076200_02_Sheet_Metal_Flashing&Trim_rev.pdf
PDF 168 KB Posted
- Attached to
- Re-Roofing - Supervisor's Office Federal contract opportunity
- Solicitation number
- 1267T019R0005
About this file
Amended Specifications
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Flow-Thru-Gravel-Stop-Product-Detail.pdf | ||
| 075323_02_EPDM_Membrane_Roofing_75MIL_REINF_rev2.pdf | ||
| BHSO_roofing-A1.2_Rev2_19July2019.pdf | ||
| 1267T019R0005_Amendment__2.docx | DOCX document | |
| BHSO_Roofing_Dwgs_Rev1_19June2019.pdf | ||
| 1267T019R0005_Amendment__1.docx | DOCX document | |
| 1267T019R0005.doc | DOC document | |
| BHSO-Roofing-Specs.pdf | ||
| BHSO-Roofing-Dwgs.pdf | ||
| 1267T019R0005.doc | DOC document | |
| BHSO-Roofing-Dwgs.pdf | ||
| BHSO-Roofing-Specs.pdf |
Show all 12
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SUPERVISOR’S OFFICE RE-ROOFING 076200-1
BLACK HILLS NATIONAL FOREST SHEET METAL FLASHING AND TRIM
SECTION 076200
SHEET METAL FLASHING AND TRIM
REVISION 1 – 6/17/2019
PART 1 – GENERAL
5.1 RELATED DOCUMENTS
A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to this Section.
5.2 SUMMARY
A. This Section includes the following sheet metal flashing and trim:
1. Formed low-slope roof flashing and trim
2. Counter flashing.
3. Parapet coping system.
4. Built in penthouse gutters.
B. Related Sections include the following:
1. Division 6 Section “Rough Carpentry” for wood nailers, curbs, and blocking.
2. Division 7 Roofing Sections “EPDM Roofing” for installing sheet metal flashing and trim integral with roofing membrane.
3. Division 7 Section "joint Sealants" for field-applied sheet metal flashing and trim sealants.
5.3 PERFORMANCE REQUIREMENTS
A. General: Install sheet metal flashing and trim to withstand wind loads, structural movement, thermally induced movement, and exposure to weather without failing, rattling, leaking, and fastener disengagement.
B. Thermal Movements: Provide sheet metal flashing and trim that allow for thermal movements resulting from the following maximum change (range) in ambient and surface temperatures by preventing buckling, opening of joints, hole elongation, overstressing of components, failure of joint sealants, failure of connections, and other detrimental effects. Provide clips that resist rotation and avoid shear stress as a result of sheet metal and trim thermal movements. Base engineering calculation on surface temperatures of materials due to both solar heat gain and nighttime-sky heat loss.
lcarroll Polygon lcarroll Polygon
SUPERVISOR’S OFFICE RE-ROOFING 076200-2
1. Temperature Change (Range): 120 deg F (67 deg C), ambient: 180 deg F (100 deg C), material surfaces.
C. Water Infiltration: Provide sheet metal flashing and trim that do not allow water infiltration to building interior.
5.4 SUBMITTALS
A. Product Data: For each type of product indicated. Include construction details, material descriptions, dimensions of individual components and profiles, and finishes.
B. Shop Drawings: Show layouts of sheet metal flashing and trim, including plans and elevations. Distinguish between shop and field-assembled work. Include the following.
1. Identify material, thickness, weight, and finish for each item and location in Project.
2. Details for forming sheet metal flashing and trim, including profiles, shapes, seams, and dimensions.
3. Details for fastening, joining, supporting, and anchoring sheet metal flashing and trim, including fasteners, clips, cleats, and attachments to adjoining work.
4. Details of expansion-joint covers, including showing direction of expansion and contraction.
C. Samples for Initial Selection: For each type of sheet metal flashing and trim indicated with factory-applied color finishes.
1. Include similar Samples of trim and accessories involving color selection.
D. Samples for Verification: For each type of exposed finish required, prepared on samples of size indicated below:
1. Sheet Metal Flashing: 12 inches (300 mm) long. Include fasteners, closures, and other attachments
2. Trim: 12 inches (300 mm) long. Include fasteners and other exposed accessories.
3. Accessories: Full-size sample.
E. Sample finish warranty.
5.5 CLOSEOUT
A. Final finish warranty.
5.6 WARRANTY
SUPERVISOR’S OFFICE RE-ROOFING 076200-3
A. Special Warranty on Finishes: Manufacturer agrees to repair finish or replace sheet metal flashing and trim that shows evidence of deterioration of factory-applied finishes within specified warranty period.
1. Finish Warranty Period: 10 years from date of Substantial Completion.
5.7 QUALITY ASSURANCE
A. Sheet Metal Flashing and Trim Standard: Comply with SMACNA's "architectural Sheet Metal Manual." Conform to dimensions and profiles shown unless more stringent requirements are indicated.
5.8 DELIVERY, STORAGE, AND HANDLING
A. Deliver sheet metal flashing materials and fabrications undamaged. Protect sheet metal flashing and trim materials and fabrications during transportation and handling.
B. Unload, store, and install sheet metal flashing materials and fabrications in a manner to prevent bending, warping, twisting, and surface damage.
C. Stack materials on platforms or pallets, covered with suitable weather-tight and ventilation covering. Do not store sheet metal flashing and trim materials in contract with other materials that might cause staining, denting, or other surface damage.
5.9 COORDINATION
A. Coordinate installation of sheet metal flashing and trim with interfacing and adjoining construction to provide a leak-proof, secure, and non-corrosive installation.
PART 2 – PRODUCTS
6.1 SHEET METALS
A. Pre-painted, Metallic-Coated Steel Sheets: Steel sheet metallic coated by the hot-dip process and pre-painted by the coil-process to comply with ASTM A 755/A 755M.
1. Zinc-Coated (Galvanized) Steel Sheet: ASTM A 653/A 653M, G90 (Z275) coating designation; structural quality.
2. Exposed Finished: Apply the following coil coating:
a. Siliconized-Polyester Coating: Epoxy primer and silicone-modified, polyester- enamel topcoat; with a dry film thickness of not less than
0.2 mil (0.005 mm) for primer and 0.8 mil (0.02 mm) for topcoat.
SUPERVISOR’S OFFICE RE-ROOFING 076200-4
1) Color: As selected by CO from manufacturer's full range.
a) Humidity Resistance: 1000 hours.
b) Salt-Spray Resistance: 1000 hours.
2) Fluoropolymer 3-Coat System: Manufacturer's standard 3-coat, thermocured system consisting of specially formulated inhibitive primer, fluoropolymer color coat, and clear fluoropolymer topcoat, with both color coat and clear topcoat containing not less than 70 percent polyvinylidene fluoride resin by weight, with a minimum total dry film thickness of 1.5 mill (0.038 mm); complying with physical properties and coating performance requirements of AAMA 2605, except as modified below:
a) Humidity Resistance: 1000 hours.
b) Salt-Spray Resistance: 1000 hours.
3) Color: As selected by CO from manufacturer's full range.
6.2 UNDERLAYMENT MATERIALS
A. Polyethylene Sheet: 6 mil (0.15 mm) thick polyethylene sheet complying with
ASTMC4397.
B. Felts: ASTM D 226, Type II (No. 30), asphalt-saturated organic felt, non-perforated.
C. Slip Sheet: Rosin-sized paper, minimum 3 lb/ sq. ft. (0.16 kg/sq.m).
6.3 MISCELLANEOUS MATERIALS
A. General: Provide materials and types of fasteners, solder, welding rods, protective coatings, separators, sealants, and other miscellaneous items as required for complete sheet metal flashing and trim installation.
B. Fasteners: Wood screws, annular threaded nails, self-tapping screws, self-locking rivets and bolts, and other suitable fasteners designed to withstand design loads.
1. Exposed Fasteners: Heads matching color of sheet metal by means of plastic caps or factory-applied coating.
2. Fasteners for Flashing and Trim: Blind fasteners or self-drilling screws, gasketed, with hex washer head.
3. Blind Fasteners: High-strength aluminum or stainless-steel rivets.
4. Spikes and Ferrules: Same material as gutter; with spike with ferrule matching internal gutter width.
C. Solder for Lead: ASTM B 32, Grade Sn50, 50 percent tin and 50 percent lead.
SUPERVISOR’S OFFICE RE-ROOFING 076200-5
D. Sealing Tape: Pressure-sensitive, 100 percent solids, polyisobutylene compound sealing tape with release-paper backing. Provide permanently elastic, non-sag, non-toxic, non-staining tape.
E. Elastomeric Sealant: ASTM C 920, Generic type recommended by manufacturer of metal and fabricator of components being sealed and comply with FS TT-S- 00230, or TT-S-001543.
F. Butyl Sealant: ASTM C 1311, single-component, solvent-release butyl rubber sealant, polyisobutylene plasticized, heavy bodied for hooked-type expansion joints with limited movement.
G. Epoxy Seam Sealer: Two-part, non-corrosive, aluminum seam-cementing compound, recommended by aluminum manufacturer for exterior nonmoving joints, including riveted joints.
H. Bituminous Coating: Cold-applied asphalt mastic, SSPC-paint 12, compounded for 15-mil (0.4 mm) dry film thickness per coat. Provide inert-type non-corrosive compound free of asbestos fibers, sulfur components, and other deleterious impurities.
I. Asphalt Roofing Cement: ASTM D 4586, asbestos free, of consistency required for application.
6.4 FABRICATION, GENERAL
A. General: Custom fabricated sheet metal flashing and trim to comply with recommendations in SMACNA's "Architectural Sheet Metal Manual" that apply to design, dimensions, metal, and other characteristics of item indicated. Shop fabricated items where practicable. Obtain field measurements for accurate fit before shop fabrication.
B. Fabricate sheet metal flashing and trim in thickness or weight needed to comply with performance requirements, but not less than that specified for each application and; metal.
C. Fabricate sheet metal flashing and trim without excessive oil canning, buckling, and tool marks and true to line and levels indicated, with exposed edges folded back to form hems.
1. Seams for Aluminum: Fabricate nonmoving seams with flat-lock seams.
Form seams and seal with epoxy seam sealer. Rivet joints for additional strength.
2. Seams for Other Than Aluminum: Fabricate nonmoving seams in accessories with flat-lock seams. Tin edges to be seamed, form seams, and solder.
D. Sealed Joints: Form nonexpansion but movable joints in metal to accommodate elastomeric sealant to comply with SMACNA recommendations.
SUPERVISOR’S OFFICE RE-ROOFING 076200-6
E. Expansion Provisions: Where lapped or bayonet-type expansion provisions in the Work cannot be used, form expansion joints of intermeshing hooked flanges, not less than 1 inch (25 mm) deep, filled with sealant concealed within joints.
F. Conceal fasteners and expansion provisions where possible on exposed-to-view sheet metal flashing and trim, unless otherwise indicated.
G. Fabricate cleats and attachment devices from same material as accessory being anchored or from compatible, noncorrosive metal.
1. Thickness: As recommended by SMACNA's Architectural Sheet Metal Manual" for application but not less than thickness of metal being secured.
6.5 LOW-SLOPE ROOF SHEET METAL FABRICATIONS
A. Roof Edge Flashing (Gravel Stop) and Fascia Caps: See Division 7 Section “EPDM Roofing”.
B. Parapet caps: Fabricate from the following material:
1. Prepainted, Metallic-Coated Steel 0.0276 inch (0 .7mm) thick.
C. Counterflashing: Fabricate from the following material:
1. Prepainted, Metallic-Coated Steel: 0.0217 inch (0.55 mm) thick.
D. Roof-Penetration Flashing: Fabricate from the following material:
1. Prepainted, Metallic-Coated Steel: 0.0276 inch (0.7 mm) thick.
E. Roof-Drain Flashing: Fabricate from the following material:
1. Match existing.
F. Penthouse gutters: Fabricate from the following material:
1. Prepainted, Metallic-Coated Steel 0.0276 inch (0 .7mm) thick.
6.6 MISCELLANEOUS SHEET METAL FABRICATIONS
6.7 FINISHES
A. Comply with NAAMM's "Metal Finishes Manual for Architectural and Metal Products" for recommendations for applying and designating finishes.
B. Protect mechanical and painted finishes on exposed surfaces from damage by applying a strippable, temporary protective covering before shipping.
C. Appearance of Finished Work: Variations in appearance of abutting or adjacent pieces are acceptable if they are within one-half of the range of approved Samples. Noticeable variations in the same piece are not acceptable. Variations in appearance of other components are acceptable if they are within the range of approved Samples and are assembled or installed to minimize contrast.
SUPERVISOR’S OFFICE RE-ROOFING 076200-7
PART 3 – EXECUTIONS
7.1 EXAMINATION
A. Examine substrates, areas, and conditions, with Installer present, to verify actual locations, dimensions and other conditions affecting performance of work
1. Verify that substrate is sound, dry, smooth, clean, sloped for drainage, and securely anchored.
2. Proceed with installation only after unsatisfactory conditions have been corrected.
7.2 INSTALLATION, GENERAL
A. General: Anchor sheet metal flashing and trim and other components of the Work securely in place, with provisions for thermal and structural movement. Use fasteners, solder, welding rods, protective coating, separators, sealants, and other miscellaneous items as required to complete sheet metal flashing and trim system.
1. Torch cutting of sheet metal flashing and trim is not permitted.
B. Metal Protection: Where dissimilar metals will contact each other or corrosive substrates, protect against galvanic action by painting contact surfaces with bituminous coating or by other permanent separation as recommended by fabricator or manufacturers of dissimilar metals
1. Underlayment; Where installing metal flashing directly on cementitious or wood substrates, install a course of felt underlayment and cover with a slip sheet or install a course of polyethylene underlayment.
2. Bed flanges in thick coat of asphalt roofing cement where required for waterproof performance.
C. Install exposed sheet metal, flashing, and trim without excessive oil canning, buckling, and tool marks.
D. Install sheet metal flashing and trim true to line and levels indicated. Provide uniform, neat seams with minimum exposure of solder, welds, and elastomeric sealant.
E. Install sheet metal flashing and trim to fit substrates and to result in watertight performance. Verify shapes and dimensions of surfaces to be covered before fabricating sheet metal.
1. Space cleats not more than 12 inches (300 mm) apart. Anchor each cleat with two fasteners. Bend tabs over fasteners.
F. Expansion Provisions: Provide for thermal expansion of exposed flashing and trim. Space movement joints at a maximum of 10 feet(3 m) with no joints allowed within 24 inches (600 mm) of corner or intersection. Where lapped or bayonet-type expansion provisions cannot be used or would not be sufficiently watertight, form
SUPERVISOR’S OFFICE RE-ROOFING 076200-8
expansion joints of intermeshing hooked flanges, not less than 1 inch (25 m m ) deep, filled with elastomeric sealant concealed within joints.
G. Fasteners: Use fasteners of sizes that will penetrate substrate not less than 1-14 inches (32 mm) for nails and not less than 3/4 inch (19 mm) for wood screws.
1. Galvanized or Prepainted, Metallic-Coated Steel: Use stainless-steel fasteners.
H. Seal joints with elastomeric sealant as required for watertight construction.
1. Where sealant-filled joints are used, embed hooked flanges of joint members not less than 1 inch (25 m m ) into sealant. Form joints to completely conceal sealant. When ambient temperature at time of installation is moderate, between 40 and 70 deg F (4 and 21 deg C), set joint members for 50 percent movement either way. Adjust setting proportionately for installation at higher ambient temperatures. Do not install sealant-type joints at temperatures below 40 deg F (4 deg C).
2. Prepare joints and apply sealants.
7.3 ROOF DRAINAGE SYSTEM INSTALLATION
A. General: Install gutters that were removed during Demolition work. Install sheet metal roof drainage items to produce complete roof drainage system according to SMACNA recommendations and as indicated. Coordinate installation of roof perimeter flashing with installation of roof drainage system.
B. Hanging Gutters: Attach gutters at eave or fascia to firmly anchored gutter brackets or straps spaced not more than 36 inches apart. Provide end closures and seal watertight with sealant. Slope to downspouts.
1. Fasten gutter spacers to front and back of gutter.
2. Loosely lock straps to front gutter bead ad anchor to roof deck.
3. Anchor back of gutter that extends into roof deck with cleats spaced not more than 24 inches (600 mm) apart.
4. Anchor gutter with spikes and ferrules spaced not more than 24 inches (600
m) apart.
5. Install gutter with expansion joints at locations indicated but not exceeding
50 feet (15.24 m) apart. Install expansion joint caps.
C. Expansion-Joint Covers: Install expansion-joint covers at locations and of configuration indicated. Lap joints a minimum of 4 inches (100 mm) in direction of water flow.
D. Splash blocks: Reset existing splash blocks after roofing work is complete.
7.4 ROOF FLASHING INSTALLATION
SUPERVISOR’S OFFICE RE-ROOFING 076200-9
A. General: Install sheet metal roof flashing and trim to comply with performance requirements and SMACNA's "Architectural Sheet Metal Manual." Provide concealed fasteners where possible, set units true to line, and level as indicated.
Install work with laps, joints, and seams that will be permanently watertight
B. Counterflashing: Coordinate installation of counterflashing with installation of base flashing. Insert counterflashing in reglets or receivers and fit tightly to base flashing. Extend counterflashing 4 inches ((100 mm) and bed with elastomeric sealant.
1. Secure in a waterproof manner by means of snap-in installation and sealant or lead wedges and sealant.
C. Roof-Penetration Flashing: Coordinate installation of roof-penetration flashing with installation of roofing and other items penetrating roof. Install flashing as follows:
1. Turn lead flashing down inside vent piping, being careful not to block vent piping with flashing.
2. Seal with elastomeric sealant and clamp flashing to pipes penetrating roof except for lead flashing on vent piping.
7.5 CLEANING AND PROTECTION
A. Clean exposed metal surfaces of substances that interfere with uniform oxidation and weathering.
B. Clean and neutralize flux materials. Clean off excess sealants.
C. Remove temporary protective coverings and strippable films as sheet metal flashing and trim are installed. On completion of installation, clean finished surfaces, including removing unused fasteners, metal filings, pop rivet stems, and pieces of flashing. Maintain in a clean condition during construction.
D. Replace sheet metal flashing and trim that have been damaged or that have deteriorated beyond successful repair by finish touchup or similar minor repair procedures.
END OF SECTION 076200