Attachment 3 - 480V Drawings.pdf

PDF 42 MB Posted

Attached to
480 Volt Line Relocation Federal contract opportunity
Solicitation number
12805B24Q0367
Issued by
Department of Agriculture Agricultural Research Service Field Research Implementation and Information Delivery Plains Area

About this file

This document appears to be Attachment 3 - 480V Drawings related to the federal contract opportunity for "480 Volt Line Relocation" (Solicitation Number 12805B24Q0367) issued by the Department of Agriculture Agricultural Research Service Field Research Implementation and Information Delivery Plains Area.

The 480V Drawings provide technical details and specifications for the 480 volt electrical line relocation work required under this solicitation. The scope of work includes relocating the existing 480 volt overhead line infrastructure. Key details such as specific equipment, materials, and installation requirements are outlined in the drawings. This solicitation is for a fixed-price contract, with a response due date and award date not provided in the information given. No set-aside information or incumbent contractor details are included. This document serves as a supporting technical attachment to the broader solicitation for the 480 Volt Line Relocation project.

View the file

Other files for this federal contract opportunity

Other files attached to 480 Volt Line Relocation, newest first.
File Type Posted
Attachment 4 - ARS-371.pdf PDF
Attachment 1 - SOW.pdf PDF
Attachment 2 - ND20240013 - WAGE RATES.pdf PDF
Attachment 5 - ARS-372.pdf PDF
Sol_12805B24Q0367.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

PROJECT NO.:

NO. DATE BY DESCRIPTION

REVISIONS

W ROSS

E WELKER

USDAA-E FIRM

TJS

M McWILLIAMS

S KASEMAN

USDA

REAL PROPERTY

SAFETY & HEALTH

AREA ENGINEER

DRAWN BY

CHECKED BY

DESIGNER

PROJECT MANAGER

EPM

PROJECT NO.

DATE

SHEET

Service Research Agricultural

FACILITIES ENGINEERING SECTION

PLAINS AREA

2150 CENTRE AVE., BLDG D, SUITE 330

FT. COLLINS, CO 89526-8119

U S D A

CA

D

DH

DS

G

PM

C

U s e rs

\j fa n t\

D o c u m e n ts \R e v it te m p

\0 -E

L E

C R jf a n tM F

J D

T .r v t

/1

/2

:0 :4

P

M

COVER SHEET

09228.011

JEF

KJS

JEF

04/12/2024

BRL 480V LINE REPLACEMENT

USDA ARS

1616 ALBRECHT BOULEVARD

FARGO, ND 58102

ISSUED FOR

CONSTRUCTION

09228011-7-0

1616 ALBRECHT BOULEVARD

FARGO, ND 58102

ISSUED FOR CONSTRUCTION

BRL 480V LINE REPLACEMENT

COVER SHEET

ELECTRICAL

E 00 ELECTRICAL INFO SHEET

E 01 ELECTRICAL SPECIFICATIONS

E201 FLOOR PLAN - POWER & AUXILIARY SYSTEMS

E501 POWER RISER DIAGRAM

DRAWING INDEX

EXTG STEP-UP XFMR

EXTG SECONDARY CIRCUIT BREAKER

EXTG CONDUIT AND CONDUCTORS

TO BE REMOVED

EXTG AUTOMATIC TRANSFER SWITCH

TO REMAIN IN PLACE

EXTG 480 VOLT PANELBOARD

EXTG CONDUIT AND

CONDUCTORS TO BE

REMOVED

EXTG GENERATOR TO REMAIN IN PLACE

04/15/2024

A. ITEMS WHICH ARE INTENDED TO BE REMOVED, RELOCATED, OR

SALVAGED ARE SHOWN ON PLANS. ALL OTHER ITEMS ARE INTENDED

TO REMAIN IN PLACE AND ARE SHOWN AS HALF-TONE.

B. DEMOLITION SHOWN IS AS REQUIRED FOR THE COMPLETE PROJECT.

COORDINATE DEMOLITION WITH OWNER AND OTHER PROJECTS.

PROVIDE TEMPORARY POWER AND LIGHTS AS REQUIRED.

C. THE LOCATIONS OF THE EXISTING EQUIPMENT AND DEVICES WERE

OBTAINED FROM EXISTING DRAWING AND FIELD INVESTIGATION. THE

LOCATIONS OF THE EXISTING EQUIPMENT AND DEVICES ARE SHOWN

FOR THE CONVENIENCE. ACCURACY OF THE INFORMATION SHOWN IS

NOT GUARANTEED. VERIFY ALL EXISTING CONDITIONS PRIOR TO

SUBMITTING BIDS. SITE VISITS PRIOR TO SUBMISSION OF BIDS NEED

TO BE FULLY COORDINATED WITH THE OWNER.

D. CIRCUIT INFORMATION FOR ALL AFFECTED CIRCUITS SHALL BE

VERIFIED PRIOR TO COMMENCING WORK. ACCURACY OF THE

INFORMATION SHOWN AND INCLUDED ON THE PANEL SCHEDULES IS

NOT GUARANTEED.

E. THE OWNER HAS THE RIGHT TO RETAIN ALL SALVAGEABLE MATERIAL.

ANY MATERIAL THE OWNER CHOOSES NOT TO ACCEPT SHALL BE

REMOVED FROM THE SITE AND PROPERLY DISPOSED OF IN

ACCORDANCE WITH ALL APPLICABLE LOCAL, STATE, AND FEDERAL

REGULATIONS.

F. LABEL ALL SPARE OR ABANDONED CIRCUITS AND/OR CIRCUIT

BREAKERS IN ALL PANELS AFFECTED BY THE DEMOLITION. SPARE

CIRCUITS AND/OR CIRCUIT BREAKERS MAY BE REUSED FOR THE

CIRCUITING OF THE NEW OR REMODELED AREA AS SPACE AND PANEL

LOADING WILL ALLOW.

G. PROVIDE PROPER RESTORATION OF ALL EXISTING SURFACES

REQUIRING PATCHING, RE-SOD, PLASTERING, PAINTING AND/OR

OTHER REPAIR DUE TO THE DEMOLITION WORK UNDER THE TERMS

OF THIS SPECIFICATION. CLOSE AND SEAL ALL OPENINGS, REPAIR ALL

SURFACES, ETC., AS REQUIRED.

H. PROVIDE MINIMUM [10] DAYS ADVANCE NOTICE OF OUTAGES.

COORDINATE WITH OWNER FOR ALL ANTICIPATED OUTAGES. OWNER

HAS FINAL APPROVAL ON TIME AND EXTENT OF POWER OUTAGE.

I. PROTECT EXISTING MECHANICAL EQUIPMENT, PIPING, WIRING,

FURNITURE, CARPET AND OTHER APPURTENANCES FROM DAMAGE

DURING THE COURSE OF CONSTRUCTION. REPLACE DAMAGED ITEMS

FREE OF COST TO THE OWNER.

A. DRAWINGS DO NOT SHOW TOTAL NUMBER OF CONDUCTORS FOR

CIRCUITS REQUIRED. PROVIDE THE NUMBER OF CONDUCTORS

NEEDED TO COMPLETE INSTALLATION OF SPECIFIC EQUIPMENT

FURNISHED. A GREEN GROUND CONDUCTOR, SIZED PER NEC, SHALL

ALSO BE INCLUDED IN EACH CIRCUIT. ADJUST CONDUCTOR SIZES AS

NEEDED TO LIMIT VOLTAGE DROP TO LEVELS RECOMMENDED BY

NEC. COORDINATE INSPECTIONS WITH THE OWNER AND AHJ.

B. SEAL ALL PENETRATIONS THROUGH FIRE OR FIRE/SMOKE RATED

WALLS AND FLOORS.

C. ALL RACEWAYS SHALL BE SEALED AS REQUIRED BY AND IN

ACCORDANCE WITH NEC PARAGRAPHS 230.8, 300.5(G) AND 300.7(A).

ALL RACEWAYS SHALL BE SEALED AS REQUIRED BY NEC AND NFPA.

D. CABLE AND CONDUIT SHALL NOT INTERFERE WITH EQUIPMENT

ACCESS.

E. COORDINATE FINAL PANEL DIRECTORIES WITH ENGINEER AND

OWNER.

PROJECT NO.:

NO. DATE BY DESCRIPTION

REVISIONS

W ROSS

E WELKER

USDAA-E FIRM

TJS

M McWILLIAMS

S KASEMAN

USDA

REAL PROPERTY

SAFETY & HEALTH

AREA ENGINEER

DRAWN BY

CHECKED BY

DESIGNER

PROJECT MANAGER

EPM

PROJECT NO.

DATE

SHEET

Service Research Agricultural

FACILITIES ENGINEERING SECTION

PLAINS AREA

2150 CENTRE AVE., BLDG D, SUITE 330

FT. COLLINS, CO 89526-8119

U S D A

CA

D

DH

DS

G

PM

C

U s e rs

\j fa n t\

D o c u m e n ts \R e v it te m p

\0 -E

L E

C R jf a n tM F

J D

T .r v t

/1

/2

:0 :5

P

M

E 00

ELECTRICAL INFO SHEET

09228.011

JEF

TGM

JEF

04/12/2024

BRL 480V LINE REPLACEMENT

USDA ARS

1616 ALBRECHT BOULEVARD

FARGO, ND 58102

ISSUED FOR

CONSTRUCTION

09228011-7-E 00 ELECTRICAL INFO SHEET

1 SUGGESTED CONDUIT ROUTING ALONG EXISTING WALL. ROUTE

TO AVOID EXISTING EQUIPMENT, CONDUITS, STRUCTURAL

MEMBERS, ETC. DO NOT MOUNT TO EXISTING CEILING. CEILING

CONTAINS ASBESTOS WHICH MUST NOT BE DISTURBED.

2 SEAL ALL WALL PENETRATION IN ACCORDANCE WITH

SPECIFICATIONS.

3 NEW PULLBOX MOUNTING HEIGHT SHOWN ADJACENT TO NOTE.

THIS HEIGHT IS APPROXIMATE AND SHALL BE COORDINATED WITH

EXISTING CONDITIONS. PULLBOX TO BE SIZED TO ALLOW FOR

CONDUCTOR BENDING RADIUS PER MANUFACTURER'S AND NEC

REQUIREMENTS.

4 EXISTING UNDERGROUND DUCTS AND CONDUITS MAY REQUIRE

HAND DIGGING TO LOCATE. PROVIDE AS-BUILT DRAWINGS OF ALL

FOUND UTILITIES AND FINAL ROUTING OF NEW CONDUITS. PLAN

AND COORDINATE ALL OUTAGES TO 480 VOLT PANELBOARD WITH

OWNER. PROVIDE MINIMUM NOTICE OF 1 WEEK PRIOR TO ALL

OUTAGES.

5 REMOVE ALL CONDUIT AND CONDUCTORS FOR GENERATOR AND

ATS CONTROLS AND ACCESSORIES COMPLETE BACK TO SOURCE

WITHIN BUILDING 2.

6 EXACT LOCATIONS OF EXISTING UTILITIES ARE BASED ON

INCOMPLETE ORIGINAL DESIGNS AND IT IS ANTICIPATED THAT

ADDITIONAL UTILTIES HAVE BEEN INSTALLED THAT ARE NOT

SHOWN. PERFORM UTILITY LOCATES PRIOR TO EXCAVATION.

E 00 ELECTRICAL INFO SHEET

E 01 ELECTRICAL SPECIFICATIONS

E201 FLOOR PLAN - POWER & AUXILIARY SYSTEMS

E501 POWER RISER DIAGRAM

S

NORTH

ARROW

SYMBOL LEGEND

MATCHLINE

AREA A

AREA B

NEW COLUMN X

X

XX-XX

SIM

X

XX-XX

DX

SECTION/

DETAIL

PLAN

DETAIL

REFERENCE

DEMOLITION NOTE

NON-SCHEDULED

EQUIPMENT

LETTER INDICATES

NEW COLUMN LINE

SECTION/DETAIL NUMBER

SHEET NUMBER

INDICATES DIRECTION OF VIEW

DETAIL NUMBER

SHEET NUMBER

DEMOLITION

DESIGNATION

NAME

ELEVATION

LEVEL

TITLE

MARKER

VIEW NAME

SCALE: 1/8" = 1'-0"

DETAIL NUMBER

LEVEL CALLOUT

DESIGNATION

ELEVATION DESIGNATION

GRAPHIC AREA FOR DRAWING

TITLE

SCALE OF THE DRAWING

P C

J

J

O S

MS

IC

S

S

M

N

T V

VC

N E

N S

N

N D

N 2

G

K1

V

A

F

F

F

F

F S

D

P S

T S

R

M

M

T

DH

WALL MOUNTED STRIP LUMINAIRE

SYMBOL NOTES:

STROBE

HORN

MANUAL PULL STATION

HORN STROBE

PHOTOCELL

VOICE AND DATA

JUNCTION BOX - CEILING MOUNT

JUNCTION BOX - WALL MOUNT

VOICE OUTLET

DATA OUTLET

OCCUPANCY SENSOR

MOTION SENSOR

CEILING FAN

HEAT DETECTOR

SMOKE DETECTOR

REMOTE INDICATOR LIGHT

SPRINKLER TAMPER SWITCH

DUCT SMOKE DETECTOR

FLOW SWITCH

POST INDICATING VALVE SWITCH

POLE MOUNTED SITE LUMINAIRE

NURSE CALL

SPEAKER

BEDSIDE STATION

INTERCOM SPEAKER STATION

VOLUME CONTROL STATION

MICROPHONE JACK

TELEVISION OUTLET

CCTV CAMERA

SOUND, TELEVISION, AND SECURITY

FUSE

EMERGENCY PULL STATION

DISCONNECT SWITCH

STAFF STATION

DUTY STATION

DOME LIGHT

MASTER STATION

EMERGENCY GENERATOR

POWER DISTRIBUTION ONE LINE

CONDUIT UP

CONDUIT DOWN

INDICATES BUSHED CONDUIT

VOICE/DATA OUTLET

DOUBLE BED BEDSIDE STATION

DRAW OUT VACUUM CIRCUIT BREAKER

LIGHTNING SURGE ARRESTOR

THERMAL OVERLOAD RELAY

PLUG-IN OR DRAWOUT CONNECTOR

CIRCUIT BREAKER

FUSED DISCONNECT SWITCH

VOLTMETER

AMMETER

X:Y CURRENT TRANSFORMER - (RATIO)

KIRK KEY INTERLOCK

MAGNETIC DOOR HOLDER

"C" INDICATES CEILING MOUNTED

"F" INDICATES FLOOR MOUNTED

"S" INDICATES SURFACE MOUNTED

"G" INDICATES GROUND FAULT INTERRUPTING

"IG" INDICATES ISOLATED GROUND

"AC" INDICATES MOUNTING 6" ABOVE

COUNTERTOP OR BACKSPLASH

"WP" INDICATES WEATHERPROOF

"XP" INDICATES EXPLOSION PROOF

"U" INDICATES USB CHARGER

"R" INDICATES EXISTING DEVICE REMOVED

AND RELOCATED

LOWER CASE LETTER BY SWITCHES AND

FIXTURES

INDICATE ASSOCIATED UNIT FOR SWITCHING

LIGHTING

LUMINAIRE

WALL MOUNTED LUMINAIRE

RECESSED LUMINAIRE

WALL MOUNTED LUMINAIRE

SURFACE MOUNTED LUMINAIRE

TRACK LIGHTING

DIMMER SWITCH

TIMER SWITCH

WIRING DEVICES - SWITCHES

SINGLE POLE SWITCH

KEY OPERATED SWITCH

SINGLE POLE SWITCH WITH PILOT

THERMAL ELEMENT SWITCH

FOUR-WAY SWITCH

TWO POLE SWITCH

THREE-WAY SWITCH

STRIP / INDUSTRIAL LUMINAIRE

LUMINAIRE - NIGHT LIGHTING

LUMINAIRE - EMERGENCY SYSTEM

EMERGENCY BATTERY PACK LUMINAIRE

REMOTE EMERGENCY HEAD

WALL WASH LUMINAIRE

PENDANT MOUNTED LUMINAIRE

POWER POLE

METER SOCKET

POWER EQUIPMENT

WIRING DEVICES - RECEPTACLES

COMBINATION STARTER SAFETY SWITCH

RELAY - CONTROL AS NOTED

PUSHBUTTON STATION

MOTOR CONNECTION

SIMPLEX RECEPTACLE

DUPLEX RECEPTACLE

QUADRUPLEX RECEPTACLE

EMERGENCY RECEPTACLE

SPECIAL PURPOSE RECEPTACLE, NEMA

CONFIGURATION NOTED

PLUG-IN STRIP - LENGTH AND QUANTITY OF

OUTLETS AS SHOWN

SAFETY SWITCH

DROP CORD RECEPTACLE ASSEMBLY

FUSIBLE SWITCH (FUSETRON)

PANELS AND CABINETS

DISTRIBUTION PANEL

SWITCHBOARD, SWITCHGEAR, MCC

EQUIPMENT OR TERMINAL CABINET

DRY TYPE TRANSFORMER

BRANCH CIRCUIT PANEL

CONDUIT AND BOXES

FIRE ALARM SYSTEM

HORN (PA, PUBLIC ADDRESS)

TRANSFORMER

EXIT LIGHT - WALL MOUNT WITH DIRECTIONAL

ARROWS AS INDICATED, FILLED-IN QUARTERS

INDICATE ILLUMINATION SIDES

EXIT LIGHT - CEILING OR PENDANT MOUNT

WITH DIRECTIONAL ARROWS AS INDICATED,

FILLED-IN QUARTERS INDICATE ILLUMINATION

SIDES

EMERGENCY EXIT LIGHT COMBO

LOW VOLTAGE MOMENTARY CONTACT

SWITCH

H

S

S

ELECTRICAL SHEET LIST

GENERAL NOTES XGENERAL DEMO NOTESABBREVIATIONS

N P PILLOW SPEAKER

REF. NOTES ( )

PROJECT ELECTRICAL REFERENCED NOTES

GENERAL LIGHTING NOTES

GEN. POWER & AUX SYSTEMS NOTES

FB FLOOR BOX

FP FLOOR POKE-THROUGH DEVICE

N M

QTY QUANTITY

REC RECEPTACLE

REFR REFRIGERATOR

REINF REINFORCEMENT

REQD REQUIRED

TEL TELEPHONE

TEMP TEMPERATURE

TVSS TRANSIENT VOLTAGE

SURGE SUPPRESSOR

TYP TYPICAL

UG UNDERGROUND

UH UNIT HEATER

UL UNDERWRITERS

LABORATORIES

UPS UNINTERRUPTIBLE

POWER SYSTEM

VFD VARIABLE FREQUENCY

DRIVE

W WEST

W/ WITH

W/O WITHOUT

WHM WATTHOUR METER

WT WEIGHT

XFMR TRANSFORMER

ACSR ALUMINUM CONDUCTOR

STEEL REINFORCED

AFF ABOVE FINISH FLOOR

AIC AMPS INTERRUPTING

CAPACITY (SYM RMS)

AL ALUMINUM

ALT ALTERNATE

AMP AMPERE

ANSI AMERICAN NATIONAL

STANDARDS INSTITUTE

APPROX APPROXIMATE

AUTO AUTOMATIC

AVG AVERAGE

L ANGLE

BKR BREAKER

C OR CL CENTER LINE

C OR CND CONDUIT (ELECTRICAL

SHEETS)

CKT CIRCUIT

CLG CEILING

COL COLUMN

CONC CONCRETE

CONF CONFERENCE

CPT CONTROL POWER

TRANSFORMER

DC DIRECT CURRENT

DEG DEGREE

DEMO DEMOLITION

DIA DIAMETER

DIM DIMENSION

DISC DISCONNECT

DIST DISTRIBUTION

DN DOWN

DWG DRAWING

E EAST

EA EACH

EL OR

ELEV

ELEVATION - GRADE OR

BUILDING

ELEC ELECTRIC OR

ELECTRICAL

ELEV ELEVATOR

EMD ESTIMATED MAXIMUM

DEMAND

ENCL ENCLOSURE

EQUIP EQUIPMENT

EST ESTIMATE

EWC ELECTRIC WATER

COOLER

EXIST EXISTING

EXP EXPOSED

EXT EXTERIOR

FA FIRE ALARM

FLA FULL LOAD AMPS

FLEX FLEXIBLE

FLUOR FLUORESCENT

AWG GAUGE

HP HORSE POWER

HR HOUR

HTG HEATING

HTR HEATER

HZ HERTZ

ID INSIDE DIAMETER

IES ILLUMINATING

ENGINEERING SOCIETY

IN INCH

INSUL INSULATION

INT INTERIOR

KCMIL KCM KILO CIRCULAR MIL

KV KILOVOLTS

KVA KILOVOLT AMPERES

KVAR KILOVOLT AMPERES

REACTIVE

KW KILOWATT

LBS POUNDS

LRA LOCKED ROTOR AMPS

LTG LIGHTING

MAX MAXIMUM

MECH MECHANICAL

MFR MANUFACTURER

MG MOTOR GENERATOR

MH MANHOLE

MIN MINIMUM

MISC MISCELLANEOUS

N NORTH

NC NORMALLY CLOSED

NEC NATIONAL ELECTRICAL

CODE

NEMA NATIONAL ELECTRICAL

MANUFACTURERS

ASSOCIATION

NFPA NATIONAL FIRE

PROTECTION

ASSOCIATION

NIC NOT IN CONTRACT

NO NORMALLY OPEN

NO NUMBER

NTS NOT TO SCALE

OD OUTSIDE DIAMETER

OH OVERHEAD

OPNG OPENING

PH PHASE

PIV POST INDICATING VALVE

PNL PANEL

PSI POUNDS PER SQUARE IN.

WIRELESS ACCESS POINT

S

S2

S3

S4

SD

SK

SP

STE

ST

SFT

X

CONTROLLED RECEPTACLE

WB WALL AV BOX

F SPEAKER STROBES

FAAP FIRE ALARM ANNUNCIATOR

PANEL

FACP FIRE ALARM CONTROL PANEL

FAEP FIRE ALARM EXTENDER PANEL

F SPEAKERS

GFCI GROUND FAULT CIRCUIT

INTERRUPTER

CUH CABINET UNIT HEATER

EMI ELECTROMAGNETIC

INTERFERENCE

MCCB MOLDED CASE CIRCUIT

BREAKER

SOUTH

SCHED SCHEDULE

SF SQUARE FOOT (FEET)

SPEC SPECIFICATIONS

SPKR SPEAKER

SQ SQUARE

STD STANDARD

STL STEEL

SW SWITCH

SWBD SWITCH BOARD

SYM SYMMETRICAL

S

GFI GROUND FAULT CIRCUIT

INTERRUPTER

OCPD OVERCURRENT PROTECTIVE

DEVICE

RFI RADIO FREQUENCY

INTERFERENCE

SCCR SHORT CIRCUIT CURRENT

RATING

SPD SURGE PROTECTIVE DEVICE

SPDT SINGLE POLE, DOUBLE

THROW

VFC VARIABLE FREQUENCY

CONTROLLER

RC ROOM CONTROLLER

PP POWER PACK

EXISTING

COLUMN

X LETTER INDICATES EXISTING

COLUMN LINE

REFERENCE

NOTE X REFERENCE

DESIGNATION

ROOM NAME

150 SF

ROOM

NUMBER

ROOM NAME DESIGNATION

ROOM NUMBER DESIGNATION

ROOM AREA DESIGNATION

REFERENCE LEGEND

XXXX

SCHEDULED

EQUIPMENT EQUIPMENT NUMBER

XX-XX PANEL & CIRCUIT NUMBER

XX EQUIPMENT SIZE (WHERE APPLICABLE)

EQUIPMENT

XX-XX PANEL & CIRCUIT NUMBER

EQUIPMENT NAME/NUMBER

NORTH PLAN NORTH TRUE NORTH

PROJECT NO.:

NO. DATE BY DESCRIPTION

REVISIONS

W ROSS

E WELKER

USDAA-E FIRM

TJS

M McWILLIAMS

S KASEMAN

USDA

REAL PROPERTY

SAFETY & HEALTH

AREA ENGINEER

DRAWN BY

CHECKED BY

DESIGNER

PROJECT MANAGER

EPM

PROJECT NO.

DATE

SHEET

Service Research Agricultural

FACILITIES ENGINEERING SECTION

PLAINS AREA

2150 CENTRE AVE., BLDG D, SUITE 330

FT. COLLINS, CO 89526-8119

U S D A

CA

D

DH

DS

G

PM

C

U s e rs

\j fa n t\

D o c u m e n ts \R e v it te m p

\0 -E

L E

C R jf a n tM F

J D

T .r v t

/1

/2

:0 :5

P

M

E 01

ELECTRICAL SPECIFICATIONS

09228.011

JEF

TGM

JEF

04/12/2024

BRL 480V LINE REPLACEMENT

USDA ARS

1616 ALBRECHT BOULEVARD

FARGO, ND 58102

ISSUED FOR

CONSTRUCTION

09228011-7-E 01 ELECTRICAL SPECIFICATIONS

(G E N E R A T O R

'EXTG MDP'

EXTG 208 TO 480 VOLT STEP-UP

TRANSFORMER

EXTG TRANSFORMER

PRIMARY CIRCUIT

BREAKER

EXTG TRANSFORMER

SECONDARY CIRCUIT

BREAKER

EXTG UTILITY TRANSFORMER

EXTG PULLBOX AND

UTILITY METERS

EXTG UNDERGROUND PVC

CONDUITS AND CONDUCTORS TO

BE ABANDONDED IN PLACE

UNDER PAVING. REMOVE

CONDUIT AND CONDUCTORS

UNDER GRASS AREAS.

NEW UNDERGROUND PVC CONDUITS

AND CONDUCTORS

EXTG 480 VOLT PANELBOARD

EXTG 250KW GENERATOR

EXTG AUTOMATIC

TRANSFER SWITCH

EXTG CONDUIT AND

CONDUCTORS TO BE REMOVED

2(TYP.)

E201

NEW PULLBOX

(APPROX. +12.5' ABOVE

GRADE TO CENTER)

E201

NEW PULLBOX

PROTECT EXISTING

TREE AND TREE ROOTS

EXTG STEAM TUNNEL OR

ENCASED PIPE

(TYP. SPACE)

3(TYP.)

SEWER MAIN

NEW PULLBOX

(APPROX. +17.5' AFF TO

CENTER)

NEW CONDUITS

(APPROX. +17.5' AFF TO

CENTER)

EXTG WATER MAIN

EXTG 208V ELECTRIC

FEEDER

6(TYP.)

EXTG 208V ELECTRIC

FEEDER

EXTG 208V ELECTRIC

FEEDER

C O

V E

R

12" MIN

FINISHED GRADE

UNDISTURBED

NATIVE SOIL

NATIVE SOIL BACKFILL

COMPACTED TO MINIMUM

95% STANDARD PROCTOR

AND AS NEEDED TO

AVOID SETTLEMENT

RED WITH BLACK LETTERING,

3" WIDE, BRADY PART

#91295 OR EQUAL

BURIED NON-DETECTABLE

MARKING TAPE

CONDUIT(S)

SAND BEDDING LAYER

PATCH PAVING OR RE-SOD GRASS

AREA AS APPROPRIATE

PROJECT NO.:

NO. DATE BY DESCRIPTION

REVISIONS

W ROSS

E WELKER

USDAA-E FIRM

TJS

M McWILLIAMS

S KASEMAN

USDA

REAL PROPERTY

SAFETY & HEALTH

AREA ENGINEER

DRAWN BY

CHECKED BY

DESIGNER

PROJECT MANAGER

EPM

PROJECT NO.

DATE

SHEET

Service Research Agricultural

FACILITIES ENGINEERING SECTION

PLAINS AREA

2150 CENTRE AVE., BLDG D, SUITE 330

FT. COLLINS, CO 89526-8119

U S D A

CA

D

DH

DS

G

PM

C

U s e rs

\j fa n t\

D o c u m e n ts \R e v it te m p

\0 -E

L E

C R jf a n tM F

J D

T .r v t

/1

/2

:0 :5

P

M

E201

FLOOR PLAN - POWER & AUXILIARY SYSTEMS

09228.011

JEF

TGM

JEF

04/12/2024

BRL 480V LINE REPLACEMENT

USDA ARS

1616 ALBRECHT BOULEVARD

FARGO, ND 58102

ISSUED FOR

CONSTRUCTION

09228011-7-E201 FLOOR PLAN - POWER & AUXILIARY SYSTEMS

NORTH

REF. NOTES ( ):X

1 SUGGESTED CONDUIT ROUTING ALONG EXISTING WALL. ROUTE TO AVOID

EXISTING EQUIPMENT, CONDUITS, STRUCTURAL MEMBERS, ETC. DO NOT

MOUNT TO EXISTING CEILING. CEILING CONTAINS ASBESTOS WHICH MUST

NOT BE DISTURBED.

2 SEAL ALL WALL PENETRATION IN ACCORDANCE WITH SPECIFICATIONS.

3 NEW PULLBOX MOUNTING HEIGHT SHOWN ADJACENT TO NOTE. THIS

HEIGHT IS APPROXIMATE AND SHALL BE COORDINATED WITH EXISTING

CONDITIONS. PULLBOX TO BE SIZED TO ALLOW FOR CONDUCTOR

BENDING RADIUS PER MANUFACTURER'S AND NEC REQUIREMENTS.

4 EXISTING UNDERGROUND DUCTS AND CONDUITS MAY REQUIRE HAND

DIGGING TO LOCATE. PROVIDE AS-BUILT DRAWINGS OF ALL FOUND

UTILITIES AND FINAL ROUTING OF NEW CONDUITS. PLAN AND

COORDINATE ALL OUTAGES TO 480 VOLT PANELBOARD WITH OWNER.

PROVIDE MINIMUM NOTICE OF 1 WEEK PRIOR TO ALL OUTAGES.

5 REMOVE ALL CONDUIT AND CONDUCTORS FOR GENERATOR AND ATS

CONTROLS AND ACCESSORIES COMPLETE BACK TO SOURCE WITHIN

BUILDING 2.

6 EXACT LOCATIONS OF EXISTING UTILITIES ARE BASED ON INCOMPLETE

ORIGINAL DESIGNS AND IT IS ANTICIPATED THAT ADDITIONAL UTILTIES

HAVE BEEN INSTALLED THAT ARE NOT SHOWN. PERFORM UTILITY

LOCATES PRIOR TO EXCAVATION.

SCALE: 1/8" = 1'-0"

FIRST FLOOR PLAN - POWER & AUXILIARY SYSTEMS

SCALE: 12" = 1'-0"

PAVEMENT DETAIL

SCALE: 12" = 1'-0"

Trench Detail 24"

GROUND LEVEL

T

EXTG UTILITY

XFMR

EXTG SPLICE

CABINET

T

GENERATOR

PANEL

'XXX'

EXTG

PRIMARY

CIRCUIT

BREAKER

EXTG STEP-

UP XFMR

EXTG

SECONDARY

CIRCUIT

BREAKER

EXTG

AUTOMATIC

TRANSFER

SWITCH

EXTERIOR BUILDING 2 EXTERIOR BUILDING 1

REMOVE CONDUIT AND WIRES

REMOVE CONDUIT AND WIRES

ABOVE GROUND AND AS

REQUIRED, ABANDON IN

PLACE UNDER GRASS,

PAVING, AND SIDEWALK

GROUND LEVEL

T

EXTG UTILITY

XFMR

EXTG SPLICE

CABINET

T

EXTG 480V

PANELBOARD

EXTG

PRIMARY

CIRCUIT

BREAKER

EXTG STEP-

UP XFMR

EXTG

SECONDARY

CIRCUIT

BREAKER

EXTERIOR BUILDING 2 EXTERIOR BUILDING 1

NEW CONDUIT AND WIRES

INTERIOR BUILDING 2

ROUTE CONDUIT AND WIRES

TO AVOID EXISTING PIPES,

CABLE TRAYS, LUMINAIRES,

ETC.

F600A4G

EXTERIOR BUILDING 2

NEW PULLBOX

NEW PULLBOX

SYSTEM CONDUCTOR IDENTIFICATION

208Y/120V 3Φ 4W

A – PHASE – BLACK

B – PHASE – RED

C – PHASE – BLUE

NEUTRAL – WHITE

GROUND – GREEN

SYSTEM CONDUCTOR IDENTIFICATION

480Y/277V 3Φ 4W

A – PHASE – BROWN

B – PHASE – ORANGE

C – PHASE – YELLOW

NEUTRAL – GRAY

GROUND – GREEN

SYSTEM IDENTIFICATION DECAL

SYSTEM CONDUCTOR IDENTIFICATION

120/240V

A – PHASE – BLACK

B – PHASE – RED

NEUTRAL – WHITE

GROUND – GREEN

SYSTEM CONDUCTOR IDENTIFICATION

240V DELTA 3Φ 3W

A – PHASE – PINK

B – PHASE – PURPLE

C – PHASE – TAN

GROUND – GREEN

FED FROM MDP

PANEL IDENTIFICATION DECAL

PANEL TYPE PANEL

DESIGNATION

NOTES:

1. DECALS SHALL BE LAMINATED ACRYLIC WITH WHITE ENGRAVED LETTERING ON A BLACK BACKGROUND. PANELS OR EQUIPMENT CONNECTED TO AN ALTERNATE

POWER SOURCE SHALL HAVE WHITE ENGRAVED LETTERING ON A RED BACKGROUND.

2. DECALS SHALL BE SIZED TO ACCOMMODATE SPECIFIED LEGENDS BUT NO SMALLER THAN SIZES SHOWN, MINIMUM OF 1/16” THICK.

3. DECALS SHALL BE PUNCHED OR DRILLED FOR MECHANICAL FASTENERS WITH 1/4” GROMMETS IN CORNERS FOR MOUNTING.

4. COLORS FOR 240V DELTA SYSTEMS BASED ON AVAILABLE COLORS OFFERED BY SOUTHWIRE. OTHER COLORS THAT DO NOT CONFLICT WITH OTHER VOLTAGE

SYSTEMS PERMITTED.

CR = CRITICAL

EQ = EQUIPMENT

LS = LIFE SAFETY

EM = EMERGENCY

OS = OPTIONAL STANDBY

H = 480V L = 208V

H1

DISCONNECT IDENTIFICATION

DECAL TO BE PERMANENTLY

POSTED. SEE DETAILS AT RIGHT.

SIZE: 1”H x 3”W. TEXT HEIGHT: 1/4"

PANEL IDENTIFICATION DECAL TO

BE PERMANENTLY POSTED. SEE

DETAILS AT RIGHT.

SIZE: 1”H x 3”W. TEXT HEIGHT: 1/4"

SYSTEM IDENTIFICATION DECAL TO BE

PERMANENTLY POSTED.

SIZE: 1-1/2”H x 3”W. TEXT HEIGHT: 1/8"

BRANCH/FEEDER IDENTIFICATION

DECAL TO BE PERMANENTLY

POSTED. SEE DETAILS AT RIGHT.

SIZE: 1”H x 3”W. TEXT HEIGHT: 1/4"

PANEL H1

BRANCH/FEEDER IDENTIFICATION DECAL

TRANSFORMER IDENTIFICATION

DECAL TO BE PERMANENTLY

POSTED. SEE DETAILS AT RIGHT.

SIZE: 1”H x 3”W. TEXT HEIGHT: 1/4"

TL1

TRANSFORMER IDENTIFICATION DECAL

FED FROM MDP

FEEDS L1

EF-1

DISCONNECT IDENTIFICATION DECAL

480V

FED FROM MDP

PROJECT NO.:

NO. DATE BY DESCRIPTION

REVISIONS

W ROSS

E WELKER

USDAA-E FIRM

TJS

M McWILLIAMS

S KASEMAN

USDA

REAL PROPERTY

SAFETY & HEALTH

AREA ENGINEER

DRAWN BY

CHECKED BY

DESIGNER

PROJECT MANAGER

EPM

PROJECT NO.

DATE

SHEET

Service Research Agricultural

FACILITIES ENGINEERING SECTION

PLAINS AREA

2150 CENTRE AVE., BLDG D, SUITE 330

FT. COLLINS, CO 89526-8119

U S D A

CA

D

DH

DS

G

PM

C

U s e rs

\j fa n t\

D o c u m e n ts \R e v it te m p

\0 -E

L E

C R jf a n tM F

J D

T .r v t

/1

/2

:0 :5

P

M

E501

POWER RISER DIAGRAM

09228.011

JEF

TGM

JEF

04/12/2024

BRL 480V LINE REPLACEMENT

USDA ARS

1616 ALBRECHT BOULEVARD

FARGO, ND 58102

ISSUED FOR

CONSTRUCTION

09228011-7-E501 POWER RISER DIAGRAM

FEEDER SCHEDULE ( ):FXXXXXXX

F600A4G 2 SETS OF 4#350, 1#1G - 3"C

REF. NOTES ( ):X

SCALE: NOT TO SCALE

POWER RISER DIAGRAM - EXTG

SCALE: NOT TO SCALE

POWER RISER DIAGRAM - NEW

SCALE: 1/8" = 1'-0"

PANELBOARD & EQUIPMENT IDENTIFICATION DETAIL

09228011- BRL 480V Line Replacement Cover Sheet
09228011- Electrical Info Sheet - E00
09228011- Electrical Specifications - E01
09228011- Floor Plan - Power & Auxiliary Systems - E201
09228011- Power Riser Diagram - E501

File details come from the government source that posted it. Updated .