Questions and Answers Document through 1/18/2018
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| SF30_-_Amend_0002_-_1282A718Q0008_-.pdf | ||
| Corrected_Pages_8-9_-_Amendment_0001_Only.pdf | ||
| Amendment_0001_-_SF-30_-_1282A718Q0008.pdf | ||
| Attachment_2_-_AsBuilt_Drawings-20170801.pdf | ||
| Attachment_1_-_Specificaitons-20171030.pdf | ||
| Attachment_3_-_Modified_Drawings-20170901.pdf | ||
| Attachment_4_-_DB_Wage_Determinations_-_OR170023_-_9-27-2017.pdf | ||
| Attachment_5_-_Quote_Subm._Pkg..docx | DOCX document | |
| Solicitation_1282A718Q0008_-_SF-1442-Schedule-SOW-TandCs.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
1/18/2018 Timberlake JCC Water Plant Modification RFI Answers Page - 1/2
1. TIMBERLAKE JCC WATER PLANT MODIFICATION
SOLICITATION #: 1282A718Q0008 – AMENDMENT 0002 RFI
ANSWERS 1/18/2018
Question: The submersible pressure transducer in spec section 260902-1/4 states it needs to be FDA approved and ask for a Teflon coating on the cable. Our vendor contacted the manufacture and came back with this response below. is FDA approval needed and or the Teflon coated cable?
Also they require a 10 piece minimum for the special pressure range. Please advise.
Additionally the manufacturer does not have a FDA approved or Teflon cable material, so they cannot comply with the specs.
Answer:
1.01 SECTION 260902 SUBMERSIBLE LEVEL TRANSDUCER
A. Section 260902 2.01 Q For Potable Water level transducer, replace part number:
Gems Model 2600BGF1009M3GBxxx with the following part number:
B. Gems Model 2600BGF1509M3HB001 – down-ranged to 0-10 psi and first 20ft of cable to be Teflon coated. (cable length is 15 meters (49.2 ft)
C. The remainder of this section 260902 is unchanged.
D. This transducer is a modified part with additional Teflon coating added to the first 20
ft. of cable.
E. A Gems distributor that can provide this modified transducer is:
1. Ewing-Foley, Inc.
2. 10516 NE 37th Circle
3. Kirkland, WA 98033
4. (425) 822-9666
5. Direct: (425) 893-1410
F. Other submersible transducers that meet this specification will also be accepted for review.
Question: In specifications under the (DC to Frequency Converter) INTEGRATOR, they are calling for Wilkerson MM7501. That unit is obsolete with no replacement at this time and I do not see and or equal for the product. Please advise.
Answer:
1.02 SECTION 260900 2.31 INTEGRATOR (DC TO FREQUENCY CONVERTER
A. Section 260900 2.31 A12 Replace part number:
“Wilkerson MM7501 integrator” with the following part number
B. Action PAK DC to Frequency Converters Model AP7501-6061-1 C. Provide an 11 pin base for panel mounting with this unit. (Original unit had 8 pin base) D. Modify drawings to reflect different relay base pin configuration.
1/18/2018 Timberlake JCC Water Plant Modification RFI Answers Page - 2/2
E. Provide detailed project specific calibration instructions as required in section 2.31B F. Unit shall meet these following specifications: Replace section 2.31A1-12 with the following specification:
1. Input Impedance:
2. Voltage Input: Greater than 100Kohms
3. Current Input: Less than 500mV shunt @ full scale (e.g. 20W for 20mA) 4-20ma input, relay dry contact output.
4. Input Protection: Withstands 200% of span
5. Linearity (Best Straight Line & Linear Input): 0.25% of span, typical
6. Low Input Cutout: Adjustable, 0-10% of span (factory set at 1%),
7. LED cutout indication
8. 11 pin octal plug in base for connections, provide matching relay base.
9. Output: AP7500: Square-wave, 0/6V, 1:1 mark/ space ratio, source 10mA, sink
50mA. Provide mechanical relay output. Calibrate to match water meter flow, for 1 pulse per 100 gallons of flow.
10. Option C 50mA sink, 30V.
11. AP7501: Isolated DPDT relay contacts, rated 120VAC @5A or 28VDC @ 5A
(100mSec min. on time).
12. Contact Material: Silver Cadmium Oxide
13. Life: 105 operations at rated load
14. Response Time: 100 milliseconds typical, 200 milliseconds max
15. Over range Capability: Output is linear to 120% of input
16. Stability: Better than 0.05% of span per degree C
17. Common Mode Rejection: DC: > 100dB 60 Hz: > 80dB
18. Maximum Common Mode Voltage: 50V
19. Temperature Range: Operating: 0 to 60°C (32 to 140°F) Storage: -20 to 85°C (-4 to 185°F)
20. Power: Consumption: 3W typical, 5W max
21. Standard: 120 VAC (±10%, 50-400Hz)
22. Weight: 0.62lbs
G. A distributor that can provide this integrator is:
1. CFM-SF, Inc
2. Martinez, CA, Irvine, CA
3. 815 Arnold Drive #118
4. Martinez, CA 94553
5. (925) 370-1500
H. Other integrators that meet this specification will also be accepted for review.
END OF SECTION
| 1. Timberlake jcc water plant modification SOLICITATION #: 1282A718Q0008 – Amendment 0002 rfi answers 1/18/2018 |
| 1.01 Section 260902 submersible level transducer |
| A. Section 260902 2.01 Q For Potable Water level transducer, replace part number: Gems Model 2600BGF1009M3GBxxx with the following part number: |
| B. Gems Model 2600BGF1509M3HB001 – down-ranged to 0-10 psi and first 20ft of cable to be Teflon coated. (cable length is 15 meters (49.2 ft) |
| C. The remainder of this section 260902 is unchanged. |
| D. This transducer is a modified part with additional Teflon coating added to the first 20 ft. of cable. |
| E. A Gems distributor that can provide this modified transducer is: |
| 1. Ewing-Foley, Inc. |
| 2. 10516 NE 37th Circle |
| 3. Kirkland, WA 98033 |
| 4. (425) 822-9666 |
| 5. Direct: (425) 893-1410 |
F. Other submersible transducers that meet this specification will also be accepted for review.
| 1.02 section 260900 2.31 INTEGRATOR (dc to frequency converter |
| A. Section 260900 2.31 A12 Replace part number: “Wilkerson MM7501 integrator” with the following part number |
| B. Action PAK DC to Frequency Converters Model AP7501-6061-1 |
| C. Provide an 11 pin base for panel mounting with this unit. (Original unit had 8 pin base) |
| D. Modify drawings to reflect different relay base pin configuration. |
| E. Provide detailed project specific calibration instructions as required in section 2.31B |
| F. Unit shall meet these following specifications: Replace section 2.31A1-12 with the following specification: |
| 1. Input Impedance: |
| 2. Voltage Input: Greater than 100Kohms |
| 3. Current Input: Less than 500mV shunt @ full scale (e.g. 20W for 20mA) 4-20ma input, relay dry contact output. |
| 4. Input Protection: Withstands 200% of span |
| 5. Linearity (Best Straight Line & Linear Input): 0.25% of span, typical |
| 6. Low Input Cutout: Adjustable, 0-10% of span (factory set at 1%), |
| 7. LED cutout indication |
| 8. 11 pin octal plug in base for connections, provide matching relay base. |
| 9. Output: AP7500: Square-wave, 0/6V, 1:1 mark/ space ratio, source 10mA, sink 50mA. Provide mechanical relay output. Calibrate to match water meter flow, for 1 pulse per 100 gallons of flow. |
| 10. Option C 50mA sink, 30V. |
| 11. AP7501: Isolated DPDT relay contacts, rated 120VAC @5A or 28VDC @ 5A (100mSec min. on time). |
| 12. Contact Material: Silver Cadmium Oxide |
| 13. Life: 105 operations at rated load |
| 14. Response Time: 100 milliseconds typical, 200 milliseconds max |
| 15. Over range Capability: Output is linear to 120% of input |
| 16. Stability: Better than 0.05% of span per degree C |
| 17. Common Mode Rejection: DC: > 100dB 60 Hz: > 80dB |
| 18. Maximum Common Mode Voltage: 50V |
| 19. Temperature Range: Operating: 0 to 60 C (32 to 140 F) Storage: -20 to 85 C (-4 to 185 F) |
| 20. Power: Consumption: 3W typical, 5W max |
| 21. Standard: 120 VAC (±10%, 50-400Hz) |
| 22. Weight: 0.62lbs |
| G. A distributor that can provide this integrator is: |
| 1. CFM-SF, Inc |
| 2. Martinez, CA, Irvine, CA |
| 3. 815 Arnold Drive #118 |
| 4. Martinez, CA 94553 |
| 5. (925) 370-1500 |
H. Other integrators that meet this specification will also be accepted for review.
File details come from the government source that posted it.