Drawings.pdf
PDF 7 MB Posted
- Attached to
- Safety & Health Upgrades, Pocatello Supply Depot
- Solicitation number
- 12639519R0011
About this file
Attachment 2, Drawings
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 12639519R0011-0006.pdf | ||
| 12639519R0011-0005.pdf | ||
| 12639519R0011-0004.pdf | ||
| Offeror_questions_and_responses_USDAPocatello_5_21_19.pdf | ||
| 12639519R0011-0003.pdf | ||
| Site_visit_attendees;_contact_list.docx | DOCX document | |
| 12639519R0011-0002.pdf | ||
| 12639519R0011-0001.pdf | ||
| Specifications.pdf | ||
| USDA_Sustainable_Buildings_Implementation_Plan.doc | DOC document | |
| All_Green_Products.xls | XLS spreadsheet | |
| 12639519R0011.pdf | ||
| DOL_Wage_Determination_ID35.pdf |
Show all 13
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
USDA APHIS
PSD RENOVATIONS
3.27.2019
100% CONSTRUCTION DOCUMENTS
PROJECT LOCATION
USDA APHIS
POCATELLO SUPPLY DEPOT
238 E Dillon St, Pocatello, ID 83201
VICINITY MAP: Locator
OWNER
USDA APHIS
CONTACT: JAMES ROLOFF
USDA, APHIS, PROCUREMENT BRANCH
250 MARQUETTE AVE.
MINNEAPOLIS, MN 55401
612.336.3223
ARCHITECT/ENGINEER
CTA Architects Engineers
800 W. Main St. #800
BOISE, IDAHO
208.336.4900
Project Manager: SCOTT ROBERTS
MECHANICAL ENGINEER
CTA Architects Engineers
800 W. Main St. #800
BOISE, IDAHO
208.336.4900
CONTACT: TIM JOHNSON
ELECTRICAL ENGINEER
CTA Architects Engineers
800 W. Main St. #800
BOISE, IDAHO
208.336.4900
CONTACT: RANDY DINGER
SHEET INDEX
PLUMBING
P100 PACKAGE #1 - PLUMBING SCHEDULES
P102 MIXING ROOM PLUMBING PLANS
P110 PACKAGE #2 - PLUMBING SCHEDULES AND DETAILS
P111 BASEMENT PLUMBING PLANS
MECHANICAL
MP001 PACKAGE #1 AND #2 - OVERALL MECHANICAL AND PLUMBING PLANS
M100 PACKAGE #1 HVAC SCHEDULES
M101 CARTRIDGE ROOM AND FUSE EXHAUST HVAC PLANS
M102 MIXING ROOM HVAC PLANS
M103 CYANIDE ROOM AND ROOF HVAC PLANS
M104 HVAC DETAILS AND CONTROLS
M110 PACKAGE #2 HVAC SCHEDULES
M111 HVAC PLANS
ELECTRICAL
E001 PACKAGE #1 AND #2 - OVERALL DEMOLITION PLANS
E002 PACKAGE #1 - ENLARGED DEMOLITION PLANS
E003 PACKAGE #1 - ENLARGED DEMOLITION PLANS
E011 PACKAGE #2 - ENLARGED DEMOLITION PLANS
E012 ELECTRICAL DEMOLITION PLANS
E013 ENLARGED DEMOLITION PLANS
E101 PACKAGE #1 AND #2 - OVERALL PLANS
E102 PACKAGE #1 - ENLARGED PLANS
E103 PACKAGE #1 - ENLARGED PLANS
E111 PACKAGE #2 - ENLARGED PLANS
E112 ELECTRICAL PLANS - FIRE ALARM
E113 ELECTRICAL PLAN BASEMENT - FIRE ALARM
E601 SCHEDULES AND DETAILS
E602 PANEL SCHEDULES
GENERAL
G101 COVER SHEET
G102 LEGEND/SYMBOL SHEET
G103 EXISTING CONDITION IMAGES
ARCHITECTURAL
A001 PACKAGE #1 AND #2 - OVERALL DEMOLITION PLANS
A002 PACKAGE #1 - ENLARGED DEMOLITION PLANS
A003 PACKAGE #1 - ENLARGED DEMOLITION PLANS
A011 PACKAGE #2 - ENLARGED DEMOLITION PLANS
A101 PACKAGE #1 AND #2 - OVERALL PLANS
A102 PACKAGE #1 - ENLARGED PLANS
A103 PACKAGE #1 - ENLARGED PLANS
A104 PACKAGE #1- ENLARGED MEZZANINE PLANS
A111 PACKAGE #2 - ENLARGED PLANS
A601 SCHEDULES AND DETAILS
A801 PACKAGE #2 - INTERIOR ELEVATIONS AND DETAILS
IMAGE OF THE SUPPLY DEPOT
THE FOLLOWING DRAWINGS AND DOCUMENTS ARE DELINEATED INTO
TWO SEPARATE PACKAGES:
PACKAGE #1 - SAFETY AND HEALTH REVIEW: INCLUDES THE WORK
RELATED TO THE FOLLOWING ROOMS, AREAS, AND ITEMS. REFERENCE
THE ASSOCIATED DOCUMENTS, DRAWINGS, AND SPECIFICATIONS TO
FIND FURTHER INFORMATION AND ALL WORK RELATED TO THESE
AREAS.
A. CYANIDE ROOM
B. GRAIN BAIT MIXING ROOM
C. CARTRIDGE ROOM
D. NORTH WAREHOUSE HOT LABEL MAKER
E. GAS CARTRIDGE FUSES
F. PERSONNEL DOOR
G. RAILING AND FALL PROTECTION AT AREAS INDICATED
PACKAGE #2 - FACILITY CONDITION REASSESSMENT: INCLUDES THE
WORK RELATED TO THE FOLLOWING ROOMS, AREAS, AND ITEMS.
REFERENCE THE ASSOCIATED DOCUMENTS, DRAWINGS, AND
SPECIFICATIONS TO FIND FURTHER INFORMATION AND ALL WORK
RELATED TO THESE AREAS.
A. ENERGY CONSERVATION MEASURES - OFFICE LIGHTING
B. BASEMENT RESTROOMS
C. OFFICE HVAC SYSTEM
D. WATER HEATER REPLACEMENT
E. FIRE ALARM SYSTEM
TASK ORDER NO. AG-6395-C-16-0117
HAZARDOUS MATERIALS AND CHEMICALS INFORMATION:
ALONG WITH THE FOLLOWING VERBIAGE, REFERENCE SPECIFICATION SECTION
028416 PRIOR TO ANY DEMOLITION WORK OCCURRING.
THE FOLLOWING ACUTELY HAZARDOUS SUBSTANCES ARE KNOWN TO BE
PRESENT IN AREAS OF THE FACILITY TO BE RENOVATED. THESE INCLUDE
SODIUM CYANIDE (CHEMICAL FORMULA NaCN) IN THE CYANIDE ROOM AND
STRYCHNINE AND ZINC PHOSPHIDE IN THE MIXING ROOM. A BRIEF SUMMARY OF
THE PROCESSES ASSOCIATED WITH THESE SUBSTANCES ARE PROVIDED
BELOW.
THESE ARE BY NO MEANS SUFFICIENT SPECIFICATIONS TO ENSURE WORKER
SAFETY OR COMPLIANCE WITH LOCAL, STATE, AND FEDERAL WORKER
PROTECTION LAWS AND REGULATIONS DURING PLANNED ACTIVITIES.
ADDITIONALLY, RESOURCE CONSERVATION AND RECOVERY ACT (RCRA)
HAZARDOUS WASTE(S) WILL LIKELY BE GENERATED WHILE PERFORMING THE
SCOPE OF THIS WORK. THE REMOVAL, HANDLING, AND DISPOSAL OF
CONTAMINATED MATERIALS REQUIRES SPECIALIZED KNOWLEDGE TO ENSURE
WORKER SAFETY AND COMPLIANCE WITH LOCAL, STATE, AND FEDERAL
REGULATIONS. ADDITIONALLY, THERE MAY BE OTHER HAZARDOUS
SUBSTANCES PRESENT AND/OR ENCOUNTERED WHILE PERFORMING THE
SCOPE OF WORK, INCLUDING BUT NOT LIMITED TO: ASBESTOS CONTAINING
BUILDING MATERIALS, LEAD CONTAINING COATINGS, AND BIOLOGICAL HAZARDS
THAT ARE NOT DISCUSSED HEREIN.
GENERAL NaCN NOTES - CURRENT PROCESS AND CONDITIONS - TAKES PLACE
WITHIN CYANIDE ROOM:
· MATERIAL IS GROUND TO A POWDER UNDER A HOOD
· GROUND MATERIAL IS MIXED WITH DYE AND ANTI-CAKING COMPOUND
· MIXTURE IS COOKED IN HOODED OVEN TO DRIVE OFF MOISTURE.
· CURRENT PPE IS LEVEL C: AIR PURIFYING RESPIRATOR (N95 PARTICULATE
CARTRIDGE), LONG SLEEVE CLOTHING (TYVEK), NITRILE GLOVES, AND
SAFETY GLASSES.
· THE USDA HAS INDICATED THAT A NEGATIVE EXPOSURE
ASSESSMENT WAS CONDUCTED DURING THEIR GENERAL WORK
ACTIVITIES HANDLING THE CYANIDE. THE RESULTS OF THE NEA
INDICATE THAT USDA WORKERS WERE NOT BEING EXPOSED TO
CONTAMINANT AT LEVELS THAT WOULD REQUIRE A RESPIRATOR.
HOWEVER, EMPLOYEES ARE REQUIRED TO WEAR AN AIR-PURIFYING
ASPIRATOR AS A PRECAUTION.
· HISTORICALLY QUANTITIES OF NaCN HAVE BEEN WELL CONTROLLED, UNDOCUMENTED QUANTITIES OF NaCN WOULD NOT BE LIKELY DURING
DEMOLITION.
· DYE IS PRESENT THROUGHOUT AREA AND MAY OR MAY NOT INDICATE
PRESENCE OF NaCN - CONTRACTOR SHOULD ASSUME DYE CONTAINS NaCN
AND TAKE THE PROPER PRECAUTIONS WHEN THE DYE IS ENCOUNTERED
DURING CONSTRUCTION.
· SPILLED RESIDUAL SHOULD BE AMENABLE TO RECOVERY THROUGH HEPA
(HIGH EFFICIENCY PARTICULATE AIR) VACUUMING.
· DUCT WORK LIKELY CONTAMINATED ALTHOUGH AMBIENT MOISTURE
WOULD RESULT IN NaCN CONVERTING TO HCN (HYDROGEN CYANIDE)
AND OFF-GASSING OVER TIME, MINIMIZING TOXICITY.
· THE USDA HAS INDICATED THERE ARE AT LEAST 4 AREAS WITHIN
THE NaCN ROOM WHERE NaCN MAY HAVE ACCUMULATED MORE
THAN OTHER AREAS DUE TO VARIOUS FACTORS. THESE AREAS WILL
NEED TO BE IDENTIFIED BY LOCAL USDA REPRESENTATIVES PRIOR
TO INITIATING THIS SCOPE OF WORK.
GENERAL MIXING ROOM NOTES - CURRENT PROCESS AND CONDITIONS:
· STRYCHNINE LIKELY NOT PRESENT ANYMORE.
· ZINC PHOSPHIDE PRIMARY CONTAMINANT WITHIN ROOM.
· STRYCHNINE AND ZINC PHOSPHIDE ARE SOLIDS THAT CAN BE RECOVERED
BY A HEPA VACUUM.
· CURRENT PPE IS LEVEL C: AIR PURIFYING RESPIRATOR (N95 PARTICULATE
CARTRIDGE), LONG SLEEVE CLOTHING/LAB COAT (NO TYVEK) , NITRILE
GLOVES, AND SAFETY GLASSES.
GENERAL MANUFACTURER NOTE:
ALL MANUFACTURER'S LISTED WITHIN THESE DRAWINGS AND
ASSOCIATED SPECIFICATIONS SHALL BE CONSIDERED AN 'OR EQUAL'
PRODUCT.
DRAWN BY |
REVISIONS
© | ALL RIGHTS RESERVED
w w w . c t a g r o u p . c o m
8 0 0 . 7 5 7 . 9 5 2 2
CHECKED BY |
U S
D A
P H
I S
P S
D
R
E N
O V
A T
I O
N S
P O
C A
T E
L L
O
I D
A H
O
100% CD
3.27.19
N O
T
F
O R
C
N
S T
R U
C T
I O
N
P
R E
L I M
I N
A R
Y
D
E S
I G
N
06.29.17 11:09 PM | G:\USDAAPHIS_PSD1\BIMCAD\Arch\G-101.dwg
G101
COVER SHEET
JC
SR
Solicitation 12639519R0011 Attachment 2
SYMBOL DESCRIPTION
LIGHTING
LAY-IN OR RECESSED FIXTURE, SIZE ON PLANS
WALL MOUNTED FIXTURE, SIZE ON PLANS
SURFACE MOUNTED FIXTURE, SIZE ON PLANS
PENDANT OR SURFACE MOUNTED FIXTURE, SIZE ON PLANS
RECESSED DOWNLIGHT FIXTURE
SURFACE MOUNTED FIXTURE
WALL MOUNTED FIXTURE
CEILING MOUNTED, WALL MOUNTED EXIT LIGHT
(W/ DIRECTIONAL ARROWS)
PENDANT MOUNTED FIXTURE, SIZE ON PLANS
SHADED FIXTURE INDICATES FIXTURE IS UNSWITCHED AND
ALSO INDICATES EMERGENCY POWER.
2 HEAD EMERGENCY LIGHT BATTERY PACK
ELECTRICAL SYMBOLS LEGEND
SYMBOL DESCRIPTION
LAY-IN OR RECESSED FIXTURE, SIZE ON PLANS
WALL MOUNTED FIXTURE, SIZE ON PLANS
SURFACE MOUNTED FIXTURE, SIZE ON PLANS
PENDANT OR SURFACE MOUNTED FIXTURE, SIZE ON PLANS
RECESSED DOWNLIGHT FIXTURE
SURFACE MOUNTED FIXTURE
WALL MOUNTED FIXTURE
CEILING MOUNTED, WALL MOUNTED EXIT LIGHT
(W/ DIRECTIONAL ARROWS)
PENDANT MOUNTED FIXTURE, SIZE ON PLANS
SHADED FIXTURE INDICATES FIXTURE IS UNSWITCHED AND
ALSO INDICATES EMERGENCY POWER.
2 HEAD EMERGENCY LIGHT BATTERY PACK
CLG
CLG
SWITCH - SPST
2 SINGLE POLE, DOUBLE THROW
3 THREEWAY
4 FOURWAY
K KEY OPERATED
P PILOT LIGHT
WP WEATHERPROOF
OS OCCUPANCY SENSOR
D DIMMER
MC SPOT-MOMENTARY CONTACT
LV LOW VOLTAGE
T TIMER SWITCH
TS TEST SWITCH
OCCUPANCY SENSOR SWITCH (CEILING) - SUBSCRIPT IS TYPE
RECEPTACLE - SIMPLEX
RECEPTACLE - DUPLEX
GFI RECEPTACLE - DUPLEX (GROUND FAULT INTERRUPT)
USB DEVICE RECEPT W/2 USB PORTS
DC DROP CORD
WP WEATHERPROOF COVER & WEATHER
RESISTANT RECEPTACLE
TR TAMPER RESISTANT
S SURGE PROTECTED
IG ISOLATED GROUND
FILLED CENTER INDICATES HOSPITAL GRADE
EMERGENCY RECEPTACLE
RECEPTACLE - DOUBLE DUPLEX
GFI RECEPTACLE - DOUBLE DUPLEX
- SAME INDICATORS AS SHOWN FOR DUPLEX RECEPTACLE
RECEPTACLE - 208V
R RANGE - NEMA 14-50R
D DRYER - NEMA 10-30R
W WELDER - NEMA 14-50R
* NEMA CONFIGURATION AS NOTED
208V RECEPTACLE IN RECESSED FLOORBOX
DUPLEX RECEPTACLE/GFI IN RECESSED FLOORBOX
DOUBLE DUPLEX RECEPTACLE/GFI IN RECESSED FLOORBOX
J-BOX - BOX INDICATES FLOOR MOUNTING -4"X4"X2-1/8" DEEP
UNLESS OTHERWISE NOTED
SPECIAL PURPOSE CONNECTION - BOX INDICATES FLOOR
MOUNTING - WORK AS NOTED
RECEPTACLE - DUPLEX, MOUNTING IN CEILING
MANUAL MOTOR DISCONNECT/STARTER SWITCH
COMBINATION STARTER/DISCONNECT SWITCH
DISCONNECT SWITCH
CONTACTOR
ELECTRIC MOTOR CONNECTION
EMERGENCY PUSHBUTTON
PHOTOCELL, PHOTOCELL WALL MOUNTED
EXISTING PANELBOARD, SURFACE MOUNTED
EXISTING PANELBOARD, FLUSH MOUNTED
TIME CLOCK
VARIABLE FREQUENCY DRIVE
THERMOSTAT/TEMPERATURE SENSOR BY MC OR TC, J-BOX
AND CONDUIT TO CEILING BY EC
CARBON MONOXIDE DETECTOR BY MC, J-BOX & CONDUIT TO
CEILING BY EC
PP
POWER POLE
RELAY
CIRCUIT BREAKER
CONTROL PANEL
LRP LIGHTING RELAY PANEL
TCP TEMPERATURE CONTROL PANEL
GAP GENERATOR ANNUNCIATOR PANEL
PACP PA CONTROL PANEL
MGA MED GAS ALARM PANEL
PANELBOARD, SURFACE MOUNTED
PANELBOARD, FLUSH MOUNTED
GFI RECEPTACLE - DUPLEX, MOUNTING IN CEILING
T
SYMBOL DESCRIPTION
DEVICES AND POWER
CO₂
STROBE (NUMBER INDICATES CANDELA RATING)
SPEAKER/STROBE (NUMBER INDICATES CANDELA RATING)
SPEAKER
MANUAL PULLSTATION
IPS INDOOR PROTECTIVE SHIELD
MAGNETIC DOOR HOLDER, BY DIV 28
FIRE/SMOKE DAMPER
SMOKE DETECTOR, SMOKE DETECTOR WALL MOUNTED
HEAT DETECTOR, HEAT DETECTOR WALL MOUNTED
CONNECTION TO TAMPER SWITCH, SWITCH BY OTHERS
CONNECTION TO FLOW SWITCH, SWITCH BY OTHERS
CONNECTION TO PRESSURE SWITCH, SWITCH BY OTHERS
BEAM DETECTOR TRANSMITTER
BEAM DETECTOR RECEIVER
DUCT SMOKE DETECTOR
FIRE ALARM REMOTE ANNUNICATOR
FIRE ALARM CONTROL PANEL
SPEAKER/STROBE (NUMBER INDICATES CANDELA RATING),
CEILING MOUNTED
FIRE ALARM SIGNAL EXTENDER PANEL
SYMBOL DESCRIPTION
FIRE ALARM
ABOVE COUNTER, 4" BACK SPLASHAC
AUTOMATIC TRANSFER SWITCHATS
ABOVE FINISHED GRADEAFG
ABOVE FINISHED FLOORAFF
BELOW GRADEBLG
BOTTOM OF DEVICEBOD
CONDUITC
CARD ACCESS SYSTEMCAS
CLOSED CIRCUIT TVCCTV
CEILINGCLG
CENTER OF DEVICECOD
COPPERCU
DIGITAL VIDEO RECORDERDVR
EXISTING(E)
ELECTRICAL CONTRACTOREC
EXHAUST FANEF
GENERAL CONTRACTORGC
GROUNDGND
FIELD ADJUSTABLE LONG TIME, SHORT TIME AND
INSTANTANEOUS
LSI
FIELD ADJUSTABLE LONG TIME, SHORT TIME, INSTANTANEOUS
AND GROUND FAULT
LSIG
MECHANICAL CONTRACTORMC
NEW(N)
NIGHT LIGHTNL
PAN-TILT-ZOOMPTZ
QUANTITYQTY
RELOCATED(R)
SURFACESF
TELECOMMUNICATIONS MAIN GROUNDING BUS BARTMGB
TELECOMMUNICATIONS BONDING BACKBONETBB
TEMPERATURE CONTROL CONTRACTORTC
TELEPHONE TERMINAL BOARDTTB
TYPICALTYP
UNDERGROUNDUG
UNLESS OTHERWISE NOTEDUON
WITHW/
WIRE MOLDWM
WEATHER PROOF (WHILE IN USE)WP
TRANSFORMERXFMR
SWITCH DESIGNATIONa,b,c etc
CIRCUIT DESIGNATION, PANEL BN1L, CIRCUITS 2,4,6BN1L-2,4,6
INDICATES DETAIL 1 ON SHEET E5011/E501
SHEET WORK NOTE
HOME RUN TO PANEL
CONDUIT CONCEALED IN CEILING OR WALL
CONDUIT CONCEALED UNDER FLOOR
LOW VOLTAGE CIRCUIT
FIBER OPTIC CABLE
CABLE TRAY
CIRCUIT, NUMBER OF HASH MARKS INDICATES NUMBER OF
CONDUCTORS IN CABLE/RACEWAY. GROUND WIRE IS NOT
SHOWN BUT SHALL BE INCLUDED. NO HASH MARKS INDICATES
2 CONDUCTORS PLUS GROUND.
SHEET DEMO WORK NOTE
SYMBOL DESCRIPTION
ABBREVIATIONS AND MISCELLANEOUS
LV
DRAWN BY |
REVISIONS
© | ALL RIGHTS RESERVED
w w w . c t a g r o u p . c o m
8 0 0 . 7 5 7 . 9 5 2 2
CHECKED BY |
U S
H
I S
P S
D
R
E N
O V
A T
I O
N S
P O
C A
T E
L L
O
I D
A H
O
100% CD
3.27.19
N O
T
F
N
S T
R U
C T
I O
N
P
R E
L I M
I N
A R
Y
D
E S
I G
N
06.29.17 11:09 PM | G:\USDAAPHIS_PSD1\BIMCAD\Arch\G-102.dwg
G102
LEGEND/SYMBOL
SHEET
JC
SR
AutoCAD SHX Text
PC
AutoCAD SHX Text
VFD
AutoCAD SHX Text R
AutoCAD SHX Text
PC
AutoCAD SHX Text M
AutoCAD SHX Text M
AutoCAD SHX Text J
AutoCAD SHX Text J
AutoCAD SHX Text
OS
AutoCAD SHX Text
TC
AutoCAD SHX Text J
AutoCAD SHX Text F
AutoCAD SHX Text F
AutoCAD SHX Text F
AutoCAD SHX Text F
AutoCAD SHX Text F
AutoCAD SHX Text M
AutoCAD SHX Text
FSD
AutoCAD SHX Text
SD
AutoCAD SHX Text
SD
AutoCAD SHX Text
HD
AutoCAD SHX Text
HD
AutoCAD SHX Text
FS
AutoCAD SHX Text
PS
AutoCAD SHX Text
TS
AutoCAD SHX Text
FACP
AutoCAD SHX Text
FARA
AutoCAD SHX Text
SD
AutoCAD SHX Text
BD
AutoCAD SHX Text
BD
AutoCAD SHX Text
FASP
G103
EXISTING GRAIN BAIT MIXING ROOM CONDITIONS
N.T.S.
DRAWN BY |
REVISIONS
© | ALL RIGHTS RESERVED
w w w . c t a g r o u p . c o m
8 0 0 . 7 5 7 . 9 5 2 2
CHECKED BY |
U S
H
I S
P S
D
R
E N
O V
A T
I O
N S
P O
C A
T E
L L
O
I D
A H
O
100% CD
3.27.19
N O
T
F
N
S T
R U
C T
I O
N
P
R E
L I M
I N
A R
Y
D
E S
I G
N
06.11.18 06:11 PM | G:\USDAAPHIS_PSD1\BIMCAD\Arch\G-103.dwg
G103
EXISTING
CONDITION IMAGES
JC
SR
G103
EXISTING CARTRIDGE ROOM CONDITIONS
N.T.S.
NOTE: THESE IMAGES ARE INTENDED TO GIVE THE CONTRACTOR A GENERAL
UNDERSTANDING OF THE EXISTING CONDITIONS. THESE IMAGES ARE NOT
INTENDED TO BE DESIGN DRAWINGS. ALL ITEMS TO BE VERIFIED IN FIELD.
REFERENCE CONTRACT DOCUMENT DRAWINGS AND SPECIFICATIONS FOR
FURTHER INFORMATION OF WORK TO OCCUR.
G103
EXISTING CYANIDE ROOM CONDITIONS
N.T.S.
G103
EXISTING BASEMENT RESTROOM CONDITIONS
N.T.S.
G103
EXISTING PERSONNEL DOOR CONDITIONS
N.T.S.
G103
EXISTING CYANIDE ROOFTOP CONDITIONS
N.T.S.
G103
EXISTING GAS CARTRIDGE FUSE STORAGE CONDITIONS
N.T.S.
G103
EXISTING HOT LABEL MAKER AREA CONDITIONS
N.T.S.
A011
A002
PACKAGE #2
PACKAGE #1
RAMP
BASEMENT
WAREHOUSE
ALPHACHLORALOSE
LAB
M-44
MACHINE
SHOP
ADC
STORAGE
COAL
STORAGE
RM.
ROOM
LOCKERS
ELECTRIC
DISTRIBUTION
ROOM
FREIGHT
BASEMENT
WAREHOUSE
STORAGE
ROOM
MECH.
ROOM
GRAIN
ELEVATOR
AREA
AT
BASEMENT
LEVEL
STRG.
GAS CARTRIDGE
FUSE STORAGE
GAS CARTRIDGE
FUSE STORAGE
R.R.
GENERAL NOTES:
A. MAINTAIN THE INTEGRITY OF ALL REMAINING BUILDING SYSTEMS AND RATINGS.
REPAIR ANY DAMAGE DONE TO SURROUNDING AREAS/CONSTRUCTION DURING
DEMOLITION.
B. ALL EXISTING CONDITIONS ARE NOT INDICATED ON THE DRAWINGS. CONTRACTOR
SHALL CAREFULLY EXAMINE THE EXISTING INSTALLATION AND ALL PROJECT
DRAWINGS TO BECOME FAMILIAR WITH THE SCOPE OF WORK.
C. CONTRACTOR SHALL PATCH AND REPAIR ANY DAMAGE OR PENETRATIONS AT ALL
ELEMENTS TO REMAIN (INCLUDING BUT NOT LIMITED TO WALLS, CEILINGS,
FLOORS, ETC.) CAUSED BY DEMOLITION ACTIVITIES OR REMOVAL OF ELECTRICAL,
MECHANICAL, AND ARCHITECTURAL ELEMENTS. REPLACE ITEMS NOT REPAIRABLE
TO ORIGINAL STATE. EXISTING FINISH MATERIALS, INCLUDING CEILINGS, TRIM,
ETC., SHALL BE PROTECTED AND RETAINED, UNLESS NOTED OTHERWISE.
D. PORTIONS OF THE BUILDING ARE TO REMAIN CONTINUOUSLY OCCUPIED
THROUGHOUT CONSTRUCTION. CONTRACTOR TO MAINTAIN CLEAR PATH OF
EGRESS THROUGHOUT CONSTRUCTION.
E. UNLESS NOTED OTHERWISE ALL DIMENSIONS ARE TO THE FACE OF STUD.
G. RE: G101 AND SPECIFICATIONS FOR HAZARDOUS MATERIALS INFORMATION.
SHEET NOTES:
LEGEND:
DASHED LINES INDICATE ASSEMBLIES/SYSTEMS TO BE DEMOLISHED AND
REMOVED. PROTECT ADJACENT EXISTING CONSTRUCTION TO REMAIN.
SOLID LINES INICATE EXISTING ELEMENTS TO REMAIN AND BE PROTECTED
DURING CONSTRUCTION.
A002
A002
A002
A003
AT FLOOR LEVEL ABOVE
PACKAGE #1
PACKAGE #1
PACKAGE #1
PACKAGE #1
A011
PACKAGE #2
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
R.R.
R.R.
WAREHOUSE
CENTRAL
WAREHOUSE
CARTRIDGE
MIXER
ROOM
DOWN RAMP TO BASEMENT
CHARGING
ROOM
FAS
ROOM
R.R.
FREIGHT
SHIPPING/WORKROOM
CLO.
PARKING LOT
NORTH
WAREHOUSE
STORAGE
ROOM
A003
PACKAGE #1
PACKAGE #1 - SAFETY AND HEALTH REVIEW: INCLUDES THE WORK RELATED TO THE
FOLLOWING ROOMS, AREAS, AND ITEMS. REFERENCE THE ASSOCIATED DOCUMENTS,
DRAWINGS, AND SPECIFICATIONS TO FIND FURTHER INFORMATION AND ALL WORK
RELATED TO THESE AREAS.
A. CYANIDE ROOM
B. GRAIN BAIT MIXING ROOM
C. CARTRIDGE ROOM
D. NORTH WAREHOUSE HOT LABEL MAKER
E. GAS CARTRIDGE FUSES
F. PERSONNEL DOOR
PACKAGE #2 - FACILITY CONDITION REASSESSMENT: INCLUDES THE WORK RELATED TO
THE FOLLOWING ROOMS, AREAS, AND ITEMS. REFERENCE THE ASSOCIATED
DOCUMENTS, DRAWINGS, AND SPECIFICATIONS TO FIND FURTHER INFORMATION AND
ALL WORK RELATED TO THESE AREAS.
A. ENERGY CONSERVATION MEASURES - OFFICE LIGHTING
B. BASEMENT RESTROOMS
C. OFFICE HVAC SYSTEM
D. WATER HEATER REPLACEMENT
E. FIRE ALARM SYSTEM
A001
OVERALL DEMOLITION PLAN FIRST FLOOR
1/16"=1'-0"
A001
OVERALL DEMOLITION PLAN BASEMENT
1/16"=1'-0"
A001
OVERALL DEMOLITION ROOF PLAN
1/16"=1'-0"
DRAWN BY |
REVISIONS
© | ALL RIGHTS RESERVED
w w w . c t a g r o u p . c o m
8 0 0 . 7 5 7 . 9 5 2 2
CHECKED BY |
U S
H
I S
P S
D
R
E N
O V
A T
I O
N S
P O
C A
T E
L L
O
I D
A H
O
100% CD
3.27.19
N O
T
F
N
S T
R U
C T
I O
N
P
R E
L I M
I N
A R
Y
D
E S
I G
N
06.29.17 11:09 PM | G:\USDAAPHIS_PSD1\BIMCAD\Arch\A-001.dwg
A001
PACKAGE #1 AND
#2 - OVERALL
DEMOLITION
PLANS
JC
GENERAL NOTES:
A. MAINTAIN THE INTEGRITY OF ALL REMAINING BUILDING SYSTEMS AND RATINGS.
REPAIR ANY DAMAGE DONE TO SURROUNDING AREAS/CONSTRUCTION DURING
DEMOLITION.
B. ALL EXISTING CONDITIONS ARE NOT INDICATED ON THE DRAWINGS. CONTRACTOR
SHALL CAREFULLY EXAMINE THE EXISTING INSTALLATION AND ALL PROJECT
DRAWINGS TO BECOME FAMILIAR WITH THE SCOPE OF WORK.
C. CONTRACTOR SHALL PATCH AND REPAIR ANY DAMAGE OR PENETRATIONS AT ALL
ELEMENTS TO REMAIN (INCLUDING BUT NOT LIMITED TO WALLS, CEILINGS,
FLOORS, ETC.) CAUSED BY DEMOLITION ACTIVITIES OR REMOVAL OF ELECTRICAL,
MECHANICAL, AND ARCHITECTURAL ELEMENTS. REPLACE ITEMS NOT REPAIRABLE
TO ORIGINAL STATE. EXISTING FINISH MATERIALS, INCLUDING CEILINGS, TRIM,
ETC., SHALL BE PROTECTED AND RETAINED, UNLESS NOTED OTHERWISE.
D. PORTIONS OF THE BUILDING ARE TO REMAIN CONTINUOUSLY OCCUPIED
THROUGHOUT CONSTRUCTION. CONTRACTOR TO MAINTAIN CLEAR PATH OF
EGRESS THROUGHOUT CONSTRUCTION.
E. UNLESS NOTED OTHERWISE ALL DIMENSIONS ARE TO THE FACE OF STUD.
F. RE: A001 FOR OVERALL FLOOR PLANS.
G. RE: G101 AND SPECIFICATIONS FOR HAZARDOUS MATERIALS INFORMATION.
SHEET NOTES:
LEGEND:
DASHED LINES INDICATE ASSEMBLIES/SYSTEMS TO BE DEMOLISHED AND
REMOVED. PROTECT ADJACENT EXISTING CONSTRUCTION TO REMAIN.
SOLID LINES INICATE EXISTING ELEMENTS TO REMAIN AND BE PROTECTED
DURING CONSTRUCTION.
1. REMOVE EXISTING CASEWORK.
2. REMOVE EXISTING DOOR, FRAME, AND HARDWARE. PREP FOR NEW DOOR AND
FRAME.
3. REMOVE EXISTING PLUMBING FIXTURE, RE: PLUMBING DRAWINGS.
4. CLEAN AND PREP ALL WALLS AND FLOORS WITHIN ROOM NOTED FOR NEW PAINT.
5. REMOVE EXISTING CARTRIDGE FUSE STORAGE - PREP FOR NEW STORAGE BOXES
- RE: SPECIFICATIONS AND NEW PLANS.
6. PROTECT EXISTING EQUIPMENT AND RELOCATE PER NEW FLOOR PLANS, RE:
A102.
7. PROTECT EXISTING CASEWORK FOR RE-INSTALLATION, RE: NEW FLOOR PLAN ON
A102.
8. RE: MECHANICAL AND ELECTRICAL DRAWINGS FOR FURTHER WORK TO OCCUR
WITHIN ROOM NOTED.
9. EXISTING SCALE AND ASSOCIATED ITEMS TO REMAIN. RE: A102 FOR NEW FLOOR
PLAN.
STORAGE
ROOM
EXTERIOR
PAVEMENT/PARKING
GRAIN
ELEVATOR
MIXER
ROOM
CARTRIDGE
A002
ENLARGED DEMOLITION PLAN CARTRIDGE ROOM
1/4"=1'-0"
A002
ENLARGED DEMOLITION PLAN PERSONNEL DOOR
1/4"=1'-0"
A002
ENLARGED DEMOLITION PLAN MIXER ROOM
1/4"=1'-0"
A002
ENLARGED DEMOLITION PLAN CARTRIDGE FUSE STORAGE
1/4"=1'-0"
DRAWN BY |
REVISIONS
© | ALL RIGHTS RESERVED
w w w . c t a g r o u p . c o m
8 0 0 . 7 5 7 . 9 5 2 2
CHECKED BY |
U S
H
I S
P S
D
R
E N
O V
A T
I O
N S
P O
C A
T E
L L
O
I D
A H
O
100% CD
3.27.19
N O
T
F
N
S T
R U
C T
I O
N
P
R E
L I M
I N
A R
Y
D
E S
I G
N
06.11.18 06:10 PM | G:\USDAAPHIS_PSD1\BIMCAD\Arch\A-002.dwg
A002
PACKAGE #1 -
ENLARGED
DEMOLITION PLANS
REPAIR ANY DAMAGE DONE TO SURROUNDING AREAS/CONSTRUCTION DURING
DEMOLITION.
B. ALL EXISTING CONDITIONS ARE NOT INDICATED ON THE DRAWINGS. CONTRACTOR
SHALL CAREFULLY EXAMINE THE EXISTING INSTALLATION AND ALL PROJECT
DRAWINGS TO BECOME FAMILIAR WITH THE SCOPE OF WORK.
C. CONTRACTOR SHALL PATCH AND REPAIR ANY DAMAGE OR PENETRATIONS AT ALL
ELEMENTS TO REMAIN (INCLUDING BUT NOT LIMITED TO WALLS, CEILINGS,
FLOORS, ETC.) CAUSED BY DEMOLITION ACTIVITIES OR REMOVAL OF ELECTRICAL,
MECHANICAL, AND ARCHITECTURAL ELEMENTS. REPLACE ITEMS NOT REPAIRABLE
TO ORIGINAL STATE. EXISTING FINISH MATERIALS, INCLUDING CEILINGS, TRIM,
ETC., SHALL BE PROTECTED AND RETAINED, UNLESS NOTED OTHERWISE.
D. PORTIONS OF THE BUILDING ARE TO REMAIN CONTINUOUSLY OCCUPIED
THROUGHOUT CONSTRUCTION. CONTRACTOR TO MAINTAIN CLEAR PATH OF
EGRESS THROUGHOUT CONSTRUCTION.
E. UNLESS NOTED OTHERWISE ALL DIMENSIONS ARE TO THE FACE OF STUD.
F. RE: A001 FOR OVERALL FLOOR PLANS.
G. RE: G101 AND SPECIFICATIONS FOR HAZARDOUS MATERIALS INFORMATION.
SHEET NOTES:
LEGEND:
DASHED LINES INDICATE ASSEMBLIES/SYSTEMS TO BE DEMOLISHED AND
REMOVED. PROTECT ADJACENT EXISTING CONSTRUCTION TO REMAIN.
SOLID LINES INICATE EXISTING ELEMENTS TO REMAIN AND BE PROTECTED
DURING CONSTRUCTION.
1. REMOVE EXISTING UPPER AND LOWER CASEWORK AND COUNTERTOP.
2. REMOVE EXISTING DOOR, FRAME, AND HARDWARE. PREP FOR NEW.
3. REMOVE EXISTING PLUMBING FIXTURE, RE: PLUMBING DRAWINGS.
4. EXISTING ROOF ACCESS ROOFTOP ABOVE.
5. EXISTING SHINGLE ROOF TO REMAIN.
6. REMOVE EXISTING LAB EQUIPMENT AND VENTILATION HOOD, WHERE OCCURS.
7. EXISTING STRUCTURE TO REMAIN, RE: MECHANICAL DRAWINGS FOR DEMOLITION
WORK TO OCCUR WITHIN THIS AREA.
8. CLEAN ENTIRETY OF EXISTING FLAT ROOF AREA SHOWN AND PREP FOR NEW
MECHANICAL WORK TO OCCUR. EXISTING ROOF TOP CONTAIN BIRD FECES THAT
WILL NEED TO BE REMOVED DURING CLEANING - FOLLOW ALL OSHA GUIDELINES/
RECOMMENDATIONS PERTAINING TO THIS REMOVAL. HEATH HAZARDS ARE
ASSOCIATED WITH THIS REMOVAL
9. REMOVE EXISTING WALL MOUNTED SOAP AND PAPER TOWEL DISPENSER.
10. EXISTING EQUIPMENT CURB AND OPENING TO REMAIN TO ACCOMMODATE NEW
EQUIPMENT. RE: MECHANICAL DRAWINGS FOR FURTHER DEMOLITION
INFORMATION.
11. RE: MECHANICAL AND ELECTRICAL DRAWINGS FOR FURTHER WORK TO OCCUR
WITHIN ROOM/NOTED AREA.
CYANIDE
ROOM
ROOF
ACCESS
(E) TABLE
(E) TABLE
(E) GRADER
(E) MIXER
(E) TABLE(E) STRG.(E) STRG.
(E) TABLE
(E) KILN
(E) STRG.
A003
ENLARGED DEMOLITION PLAN CYANIDE ROOM
1/4"=1'-0"
A003
ENLARGED DEMOLITION PLAN CYANIDE ROOF TOP
1/4"=1'-0"
DRAWN BY |
REVISIONS
© | ALL RIGHTS RESERVED
w w w . c t a g r o u p . c o m
8 0 0 . 7 5 7 . 9 5 2 2
CHECKED BY |
U S
H
I S
P S
D
R
E N
O V
A T
I O
N S
P O
C A
T E
L L
O
I D
A H
O
100% CD
3.27.19
N O
T
F
N
S T
R U
C T
I O
N
P
R E
L I M
I N
A R
Y
D
E S
I G
N
06.11.18 06:11 PM | G:\USDAAPHIS_PSD1\BIMCAD\Arch\A-003.dwg
A003
PACKAGE #1 -
ENLARGED
DEMOLITION PLANS
REPAIR ANY DAMAGE DONE TO SURROUNDING AREAS/CONSTRUCTION DURING
DEMOLITION.
B. ALL EXISTING CONDITIONS ARE NOT INDICATED ON THE DRAWINGS. CONTRACTOR
SHALL CAREFULLY EXAMINE THE EXISTING INSTALLATION AND ALL PROJECT
DRAWINGS TO BECOME FAMILIAR WITH THE SCOPE OF WORK.
C. CONTRACTOR SHALL PATCH AND REPAIR ANY DAMAGE OR PENETRATIONS AT ALL
ELEMENTS TO REMAIN (INCLUDING BUT NOT LIMITED TO WALLS, CEILINGS,
FLOORS, ETC.) CAUSED BY DEMOLITION ACTIVITIES OR REMOVAL OF ELECTRICAL,
MECHANICAL, AND ARCHITECTURAL ELEMENTS. REPLACE ITEMS NOT REPAIRABLE
TO ORIGINAL STATE. EXISTING FINISH MATERIALS, INCLUDING CEILINGS, TRIM,
ETC., SHALL BE PROTECTED AND RETAINED, UNLESS NOTED OTHERWISE.
D. PORTIONS OF THE BUILDING ARE TO REMAIN CONTINUOUSLY OCCUPIED
THROUGHOUT CONSTRUCTION. CONTRACTOR TO MAINTAIN CLEAR PATH OF
EGRESS THROUGHOUT CONSTRUCTION.
E. UNLESS NOTED OTHERWISE ALL DIMENSIONS ARE TO THE FACE OF STUD.
F. RE: A001 FOR OVERALL FLOOR PLANS.
G. RE: G101 AND SPECIFICATIONS FOR HAZARDOUS MATERIALS INFORMATION.
SHEET NOTES:
LEGEND:
DASHED LINES INDICATE ASSEMBLIES/SYSTEMS TO BE DEMOLISHED AND
REMOVED. PROTECT ADJACENT EXISTING CONSTRUCTION TO REMAIN.
SOLID LINES INICATE EXISTING ELEMENTS TO REMAIN AND BE PROTECTED
DURING CONSTRUCTION.
1. REMOVE EXISTING WALL TO EXTENTS INDICATED.
2. RE: MECHANICAL DRAWINGS FOR WORK TO OCCUR WITHIN AREA NOTED.
PROTECT ALL EXISTING ITEMS TO REMAIN.
3. REMOVE EXISTING DOOR, FRAME, AND HARDWARE. PREP FOR NEW DOOR AND
FRAME.
4. REMOVE EXISTING PLUMBING FIXTURE.
5. REMOVE EXISTING TOILET PARTITIONS.
6. REMOVE EXISTING SHOWER BENCH.
7. REMOVE EXISTING SHOWER HEAD AND ALL ASSOCIATED ITEMS.
8. REMOVE EXISTING FLOOR DRAIN, RE: PLUMBING DRAWINGS.
9. EXISTING WINDOW ABOVE TO REMAIN, PROTECT.
10. REMOVE ENTIRETY OF EXISTING CONCRETE SLAB AND ALL ASSOCIATED ITEMS,
INCLUDING EXISTING PLUMBING PIPING, WITHIN ROOM NOTED, PREP FOR NEW
SLAB, RE: A111.
11. REMOVE ALL EXISTING BATHROOM ACCESSORIES WITHIN ROOM NOTED.
12. REMOVE SECTION OF EXISTING CONCRETE WALL PER DIMENSIONS ON THIS PLAN
AND DETAILS ON A601.
13. EXISTING CONCRETE LOCKERS TO REMAIN.
14. RE: MECHANICAL AND PLUMBING DRAWINGS FOR REMOVAL OF EXISTING FIRE
HOSE CABINET.
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
R.R.
R.R.
CLO.
R.R.
LOCKERS
STORAGE
7'-0" 1'-0"
12 14
A011
ENLARGED DEMOLITION PLAN BASEMENT RESTROOMS
1/4"=1'-0"
DRAWN BY |
REVISIONS
© | ALL RIGHTS RESERVED
w w w . c t a g r o u p . c o m
8 0 0 . 7 5 7 . 9 5 2 2
CHECKED BY |
U S
H
I S
P S
D
R
E N
O V
A T
I O
N S
P O
C A
T E
L L
O
I D
A H
O
100% CD
3.27.19
N O
T
F
N
S T
R U
C T
I O
N
P
R E
L I M
I N
A R
Y
D
E S
I G
N
06.11.18 06:10 PM | G:\USDAAPHIS_PSD1\BIMCAD\Arch\A-011.dwg
A011
PACKAGE #2 -
ENLARGED
DEMOLITION
PLANS
JC
SR
A011
ENLARGED DEMOLITION FLOOR PLAN OFFICES
1/4"=1'-0"
A111
A102
PACKAGE #2
PACKAGE #1
RAMP
BASEMENT
WAREHOUSE
ALPHACHLORALOSE
LAB
M-44
MACHINE
SHOP
ADC
STORAGE
COAL
STORAGE
RM.
ROOM
LOCKERS
ELECTRIC
DISTRIBUTION
ROOM
FREIGHT
BASEMENT
WAREHOUSE
STORAGE
ROOM
ROOM
GRAIN
ELEVATOR
AREA
AT
BASEMENT
LEVEL
GAS CARTRIDGE
FUSE STORAGE
A102
A102
A102
A103
AT FLOOR
LEVEL
ABOVE
PACKAGE #1
PACKAGE #1
PACKAGE #1
PACKAGE #1
A111
PACKAGE #2
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
R.R.
R.R.
WAREHOUSE
CENTRAL
WAREHOUSE
CARTRIDGE
MIXER
ROOM
DOWN RAMP TO BASEMENT
CHARGING
ROOM
FAS
ROOM
R.R.
FREIGHT
SHIPPING/WORKROOM
CLO.
PARKING LOT
NORTH
WAREHOUSE
STORAGE
ROOM
A104
PACKAGE #1
AT MECHANICAL
MEZZANINE
ABOVE
A104
PACKAGE #1
AT MECHANICAL
MEZZANINE
ABOVE
A103
PACKAGE #1
RS
RL
R S
R L
GENERAL NOTES:
A. MAINTAIN THE INTEGRITY OF ALL REMAINING BUILDING SYSTEMS AND RATINGS.
REPAIR ANY DAMAGE DONE TO SURROUNDING AREAS/CONSTRUCTION DURING
DEMOLITION.
B. ALL EXISTING CONDITIONS ARE NOT INDICATED ON THE DRAWINGS. CONTRACTOR
SHALL CAREFULLY EXAMINE THE EXISTING INSTALLATION AND ALL PROJECT
DRAWINGS TO BECOME FAMILIAR WITH THE SCOPE OF WORK.
C. CONTRACTOR SHALL PATCH AND REPAIR ANY DAMAGE OR PENETRATIONS AT ALL
ELEMENTS TO REMAIN (INCLUDING BUT NOT LIMITED TO WALLS, CEILINGS,
FLOORS, ETC.) CAUSED BY DEMOLITION ACTIVITIES OR REMOVAL OF ELECTRICAL,
MECHANICAL, AND ARCHITECTURAL ELEMENTS. REPLACE ITEMS NOT REPAIRABLE
TO ORIGINAL STATE. EXISTING FINISH MATERIALS, INCLUDING CEILINGS, TRIM,
ETC., SHALL BE PROTECTED AND RETAINED, UNLESS NOTED OTHERWISE.
D. PORTIONS OF THE BUILDING ARE TO REMAIN CONTINUOUSLY OCCUPIED
THROUGHOUT CONSTRUCTION. CONTRACTOR TO MAINTAIN CLEAR PATH OF
EGRESS THROUGHOUT CONSTRUCTION.
E. UNLESS NOTED OTHERWISE ALL DIMENSIONS ARE TO THE FACE OF STUD.
F. RE: A101 FOR OVERALL FLOOR PLANS.
1. NEW MECHANICAL ROOF PENETRATION, RE: A601 AND MECHANICAL DRAWINGS
FOR DETAILS.
2. RE: ELECTRICAL, MECHANICAL AND PLUMBING DRAWINGS FOR WORK TO OCCUR
WITHIN ROOM NOTED.
SHEET NOTES:
INTERIOR ELEVATION NUMBER /
SHEET WHERE DRAWN
F.E.F. FACE OF EXISTNG FINISH
DIMENSION TO FACE OF
STUD OR EXISTING WALL
DOOR NUMBER (SEE SHEET A101)
PLAN LEGEND
DETAIL OR SECTION NUMBER
SHEET WHERE DRAWN
PLAN NOTE
ROOM NAME
WALL TYPE
WALL TYPE NOTE
X
X
X
A101
101-1
A801
A
B
C
D
PACKAGE #1 - SAFETY AND HEALTH REVIEW: INCLUDES THE WORK RELATED TO THE
FOLLOWING ROOMS, AREAS, AND ITEMS. REFERENCE THE ASSOCIATED DOCUMENTS,
DRAWINGS, AND SPECIFICATIONS TO FIND FURTHER INFORMATION AND ALL WORK
RELATED TO THESE AREAS.
A. CYANIDE ROOM
B. GRAIN BAIT MIXING ROOM
C. CARTRIDGE ROOM
D. NORTH WAREHOUSE HOT LABEL MAKER
E. GAS CARTRIDGE FUSES
F. PERSONNEL DOOR
PACKAGE #2 - FACILITY CONDITION REASSESSMENT: INCLUDES THE WORK RELATED TO
THE FOLLOWING ROOMS, AREAS, AND ITEMS. REFERENCE THE ASSOCIATED
DOCUMENTS, DRAWINGS, AND SPECIFICATIONS TO FIND FURTHER INFORMATION AND
ALL WORK RELATED TO THESE AREAS.
A. ENERGY CONSERVATION MEASURES - OFFICE LIGHTING
B. BASEMENT RESTROOMS
C. OFFICE HVAC SYSTEM
D. WATER HEATER REPLACEMENT
E. FIRE ALARM SYSTEM
A101
OVERALL FLOOR PLAN FIRST FLOOR
1/16"=1'-0"
A101
OVERALL FLOOR PLAN BASEMENT
1/16"=1'-0"
A101
OVERALL ROOF PLAN
1/16"=1'-0"
DRAWN BY |
REVISIONS
© | ALL RIGHTS RESERVED
w w w . c t a g r o u p . c o m
8 0 0 . 7 5 7 . 9 5 2 2
CHECKED BY |
U S
H
I S
P S
D
R
E N
O V
A T
I O
N S
P O
C A
T E
L L
O
I D
A H
O
100% CD
3.27.19
N O
T
F
N
S T
R U
C T
I O
N
P
R E
L I M
I N
A R
Y
D
E S
I G
N
06.11.18 06:12 PM | G:\USDAAPHIS_PSD1\BIMCAD\Arch\A-101.dwg
A101
PACKAGE #1 AND #2 -
OVERALL PLANS
REPAIR ANY DAMAGE DONE TO SURROUNDING AREAS/CONSTRUCTION DURING
DEMOLITION.
B. ALL EXISTING CONDITIONS ARE NOT INDICATED ON THE DRAWINGS. CONTRACTOR
SHALL CAREFULLY EXAMINE THE EXISTING INSTALLATION AND ALL PROJECT
DRAWINGS TO BECOME FAMILIAR WITH THE SCOPE OF WORK.
C. CONTRACTOR SHALL PATCH AND REPAIR ANY DAMAGE OR PENETRATIONS AT ALL
ELEMENTS TO REMAIN (INCLUDING BUT NOT LIMITED TO WALLS, CEILINGS,
FLOORS, ETC.) CAUSED BY DEMOLITION ACTIVITIES OR REMOVAL OF ELECTRICAL,
MECHANICAL, AND ARCHITECTURAL ELEMENTS. REPLACE ITEMS NOT REPAIRABLE
TO ORIGINAL STATE. EXISTING FINISH MATERIALS, INCLUDING CEILINGS, TRIM,
ETC., SHALL BE PROTECTED AND RETAINED, UNLESS NOTED OTHERWISE.
D. PORTIONS OF THE BUILDING ARE TO REMAIN CONTINUOUSLY OCCUPIED
THROUGHOUT CONSTRUCTION. CONTRACTOR TO MAINTAIN CLEAR PATH OF
EGRESS THROUGHOUT CONSTRUCTION.
E. UNLESS NOTED OTHERWISE ALL DIMENSIONS ARE TO THE FACE OF STUD.
F. RE: A101 FOR OVERALL FLOOR PLANS.
SHEET NOTES:
FACE OF EXISTNG FINISH
1. NEW DOOR AND FRAME, COORDINATE WITH DOOR SCHEDULE AND ELECTRICAL
DRAWINGS FOR NEW ACCESS CONTROL TO BE DONE AT DOOR. PATCH, REPAIR
AND RE-FINISH WALL AS REQUIRED FOR ELECTRICAL WORK, RE: ELECTRICAL
DRAWINGS. FINISHES TO MATCH EXISTING FINISHES, VERIFY IN FIELD. RE: A-601
HEAD, JAMB DETAILS. THE SIZE OF THIS DOOR AND FRAME IS A CUSTOM SIZE,
REFERENCE A-601 FOR DOOR SCHEDULE AND NOTATIONS.
2. NEW FUSE STORAGE 'B1200 HAZMAT DRUM STORAGE LOCKER' OR EQUAL.
COORDINATE EXACT PLACEMENT ON SITE WITH GOVERNMENT OFFICIAL, RE:
MECHANICAL AND ELECTRICAL DRAWINGS FOR FURTHER ITEMS AND DETAILS.
3. RELOCATED EXISTING METAL CASEWORK.
4. NEW METAL WIRE SHELVING UNIT - (4) SHELVES HIGH - UNIT TO BE 48"X18"DX72"H.
5. RELOCATED EXISTING MIXER.
6. PAINT ALL WALLS WITHIN ROOM NOTED, PAINT WITH EPOXY HIGH PERFORMANCE
COATING, RE: SPECIFICATIONS. PROTECT EXISTING EQUIPMENT WHEN PAINTING,
MOVE FURNITURE AND EQUIPMENT AS NECESSARY TO ACCOMMODATE PAINT.
7. PAINT FLOOR WITHIN ROOM NOTED, PAINT WITH EPOXY HIGH PERFORMANCE
COATING, RE: SPECIFICATIONS.
8. NEW SINK, RE: PLUMBING DRAWINGS AND SPECIFICATIONS.
9. NEW EYEWASH, RE: PLUMBING DRAWINGS AND SPECIFICATIONS.
10. EXISTING FLOOR DRAIN TO REMAIN.
11. RELOCATED EXISTING STORAGE BINS, COORDINATE PLACEMENT WITH
GOVERNMENT REPRESENTATIVE ON SITE.
12. EXISTING SCALE AND ASSOCIATED ITEMS TO REMAIN IN PLACE.
STORAGE
ROOM
EXTERIOR
PAVEMENT/PARKING
GRAIN
ELEVATOR
MIXER
ROOM
CARTRIDGE
FUSE
STORAGE
INTERIOR ELEVATION NUMBER /
SHEET WHERE DRAWN
F.E.F. FACE OF EXISTNG FINISH
DIMENSION TO FACE OF
STUD OR EXISTING WALL
DOOR NUMBER (SEE SHEET A101)
PLAN LEGEND
DETAIL OR SECTION NUMBER
SHEET WHERE DRAWN
PLAN NOTE
ROOM NAME
WALL TYPE
WALL TYPE NOTE
X
X
X
A101
A801
A
B
C
D
101-1
A102
ENLARGED FLOOR PLAN CARTRIDGE ROOM
1/4"=1'-0"
A102
ENLARGED FLOOR PLAN PERSONNEL DOOR
1/4"=1'-0"
A102
ENLARGED FLOOR PLAN MIXER ROOM
1/4"=1'-0"
DRAWN BY |
REVISIONS
© | ALL RIGHTS RESERVED
w w w . c t a g r o u p . c o m
8 0 0 . 7 5 7 . 9 5 2 2
CHECKED BY |
U S
H
I S
P S
D
R
E N
O V
A T
I O
N S
P O
C A
T E
L L
O
I D
A H
O
100% CD
3.27.19
N O
T
F
N
S T
R U
C T
I O
N
P
R E
L I M
I N
A R
Y
D
E S
I G
N
06.11.18 06:12 PM | G:\USDAAPHIS_PSD1\BIMCAD\Arch\A-102.dwg
A102
PACKAGE #1 -
ENLARGED
PLANS
JC
SR
A102
ENLARGED FLOOR PLAN GAS CARTRIDGE FUSES
REPAIR ANY DAMAGE DONE TO SURROUNDING AREAS/CONSTRUCTION DURING
DEMOLITION.
B. ALL EXISTING CONDITIONS ARE NOT INDICATED ON THE DRAWINGS. CONTRACTOR
SHALL CAREFULLY EXAMINE THE EXISTING INSTALLATION AND ALL PROJECT
DRAWINGS TO BECOME FAMILIAR WITH THE SCOPE OF WORK.
C. CONTRACTOR SHALL PATCH AND REPAIR ANY DAMAGE OR PENETRATIONS AT ALL
ELEMENTS TO REMAIN (INCLUDING BUT NOT LIMITED TO WALLS, CEILINGS,
FLOORS, ETC.) CAUSED BY DEMOLITION ACTIVITIES OR REMOVAL OF ELECTRICAL,
MECHANICAL, AND ARCHITECTURAL ELEMENTS. REPLACE ITEMS NOT REPAIRABLE
TO ORIGINAL STATE. EXISTING FINISH MATERIALS, INCLUDING CEILINGS, TRIM,
ETC., SHALL BE PROTECTED AND RETAINED, UNLESS NOTED OTHERWISE. MATCH
EXISTING PAINT AND MATERIALS, VERIFY IN FIELD. CONFIRM AND CONSULT WITH
GOVERNMENT REPRESENTATIVE ON PATCH WORK PRIOR TO COMMENCING.
D. PORTIONS OF THE BUILDING ARE TO REMAIN CONTINUOUSLY OCCUPIED
THROUGHOUT CONSTRUCTION. CONTRACTOR TO MAINTAIN CLEAR PATH OF
EGRESS THROUGHOUT CONSTRUCTION.
E. UNLESS NOTED OTHERWISE ALL DIMENSIONS ARE TO THE FACE OF STUD.
F. RE: A101 FOR OVERALL FLOOR PLANS.
1. EXISTING ROOF ACCESS ROOFTOP ABOVE.
2. EXISTING SHINGLE ROOF TO REMAIN.
3. NEW OSHA COMPLIANT FALL PROTECTION RAILING AROUND PERIMETER OF
EXISTING ROOF WHERE SHOWN, RE: DETAILS ON A601. RAILING TO BE 'SAFETY
RAIL COMPANY: PERMANENT FACE MOUNT GUARDRAIL SYSTEM' OR EQUAL,
MOUNT/INSTALL PER MANUFACTURER RECOMMENDATIONS AND INSTRUCTIONS,
RE: A601 FOR DETAILS.
4. NEW STORAGE CABINET, CABINET TO BE ULINE 'H-1223' HEAVY DUTY STORAGE
CABINET OR EQUAL.
5. NEW MECHANICAL CONVECTION LABORATORY OVEN, RE: SPECIFICATIONS AND
MECHANICAL DRAWINGS.
6. NEW STAINLESS STEEL COUNTERTOP TO BE ULINE "INDUSTRIAL PACKING TABLE -
48 X 36", STAINLESS STEEL TOP 'H-3657-SS' " OR EQUAL.
7. RE: MECHANICAL AND ELECTRICAL DRAWINGS FOR FURTHER WORK TO OCCUR
WITHIN ROOM/AREA NOTED.
8. NEW LAB EQUIPMENT, RE: MECHANICAL DRAWINGS.
9. NEW SELF CONTAINED EYE WASH STATION, RE: PLUMBING DRAWINGS.
10. RE: MECHANICAL DRAWINGS AND DETAIL 3/A103 FOR INFILL DETAIL AT EXISTING
OPENING BEING UTILIZED FOR NEW LOUVER LOCATION AND TYPE. OPENING
OCCURS AT EXISTING EXTERIOR WALL BELOW ROOF LINE.
11. PAINT ALL WALLS WITHIN ROOM NOTED, PAINT WITH EPOXY HIGH PERFORMANCE
COATING, RE: SPECIFICATIONS. PROTECT EXISTING EQUIPMENT WHEN PAINTING,
MOVE FURNITURE AND EQUIPMENT AS NECESSARY TO ACCOMMODATE PAINT.
12. PAINT FLOOR WITHIN ROOM NOTED, PAINT WITH EPOXY HIGH PERFORMANCE
COATING, RE: SPECIFICATIONS.
13. ROUTE DUCTWORK TO FIT THROUGH RAILING OPENING, RE: MECHANICAL
DRAWINGS.
SHEET NOTES:
CYANIDE
ROOM
ROOF
ACCESS
(E) TABLE
(E) TABLE
(E) GRADER
(E) MIXER
(E) TABLE(E) STRG.(E) STRG.
(E) TABLE
(E) KILN
(E) STRG.
3'-0"
APPROX. 50'-4"
V.I.F. (VERIFY IN FIELD)
A P
P R
O X
V I F
A P
P R
O X
V I F
A601
A601
A601
GENERAL NOTES:
INTERIOR ELEVATION NUMBER /
SHEET WHERE DRAWN
F.E.F. FACE OF EXISTNG FINISH
DIMENSION TO FACE OF
STUD OR EXISTING WALL
DOOR NUMBER (SEE SHEET A101)
PLAN LEGEND
DETAIL OR SECTION NUMBER
SHEET WHERE DRAWN
PLAN NOTE
ROOM NAME
WALL TYPE
WALL TYPE NOTE
X
X
X
A101
101-1
A801
A
B
C
D
V I F
2" 'WALLGUARD CONCRETE FACED
INSULATED WALL PANEL' OR EQUAL
BACKER ROD AND SEALANT (ALL
SIDES)
INFILL CAVITY WITH BATT
INSULATION
TREATED WOOD BLOCKING AS NECESSARY
- VERIFY EXISTING WALL WIDTH IN FIELD
" GYPSUM WALL BOARD-MATCH PAINT
'PT1' PER SPECIFICATIONS, CREATE
FLUSH FINISH WITH EXISTING
ADJACENT WALL
*NOTE- REFERENCE MECHANICAL DRAWINGS - M-101 -
FOR AREAS WHERE NEW LOUVERS ARE TO OCCUR IN
THE EXTERIOR WALL - THIS DETAIL SHALL BE USED TO
INFILL THE WALL WHERE THE LOUVER DOES NOT INFILL
THE ENTIRETY OF THE EXISTING OPENING SIZE.
NEW MECHANICAL LOUVER,. RE:
MECHANICAL DRAWINGS AND
SPECIFICATIONS.
V.I.F.
VERIFY HEIGHT OF OPENING IN FIELD
A103
ENLARGED FLOOR PLAN CYANIDE ROOM
1/4"=1'-0"
A103
ENLARGED FLOOR PLAN CYANIDE ROOF TOP
1/4"=1'-0"
DRAWN BY |
REVISIONS
© | ALL RIGHTS RESERVED
w w w . c t a g r o u p . c o m
8 0 0 . 7 5 7 . 9 5 2 2
CHECKED BY |
U S
H
I S
P S
D
R
E N
O V
A T
I O
N S
P O
C A
T E
L L
O
I D
A H
O
100% CD
3.27.19
N O
T
F
N
S T
R U
C T
I O
N
P
R E
L I M
I N
A R
Y
D
E S
I G
N
06.11.18 06:12 PM | G:\USDAAPHIS_PSD1\BIMCAD\Arch\A-103.dwg
A103
PACKAGE #1
- ENLARGED
PLANS
JC
SR
A103
INFILL DETAIL AT EXTERIOR WALL OPENING
REPAIR ANY DAMAGE DONE TO SURROUNDING AREAS/CONSTRUCTION DURING
DEMOLITION.
B. ALL EXISTING CONDITIONS ARE NOT INDICATED ON THE DRAWINGS. CONTRACTOR
SHALL CAREFULLY EXAMINE THE EXISTING INSTALLATION AND ALL PROJECT
DRAWINGS TO BECOME FAMILIAR WITH THE SCOPE OF WORK.
C. CONTRACTOR SHALL PATCH AND REPAIR ANY DAMAGE OR PENETRATIONS AT ALL
ELEMENTS TO REMAIN (INCLUDING BUT NOT LIMITED TO WALLS, CEILINGS,
FLOORS, ETC.) CAUSED BY DEMOLITION ACTIVITIES OR REMOVAL OF ELECTRICAL,
MECHANICAL, AND ARCHITECTURAL ELEMENTS. REPLACE ITEMS NOT REPAIRABLE
TO ORIGINAL STATE. EXISTING FINISH MATERIALS, INCLUDING CEILINGS, TRIM,
ETC., SHALL BE PROTECTED AND RETAINED, UNLESS NOTED OTHERWISE. MATCH
EXISTING PAINT AND MATERIALS, VERIFY IN FIELD. CONFIRM AND CONSULT WITH
GOVERNMENT REPRESENTATIVE ON PATCH WORK PRIOR TO COMMENCING.
D. PORTIONS OF THE BUILDING ARE TO REMAIN CONTINUOUSLY OCCUPIED
THROUGHOUT CONSTRUCTION. CONTRACTOR TO MAINTAIN CLEAR PATH OF
EGRESS THROUGHOUT CONSTRUCTION.
E. UNLESS NOTED OTHERWISE ALL DIMENSIONS ARE TO THE FACE OF STUD.
F. RE: A101 FOR OVERALL FLOOR PLANS.
1. NEW OSHA COMPLIANT FALL PROTECTION RAILING AROUND PERIMETER OF
EXISTING MEZZANINE WHERE SHOWN. RAILING TO BE 'SAFETY RAIL COMPANY:
PERMANENT FLUSH MOUNT GUARDRAIL SYSTEM' OR EQUAL, MOUNT/INSTALL PER
MANUFACTURER RECOMMENDATIONS AND INSTRUCTIONS, MOUNT ON INSIDE
FACE OF CMU WALL.
2. EXISTING CMU BLOCK WALLS, FULLY GROUTED, TOP OF WALL IS APPROXIMATELY
14'-8" A.F.F. - VERIFY IN FIELD. RE: 4/A104 FOR EXISTING CONDITION IMAGES.
3. COORDINATE NEW RAILING WITH EXISTING MECHANICAL EQUIPEMENT AND
DUCTWORK ASSOCIATED WITH THE MECHANICAL MEZZANINE - VERIFY LOCATIONS
AND QUANTITY IN FIELD. RE: 4/A104 FOR EXISTING CONDITION IMAGES.
4. COORDINATE NEW RAILING WITH EXISTING AND NEW MECHANICAL EQUIPEMENT
AND DUCTWORK ASSOCIATED WITH THE MECHANICAL MEZZANINE - VERIFY
LOCATIONS AND QUANTITY IN FIELD. RE: MECHANICAL DRAWINGS. RE: 3/A104 FOR
EXISTING CONDITION IMAGES.
5. NEW OSHA COMPLIANT FALL PROTECTION RAILING AROUND PERIMETER OF
EXISTING MEZZANINE WHERE SHOWN. RAILING TO BE 'SAFETY RAIL COMPANY:
PERMANENT FACE MOUNT GUARDRAIL SYSTEM' OR EQUAL, MOUNT/INSTALL PER
MANUFACTURER RECOMMENDATIONS AND INSTRUCTIONS. COORDINATE
MOUNTING WITH EXISTING CONDUIT.
6. INSTALL SELF-CLOSING GATE FOR SQUARE OR ROUND POST MOUNT 23-29"
(SAFETY YELLOW) - GATE TO BE 'SAFETY RAIL COMPANY' OR EQUAL.
7. EXISTING FIXED LADDER MEZZANINE ACCESS - LADDER TO BE PROTECTED AND
MAINTAINED - PROVIDE GATE AT EXISTING LADDER.
8. NEW OSHA COMPLIANT FALL PROTECTION RAILING WHERE SHOWN ON SURFACE
OF MEZZANINE. RAILING TO BE 'SAFETY RAIL COMPANY: PERMANENT SURFACE
MOUNT GUARDRAIL SYSTEM' OR EQUAL, MOUNT/INSTALL PER MANUFACTURER
RECOMMENDATIONS AND INSTRUCTIONS. COORDINATE MOUNTING WITH
EXISTING CONDUIT.
SHEET NOTES:
MIXER
ROOM
STORAGE
ROOM
V I F
11'-8"
V.I.F.
V I F
NORTH
WAREHOUSE
1 6
19'-4"
9'-4"
28'-8"
A104
ENLARGED FLOOR PLAN MIXING ROOM MECHANICAL MEZZANINE
1/4"=1'-0"
A104
ENLARGED FLOOR PLAN NORTH WAREHOUSE MECHANICAL MEZZANINE
1/4"=1'-0"
DRAWN BY |
REVISIONS
© | ALL RIGHTS RESERVED
w w w . c t a g r o u p . c o m
8 0 0 . 7 5 7 . 9 5 2 2
CHECKED BY |
U S
H
I S
P S
D
R
E N
O V
A T
I O
N S
P O
C A
T E
L L
O
I D
A H
O
100% CD
3.27.19
N O
T
F
N
S T
R U
C T
I O
N
P
R E
L I M
I N
A R
Y
D
E S
I G
N
06.11.18 06:12 PM | G:\USDAAPHIS_PSD1\BIMCAD\Arch\A-104.dwg
A104
PACKAGE #1
- ENLARGED
PLANS
JC
SR
A104
EXISTING CONDITIONS OF MIXING ROOM MECHANICAL MEZZANINE
NOT TO SCALE
A104
EXISTING CONDITIONS OF NORTH WAREHOUSE MECHANICAL MEZZANINE
NOT TO SCALE
REPAIR ANY DAMAGE DONE TO SURROUNDING AREAS/CONSTRUCTION DURING
DEMOLITION.
B. ALL EXISTING CONDITIONS ARE NOT INDICATED ON THE DRAWINGS. CONTRACTOR
SHALL CAREFULLY EXAMINE THE EXISTING INSTALLATION AND ALL PROJECT
DRAWINGS TO BECOME FAMILIAR WITH THE SCOPE OF WORK.
C. CONTRACTOR SHALL PATCH AND REPAIR ANY DAMAGE OR PENETRATIONS AT ALL
ELEMENTS TO REMAIN (INCLUDING BUT NOT LIMITED TO WALLS, CEILINGS,
FLOORS, ETC.) CAUSED BY DEMOLITION ACTIVITIES OR REMOVAL OF ELECTRICAL,
MECHANICAL, AND ARCHITECTURAL ELEMENTS. REPLACE ITEMS NOT REPAIRABLE
TO ORIGINAL STATE. EXISTING FINISH MATERIALS, INCLUDING CEILINGS, TRIM,
ETC., SHALL BE PROTECTED AND RETAINED, UNLESS NOTED OTHERWISE.
D. PORTIONS OF THE BUILDING ARE TO REMAIN CONTINUOUSLY OCCUPIED
THROUGHOUT CONSTRUCTION. CONTRACTOR TO MAINTAIN CLEAR PATH OF
EGRESS THROUGHOUT CONSTRUCTION.
E. UNLESS NOTED OTHERWISE ALL DIMENSIONS ARE TO THE FACE OF STUD.
F. RE: A601 FOR DOOR TYPES, HARDWARE AND DETAILS.
G. RE: A801 FOR INTERIOR ELEVATIONS AND FIXTURE ACCESSIBILITY
REQUIREMENTS.
H. RE: A101 FOR OVERALL FLOOR PLANS.
1. RE: MECHANICAL AND ELECTRICAL DRAWINGS FOR WORK TO OCCUR IN THIS AREA.
2. SHOWER CONTROL WALL, RE: PLUMBING DRAWINGS.
3. SHOWER BENCH WALL, RE: SPECIFICATIONS. INSTALL BENCH PER MANUFACTURER
RECOMMENDATION.
4. WALL HUNG SINK AND ASSOCIATED MIRROR, RE: PLUMBING DRAWINGS AND A801.
5. TOILET PLUMBING FIXTURE, RE: PLUMBING DRAWINGS.
6. NEW BENCH RE: DETAILS ON A801.
7. EXISTING WALL MOUNTED COMMUNICATIONS EQUIPMENT ABOVE TO REMAIN, PROTECT ALL
ASSOCIATED ITEMS. DO NOT PAINT. VERIFY EXACT LOCATION IN FIELD.
8. RE-ROUTE EXISTING CONDUIT AS NECESSARY TO ACCOMMODATE NEW OPENING.
9. FACE OF GYPSUM CEILING, AND ASSOCIATED CEILING FRAMING TO BE 8'-0" ABOVE FINISH
FLOOR, PAINT PT1. RE: ELECTRICAL DRAWINGS FOR LIGHTING DETAILS.
10. FIBERGLASS SHOWER INSERT PER SPECIFICATIONS.
11. TILE TO CONCRETE FLOOR TRANSITION PER SPECIFICATIONS, RE: 4/A-111 FOR DETAILS.
12. MECHANICAL EQUIPMENT, RE: MECHANICAL DRAWINGS. RE: A601 FOR FURTHER DETAILS
13. NEW SLAB, S1, THROUGHOUT ENTIRETY OF AREA WHERE SLAB WAS REMOVED DURING
DEMOLITION. RE: DETAIL 4/A111. NEW SLAB TO RECEIVE TILE AND TILE COVE BASE
THROUGHOUT, INSTALL TILE PER MANUFACTURER INSTRUCTIONS AND RECOMMENDATIONS.
14. INSTALL ACCESSIBLE RESTROOM PANEL SIGNAGE PER DETAILS ON A801.
15. RE: MECHANICAL DRAWINGS FOR PIPING LOCATIONS. RE: A601 FOR THRU WALL
PENETRATION DETAILS.
16. NEW CONCRETE PAD FOR MECHANICAL EQUIPMENT. PAD TO BE SLAB TYPE 'S1'- NO VAPOR
BARRIER IS NEEDED AT THIS PAD LOCATION. REMOVE EXISTING ASPHALT AS NEEDED TO
ACCOMMODATE NEW PAD - PATCH EXISTING ASPHALT WHERE DAMAGE OCCURS.
17. FACE OF GYPSUM CEILING, AND ASSOCIATED CEILING FRAMING TO BE 9'-0" ABOVE FINISH
FLOOR, PAINT PT1. RE: ELECTRICAL DRAWINGS FOR LIGHTING DETAILS.
18. INSTALL STEEL FRAMING AROUND OPENING PER DETAILS ON A-601 - STEEL FRAMING TO BE
PAINTED TO MATCH DOOR FRAMES.
SHEET NOTES:
LOCKERS
STORAGE
5 5
B
B
B102
R.R.
B101
R.R.
1'-0"
MIN.
1'-0"
MIN.
4"
A801
A
B
C
D
A801
A
B
C
D
5'-9"5'-9"
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
R.R.
R.R.
CLO.
R S
R L
4'-0"
LOCKERS
STORAGE
B101
R.R.
B102
R.R.
A801
(1) LAYER
" TYPE 'X' EA. SIDE
4" METAL STUD AT 16" O.C.
FIBER GLASS BLANKET INSULATION, FILL STUD CAVITY.
NOTE: USE MOISTURE RESISTANT GYPSUM WALL
BOARD ON ALL WET WALL, RE: A801 AND
SPECIFICATIONS.
WALL TYPES:
(1) LAYER
" TYPE 'X' EA. SIDE
(2)STAGGERED 6" METAL STUDS AT 16" O.C.
FIBER GLASS BLANKET
INSULATION, FILL STUD CAVITY
NOTE: USE MOISTURE RESISTANT GYPSUM WALL
BOARD ON ALL WET WALLS, RE: A801 AND
SPECIFICATIONS.
VAPOR BARRIER
4" COMPACTED GRAVEL FILL
4" CONCRETE SLAB
w/#3 @ 16”OC EA WAY
1½” CLR FROM TOP OF SLAB
NOTES:
Concrete shall be f'c = 4,500psi ASTM C150 TYPE I/II, Fly Ash
ASTM C615 Class C or F, W/C +Fly Ash ratio = 0.45 max, ¾” max normal weight aggregate.
Rebar shall be ASTM A615, Grade 60.
S1
SLAB TYPES:
FF ELEV
#4 x 2'-6" DOWEL w/ 6" EMBED
SET IN EPOXY @ 16" OC
(N) CONC SLAB ON
GRADE, SEE SLAB
TYPE AND FLOOR
PLAN
(E) CONC SLAB ON GRADE
E Q
E Q
DEPRESSED SLAB - FINISH
FACE OF TILE TO MATCH
TOP OF EXISTING SLAB
TILE FLOOR FINISH, RE: PLANS
AND SPECIFICATIONS
INTERIOR ELEVATION NUMBER /
SHEET WHERE DRAWN
F.E.F. FACE OF EXISTNG FINISH
DIMENSION TO FACE OF
STUD OR EXISTING WALL
DOOR NUMBER (SEE SHEET A101)
PLAN LEGEND
DETAIL OR SECTION NUMBER
SHEET WHERE DRAWN
PLAN NOTE
ROOM NAME
WALL TYPE
WALL TYPE NOTE
X
X
X
A101
A801
A
B
C
D
101-1
A111
ENLARGED FLOOR PLAN BASEMENT RESTROOMS
1/4"=1'-0"
06.11.18 06:12 PM | G:\USDAAPHIS_PSD1\BIMCAD\Arch\A-111.dwg
A111
PACKAGE #2 -
ENLARGED
PLANS
JC
SR
A111
ENLARGED FLOOR PLAN OFFICES
1/4"=1'-0"
DRAWN BY |
REVISIONS
© | ALL RIGHTS RESERVED
w w w . c t a g r o u p . c o m
8 0 0 . 7 5 7 . 9 5 2 2
CHECKED BY |
U S
H
I S
P S
D
R
E N
O V
A T
I O
N S
P O
C A
T E
L L
O
I D
A H
O
100% CD
3.27.19
N O
T
F
N
S T
R U
C T
I O
N
P
R E
L I M
I N
A R
Y
D
E S
I G
N
A111
ENLARGED CEILING PLAN BASEMENT RESTROOMS
1/4"=1'-0"
A111
EXISTING SLAB TO NEW SLAB CONNECTION DETAIL
FINISH FLOOR
INSULATED HOLLOW
METAL DOOR TYPES
1 4
V I F
±2'-11
V.I.F.
A
8" 6"
3'-0"
HOLLOW
METAL DOOR TYPES
*FIELD VERIFY
DIMENSIONS OF
DOOR/FRAME TYPE
DOOR
NUMBER
ROOM NUMBER
B101-1
HARDWARE
GROUP
GLAZING
TYPE
B101
NOTES
1, 2
DOOR TYPE FRAME
TYPE
B
NA
1. PAINT DOOR AND FRAME, RE: SPECIFICATION.
2. DOOR TO RECEIVE KICK-PLATE AS APART OF THE HARDWARE SET PER
SPECIFICATIONS.
DOOR SCHEDULE NOTES
A. INSULATED FULLY TEMPERED.
GLAZING TYPES
NA = NOT APPLICABLE
DOOR SCHEDULE ABBREVIATIONS
B102-1 2B102 1, 22 B
NA
101-1 1101 1, 21 A
A
DOOR SCHEDULE
HARDWARE GROUPS:
GROUP 1 -
HINGE:
LOCKS:
CLOSER:
GASKETING:
THRESHOLD:
SWEEP:
SECURE CARD ACCESS J-BOX
FOR ELECTRIFIED DOOR HARDWARE FUNCTION
PER SPECIFICATIONS,
ENTRANCE LOCK WITH ELECTRIC STRIKE
PER SPECIFICATIONS.
PER SPECIFICATIONS.
PER SPECIFICATIONS.
PER SPECIFICATIONS.
GROUP 2 -
HINGES:
LOCK:
WALL STOP:
SILENCER:
PER SPECIFICATIONS,
PRIVACY FUNCTION.
PER SPECIFICATIONS.
PER SPECIFICATIONS.
FINISH FLOOR
METAL FRAME TYPES
INSULATED HOLLOW
METAL FRAME TYPES
2"
HOLLOW
2"
A601
A601
A601
A601
*FIELD VERIFY
DIMENSIONS OF
DOOR/FRAME TYPE
SEALANT PERIMETER
BOTH SIDES
INSULATED HOLLOW METAL FRAME,
RE: SCHEDULE, FRAME TO ALLOW
ELECTRICAL WIRING TO RUN
THROUGH FRAME, RE: ELECTRICAL
DRAWINGS
DOOR, RE: SCHEDULE
POSITION FRAME IN
SAME LOCATION AS
EXISTING, V.I.F.
EXISTING WALL
TO REMAIN
NEW PENETRATION
RE: MECHANICAL
DRAWINGS
RE: MECHANICAL DRAWINGS
FOR GOOSENECK
REQUIREMENTS AND LOCATION
6" MIN.
ROOF CEMENT
UNDER FLANGE
EXISTING ROOF
ASSEMBLY
SHINGLE -
LAP OVER METAL
FLANGE ASSOCIATED
WITH GOOSENECK
ROOF CEMENT
UNDER FLANGE
LAP METAL FLANGE
ASSOCIATED WITH GOOSNECK
OVER EXISTING SHINGLE
HEAD REINFORCEMENT
JAMB REINFORCEMENT (PLAN VIEW)
L3x3x
CONT ANGLE
EA SIDE OF HEAD
TYP EA SIDE
" CONT
CLOSURE PL
" CLOSURE PL w/
"Øx 4" HAS @ 6"
FROM BOT, THEN @ 32" OC.
* IF WALL IS HOLLOW PACK w/
NON-SHRINKING GROUT AND SET PL.
* IF WALL IS SOLID. PROVIDE
DRILLED HOLE & SET IN EPOXY.
L3x3x
CONT ANGLE
EA SIDE OF JAMB
INSTALLATION PROCEDURE:
1) SAWCUT HORIZONTAL SLOT INTO MASONRY ALONG NEW HEAD &
INSERT HEAD ANGLES.
2) REMOVE 2'-0" WIDE STRIP OF MASONRY AT EACH JAMB.
REMAINING CENTER SECTION OF MASONRY ACTS AS TEMPORARY
SHORING OF OPENING.
3) INSTALL JAMB REINFORCING ANGLES & CLOSURE PLATE. WELD
TOP OF JAMB ANGLE TO HEAD ANGLES.
4) REMOVE THE REMAINING CENTER SECTION OF (E) MASONRY & ADD
HEAD CLOSURE PLATE.
B
(E) MASONRY ON
CONCRETE WALL
NEW OPENING
(SEE ARCH)
A
3 SIDES
COPE HORIZ LEGS OF HEAD ANGLES &
EXTEND VERT LEG OVER JAMB ANGLES
(E) MASONRY
ON CONCRETE
WALL
3 - 12
TYP EA SIDE
3 - 12
A
B
(E) MASONRY ON
CONCRETE WALL
A601
NEW PENETRATION -
MAINTAIN 1/4" JOINT ALL
AROUND, PACK W/
GLASS FIBER OR OAKUM
AND SEAL W/ FIRE-
RESISTIVE SEALANT
PIPING OR CONDUIT
EXISTING WALL
EXTERIORINTERIOR
SEALANT AT PIPE PENETRATION DETAIL
1 1/2"=1'-0"
OSHA COMPLIANT -
FACE MOUNTED
RAILIING, TO BE
'SAFETY RAIL
COMPANY' OR EQUAL.
EXISTING GUTTER AND
ROOF EDGE AT LOW
SIDE OF EXISTING
ROOF - RAILING TO
NAVIGATE AROUND
GUTTER.
FACE MOUNTED
RAILING BEYOND
PARAPET BEYOND
TOP OF EXISTING ROOF
MOUNT TO EXISTING
EXTERIOR WALL PER
MANUFACTURER
RECOMMENDATIONS AND
INSTRUCTIONS.
POST TO BE AT 96"
O.C. MAXIMUM
OSHA COMPLIANT -
FACE MOUNTED
RAILIING, TO BE
'SAFETY RAIL
COMPANY' OR EQUAL.
EXISTING GUTTER AND
ROOF EDGE AT LOW
SIDE OF EXISTING
ROOF BEYOND -
RAILING TO NAVIGATE
AROUND GUTTER.
FACE MOUNTED
RAILING BEYOND
EXISTING PARAPET
TOP OF EXISTING ROOF
MOUNT TO EXISTING
EXTERIOR WALL PER
MANUFACTURER
RECOMMENDATIONS AND
INSTRUCTIONS.
POST TO BE AT 96"
O.C. MAXIMUM
SEALANT PERIMETER
BOTH SIDES
HOLLOW METAL FRAME, RE:
SCHEDULE
DOOR, RE: SCHEDULE
EXISTING WALL
TO REMAIN
RE: 3/A601 FOR REINFORCING OF NEW
OPENING DETAILS
DRAWN BY |
REVISIONS
© | ALL RIGHTS RESERVED
w w w . c t a g r o u p . c o m
8 0 0 . 7 5 7 . 9 5 2 2
CHECKED BY |
U S
H
I S
P S
D
R
E N
O V
A T
I O
N S
P O
C A
T E
L L
O
I D
A H
O
100% CD
3.27.19
N O
T
F
N
S T
R U
C T
I O
N
P
R E
L I M
I N
A R
Y
D
E S
I G
N
06.11.18 06:12 PM | G:\USDAAPHIS_PSD1\BIMCAD\Arch\A-601.dwg
A601
SCHEDULES
AND
DETAILS
JC
SR
A601
EXTERIOR HM DOOR HEAD/JAMB DETAIL
3"=1'-0"
A601
TYPICAL PIPE PENETRATION DETAIL
1-1/2"=1'-0"
A601
NEW OPENING IN EXISTING MASONRY
3/4"=1'-0"
A601
ROOF RAILING DETAIL I
3/4"=1'-0"
A601
ROOF RAILING DETAIL II
3/4"=1'-0"
A601
INTERIOR HM DOOR HEAD/JAMB DETAIL
3"=1'-0"
AutoCAD SHX Text B
REPAIR ANY DAMAGE DONE TO SURROUNDING AREAS/CONSTRUCTION DURING
DEMOLITION.
B. ALL EXISTING CONDITIONS ARE NOT INDICATED ON THE DRAWINGS. CONTRACTOR
SHALL CAREFULLY EXAMINE THE EXISTING INSTALLATION AND ALL PROJECT
DRAWINGS TO BECOME FAMILIAR WITH THE SCOPE OF WORK.
C. CONTRACTOR SHALL PATCH AND REPAIR ANY DAMAGE OR PENETRATIONS AT ALL
ELEMENTS TO REMAIN (INCLUDING BUT NOT LIMITED TO WALLS, CEILINGS,
FLOORS, ETC.) CAUSED BY DEMOLITION ACTIVITIES OR REMOVAL OF ELECTRICAL,
MECHANICAL, AND ARCHITECTURAL ELEMENTS. REPLACE ITEMS NOT REPAIRABLE
TO ORIGINAL STATE. EXISTING FINISH MATERIALS, INCLUDING CEILINGS, TRIM,
ETC., SHALL BE PROTECTED AND RETAINED, UNLESS NOTED OTHERWISE.
D. PORTIONS OF THE BUILDING ARE TO REMAIN CONTINUOUSLY OCCUPIED
THROUGHOUT CONSTRUCTION. CONTRACTOR TO MAINTAIN CLEAR PATH OF
EGRESS THROUGHOUT CONSTRUCTION.
E. UNLESS NOTED OTHERWISE ALL DIMENSIONS ARE TO THE FACE OF STUD.
F. COORDINATE ALL PLUMBING FIXTURES WITH PLUMBING DRAWINGS.
G. PROVIDE TREATED BLOCKING IN WALL FOR ALL MOUNTED FIXTURES AND
EQUIPMENT.
H. ALL DOORS SET WITH HINGE SIDE 4" FROM BACK OF DOOR FRAME TO FACE OF
ADJACENT WALL UNLESS DIMENSIONED OTHERWISE.
1. FRP, PLASTIC PANELING, UP TO 4'-6" A.F.F, RE: 4/A801 FOR DETAILS.
2. CLASS V SEMI-GLOSS PAINT TO CEILING, RE: SPECIFICATIONS.
3. COVED CERAMIC MOSAIC TILE BASE.
4. ADA ACCESSIBLE HEAVY DUTY HAT AND COAT HOOK, PROVIDE BLOCKING AS
NECESSARY.
5. EXISTING WALL MOUNTED COMMUNICATIONS EQUIPMENT ABOVE TO REMAIN,
PROTECT ALL ASSOCIATED ITEMS. DO NOT PAINT. VERIFY EXACT LOCATION IN FIELD.
6. WOOD BENCH, RE: 6/A801.
7. FIBERGLASS SHOWER INSERT PER SPECIFICATIONS.
8. HEAVY DUTY HAT AND COAT HOOK, PROVIDE BLOCKING AS NECESSARY.
SHEET NOTES:
GB GRAB BAR, RE: SPEC 102800. ALL GRAB BARS PER ANSI HANDICAP
ACCESSIBILITY STANDARDS. MOUNTING HEIGHT - 33" - 36" TO TOP A.F.F.
MU 24" x 36" MIRROR UNIT, RE: SPEC 102800. MOUNTING HEIGHT - 40" MAX TO BOT
MIRROR SURFACE.
PTD PAPER TOWEL DISPENSER, RE: SPEC 102800. MOUNTING HEIGHT - 40" MAX TO
BOT OF DISPENSER.
SD SOAP DISPENSER, RE: SPEC 102800. MOUNTING HEIGHT - 40" MAX TO BOT OF
DISPENSER.
TP TOILET PAPER DISPENSER, RE: SPEC 102800. MOUNTING HEIGHT - 15" MIN TO
OUTLET ABOVE FINISH FLOOR
VGB VERTICAL GRAB BAR, RE: SPEC 102800. INSTALL ALL GRAB BARS PER ANSI
HANDICAP ACCESSIBILITY STANDARDS. MOUNTING HEIGHT - 39" - 41" TO
BOTTOM A.F.F..
UG UNDER LAVATORY GAURD, RE: SPECIFICATIONS.
ENLARGED TOILET PLAN LEGEND:
TP
GB
SD
VGB
38"
18"
42"
GB
VGB
A B
C D
NORTH EAST
SOUTH WEST
MU1
UG
PTD
C
L
C
L
1'-0"1'-0"1'-0"
18"
42"
A
GB
VGB
TP
GB
SD
VGB
38"
B
C D
NORTH EAST
SOUTH WEST
MU1
UG
PTD
C
L
C
L
1'-0"1'-0" 2'-10"
DIM# MOUNTING HEIGHT
FIXTURE
GRAB BAR
URINAL
TOILET (ADA)
URINAL (ADA)
SINK (ADA)
TOILET
TOILET (ADA)
GRAB BAR (ADA)
TOILET PAPER HOLDER
GRAB BAR
GRAB BAR
GRAB BAR
MIRROR
TOILET PAPER HOLDER
TOILET PAPER HOLDER
SINK (ADA)
SINK (ADA)
A
B
C
C
D
E
F
G
G
H
J
K
L
M
N
O
P
18" VERTICAL GRAB BAR
18" VERTICAL GRAB BAR
Q
R
6" TO CENTER FROM ADJACENT WALL
18" TO CENTER FROM ADJACENT WALL
24" TO RIM ABOVE FINISH FLOOR
17" TO RIM ABOVE FINISH FLOOR
34" MAX TO SINK RIM ABOVE FINISH FLOOR
9" HIGH X 6" DEEP TOE CLEARANCE
27" MIN X 8" DEEP KNEE CLEARANCE
14" TO TOP OF SEAT
17" - 19" TOP OF SEAT
12" TO CENTER FROM ADJACENT WALL
7" - 9" TO CENTERLINE FROM TOILET
33" - 36" TO TOP A.F.F.
36" OUTSIDE TO OUTSIDE
42" OUTSIDE TO OUTSIDE
40" MAX TO BOT OF MIRROR SURFACE
19" MIN. TO CENTER ABOVE FINISH FLOOR
1…