· If we trench the gas line in with an 8” wide trencher, is there a compaction requirement?

There is no compaction requirement.

· Is it acceptable to bring the 1” lines to C3 and C4 the best way, avoiding cutting the existing concrete?

Yes, the route will need to be approved by the UDSA and meter sets will need to be located per the drawings.

· Are bollards going to be required at the meter settings and how many for each?

Four bollards will be needed per meter set, and they’ll need to be ground installed (not surface mounted).