Combined SS_ RFQ.pdf | ||
| MapsFromSOW.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Rells Fire Service Sheet
| Range Hood Systems Report | ||||||||||||||||
| Service Company | Date of Service | Time | A.M. | P.M. | ||||||||||||
| 3/28/24 | xx | |||||||||||||||
| Annual | Semi-Annual | Recharge | Installation | Renovation | ||||||||||||
| xx | ||||||||||||||||
| Location Of System Cylinders | ||||||||||||||||
| Right of hood | ||||||||||||||||
| Manufacturer | Model Number | Wet | Dry Chemical | |||||||||||||
| Ansul | R-102 | xx | ||||||||||||||
| Customer | Cylinder Size Master | Cylinder Size Slave | Cylinder Size Slave | |||||||||||||
| Fort Simcoe Job Corps | 3 gal | |||||||||||||||
| Name | Fuse Links 360 F | Fuse Links 450 F | Fuse Links 500 F | Other | ||||||||||||
| 40 Abella Ln | xx | 64 oz | ||||||||||||||
| Address | Fuel Shut-off | Electric | Gas | Size | ||||||||||||
| White Swan | Wa. | 98952 | xx | xx | ||||||||||||
| City | State | Zip | Serial Number | Last Hydro Test Date | Last Recharge Date | |||||||||||
| 509-874-8908 | S-047524 | Jan-03 | Jan-03 | |||||||||||||
| Telephone | Store No. | Manufacturer's Manual Reference | ||||||||||||||
| Miranda Olson | Disk 20 | |||||||||||||||
| Owner or Manager | Page Number: | Drawing Number: | ||||||||||||||
| COOKING APPLIANCE LOCATIONS: LEFT TO RIGHT | ||||||||||||||||
| 36" Fyer | 2.5' Skillet | 10" Stove | Pizza Oven | |||||||||||||
| 1 | All appliances properly covered w/correct nozzles | x | 20 | Replaced fuse links | x | |||||||||||
| 2 | Duct and plenum covered w/correct nozzles | x | 21 | Check travel of cable nuts/S-hooks | x | |||||||||||
| 3 | Check positioning of all nozzles | x | 22 | Piping & conduit securely bracketed | x | |||||||||||
| 4 | System installed in accordance w/MFG UL listing | x | 23 | Proper separation between fryers & flame | n/a | |||||||||||
| 5 | Hood/duct penetrations sealed w/weld or UL device | x | 24 | Proper clearance-flame to filters | n/a | |||||||||||
| 6 | Check if seals intact, evidence of tampering | x | 25 | Exhaust fan in operating order | x | |||||||||||
| 7 | If system has been discharged, report same | n/a | 26 | All filters replaced | x | |||||||||||
| 8 | Pressure gauge in proper range (If gauged) | n/a | 27 | Fuel shut-off in on position | n/a | |||||||||||
| 9 | Check cartridge weight (If applicable) | x | 28 | Manual & remote set/seals in place | x | |||||||||||
| 10 | Hydrostatic test date | o | 29 | Replace systems covers | x | |||||||||||
| 11 | 6 year maintenance date | n/a | 30 | System operational & seals in place | x | |||||||||||
| 12 | Inspect cylinder and mount | x | 31 | Slave system operational | x | |||||||||||
| 13 | Operate system from terminal link | x | 32 | Clean cylinder & mount | x | |||||||||||
| 14 | Test for proper operation from remote | x | 33 | Fan warning sign on hood | x | |||||||||||
| 15 | Check operation of micro switch | x | 34 | Personnel instructed in manual operation of system | x | |||||||||||
| 16 | Check operation of gas valve | n/a | 35 | Proper hand portable extinguishers | x | |||||||||||
| 17 | Clean nozzles | x | 36 | Portable extinguishers properly serviced | x | |||||||||||
| 18 | Proper nozzle covers in place | x | 37 | Service & Certification tag on system | x | |||||||||||
| 19 | Check fuse links and clean | n/a | NOTE DISCREPANCIES OR DEFICIENCIES BELOW | |||||||||||||
| COMMENTS: | ||||||||||||||||
| System is serviced, due for hydro test, | ||||||||||||||||
| On this date, the above system was tested and inspected in accordance with procedures of the presently adopted editions of NFPA 17, 17A, 96 and the manufacturer's manual and was operated according to these procedures with results indicated above. | ||||||||||||||||
| T. Smith | ||||||||||||||||
| Service Technician | Permit No. | Date: | Time: | AM | PM | Customers Authorized Agent | ||||||||||
| The above service technician certifies that the system was personally inspected and found conditions to be as indicated on this report |
File details come from the government source that posted it. Updated .