Attachment 3 - 480V Drawings.pdf
PDF 42 MB Posted
- Attached to
- 480 Volt Line Relocation Federal contract opportunity
- Solicitation number
- 12805B24Q0367
About this file
This document appears to be Attachment 3 - 480V Drawings related to the federal contract opportunity for "480 Volt Line Relocation" (Solicitation Number 12805B24Q0367) issued by the Department of Agriculture Agricultural Research Service Field Research Implementation and Information Delivery Plains Area.
The 480V Drawings provide technical details and specifications for the 480 volt electrical line relocation work required under this solicitation. The scope of work includes relocating the existing 480 volt overhead line infrastructure. Key details such as specific equipment, materials, and installation requirements are outlined in the drawings. This solicitation is for a fixed-price contract, with a response due date and award date not provided in the information given. No set-aside information or incumbent contractor details are included. This document serves as a supporting technical attachment to the broader solicitation for the 480 Volt Line Relocation project.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Attachment 4 - ARS-371.pdf | ||
| Attachment 1 - SOW.pdf | ||
| Attachment 2 - ND20240013 - WAGE RATES.pdf | ||
| Attachment 5 - ARS-372.pdf | ||
| Sol_12805B24Q0367.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PROJECT NO.:
NO. DATE BY DESCRIPTION
REVISIONS
W ROSS
E WELKER
USDAA-E FIRM
TJS
M McWILLIAMS
S KASEMAN
USDA
REAL PROPERTY
SAFETY & HEALTH
AREA ENGINEER
DRAWN BY
CHECKED BY
DESIGNER
PROJECT MANAGER
EPM
PROJECT NO.
DATE
SHEET
Service Research Agricultural
FACILITIES ENGINEERING SECTION
PLAINS AREA
2150 CENTRE AVE., BLDG D, SUITE 330
FT. COLLINS, CO 89526-8119
U S D A
CA
D
DH
DS
G
PM
C
U s e rs
\j fa n t\
D o c u m e n ts \R e v it te m p
\0 -E
L E
C R jf a n tM F
J D
T .r v t
/1
/2
:0 :4
P
M
COVER SHEET
09228.011
JEF
KJS
JEF
04/12/2024
BRL 480V LINE REPLACEMENT
USDA ARS
1616 ALBRECHT BOULEVARD
FARGO, ND 58102
ISSUED FOR
CONSTRUCTION
09228011-7-0
1616 ALBRECHT BOULEVARD
FARGO, ND 58102
ISSUED FOR CONSTRUCTION
BRL 480V LINE REPLACEMENT
COVER SHEET
ELECTRICAL
E 00 ELECTRICAL INFO SHEET
E 01 ELECTRICAL SPECIFICATIONS
E201 FLOOR PLAN - POWER & AUXILIARY SYSTEMS
E501 POWER RISER DIAGRAM
DRAWING INDEX
EXTG STEP-UP XFMR
EXTG SECONDARY CIRCUIT BREAKER
EXTG CONDUIT AND CONDUCTORS
TO BE REMOVED
EXTG AUTOMATIC TRANSFER SWITCH
TO REMAIN IN PLACE
EXTG 480 VOLT PANELBOARD
EXTG CONDUIT AND
CONDUCTORS TO BE
REMOVED
EXTG GENERATOR TO REMAIN IN PLACE
04/15/2024
A. ITEMS WHICH ARE INTENDED TO BE REMOVED, RELOCATED, OR
SALVAGED ARE SHOWN ON PLANS. ALL OTHER ITEMS ARE INTENDED
TO REMAIN IN PLACE AND ARE SHOWN AS HALF-TONE.
B. DEMOLITION SHOWN IS AS REQUIRED FOR THE COMPLETE PROJECT.
COORDINATE DEMOLITION WITH OWNER AND OTHER PROJECTS.
PROVIDE TEMPORARY POWER AND LIGHTS AS REQUIRED.
C. THE LOCATIONS OF THE EXISTING EQUIPMENT AND DEVICES WERE
OBTAINED FROM EXISTING DRAWING AND FIELD INVESTIGATION. THE
LOCATIONS OF THE EXISTING EQUIPMENT AND DEVICES ARE SHOWN
FOR THE CONVENIENCE. ACCURACY OF THE INFORMATION SHOWN IS
NOT GUARANTEED. VERIFY ALL EXISTING CONDITIONS PRIOR TO
SUBMITTING BIDS. SITE VISITS PRIOR TO SUBMISSION OF BIDS NEED
TO BE FULLY COORDINATED WITH THE OWNER.
D. CIRCUIT INFORMATION FOR ALL AFFECTED CIRCUITS SHALL BE
VERIFIED PRIOR TO COMMENCING WORK. ACCURACY OF THE
INFORMATION SHOWN AND INCLUDED ON THE PANEL SCHEDULES IS
NOT GUARANTEED.
E. THE OWNER HAS THE RIGHT TO RETAIN ALL SALVAGEABLE MATERIAL.
ANY MATERIAL THE OWNER CHOOSES NOT TO ACCEPT SHALL BE
REMOVED FROM THE SITE AND PROPERLY DISPOSED OF IN
ACCORDANCE WITH ALL APPLICABLE LOCAL, STATE, AND FEDERAL
REGULATIONS.
F. LABEL ALL SPARE OR ABANDONED CIRCUITS AND/OR CIRCUIT
BREAKERS IN ALL PANELS AFFECTED BY THE DEMOLITION. SPARE
CIRCUITS AND/OR CIRCUIT BREAKERS MAY BE REUSED FOR THE
CIRCUITING OF THE NEW OR REMODELED AREA AS SPACE AND PANEL
LOADING WILL ALLOW.
G. PROVIDE PROPER RESTORATION OF ALL EXISTING SURFACES
REQUIRING PATCHING, RE-SOD, PLASTERING, PAINTING AND/OR
OTHER REPAIR DUE TO THE DEMOLITION WORK UNDER THE TERMS
OF THIS SPECIFICATION. CLOSE AND SEAL ALL OPENINGS, REPAIR ALL
SURFACES, ETC., AS REQUIRED.
H. PROVIDE MINIMUM [10] DAYS ADVANCE NOTICE OF OUTAGES.
COORDINATE WITH OWNER FOR ALL ANTICIPATED OUTAGES. OWNER
HAS FINAL APPROVAL ON TIME AND EXTENT OF POWER OUTAGE.
I. PROTECT EXISTING MECHANICAL EQUIPMENT, PIPING, WIRING,
FURNITURE, CARPET AND OTHER APPURTENANCES FROM DAMAGE
DURING THE COURSE OF CONSTRUCTION. REPLACE DAMAGED ITEMS
FREE OF COST TO THE OWNER.
A. DRAWINGS DO NOT SHOW TOTAL NUMBER OF CONDUCTORS FOR
CIRCUITS REQUIRED. PROVIDE THE NUMBER OF CONDUCTORS
NEEDED TO COMPLETE INSTALLATION OF SPECIFIC EQUIPMENT
FURNISHED. A GREEN GROUND CONDUCTOR, SIZED PER NEC, SHALL
ALSO BE INCLUDED IN EACH CIRCUIT. ADJUST CONDUCTOR SIZES AS
NEEDED TO LIMIT VOLTAGE DROP TO LEVELS RECOMMENDED BY
NEC. COORDINATE INSPECTIONS WITH THE OWNER AND AHJ.
B. SEAL ALL PENETRATIONS THROUGH FIRE OR FIRE/SMOKE RATED
WALLS AND FLOORS.
C. ALL RACEWAYS SHALL BE SEALED AS REQUIRED BY AND IN
ACCORDANCE WITH NEC PARAGRAPHS 230.8, 300.5(G) AND 300.7(A).
ALL RACEWAYS SHALL BE SEALED AS REQUIRED BY NEC AND NFPA.
D. CABLE AND CONDUIT SHALL NOT INTERFERE WITH EQUIPMENT
ACCESS.
E. COORDINATE FINAL PANEL DIRECTORIES WITH ENGINEER AND
OWNER.
PROJECT NO.:
NO. DATE BY DESCRIPTION
REVISIONS
W ROSS
E WELKER
USDAA-E FIRM
TJS
M McWILLIAMS
S KASEMAN
USDA
REAL PROPERTY
SAFETY & HEALTH
AREA ENGINEER
DRAWN BY
CHECKED BY
DESIGNER
PROJECT MANAGER
EPM
PROJECT NO.
DATE
SHEET
Service Research Agricultural
FACILITIES ENGINEERING SECTION
PLAINS AREA
2150 CENTRE AVE., BLDG D, SUITE 330
FT. COLLINS, CO 89526-8119
U S D A
CA
D
DH
DS
G
PM
C
U s e rs
\j fa n t\
D o c u m e n ts \R e v it te m p
\0 -E
L E
C R jf a n tM F
J D
T .r v t
/1
/2
:0 :5
P
M
E 00
ELECTRICAL INFO SHEET
09228.011
JEF
TGM
JEF
04/12/2024
BRL 480V LINE REPLACEMENT
USDA ARS
1616 ALBRECHT BOULEVARD
FARGO, ND 58102
ISSUED FOR
CONSTRUCTION
09228011-7-E 00 ELECTRICAL INFO SHEET
1 SUGGESTED CONDUIT ROUTING ALONG EXISTING WALL. ROUTE
TO AVOID EXISTING EQUIPMENT, CONDUITS, STRUCTURAL
MEMBERS, ETC. DO NOT MOUNT TO EXISTING CEILING. CEILING
CONTAINS ASBESTOS WHICH MUST NOT BE DISTURBED.
2 SEAL ALL WALL PENETRATION IN ACCORDANCE WITH
SPECIFICATIONS.
3 NEW PULLBOX MOUNTING HEIGHT SHOWN ADJACENT TO NOTE.
THIS HEIGHT IS APPROXIMATE AND SHALL BE COORDINATED WITH
EXISTING CONDITIONS. PULLBOX TO BE SIZED TO ALLOW FOR
CONDUCTOR BENDING RADIUS PER MANUFACTURER'S AND NEC
REQUIREMENTS.
4 EXISTING UNDERGROUND DUCTS AND CONDUITS MAY REQUIRE
HAND DIGGING TO LOCATE. PROVIDE AS-BUILT DRAWINGS OF ALL
FOUND UTILITIES AND FINAL ROUTING OF NEW CONDUITS. PLAN
AND COORDINATE ALL OUTAGES TO 480 VOLT PANELBOARD WITH
OWNER. PROVIDE MINIMUM NOTICE OF 1 WEEK PRIOR TO ALL
OUTAGES.
5 REMOVE ALL CONDUIT AND CONDUCTORS FOR GENERATOR AND
ATS CONTROLS AND ACCESSORIES COMPLETE BACK TO SOURCE
WITHIN BUILDING 2.
6 EXACT LOCATIONS OF EXISTING UTILITIES ARE BASED ON
INCOMPLETE ORIGINAL DESIGNS AND IT IS ANTICIPATED THAT
ADDITIONAL UTILTIES HAVE BEEN INSTALLED THAT ARE NOT
SHOWN. PERFORM UTILITY LOCATES PRIOR TO EXCAVATION.
E 00 ELECTRICAL INFO SHEET
E 01 ELECTRICAL SPECIFICATIONS
E201 FLOOR PLAN - POWER & AUXILIARY SYSTEMS
E501 POWER RISER DIAGRAM
S
NORTH
ARROW
SYMBOL LEGEND
MATCHLINE
AREA A
AREA B
NEW COLUMN X
X
XX-XX
SIM
X
XX-XX
DX
SECTION/
DETAIL
PLAN
DETAIL
REFERENCE
DEMOLITION NOTE
NON-SCHEDULED
EQUIPMENT
LETTER INDICATES
NEW COLUMN LINE
SECTION/DETAIL NUMBER
SHEET NUMBER
INDICATES DIRECTION OF VIEW
DETAIL NUMBER
SHEET NUMBER
DEMOLITION
DESIGNATION
NAME
ELEVATION
LEVEL
TITLE
MARKER
VIEW NAME
SCALE: 1/8" = 1'-0"
DETAIL NUMBER
LEVEL CALLOUT
DESIGNATION
ELEVATION DESIGNATION
GRAPHIC AREA FOR DRAWING
TITLE
SCALE OF THE DRAWING
P C
J
J
O S
MS
IC
S
S
M
N
T V
VC
N E
N S
N
N D
N 2
G
K1
V
A
F
F
F
F
F S
D
P S
T S
R
M
M
T
DH
WALL MOUNTED STRIP LUMINAIRE
SYMBOL NOTES:
STROBE
HORN
MANUAL PULL STATION
HORN STROBE
PHOTOCELL
VOICE AND DATA
JUNCTION BOX - CEILING MOUNT
JUNCTION BOX - WALL MOUNT
VOICE OUTLET
DATA OUTLET
OCCUPANCY SENSOR
MOTION SENSOR
CEILING FAN
HEAT DETECTOR
SMOKE DETECTOR
REMOTE INDICATOR LIGHT
SPRINKLER TAMPER SWITCH
DUCT SMOKE DETECTOR
FLOW SWITCH
POST INDICATING VALVE SWITCH
POLE MOUNTED SITE LUMINAIRE
NURSE CALL
SPEAKER
BEDSIDE STATION
INTERCOM SPEAKER STATION
VOLUME CONTROL STATION
MICROPHONE JACK
TELEVISION OUTLET
CCTV CAMERA
SOUND, TELEVISION, AND SECURITY
FUSE
EMERGENCY PULL STATION
DISCONNECT SWITCH
STAFF STATION
DUTY STATION
DOME LIGHT
MASTER STATION
EMERGENCY GENERATOR
POWER DISTRIBUTION ONE LINE
CONDUIT UP
CONDUIT DOWN
INDICATES BUSHED CONDUIT
VOICE/DATA OUTLET
DOUBLE BED BEDSIDE STATION
DRAW OUT VACUUM CIRCUIT BREAKER
LIGHTNING SURGE ARRESTOR
THERMAL OVERLOAD RELAY
PLUG-IN OR DRAWOUT CONNECTOR
CIRCUIT BREAKER
FUSED DISCONNECT SWITCH
VOLTMETER
AMMETER
X:Y CURRENT TRANSFORMER - (RATIO)
KIRK KEY INTERLOCK
MAGNETIC DOOR HOLDER
"C" INDICATES CEILING MOUNTED
"F" INDICATES FLOOR MOUNTED
"S" INDICATES SURFACE MOUNTED
"G" INDICATES GROUND FAULT INTERRUPTING
"IG" INDICATES ISOLATED GROUND
"AC" INDICATES MOUNTING 6" ABOVE
COUNTERTOP OR BACKSPLASH
"WP" INDICATES WEATHERPROOF
"XP" INDICATES EXPLOSION PROOF
"U" INDICATES USB CHARGER
"R" INDICATES EXISTING DEVICE REMOVED
AND RELOCATED
LOWER CASE LETTER BY SWITCHES AND
FIXTURES
INDICATE ASSOCIATED UNIT FOR SWITCHING
LIGHTING
LUMINAIRE
WALL MOUNTED LUMINAIRE
RECESSED LUMINAIRE
WALL MOUNTED LUMINAIRE
SURFACE MOUNTED LUMINAIRE
TRACK LIGHTING
DIMMER SWITCH
TIMER SWITCH
WIRING DEVICES - SWITCHES
SINGLE POLE SWITCH
KEY OPERATED SWITCH
SINGLE POLE SWITCH WITH PILOT
THERMAL ELEMENT SWITCH
FOUR-WAY SWITCH
TWO POLE SWITCH
THREE-WAY SWITCH
STRIP / INDUSTRIAL LUMINAIRE
LUMINAIRE - NIGHT LIGHTING
LUMINAIRE - EMERGENCY SYSTEM
EMERGENCY BATTERY PACK LUMINAIRE
REMOTE EMERGENCY HEAD
WALL WASH LUMINAIRE
PENDANT MOUNTED LUMINAIRE
POWER POLE
METER SOCKET
POWER EQUIPMENT
WIRING DEVICES - RECEPTACLES
COMBINATION STARTER SAFETY SWITCH
RELAY - CONTROL AS NOTED
PUSHBUTTON STATION
MOTOR CONNECTION
SIMPLEX RECEPTACLE
DUPLEX RECEPTACLE
QUADRUPLEX RECEPTACLE
EMERGENCY RECEPTACLE
SPECIAL PURPOSE RECEPTACLE, NEMA
CONFIGURATION NOTED
PLUG-IN STRIP - LENGTH AND QUANTITY OF
OUTLETS AS SHOWN
SAFETY SWITCH
DROP CORD RECEPTACLE ASSEMBLY
FUSIBLE SWITCH (FUSETRON)
PANELS AND CABINETS
DISTRIBUTION PANEL
SWITCHBOARD, SWITCHGEAR, MCC
EQUIPMENT OR TERMINAL CABINET
DRY TYPE TRANSFORMER
BRANCH CIRCUIT PANEL
CONDUIT AND BOXES
FIRE ALARM SYSTEM
HORN (PA, PUBLIC ADDRESS)
TRANSFORMER
EXIT LIGHT - WALL MOUNT WITH DIRECTIONAL
ARROWS AS INDICATED, FILLED-IN QUARTERS
INDICATE ILLUMINATION SIDES
EXIT LIGHT - CEILING OR PENDANT MOUNT
WITH DIRECTIONAL ARROWS AS INDICATED,
FILLED-IN QUARTERS INDICATE ILLUMINATION
SIDES
EMERGENCY EXIT LIGHT COMBO
LOW VOLTAGE MOMENTARY CONTACT
SWITCH
H
S
S
ELECTRICAL SHEET LIST
GENERAL NOTES XGENERAL DEMO NOTESABBREVIATIONS
N P PILLOW SPEAKER
REF. NOTES ( )
PROJECT ELECTRICAL REFERENCED NOTES
GENERAL LIGHTING NOTES
GEN. POWER & AUX SYSTEMS NOTES
FB FLOOR BOX
FP FLOOR POKE-THROUGH DEVICE
N M
QTY QUANTITY
REC RECEPTACLE
REFR REFRIGERATOR
REINF REINFORCEMENT
REQD REQUIRED
TEL TELEPHONE
TEMP TEMPERATURE
TVSS TRANSIENT VOLTAGE
SURGE SUPPRESSOR
TYP TYPICAL
UG UNDERGROUND
UH UNIT HEATER
UL UNDERWRITERS
LABORATORIES
UPS UNINTERRUPTIBLE
POWER SYSTEM
VFD VARIABLE FREQUENCY
DRIVE
W WEST
W/ WITH
W/O WITHOUT
WHM WATTHOUR METER
WT WEIGHT
XFMR TRANSFORMER
ACSR ALUMINUM CONDUCTOR
STEEL REINFORCED
AFF ABOVE FINISH FLOOR
AIC AMPS INTERRUPTING
CAPACITY (SYM RMS)
AL ALUMINUM
ALT ALTERNATE
AMP AMPERE
ANSI AMERICAN NATIONAL
STANDARDS INSTITUTE
APPROX APPROXIMATE
AUTO AUTOMATIC
AVG AVERAGE
L ANGLE
BKR BREAKER
C OR CL CENTER LINE
C OR CND CONDUIT (ELECTRICAL
SHEETS)
CKT CIRCUIT
CLG CEILING
COL COLUMN
CONC CONCRETE
CONF CONFERENCE
CPT CONTROL POWER
TRANSFORMER
DC DIRECT CURRENT
DEG DEGREE
DEMO DEMOLITION
DIA DIAMETER
DIM DIMENSION
DISC DISCONNECT
DIST DISTRIBUTION
DN DOWN
DWG DRAWING
E EAST
EA EACH
EL OR
ELEV
ELEVATION - GRADE OR
BUILDING
ELEC ELECTRIC OR
ELECTRICAL
ELEV ELEVATOR
EMD ESTIMATED MAXIMUM
DEMAND
ENCL ENCLOSURE
EQUIP EQUIPMENT
EST ESTIMATE
EWC ELECTRIC WATER
COOLER
EXIST EXISTING
EXP EXPOSED
EXT EXTERIOR
FA FIRE ALARM
FLA FULL LOAD AMPS
FLEX FLEXIBLE
FLUOR FLUORESCENT
AWG GAUGE
HP HORSE POWER
HR HOUR
HTG HEATING
HTR HEATER
HZ HERTZ
ID INSIDE DIAMETER
IES ILLUMINATING
ENGINEERING SOCIETY
IN INCH
INSUL INSULATION
INT INTERIOR
KCMIL KCM KILO CIRCULAR MIL
KV KILOVOLTS
KVA KILOVOLT AMPERES
KVAR KILOVOLT AMPERES
REACTIVE
KW KILOWATT
LBS POUNDS
LRA LOCKED ROTOR AMPS
LTG LIGHTING
MAX MAXIMUM
MECH MECHANICAL
MFR MANUFACTURER
MG MOTOR GENERATOR
MH MANHOLE
MIN MINIMUM
MISC MISCELLANEOUS
N NORTH
NC NORMALLY CLOSED
NEC NATIONAL ELECTRICAL
CODE
NEMA NATIONAL ELECTRICAL
MANUFACTURERS
ASSOCIATION
NFPA NATIONAL FIRE
PROTECTION
ASSOCIATION
NIC NOT IN CONTRACT
NO NORMALLY OPEN
NO NUMBER
NTS NOT TO SCALE
OD OUTSIDE DIAMETER
OH OVERHEAD
OPNG OPENING
PH PHASE
PIV POST INDICATING VALVE
PNL PANEL
PSI POUNDS PER SQUARE IN.
WIRELESS ACCESS POINT
S
S2
S3
S4
SD
SK
SP
STE
ST
SFT
X
CONTROLLED RECEPTACLE
WB WALL AV BOX
F SPEAKER STROBES
FAAP FIRE ALARM ANNUNCIATOR
PANEL
FACP FIRE ALARM CONTROL PANEL
FAEP FIRE ALARM EXTENDER PANEL
F SPEAKERS
GFCI GROUND FAULT CIRCUIT
INTERRUPTER
CUH CABINET UNIT HEATER
EMI ELECTROMAGNETIC
INTERFERENCE
MCCB MOLDED CASE CIRCUIT
BREAKER
SOUTH
SCHED SCHEDULE
SF SQUARE FOOT (FEET)
SPEC SPECIFICATIONS
SPKR SPEAKER
SQ SQUARE
STD STANDARD
STL STEEL
SW SWITCH
SWBD SWITCH BOARD
SYM SYMMETRICAL
S
GFI GROUND FAULT CIRCUIT
INTERRUPTER
OCPD OVERCURRENT PROTECTIVE
DEVICE
RFI RADIO FREQUENCY
INTERFERENCE
SCCR SHORT CIRCUIT CURRENT
RATING
SPD SURGE PROTECTIVE DEVICE
SPDT SINGLE POLE, DOUBLE
THROW
VFC VARIABLE FREQUENCY
CONTROLLER
RC ROOM CONTROLLER
PP POWER PACK
EXISTING
COLUMN
X LETTER INDICATES EXISTING
COLUMN LINE
REFERENCE
NOTE X REFERENCE
DESIGNATION
ROOM NAME
150 SF
ROOM
NUMBER
ROOM NAME DESIGNATION
ROOM NUMBER DESIGNATION
ROOM AREA DESIGNATION
REFERENCE LEGEND
XXXX
SCHEDULED
EQUIPMENT EQUIPMENT NUMBER
XX-XX PANEL & CIRCUIT NUMBER
XX EQUIPMENT SIZE (WHERE APPLICABLE)
EQUIPMENT
XX-XX PANEL & CIRCUIT NUMBER
EQUIPMENT NAME/NUMBER
NORTH PLAN NORTH TRUE NORTH
PROJECT NO.:
NO. DATE BY DESCRIPTION
REVISIONS
W ROSS
E WELKER
USDAA-E FIRM
TJS
M McWILLIAMS
S KASEMAN
USDA
REAL PROPERTY
SAFETY & HEALTH
AREA ENGINEER
DRAWN BY
CHECKED BY
DESIGNER
PROJECT MANAGER
EPM
PROJECT NO.
DATE
SHEET
Service Research Agricultural
FACILITIES ENGINEERING SECTION
PLAINS AREA
2150 CENTRE AVE., BLDG D, SUITE 330
FT. COLLINS, CO 89526-8119
U S D A
CA
D
DH
DS
G
PM
C
U s e rs
\j fa n t\
D o c u m e n ts \R e v it te m p
\0 -E
L E
C R jf a n tM F
J D
T .r v t
/1
/2
:0 :5
P
M
E 01
ELECTRICAL SPECIFICATIONS
09228.011
JEF
TGM
JEF
04/12/2024
BRL 480V LINE REPLACEMENT
USDA ARS
1616 ALBRECHT BOULEVARD
FARGO, ND 58102
ISSUED FOR
CONSTRUCTION
09228011-7-E 01 ELECTRICAL SPECIFICATIONS
(G E N E R A T O R
'EXTG MDP'
EXTG 208 TO 480 VOLT STEP-UP
TRANSFORMER
EXTG TRANSFORMER
PRIMARY CIRCUIT
BREAKER
EXTG TRANSFORMER
SECONDARY CIRCUIT
BREAKER
EXTG UTILITY TRANSFORMER
EXTG PULLBOX AND
UTILITY METERS
EXTG UNDERGROUND PVC
CONDUITS AND CONDUCTORS TO
BE ABANDONDED IN PLACE
UNDER PAVING. REMOVE
CONDUIT AND CONDUCTORS
UNDER GRASS AREAS.
NEW UNDERGROUND PVC CONDUITS
AND CONDUCTORS
EXTG 480 VOLT PANELBOARD
EXTG 250KW GENERATOR
EXTG AUTOMATIC
TRANSFER SWITCH
EXTG CONDUIT AND
CONDUCTORS TO BE REMOVED
2(TYP.)
E201
NEW PULLBOX
(APPROX. +12.5' ABOVE
GRADE TO CENTER)
E201
NEW PULLBOX
PROTECT EXISTING
TREE AND TREE ROOTS
EXTG STEAM TUNNEL OR
ENCASED PIPE
(TYP. SPACE)
3(TYP.)
SEWER MAIN
NEW PULLBOX
(APPROX. +17.5' AFF TO
CENTER)
NEW CONDUITS
(APPROX. +17.5' AFF TO
CENTER)
EXTG WATER MAIN
EXTG 208V ELECTRIC
FEEDER
6(TYP.)
EXTG 208V ELECTRIC
FEEDER
EXTG 208V ELECTRIC
FEEDER
C O
V E
R
12" MIN
FINISHED GRADE
UNDISTURBED
NATIVE SOIL
NATIVE SOIL BACKFILL
COMPACTED TO MINIMUM
95% STANDARD PROCTOR
AND AS NEEDED TO
AVOID SETTLEMENT
RED WITH BLACK LETTERING,
3" WIDE, BRADY PART
#91295 OR EQUAL
BURIED NON-DETECTABLE
MARKING TAPE
CONDUIT(S)
SAND BEDDING LAYER
PATCH PAVING OR RE-SOD GRASS
AREA AS APPROPRIATE
PROJECT NO.:
NO. DATE BY DESCRIPTION
REVISIONS
W ROSS
E WELKER
USDAA-E FIRM
TJS
M McWILLIAMS
S KASEMAN
USDA
REAL PROPERTY
SAFETY & HEALTH
AREA ENGINEER
DRAWN BY
CHECKED BY
DESIGNER
PROJECT MANAGER
EPM
PROJECT NO.
DATE
SHEET
Service Research Agricultural
FACILITIES ENGINEERING SECTION
PLAINS AREA
2150 CENTRE AVE., BLDG D, SUITE 330
FT. COLLINS, CO 89526-8119
U S D A
CA
D
DH
DS
G
PM
C
U s e rs
\j fa n t\
D o c u m e n ts \R e v it te m p
\0 -E
L E
C R jf a n tM F
J D
T .r v t
/1
/2
:0 :5
P
M
E201
FLOOR PLAN - POWER & AUXILIARY SYSTEMS
09228.011
JEF
TGM
JEF
04/12/2024
BRL 480V LINE REPLACEMENT
USDA ARS
1616 ALBRECHT BOULEVARD
FARGO, ND 58102
ISSUED FOR
CONSTRUCTION
09228011-7-E201 FLOOR PLAN - POWER & AUXILIARY SYSTEMS
NORTH
REF. NOTES ( ):X
1 SUGGESTED CONDUIT ROUTING ALONG EXISTING WALL. ROUTE TO AVOID
EXISTING EQUIPMENT, CONDUITS, STRUCTURAL MEMBERS, ETC. DO NOT
MOUNT TO EXISTING CEILING. CEILING CONTAINS ASBESTOS WHICH MUST
NOT BE DISTURBED.
2 SEAL ALL WALL PENETRATION IN ACCORDANCE WITH SPECIFICATIONS.
3 NEW PULLBOX MOUNTING HEIGHT SHOWN ADJACENT TO NOTE. THIS
HEIGHT IS APPROXIMATE AND SHALL BE COORDINATED WITH EXISTING
CONDITIONS. PULLBOX TO BE SIZED TO ALLOW FOR CONDUCTOR
BENDING RADIUS PER MANUFACTURER'S AND NEC REQUIREMENTS.
4 EXISTING UNDERGROUND DUCTS AND CONDUITS MAY REQUIRE HAND
DIGGING TO LOCATE. PROVIDE AS-BUILT DRAWINGS OF ALL FOUND
UTILITIES AND FINAL ROUTING OF NEW CONDUITS. PLAN AND
COORDINATE ALL OUTAGES TO 480 VOLT PANELBOARD WITH OWNER.
PROVIDE MINIMUM NOTICE OF 1 WEEK PRIOR TO ALL OUTAGES.
5 REMOVE ALL CONDUIT AND CONDUCTORS FOR GENERATOR AND ATS
CONTROLS AND ACCESSORIES COMPLETE BACK TO SOURCE WITHIN
BUILDING 2.
6 EXACT LOCATIONS OF EXISTING UTILITIES ARE BASED ON INCOMPLETE
ORIGINAL DESIGNS AND IT IS ANTICIPATED THAT ADDITIONAL UTILTIES
HAVE BEEN INSTALLED THAT ARE NOT SHOWN. PERFORM UTILITY
LOCATES PRIOR TO EXCAVATION.
SCALE: 1/8" = 1'-0"
FIRST FLOOR PLAN - POWER & AUXILIARY SYSTEMS
SCALE: 12" = 1'-0"
PAVEMENT DETAIL
SCALE: 12" = 1'-0"
Trench Detail 24"
GROUND LEVEL
T
EXTG UTILITY
XFMR
EXTG SPLICE
CABINET
T
GENERATOR
PANEL
'XXX'
EXTG
PRIMARY
CIRCUIT
BREAKER
EXTG STEP-
UP XFMR
EXTG
SECONDARY
CIRCUIT
BREAKER
EXTG
AUTOMATIC
TRANSFER
SWITCH
EXTERIOR BUILDING 2 EXTERIOR BUILDING 1
REMOVE CONDUIT AND WIRES
REMOVE CONDUIT AND WIRES
ABOVE GROUND AND AS
REQUIRED, ABANDON IN
PLACE UNDER GRASS,
PAVING, AND SIDEWALK
GROUND LEVEL
T
EXTG UTILITY
XFMR
EXTG SPLICE
CABINET
T
EXTG 480V
PANELBOARD
EXTG
PRIMARY
CIRCUIT
BREAKER
EXTG STEP-
UP XFMR
EXTG
SECONDARY
CIRCUIT
BREAKER
EXTERIOR BUILDING 2 EXTERIOR BUILDING 1
NEW CONDUIT AND WIRES
INTERIOR BUILDING 2
ROUTE CONDUIT AND WIRES
TO AVOID EXISTING PIPES,
CABLE TRAYS, LUMINAIRES,
ETC.
F600A4G
EXTERIOR BUILDING 2
NEW PULLBOX
NEW PULLBOX
SYSTEM CONDUCTOR IDENTIFICATION
208Y/120V 3Φ 4W
A – PHASE – BLACK
B – PHASE – RED
C – PHASE – BLUE
NEUTRAL – WHITE
GROUND – GREEN
SYSTEM CONDUCTOR IDENTIFICATION
480Y/277V 3Φ 4W
A – PHASE – BROWN
B – PHASE – ORANGE
C – PHASE – YELLOW
NEUTRAL – GRAY
GROUND – GREEN
SYSTEM IDENTIFICATION DECAL
SYSTEM CONDUCTOR IDENTIFICATION
120/240V
A – PHASE – BLACK
B – PHASE – RED
NEUTRAL – WHITE
GROUND – GREEN
SYSTEM CONDUCTOR IDENTIFICATION
240V DELTA 3Φ 3W
A – PHASE – PINK
B – PHASE – PURPLE
C – PHASE – TAN
GROUND – GREEN
FED FROM MDP
PANEL IDENTIFICATION DECAL
PANEL TYPE PANEL
DESIGNATION
NOTES:
1. DECALS SHALL BE LAMINATED ACRYLIC WITH WHITE ENGRAVED LETTERING ON A BLACK BACKGROUND. PANELS OR EQUIPMENT CONNECTED TO AN ALTERNATE
POWER SOURCE SHALL HAVE WHITE ENGRAVED LETTERING ON A RED BACKGROUND.
2. DECALS SHALL BE SIZED TO ACCOMMODATE SPECIFIED LEGENDS BUT NO SMALLER THAN SIZES SHOWN, MINIMUM OF 1/16” THICK.
3. DECALS SHALL BE PUNCHED OR DRILLED FOR MECHANICAL FASTENERS WITH 1/4” GROMMETS IN CORNERS FOR MOUNTING.
4. COLORS FOR 240V DELTA SYSTEMS BASED ON AVAILABLE COLORS OFFERED BY SOUTHWIRE. OTHER COLORS THAT DO NOT CONFLICT WITH OTHER VOLTAGE
SYSTEMS PERMITTED.
CR = CRITICAL
EQ = EQUIPMENT
LS = LIFE SAFETY
EM = EMERGENCY
OS = OPTIONAL STANDBY
H = 480V L = 208V
H1
DISCONNECT IDENTIFICATION
DECAL TO BE PERMANENTLY
POSTED. SEE DETAILS AT RIGHT.
SIZE: 1”H x 3”W. TEXT HEIGHT: 1/4"
PANEL IDENTIFICATION DECAL TO
BE PERMANENTLY POSTED. SEE
DETAILS AT RIGHT.
SIZE: 1”H x 3”W. TEXT HEIGHT: 1/4"
SYSTEM IDENTIFICATION DECAL TO BE
PERMANENTLY POSTED.
SIZE: 1-1/2”H x 3”W. TEXT HEIGHT: 1/8"
BRANCH/FEEDER IDENTIFICATION
DECAL TO BE PERMANENTLY
POSTED. SEE DETAILS AT RIGHT.
SIZE: 1”H x 3”W. TEXT HEIGHT: 1/4"
PANEL H1
BRANCH/FEEDER IDENTIFICATION DECAL
TRANSFORMER IDENTIFICATION
DECAL TO BE PERMANENTLY
POSTED. SEE DETAILS AT RIGHT.
SIZE: 1”H x 3”W. TEXT HEIGHT: 1/4"
TL1
TRANSFORMER IDENTIFICATION DECAL
FED FROM MDP
FEEDS L1
EF-1
DISCONNECT IDENTIFICATION DECAL
480V
FED FROM MDP
PROJECT NO.:
NO. DATE BY DESCRIPTION
REVISIONS
W ROSS
E WELKER
USDAA-E FIRM
TJS
M McWILLIAMS
S KASEMAN
USDA
REAL PROPERTY
SAFETY & HEALTH
AREA ENGINEER
DRAWN BY
CHECKED BY
DESIGNER
PROJECT MANAGER
EPM
PROJECT NO.
DATE
SHEET
Service Research Agricultural
FACILITIES ENGINEERING SECTION
PLAINS AREA
2150 CENTRE AVE., BLDG D, SUITE 330
FT. COLLINS, CO 89526-8119
U S D A
CA
D
DH
DS
G
PM
C
U s e rs
\j fa n t\
D o c u m e n ts \R e v it te m p
\0 -E
L E
C R jf a n tM F
J D
T .r v t
/1
/2
:0 :5
P
M
E501
POWER RISER DIAGRAM
09228.011
JEF
TGM
JEF
04/12/2024
BRL 480V LINE REPLACEMENT
USDA ARS
1616 ALBRECHT BOULEVARD
FARGO, ND 58102
ISSUED FOR
CONSTRUCTION
09228011-7-E501 POWER RISER DIAGRAM
FEEDER SCHEDULE ( ):FXXXXXXX
F600A4G 2 SETS OF 4#350, 1#1G - 3"C
REF. NOTES ( ):X
SCALE: NOT TO SCALE
POWER RISER DIAGRAM - EXTG
SCALE: NOT TO SCALE
POWER RISER DIAGRAM - NEW
SCALE: 1/8" = 1'-0"
PANELBOARD & EQUIPMENT IDENTIFICATION DETAIL
| 09228011- BRL 480V Line Replacement Cover Sheet |
| 09228011- Electrical Info Sheet - E00 |
| 09228011- Electrical Specifications - E01 |
| 09228011- Floor Plan - Power & Auxiliary Systems - E201 |
| 09228011- Power Riser Diagram - E501 |
File details come from the government source that posted it. Updated .