Drawings.pdf

PDF 7 MB Posted

Attached to
Safety & Health Upgrades, Pocatello Supply Depot
Solicitation number
12639519R0011
Issued by

About this file

Attachment 2, Drawings

View the file

Other files

File Type Posted
12639519R0011-0006.pdf PDF
12639519R0011-0005.pdf PDF
12639519R0011-0004.pdf PDF
Offeror_questions_and_responses_USDAPocatello_5_21_19.pdf PDF
12639519R0011-0003.pdf PDF
Site_visit_attendees;_contact_list.docx DOCX document
12639519R0011-0002.pdf PDF
12639519R0011-0001.pdf PDF
Specifications.pdf PDF
USDA_Sustainable_Buildings_Implementation_Plan.doc DOC document
All_Green_Products.xls XLS spreadsheet
12639519R0011.pdf PDF
DOL_Wage_Determination_ID35.pdf PDF
Show all 13

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

USDA APHIS

PSD RENOVATIONS

3.27.2019

100% CONSTRUCTION DOCUMENTS

PROJECT LOCATION

USDA APHIS

POCATELLO SUPPLY DEPOT

238 E Dillon St, Pocatello, ID 83201

VICINITY MAP: Locator

OWNER

USDA APHIS

CONTACT: JAMES ROLOFF

USDA, APHIS, PROCUREMENT BRANCH

250 MARQUETTE AVE.

MINNEAPOLIS, MN 55401

612.336.3223

ARCHITECT/ENGINEER

CTA Architects Engineers

800 W. Main St. #800

BOISE, IDAHO

208.336.4900

Project Manager: SCOTT ROBERTS

MECHANICAL ENGINEER

CTA Architects Engineers

800 W. Main St. #800

BOISE, IDAHO

208.336.4900

CONTACT: TIM JOHNSON

ELECTRICAL ENGINEER

CTA Architects Engineers

800 W. Main St. #800

BOISE, IDAHO

208.336.4900

CONTACT: RANDY DINGER

SHEET INDEX

PLUMBING

P100 PACKAGE #1 - PLUMBING SCHEDULES

P102 MIXING ROOM PLUMBING PLANS

P110 PACKAGE #2 - PLUMBING SCHEDULES AND DETAILS

P111 BASEMENT PLUMBING PLANS

MECHANICAL

MP001 PACKAGE #1 AND #2 - OVERALL MECHANICAL AND PLUMBING PLANS

M100 PACKAGE #1 HVAC SCHEDULES

M101 CARTRIDGE ROOM AND FUSE EXHAUST HVAC PLANS

M102 MIXING ROOM HVAC PLANS

M103 CYANIDE ROOM AND ROOF HVAC PLANS

M104 HVAC DETAILS AND CONTROLS

M110 PACKAGE #2 HVAC SCHEDULES

M111 HVAC PLANS

ELECTRICAL

E001 PACKAGE #1 AND #2 - OVERALL DEMOLITION PLANS

E002 PACKAGE #1 - ENLARGED DEMOLITION PLANS

E003 PACKAGE #1 - ENLARGED DEMOLITION PLANS

E011 PACKAGE #2 - ENLARGED DEMOLITION PLANS

E012 ELECTRICAL DEMOLITION PLANS

E013 ENLARGED DEMOLITION PLANS

E101 PACKAGE #1 AND #2 - OVERALL PLANS

E102 PACKAGE #1 - ENLARGED PLANS

E103 PACKAGE #1 - ENLARGED PLANS

E111 PACKAGE #2 - ENLARGED PLANS

E112 ELECTRICAL PLANS - FIRE ALARM

E113 ELECTRICAL PLAN BASEMENT - FIRE ALARM

E601 SCHEDULES AND DETAILS

E602 PANEL SCHEDULES

GENERAL

G101 COVER SHEET

G102 LEGEND/SYMBOL SHEET

G103 EXISTING CONDITION IMAGES

ARCHITECTURAL

A001 PACKAGE #1 AND #2 - OVERALL DEMOLITION PLANS

A002 PACKAGE #1 - ENLARGED DEMOLITION PLANS

A003 PACKAGE #1 - ENLARGED DEMOLITION PLANS

A011 PACKAGE #2 - ENLARGED DEMOLITION PLANS

A101 PACKAGE #1 AND #2 - OVERALL PLANS

A102 PACKAGE #1 - ENLARGED PLANS

A103 PACKAGE #1 - ENLARGED PLANS

A104 PACKAGE #1- ENLARGED MEZZANINE PLANS

A111 PACKAGE #2 - ENLARGED PLANS

A601 SCHEDULES AND DETAILS

A801 PACKAGE #2 - INTERIOR ELEVATIONS AND DETAILS

IMAGE OF THE SUPPLY DEPOT

THE FOLLOWING DRAWINGS AND DOCUMENTS ARE DELINEATED INTO

TWO SEPARATE PACKAGES:

PACKAGE #1 - SAFETY AND HEALTH REVIEW: INCLUDES THE WORK

RELATED TO THE FOLLOWING ROOMS, AREAS, AND ITEMS. REFERENCE

THE ASSOCIATED DOCUMENTS, DRAWINGS, AND SPECIFICATIONS TO

FIND FURTHER INFORMATION AND ALL WORK RELATED TO THESE

AREAS.

A. CYANIDE ROOM

B. GRAIN BAIT MIXING ROOM

C. CARTRIDGE ROOM

D. NORTH WAREHOUSE HOT LABEL MAKER

E. GAS CARTRIDGE FUSES

F. PERSONNEL DOOR

G. RAILING AND FALL PROTECTION AT AREAS INDICATED

PACKAGE #2 - FACILITY CONDITION REASSESSMENT: INCLUDES THE

WORK RELATED TO THE FOLLOWING ROOMS, AREAS, AND ITEMS.

REFERENCE THE ASSOCIATED DOCUMENTS, DRAWINGS, AND

SPECIFICATIONS TO FIND FURTHER INFORMATION AND ALL WORK

RELATED TO THESE AREAS.

A. ENERGY CONSERVATION MEASURES - OFFICE LIGHTING

B. BASEMENT RESTROOMS

C. OFFICE HVAC SYSTEM

D. WATER HEATER REPLACEMENT

E. FIRE ALARM SYSTEM

TASK ORDER NO. AG-6395-C-16-0117

HAZARDOUS MATERIALS AND CHEMICALS INFORMATION:

ALONG WITH THE FOLLOWING VERBIAGE, REFERENCE SPECIFICATION SECTION

028416 PRIOR TO ANY DEMOLITION WORK OCCURRING.

THE FOLLOWING ACUTELY HAZARDOUS SUBSTANCES ARE KNOWN TO BE

PRESENT IN AREAS OF THE FACILITY TO BE RENOVATED. THESE INCLUDE

SODIUM CYANIDE (CHEMICAL FORMULA NaCN) IN THE CYANIDE ROOM AND

STRYCHNINE AND ZINC PHOSPHIDE IN THE MIXING ROOM. A BRIEF SUMMARY OF

THE PROCESSES ASSOCIATED WITH THESE SUBSTANCES ARE PROVIDED

BELOW.

THESE ARE BY NO MEANS SUFFICIENT SPECIFICATIONS TO ENSURE WORKER

SAFETY OR COMPLIANCE WITH LOCAL, STATE, AND FEDERAL WORKER

PROTECTION LAWS AND REGULATIONS DURING PLANNED ACTIVITIES.

ADDITIONALLY, RESOURCE CONSERVATION AND RECOVERY ACT (RCRA)

HAZARDOUS WASTE(S) WILL LIKELY BE GENERATED WHILE PERFORMING THE

SCOPE OF THIS WORK. THE REMOVAL, HANDLING, AND DISPOSAL OF

CONTAMINATED MATERIALS REQUIRES SPECIALIZED KNOWLEDGE TO ENSURE

WORKER SAFETY AND COMPLIANCE WITH LOCAL, STATE, AND FEDERAL

REGULATIONS. ADDITIONALLY, THERE MAY BE OTHER HAZARDOUS

SUBSTANCES PRESENT AND/OR ENCOUNTERED WHILE PERFORMING THE

SCOPE OF WORK, INCLUDING BUT NOT LIMITED TO: ASBESTOS CONTAINING

BUILDING MATERIALS, LEAD CONTAINING COATINGS, AND BIOLOGICAL HAZARDS

THAT ARE NOT DISCUSSED HEREIN.

GENERAL NaCN NOTES - CURRENT PROCESS AND CONDITIONS - TAKES PLACE

WITHIN CYANIDE ROOM:

· MATERIAL IS GROUND TO A POWDER UNDER A HOOD

· GROUND MATERIAL IS MIXED WITH DYE AND ANTI-CAKING COMPOUND

· MIXTURE IS COOKED IN HOODED OVEN TO DRIVE OFF MOISTURE.

· CURRENT PPE IS LEVEL C: AIR PURIFYING RESPIRATOR (N95 PARTICULATE

CARTRIDGE), LONG SLEEVE CLOTHING (TYVEK), NITRILE GLOVES, AND

SAFETY GLASSES.

· THE USDA HAS INDICATED THAT A NEGATIVE EXPOSURE

ASSESSMENT WAS CONDUCTED DURING THEIR GENERAL WORK

ACTIVITIES HANDLING THE CYANIDE. THE RESULTS OF THE NEA

INDICATE THAT USDA WORKERS WERE NOT BEING EXPOSED TO

CONTAMINANT AT LEVELS THAT WOULD REQUIRE A RESPIRATOR.

HOWEVER, EMPLOYEES ARE REQUIRED TO WEAR AN AIR-PURIFYING

ASPIRATOR AS A PRECAUTION.

· HISTORICALLY QUANTITIES OF NaCN HAVE BEEN WELL CONTROLLED, UNDOCUMENTED QUANTITIES OF NaCN WOULD NOT BE LIKELY DURING

DEMOLITION.

· DYE IS PRESENT THROUGHOUT AREA AND MAY OR MAY NOT INDICATE

PRESENCE OF NaCN - CONTRACTOR SHOULD ASSUME DYE CONTAINS NaCN

AND TAKE THE PROPER PRECAUTIONS WHEN THE DYE IS ENCOUNTERED

DURING CONSTRUCTION.

· SPILLED RESIDUAL SHOULD BE AMENABLE TO RECOVERY THROUGH HEPA

(HIGH EFFICIENCY PARTICULATE AIR) VACUUMING.

· DUCT WORK LIKELY CONTAMINATED ALTHOUGH AMBIENT MOISTURE

WOULD RESULT IN NaCN CONVERTING TO HCN (HYDROGEN CYANIDE)

AND OFF-GASSING OVER TIME, MINIMIZING TOXICITY.

· THE USDA HAS INDICATED THERE ARE AT LEAST 4 AREAS WITHIN

THE NaCN ROOM WHERE NaCN MAY HAVE ACCUMULATED MORE

THAN OTHER AREAS DUE TO VARIOUS FACTORS. THESE AREAS WILL

NEED TO BE IDENTIFIED BY LOCAL USDA REPRESENTATIVES PRIOR

TO INITIATING THIS SCOPE OF WORK.

GENERAL MIXING ROOM NOTES - CURRENT PROCESS AND CONDITIONS:

· STRYCHNINE LIKELY NOT PRESENT ANYMORE.

· ZINC PHOSPHIDE PRIMARY CONTAMINANT WITHIN ROOM.

· STRYCHNINE AND ZINC PHOSPHIDE ARE SOLIDS THAT CAN BE RECOVERED

BY A HEPA VACUUM.

· CURRENT PPE IS LEVEL C: AIR PURIFYING RESPIRATOR (N95 PARTICULATE

CARTRIDGE), LONG SLEEVE CLOTHING/LAB COAT (NO TYVEK) , NITRILE

GLOVES, AND SAFETY GLASSES.

GENERAL MANUFACTURER NOTE:

ALL MANUFACTURER'S LISTED WITHIN THESE DRAWINGS AND

ASSOCIATED SPECIFICATIONS SHALL BE CONSIDERED AN 'OR EQUAL'

PRODUCT.

DRAWN BY |

REVISIONS

© | ALL RIGHTS RESERVED

w w w . c t a g r o u p . c o m

8 0 0 . 7 5 7 . 9 5 2 2

CHECKED BY |

U S

D A

P H

I S

P S

D

R

E N

O V

A T

I O

N S

P O

C A

T E

L L

O

I D

A H

O

100% CD

3.27.19

N O

T

F

O R

C

N

S T

R U

C T

I O

N

P

R E

L I M

I N

A R

Y

D

E S

I G

N

06.29.17 11:09 PM | G:\USDAAPHIS_PSD1\BIMCAD\Arch\G-101.dwg

G101

COVER SHEET

JC

SR

Solicitation 12639519R0011 Attachment 2

SYMBOL DESCRIPTION

LIGHTING

LAY-IN OR RECESSED FIXTURE, SIZE ON PLANS

WALL MOUNTED FIXTURE, SIZE ON PLANS

SURFACE MOUNTED FIXTURE, SIZE ON PLANS

PENDANT OR SURFACE MOUNTED FIXTURE, SIZE ON PLANS

RECESSED DOWNLIGHT FIXTURE

SURFACE MOUNTED FIXTURE

WALL MOUNTED FIXTURE

CEILING MOUNTED, WALL MOUNTED EXIT LIGHT

(W/ DIRECTIONAL ARROWS)

PENDANT MOUNTED FIXTURE, SIZE ON PLANS

SHADED FIXTURE INDICATES FIXTURE IS UNSWITCHED AND

ALSO INDICATES EMERGENCY POWER.

2 HEAD EMERGENCY LIGHT BATTERY PACK

ELECTRICAL SYMBOLS LEGEND

SYMBOL DESCRIPTION

LAY-IN OR RECESSED FIXTURE, SIZE ON PLANS

WALL MOUNTED FIXTURE, SIZE ON PLANS

SURFACE MOUNTED FIXTURE, SIZE ON PLANS

PENDANT OR SURFACE MOUNTED FIXTURE, SIZE ON PLANS

RECESSED DOWNLIGHT FIXTURE

SURFACE MOUNTED FIXTURE

WALL MOUNTED FIXTURE

CEILING MOUNTED, WALL MOUNTED EXIT LIGHT

(W/ DIRECTIONAL ARROWS)

PENDANT MOUNTED FIXTURE, SIZE ON PLANS

SHADED FIXTURE INDICATES FIXTURE IS UNSWITCHED AND

ALSO INDICATES EMERGENCY POWER.

2 HEAD EMERGENCY LIGHT BATTERY PACK

CLG

CLG

SWITCH - SPST

2 SINGLE POLE, DOUBLE THROW

3 THREEWAY

4 FOURWAY

K KEY OPERATED

P PILOT LIGHT

WP WEATHERPROOF

OS OCCUPANCY SENSOR

D DIMMER

MC SPOT-MOMENTARY CONTACT

LV LOW VOLTAGE

T TIMER SWITCH

TS TEST SWITCH

OCCUPANCY SENSOR SWITCH (CEILING) - SUBSCRIPT IS TYPE

RECEPTACLE - SIMPLEX

RECEPTACLE - DUPLEX

GFI RECEPTACLE - DUPLEX (GROUND FAULT INTERRUPT)

USB DEVICE RECEPT W/2 USB PORTS

DC DROP CORD

WP WEATHERPROOF COVER & WEATHER

RESISTANT RECEPTACLE

TR TAMPER RESISTANT

S SURGE PROTECTED

IG ISOLATED GROUND

FILLED CENTER INDICATES HOSPITAL GRADE

EMERGENCY RECEPTACLE

RECEPTACLE - DOUBLE DUPLEX

GFI RECEPTACLE - DOUBLE DUPLEX

- SAME INDICATORS AS SHOWN FOR DUPLEX RECEPTACLE

RECEPTACLE - 208V

R RANGE - NEMA 14-50R

D DRYER - NEMA 10-30R

W WELDER - NEMA 14-50R

* NEMA CONFIGURATION AS NOTED

208V RECEPTACLE IN RECESSED FLOORBOX

DUPLEX RECEPTACLE/GFI IN RECESSED FLOORBOX

DOUBLE DUPLEX RECEPTACLE/GFI IN RECESSED FLOORBOX

J-BOX - BOX INDICATES FLOOR MOUNTING -4"X4"X2-1/8" DEEP

UNLESS OTHERWISE NOTED

SPECIAL PURPOSE CONNECTION - BOX INDICATES FLOOR

MOUNTING - WORK AS NOTED

RECEPTACLE - DUPLEX, MOUNTING IN CEILING

MANUAL MOTOR DISCONNECT/STARTER SWITCH

COMBINATION STARTER/DISCONNECT SWITCH

DISCONNECT SWITCH

CONTACTOR

ELECTRIC MOTOR CONNECTION

EMERGENCY PUSHBUTTON

PHOTOCELL, PHOTOCELL WALL MOUNTED

EXISTING PANELBOARD, SURFACE MOUNTED

EXISTING PANELBOARD, FLUSH MOUNTED

TIME CLOCK

VARIABLE FREQUENCY DRIVE

THERMOSTAT/TEMPERATURE SENSOR BY MC OR TC, J-BOX

AND CONDUIT TO CEILING BY EC

CARBON MONOXIDE DETECTOR BY MC, J-BOX & CONDUIT TO

CEILING BY EC

PP

POWER POLE

RELAY

CIRCUIT BREAKER

CONTROL PANEL

LRP LIGHTING RELAY PANEL

TCP TEMPERATURE CONTROL PANEL

GAP GENERATOR ANNUNCIATOR PANEL

PACP PA CONTROL PANEL

MGA MED GAS ALARM PANEL

PANELBOARD, SURFACE MOUNTED

PANELBOARD, FLUSH MOUNTED

GFI RECEPTACLE - DUPLEX, MOUNTING IN CEILING

T

SYMBOL DESCRIPTION

DEVICES AND POWER

CO₂

STROBE (NUMBER INDICATES CANDELA RATING)

SPEAKER/STROBE (NUMBER INDICATES CANDELA RATING)

SPEAKER

MANUAL PULLSTATION

IPS INDOOR PROTECTIVE SHIELD

MAGNETIC DOOR HOLDER, BY DIV 28

FIRE/SMOKE DAMPER

SMOKE DETECTOR, SMOKE DETECTOR WALL MOUNTED

HEAT DETECTOR, HEAT DETECTOR WALL MOUNTED

CONNECTION TO TAMPER SWITCH, SWITCH BY OTHERS

CONNECTION TO FLOW SWITCH, SWITCH BY OTHERS

CONNECTION TO PRESSURE SWITCH, SWITCH BY OTHERS

BEAM DETECTOR TRANSMITTER

BEAM DETECTOR RECEIVER

DUCT SMOKE DETECTOR

FIRE ALARM REMOTE ANNUNICATOR

FIRE ALARM CONTROL PANEL

SPEAKER/STROBE (NUMBER INDICATES CANDELA RATING),

CEILING MOUNTED

FIRE ALARM SIGNAL EXTENDER PANEL

SYMBOL DESCRIPTION

FIRE ALARM

ABOVE COUNTER, 4" BACK SPLASHAC

AUTOMATIC TRANSFER SWITCHATS

ABOVE FINISHED GRADEAFG

ABOVE FINISHED FLOORAFF

BELOW GRADEBLG

BOTTOM OF DEVICEBOD

CONDUITC

CARD ACCESS SYSTEMCAS

CLOSED CIRCUIT TVCCTV

CEILINGCLG

CENTER OF DEVICECOD

COPPERCU

DIGITAL VIDEO RECORDERDVR

EXISTING(E)

ELECTRICAL CONTRACTOREC

EXHAUST FANEF

GENERAL CONTRACTORGC

GROUNDGND

FIELD ADJUSTABLE LONG TIME, SHORT TIME AND

INSTANTANEOUS

LSI

FIELD ADJUSTABLE LONG TIME, SHORT TIME, INSTANTANEOUS

AND GROUND FAULT

LSIG

MECHANICAL CONTRACTORMC

NEW(N)

NIGHT LIGHTNL

PAN-TILT-ZOOMPTZ

QUANTITYQTY

RELOCATED(R)

SURFACESF

TELECOMMUNICATIONS MAIN GROUNDING BUS BARTMGB

TELECOMMUNICATIONS BONDING BACKBONETBB

TEMPERATURE CONTROL CONTRACTORTC

TELEPHONE TERMINAL BOARDTTB

TYPICALTYP

UNDERGROUNDUG

UNLESS OTHERWISE NOTEDUON

WITHW/

WIRE MOLDWM

WEATHER PROOF (WHILE IN USE)WP

TRANSFORMERXFMR

SWITCH DESIGNATIONa,b,c etc

CIRCUIT DESIGNATION, PANEL BN1L, CIRCUITS 2,4,6BN1L-2,4,6

INDICATES DETAIL 1 ON SHEET E5011/E501

SHEET WORK NOTE

HOME RUN TO PANEL

CONDUIT CONCEALED IN CEILING OR WALL

CONDUIT CONCEALED UNDER FLOOR

LOW VOLTAGE CIRCUIT

FIBER OPTIC CABLE

CABLE TRAY

CIRCUIT, NUMBER OF HASH MARKS INDICATES NUMBER OF

CONDUCTORS IN CABLE/RACEWAY. GROUND WIRE IS NOT

SHOWN BUT SHALL BE INCLUDED. NO HASH MARKS INDICATES

2 CONDUCTORS PLUS GROUND.

SHEET DEMO WORK NOTE

SYMBOL DESCRIPTION

ABBREVIATIONS AND MISCELLANEOUS

LV

DRAWN BY |

REVISIONS

© | ALL RIGHTS RESERVED

w w w . c t a g r o u p . c o m

8 0 0 . 7 5 7 . 9 5 2 2

CHECKED BY |

U S

H

I S

P S

D

R

E N

O V

A T

I O

N S

P O

C A

T E

L L

O

I D

A H

O

100% CD

3.27.19

N O

T

F

N

S T

R U

C T

I O

N

P

R E

L I M

I N

A R

Y

D

E S

I G

N

06.29.17 11:09 PM | G:\USDAAPHIS_PSD1\BIMCAD\Arch\G-102.dwg

G102

LEGEND/SYMBOL

SHEET

JC

SR

AutoCAD SHX Text

PC

AutoCAD SHX Text

VFD

AutoCAD SHX Text R

AutoCAD SHX Text

PC

AutoCAD SHX Text M

AutoCAD SHX Text M

AutoCAD SHX Text J

AutoCAD SHX Text J

AutoCAD SHX Text

OS

AutoCAD SHX Text

TC

AutoCAD SHX Text J

AutoCAD SHX Text F

AutoCAD SHX Text F

AutoCAD SHX Text F

AutoCAD SHX Text F

AutoCAD SHX Text F

AutoCAD SHX Text M

AutoCAD SHX Text

FSD

AutoCAD SHX Text

SD

AutoCAD SHX Text

SD

AutoCAD SHX Text

HD

AutoCAD SHX Text

HD

AutoCAD SHX Text

FS

AutoCAD SHX Text

PS

AutoCAD SHX Text

TS

AutoCAD SHX Text

FACP

AutoCAD SHX Text

FARA

AutoCAD SHX Text

SD

AutoCAD SHX Text

BD

AutoCAD SHX Text

BD

AutoCAD SHX Text

FASP

G103

EXISTING GRAIN BAIT MIXING ROOM CONDITIONS

N.T.S.

DRAWN BY |

REVISIONS

© | ALL RIGHTS RESERVED

w w w . c t a g r o u p . c o m

8 0 0 . 7 5 7 . 9 5 2 2

CHECKED BY |

U S

H

I S

P S

D

R

E N

O V

A T

I O

N S

P O

C A

T E

L L

O

I D

A H

O

100% CD

3.27.19

N O

T

F

N

S T

R U

C T

I O

N

P

R E

L I M

I N

A R

Y

D

E S

I G

N

06.11.18 06:11 PM | G:\USDAAPHIS_PSD1\BIMCAD\Arch\G-103.dwg

G103

EXISTING

CONDITION IMAGES

JC

SR

G103

EXISTING CARTRIDGE ROOM CONDITIONS

N.T.S.

NOTE: THESE IMAGES ARE INTENDED TO GIVE THE CONTRACTOR A GENERAL

UNDERSTANDING OF THE EXISTING CONDITIONS. THESE IMAGES ARE NOT

INTENDED TO BE DESIGN DRAWINGS. ALL ITEMS TO BE VERIFIED IN FIELD.

REFERENCE CONTRACT DOCUMENT DRAWINGS AND SPECIFICATIONS FOR

FURTHER INFORMATION OF WORK TO OCCUR.

G103

EXISTING CYANIDE ROOM CONDITIONS

N.T.S.

G103

EXISTING BASEMENT RESTROOM CONDITIONS

N.T.S.

G103

EXISTING PERSONNEL DOOR CONDITIONS

N.T.S.

G103

EXISTING CYANIDE ROOFTOP CONDITIONS

N.T.S.

G103

EXISTING GAS CARTRIDGE FUSE STORAGE CONDITIONS

N.T.S.

G103

EXISTING HOT LABEL MAKER AREA CONDITIONS

N.T.S.

A011

A002

PACKAGE #2

PACKAGE #1

RAMP

BASEMENT

WAREHOUSE

ALPHACHLORALOSE

LAB

M-44

MACHINE

SHOP

ADC

STORAGE

COAL

STORAGE

RM.

ROOM

LOCKERS

ELECTRIC

DISTRIBUTION

ROOM

FREIGHT

BASEMENT

WAREHOUSE

STORAGE

ROOM

MECH.

ROOM

GRAIN

ELEVATOR

AREA

AT

BASEMENT

LEVEL

STRG.

GAS CARTRIDGE

FUSE STORAGE

GAS CARTRIDGE

FUSE STORAGE

R.R.

GENERAL NOTES:

A. MAINTAIN THE INTEGRITY OF ALL REMAINING BUILDING SYSTEMS AND RATINGS.

REPAIR ANY DAMAGE DONE TO SURROUNDING AREAS/CONSTRUCTION DURING

DEMOLITION.

B. ALL EXISTING CONDITIONS ARE NOT INDICATED ON THE DRAWINGS. CONTRACTOR

SHALL CAREFULLY EXAMINE THE EXISTING INSTALLATION AND ALL PROJECT

DRAWINGS TO BECOME FAMILIAR WITH THE SCOPE OF WORK.

C. CONTRACTOR SHALL PATCH AND REPAIR ANY DAMAGE OR PENETRATIONS AT ALL

ELEMENTS TO REMAIN (INCLUDING BUT NOT LIMITED TO WALLS, CEILINGS,

FLOORS, ETC.) CAUSED BY DEMOLITION ACTIVITIES OR REMOVAL OF ELECTRICAL,

MECHANICAL, AND ARCHITECTURAL ELEMENTS. REPLACE ITEMS NOT REPAIRABLE

TO ORIGINAL STATE. EXISTING FINISH MATERIALS, INCLUDING CEILINGS, TRIM,

ETC., SHALL BE PROTECTED AND RETAINED, UNLESS NOTED OTHERWISE.

D. PORTIONS OF THE BUILDING ARE TO REMAIN CONTINUOUSLY OCCUPIED

THROUGHOUT CONSTRUCTION. CONTRACTOR TO MAINTAIN CLEAR PATH OF

EGRESS THROUGHOUT CONSTRUCTION.

E. UNLESS NOTED OTHERWISE ALL DIMENSIONS ARE TO THE FACE OF STUD.

G. RE: G101 AND SPECIFICATIONS FOR HAZARDOUS MATERIALS INFORMATION.

SHEET NOTES:

LEGEND:

DASHED LINES INDICATE ASSEMBLIES/SYSTEMS TO BE DEMOLISHED AND

REMOVED. PROTECT ADJACENT EXISTING CONSTRUCTION TO REMAIN.

SOLID LINES INICATE EXISTING ELEMENTS TO REMAIN AND BE PROTECTED

DURING CONSTRUCTION.

A002

A002

A002

A003

AT FLOOR LEVEL ABOVE

PACKAGE #1

PACKAGE #1

PACKAGE #1

PACKAGE #1

A011

PACKAGE #2

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

R.R.

R.R.

WAREHOUSE

CENTRAL

WAREHOUSE

CARTRIDGE

MIXER

ROOM

DOWN RAMP TO BASEMENT

CHARGING

ROOM

FAS

ROOM

R.R.

FREIGHT

SHIPPING/WORKROOM

CLO.

PARKING LOT

NORTH

WAREHOUSE

STORAGE

ROOM

A003

PACKAGE #1

PACKAGE #1 - SAFETY AND HEALTH REVIEW: INCLUDES THE WORK RELATED TO THE

FOLLOWING ROOMS, AREAS, AND ITEMS. REFERENCE THE ASSOCIATED DOCUMENTS,

DRAWINGS, AND SPECIFICATIONS TO FIND FURTHER INFORMATION AND ALL WORK

RELATED TO THESE AREAS.

A. CYANIDE ROOM

B. GRAIN BAIT MIXING ROOM

C. CARTRIDGE ROOM

D. NORTH WAREHOUSE HOT LABEL MAKER

E. GAS CARTRIDGE FUSES

F. PERSONNEL DOOR

PACKAGE #2 - FACILITY CONDITION REASSESSMENT: INCLUDES THE WORK RELATED TO

THE FOLLOWING ROOMS, AREAS, AND ITEMS. REFERENCE THE ASSOCIATED

DOCUMENTS, DRAWINGS, AND SPECIFICATIONS TO FIND FURTHER INFORMATION AND

ALL WORK RELATED TO THESE AREAS.

A. ENERGY CONSERVATION MEASURES - OFFICE LIGHTING

B. BASEMENT RESTROOMS

C. OFFICE HVAC SYSTEM

D. WATER HEATER REPLACEMENT

E. FIRE ALARM SYSTEM

A001

OVERALL DEMOLITION PLAN FIRST FLOOR

1/16"=1'-0"

A001

OVERALL DEMOLITION PLAN BASEMENT

1/16"=1'-0"

A001

OVERALL DEMOLITION ROOF PLAN

1/16"=1'-0"

DRAWN BY |

REVISIONS

© | ALL RIGHTS RESERVED

w w w . c t a g r o u p . c o m

8 0 0 . 7 5 7 . 9 5 2 2

CHECKED BY |

U S

H

I S

P S

D

R

E N

O V

A T

I O

N S

P O

C A

T E

L L

O

I D

A H

O

100% CD

3.27.19

N O

T

F

N

S T

R U

C T

I O

N

P

R E

L I M

I N

A R

Y

D

E S

I G

N

06.29.17 11:09 PM | G:\USDAAPHIS_PSD1\BIMCAD\Arch\A-001.dwg

A001

PACKAGE #1 AND

#2 - OVERALL

DEMOLITION

PLANS

JC

GENERAL NOTES:

A. MAINTAIN THE INTEGRITY OF ALL REMAINING BUILDING SYSTEMS AND RATINGS.

REPAIR ANY DAMAGE DONE TO SURROUNDING AREAS/CONSTRUCTION DURING

DEMOLITION.

B. ALL EXISTING CONDITIONS ARE NOT INDICATED ON THE DRAWINGS. CONTRACTOR

SHALL CAREFULLY EXAMINE THE EXISTING INSTALLATION AND ALL PROJECT

DRAWINGS TO BECOME FAMILIAR WITH THE SCOPE OF WORK.

C. CONTRACTOR SHALL PATCH AND REPAIR ANY DAMAGE OR PENETRATIONS AT ALL

ELEMENTS TO REMAIN (INCLUDING BUT NOT LIMITED TO WALLS, CEILINGS,

FLOORS, ETC.) CAUSED BY DEMOLITION ACTIVITIES OR REMOVAL OF ELECTRICAL,

MECHANICAL, AND ARCHITECTURAL ELEMENTS. REPLACE ITEMS NOT REPAIRABLE

TO ORIGINAL STATE. EXISTING FINISH MATERIALS, INCLUDING CEILINGS, TRIM,

ETC., SHALL BE PROTECTED AND RETAINED, UNLESS NOTED OTHERWISE.

D. PORTIONS OF THE BUILDING ARE TO REMAIN CONTINUOUSLY OCCUPIED

THROUGHOUT CONSTRUCTION. CONTRACTOR TO MAINTAIN CLEAR PATH OF

EGRESS THROUGHOUT CONSTRUCTION.

E. UNLESS NOTED OTHERWISE ALL DIMENSIONS ARE TO THE FACE OF STUD.

F. RE: A001 FOR OVERALL FLOOR PLANS.

G. RE: G101 AND SPECIFICATIONS FOR HAZARDOUS MATERIALS INFORMATION.

SHEET NOTES:

LEGEND:

DASHED LINES INDICATE ASSEMBLIES/SYSTEMS TO BE DEMOLISHED AND

REMOVED. PROTECT ADJACENT EXISTING CONSTRUCTION TO REMAIN.

SOLID LINES INICATE EXISTING ELEMENTS TO REMAIN AND BE PROTECTED

DURING CONSTRUCTION.

1. REMOVE EXISTING CASEWORK.

2. REMOVE EXISTING DOOR, FRAME, AND HARDWARE. PREP FOR NEW DOOR AND

FRAME.

3. REMOVE EXISTING PLUMBING FIXTURE, RE: PLUMBING DRAWINGS.

4. CLEAN AND PREP ALL WALLS AND FLOORS WITHIN ROOM NOTED FOR NEW PAINT.

5. REMOVE EXISTING CARTRIDGE FUSE STORAGE - PREP FOR NEW STORAGE BOXES

- RE: SPECIFICATIONS AND NEW PLANS.

6. PROTECT EXISTING EQUIPMENT AND RELOCATE PER NEW FLOOR PLANS, RE:

A102.

7. PROTECT EXISTING CASEWORK FOR RE-INSTALLATION, RE: NEW FLOOR PLAN ON

A102.

8. RE: MECHANICAL AND ELECTRICAL DRAWINGS FOR FURTHER WORK TO OCCUR

WITHIN ROOM NOTED.

9. EXISTING SCALE AND ASSOCIATED ITEMS TO REMAIN. RE: A102 FOR NEW FLOOR

PLAN.

STORAGE

ROOM

EXTERIOR

PAVEMENT/PARKING

GRAIN

ELEVATOR

MIXER

ROOM

CARTRIDGE

A002

ENLARGED DEMOLITION PLAN CARTRIDGE ROOM

1/4"=1'-0"

A002

ENLARGED DEMOLITION PLAN PERSONNEL DOOR

1/4"=1'-0"

A002

ENLARGED DEMOLITION PLAN MIXER ROOM

1/4"=1'-0"

A002

ENLARGED DEMOLITION PLAN CARTRIDGE FUSE STORAGE

1/4"=1'-0"

DRAWN BY |

REVISIONS

© | ALL RIGHTS RESERVED

w w w . c t a g r o u p . c o m

8 0 0 . 7 5 7 . 9 5 2 2

CHECKED BY |

U S

H

I S

P S

D

R

E N

O V

A T

I O

N S

P O

C A

T E

L L

O

I D

A H

O

100% CD

3.27.19

N O

T

F

N

S T

R U

C T

I O

N

P

R E

L I M

I N

A R

Y

D

E S

I G

N

06.11.18 06:10 PM | G:\USDAAPHIS_PSD1\BIMCAD\Arch\A-002.dwg

A002

PACKAGE #1 -

ENLARGED

DEMOLITION PLANS

REPAIR ANY DAMAGE DONE TO SURROUNDING AREAS/CONSTRUCTION DURING

DEMOLITION.

B. ALL EXISTING CONDITIONS ARE NOT INDICATED ON THE DRAWINGS. CONTRACTOR

SHALL CAREFULLY EXAMINE THE EXISTING INSTALLATION AND ALL PROJECT

DRAWINGS TO BECOME FAMILIAR WITH THE SCOPE OF WORK.

C. CONTRACTOR SHALL PATCH AND REPAIR ANY DAMAGE OR PENETRATIONS AT ALL

ELEMENTS TO REMAIN (INCLUDING BUT NOT LIMITED TO WALLS, CEILINGS,

FLOORS, ETC.) CAUSED BY DEMOLITION ACTIVITIES OR REMOVAL OF ELECTRICAL,

MECHANICAL, AND ARCHITECTURAL ELEMENTS. REPLACE ITEMS NOT REPAIRABLE

TO ORIGINAL STATE. EXISTING FINISH MATERIALS, INCLUDING CEILINGS, TRIM,

ETC., SHALL BE PROTECTED AND RETAINED, UNLESS NOTED OTHERWISE.

D. PORTIONS OF THE BUILDING ARE TO REMAIN CONTINUOUSLY OCCUPIED

THROUGHOUT CONSTRUCTION. CONTRACTOR TO MAINTAIN CLEAR PATH OF

EGRESS THROUGHOUT CONSTRUCTION.

E. UNLESS NOTED OTHERWISE ALL DIMENSIONS ARE TO THE FACE OF STUD.

F. RE: A001 FOR OVERALL FLOOR PLANS.

G. RE: G101 AND SPECIFICATIONS FOR HAZARDOUS MATERIALS INFORMATION.

SHEET NOTES:

LEGEND:

DASHED LINES INDICATE ASSEMBLIES/SYSTEMS TO BE DEMOLISHED AND

REMOVED. PROTECT ADJACENT EXISTING CONSTRUCTION TO REMAIN.

SOLID LINES INICATE EXISTING ELEMENTS TO REMAIN AND BE PROTECTED

DURING CONSTRUCTION.

1. REMOVE EXISTING UPPER AND LOWER CASEWORK AND COUNTERTOP.

2. REMOVE EXISTING DOOR, FRAME, AND HARDWARE. PREP FOR NEW.

3. REMOVE EXISTING PLUMBING FIXTURE, RE: PLUMBING DRAWINGS.

4. EXISTING ROOF ACCESS ROOFTOP ABOVE.

5. EXISTING SHINGLE ROOF TO REMAIN.

6. REMOVE EXISTING LAB EQUIPMENT AND VENTILATION HOOD, WHERE OCCURS.

7. EXISTING STRUCTURE TO REMAIN, RE: MECHANICAL DRAWINGS FOR DEMOLITION

WORK TO OCCUR WITHIN THIS AREA.

8. CLEAN ENTIRETY OF EXISTING FLAT ROOF AREA SHOWN AND PREP FOR NEW

MECHANICAL WORK TO OCCUR. EXISTING ROOF TOP CONTAIN BIRD FECES THAT

WILL NEED TO BE REMOVED DURING CLEANING - FOLLOW ALL OSHA GUIDELINES/

RECOMMENDATIONS PERTAINING TO THIS REMOVAL. HEATH HAZARDS ARE

ASSOCIATED WITH THIS REMOVAL

9. REMOVE EXISTING WALL MOUNTED SOAP AND PAPER TOWEL DISPENSER.

10. EXISTING EQUIPMENT CURB AND OPENING TO REMAIN TO ACCOMMODATE NEW

EQUIPMENT. RE: MECHANICAL DRAWINGS FOR FURTHER DEMOLITION

INFORMATION.

11. RE: MECHANICAL AND ELECTRICAL DRAWINGS FOR FURTHER WORK TO OCCUR

WITHIN ROOM/NOTED AREA.

CYANIDE

ROOM

ROOF

ACCESS

(E) TABLE

(E) TABLE

(E) GRADER

(E) MIXER

(E) TABLE(E) STRG.(E) STRG.

(E) TABLE

(E) KILN

(E) STRG.

A003

ENLARGED DEMOLITION PLAN CYANIDE ROOM

1/4"=1'-0"

A003

ENLARGED DEMOLITION PLAN CYANIDE ROOF TOP

1/4"=1'-0"

DRAWN BY |

REVISIONS

© | ALL RIGHTS RESERVED

w w w . c t a g r o u p . c o m

8 0 0 . 7 5 7 . 9 5 2 2

CHECKED BY |

U S

H

I S

P S

D

R

E N

O V

A T

I O

N S

P O

C A

T E

L L

O

I D

A H

O

100% CD

3.27.19

N O

T

F

N

S T

R U

C T

I O

N

P

R E

L I M

I N

A R

Y

D

E S

I G

N

06.11.18 06:11 PM | G:\USDAAPHIS_PSD1\BIMCAD\Arch\A-003.dwg

A003

PACKAGE #1 -

ENLARGED

DEMOLITION PLANS

REPAIR ANY DAMAGE DONE TO SURROUNDING AREAS/CONSTRUCTION DURING

DEMOLITION.

B. ALL EXISTING CONDITIONS ARE NOT INDICATED ON THE DRAWINGS. CONTRACTOR

SHALL CAREFULLY EXAMINE THE EXISTING INSTALLATION AND ALL PROJECT

DRAWINGS TO BECOME FAMILIAR WITH THE SCOPE OF WORK.

C. CONTRACTOR SHALL PATCH AND REPAIR ANY DAMAGE OR PENETRATIONS AT ALL

ELEMENTS TO REMAIN (INCLUDING BUT NOT LIMITED TO WALLS, CEILINGS,

FLOORS, ETC.) CAUSED BY DEMOLITION ACTIVITIES OR REMOVAL OF ELECTRICAL,

MECHANICAL, AND ARCHITECTURAL ELEMENTS. REPLACE ITEMS NOT REPAIRABLE

TO ORIGINAL STATE. EXISTING FINISH MATERIALS, INCLUDING CEILINGS, TRIM,

ETC., SHALL BE PROTECTED AND RETAINED, UNLESS NOTED OTHERWISE.

D. PORTIONS OF THE BUILDING ARE TO REMAIN CONTINUOUSLY OCCUPIED

THROUGHOUT CONSTRUCTION. CONTRACTOR TO MAINTAIN CLEAR PATH OF

EGRESS THROUGHOUT CONSTRUCTION.

E. UNLESS NOTED OTHERWISE ALL DIMENSIONS ARE TO THE FACE OF STUD.

F. RE: A001 FOR OVERALL FLOOR PLANS.

G. RE: G101 AND SPECIFICATIONS FOR HAZARDOUS MATERIALS INFORMATION.

SHEET NOTES:

LEGEND:

DASHED LINES INDICATE ASSEMBLIES/SYSTEMS TO BE DEMOLISHED AND

REMOVED. PROTECT ADJACENT EXISTING CONSTRUCTION TO REMAIN.

SOLID LINES INICATE EXISTING ELEMENTS TO REMAIN AND BE PROTECTED

DURING CONSTRUCTION.

1. REMOVE EXISTING WALL TO EXTENTS INDICATED.

2. RE: MECHANICAL DRAWINGS FOR WORK TO OCCUR WITHIN AREA NOTED.

PROTECT ALL EXISTING ITEMS TO REMAIN.

3. REMOVE EXISTING DOOR, FRAME, AND HARDWARE. PREP FOR NEW DOOR AND

FRAME.

4. REMOVE EXISTING PLUMBING FIXTURE.

5. REMOVE EXISTING TOILET PARTITIONS.

6. REMOVE EXISTING SHOWER BENCH.

7. REMOVE EXISTING SHOWER HEAD AND ALL ASSOCIATED ITEMS.

8. REMOVE EXISTING FLOOR DRAIN, RE: PLUMBING DRAWINGS.

9. EXISTING WINDOW ABOVE TO REMAIN, PROTECT.

10. REMOVE ENTIRETY OF EXISTING CONCRETE SLAB AND ALL ASSOCIATED ITEMS,

INCLUDING EXISTING PLUMBING PIPING, WITHIN ROOM NOTED, PREP FOR NEW

SLAB, RE: A111.

11. REMOVE ALL EXISTING BATHROOM ACCESSORIES WITHIN ROOM NOTED.

12. REMOVE SECTION OF EXISTING CONCRETE WALL PER DIMENSIONS ON THIS PLAN

AND DETAILS ON A601.

13. EXISTING CONCRETE LOCKERS TO REMAIN.

14. RE: MECHANICAL AND PLUMBING DRAWINGS FOR REMOVAL OF EXISTING FIRE

HOSE CABINET.

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

R.R.

R.R.

CLO.

R.R.

LOCKERS

STORAGE

7'-0" 1'-0"

12 14

A011

ENLARGED DEMOLITION PLAN BASEMENT RESTROOMS

1/4"=1'-0"

DRAWN BY |

REVISIONS

© | ALL RIGHTS RESERVED

w w w . c t a g r o u p . c o m

8 0 0 . 7 5 7 . 9 5 2 2

CHECKED BY |

U S

H

I S

P S

D

R

E N

O V

A T

I O

N S

P O

C A

T E

L L

O

I D

A H

O

100% CD

3.27.19

N O

T

F

N

S T

R U

C T

I O

N

P

R E

L I M

I N

A R

Y

D

E S

I G

N

06.11.18 06:10 PM | G:\USDAAPHIS_PSD1\BIMCAD\Arch\A-011.dwg

A011

PACKAGE #2 -

ENLARGED

DEMOLITION

PLANS

JC

SR

A011

ENLARGED DEMOLITION FLOOR PLAN OFFICES

1/4"=1'-0"

A111

A102

PACKAGE #2

PACKAGE #1

RAMP

BASEMENT

WAREHOUSE

ALPHACHLORALOSE

LAB

M-44

MACHINE

SHOP

ADC

STORAGE

COAL

STORAGE

RM.

ROOM

LOCKERS

ELECTRIC

DISTRIBUTION

ROOM

FREIGHT

BASEMENT

WAREHOUSE

STORAGE

ROOM

ROOM

GRAIN

ELEVATOR

AREA

AT

BASEMENT

LEVEL

GAS CARTRIDGE

FUSE STORAGE

A102

A102

A102

A103

AT FLOOR

LEVEL

ABOVE

PACKAGE #1

PACKAGE #1

PACKAGE #1

PACKAGE #1

A111

PACKAGE #2

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

R.R.

R.R.

WAREHOUSE

CENTRAL

WAREHOUSE

CARTRIDGE

MIXER

ROOM

DOWN RAMP TO BASEMENT

CHARGING

ROOM

FAS

ROOM

R.R.

FREIGHT

SHIPPING/WORKROOM

CLO.

PARKING LOT

NORTH

WAREHOUSE

STORAGE

ROOM

A104

PACKAGE #1

AT MECHANICAL

MEZZANINE

ABOVE

A104

PACKAGE #1

AT MECHANICAL

MEZZANINE

ABOVE

A103

PACKAGE #1

RS

RL

R S

R L

GENERAL NOTES:

A. MAINTAIN THE INTEGRITY OF ALL REMAINING BUILDING SYSTEMS AND RATINGS.

REPAIR ANY DAMAGE DONE TO SURROUNDING AREAS/CONSTRUCTION DURING

DEMOLITION.

B. ALL EXISTING CONDITIONS ARE NOT INDICATED ON THE DRAWINGS. CONTRACTOR

SHALL CAREFULLY EXAMINE THE EXISTING INSTALLATION AND ALL PROJECT

DRAWINGS TO BECOME FAMILIAR WITH THE SCOPE OF WORK.

C. CONTRACTOR SHALL PATCH AND REPAIR ANY DAMAGE OR PENETRATIONS AT ALL

ELEMENTS TO REMAIN (INCLUDING BUT NOT LIMITED TO WALLS, CEILINGS,

FLOORS, ETC.) CAUSED BY DEMOLITION ACTIVITIES OR REMOVAL OF ELECTRICAL,

MECHANICAL, AND ARCHITECTURAL ELEMENTS. REPLACE ITEMS NOT REPAIRABLE

TO ORIGINAL STATE. EXISTING FINISH MATERIALS, INCLUDING CEILINGS, TRIM,

ETC., SHALL BE PROTECTED AND RETAINED, UNLESS NOTED OTHERWISE.

D. PORTIONS OF THE BUILDING ARE TO REMAIN CONTINUOUSLY OCCUPIED

THROUGHOUT CONSTRUCTION. CONTRACTOR TO MAINTAIN CLEAR PATH OF

EGRESS THROUGHOUT CONSTRUCTION.

E. UNLESS NOTED OTHERWISE ALL DIMENSIONS ARE TO THE FACE OF STUD.

F. RE: A101 FOR OVERALL FLOOR PLANS.

1. NEW MECHANICAL ROOF PENETRATION, RE: A601 AND MECHANICAL DRAWINGS

FOR DETAILS.

2. RE: ELECTRICAL, MECHANICAL AND PLUMBING DRAWINGS FOR WORK TO OCCUR

WITHIN ROOM NOTED.

SHEET NOTES:

INTERIOR ELEVATION NUMBER /

SHEET WHERE DRAWN

F.E.F. FACE OF EXISTNG FINISH

DIMENSION TO FACE OF

STUD OR EXISTING WALL

DOOR NUMBER (SEE SHEET A101)

PLAN LEGEND

DETAIL OR SECTION NUMBER

SHEET WHERE DRAWN

PLAN NOTE

ROOM NAME

WALL TYPE

WALL TYPE NOTE

X

X

X

A101

101-1

A801

A

B

C

D

PACKAGE #1 - SAFETY AND HEALTH REVIEW: INCLUDES THE WORK RELATED TO THE

FOLLOWING ROOMS, AREAS, AND ITEMS. REFERENCE THE ASSOCIATED DOCUMENTS,

DRAWINGS, AND SPECIFICATIONS TO FIND FURTHER INFORMATION AND ALL WORK

RELATED TO THESE AREAS.

A. CYANIDE ROOM

B. GRAIN BAIT MIXING ROOM

C. CARTRIDGE ROOM

D. NORTH WAREHOUSE HOT LABEL MAKER

E. GAS CARTRIDGE FUSES

F. PERSONNEL DOOR

PACKAGE #2 - FACILITY CONDITION REASSESSMENT: INCLUDES THE WORK RELATED TO

THE FOLLOWING ROOMS, AREAS, AND ITEMS. REFERENCE THE ASSOCIATED

DOCUMENTS, DRAWINGS, AND SPECIFICATIONS TO FIND FURTHER INFORMATION AND

ALL WORK RELATED TO THESE AREAS.

A. ENERGY CONSERVATION MEASURES - OFFICE LIGHTING

B. BASEMENT RESTROOMS

C. OFFICE HVAC SYSTEM

D. WATER HEATER REPLACEMENT

E. FIRE ALARM SYSTEM

A101

OVERALL FLOOR PLAN FIRST FLOOR

1/16"=1'-0"

A101

OVERALL FLOOR PLAN BASEMENT

1/16"=1'-0"

A101

OVERALL ROOF PLAN

1/16"=1'-0"

DRAWN BY |

REVISIONS

© | ALL RIGHTS RESERVED

w w w . c t a g r o u p . c o m

8 0 0 . 7 5 7 . 9 5 2 2

CHECKED BY |

U S

H

I S

P S

D

R

E N

O V

A T

I O

N S

P O

C A

T E

L L

O

I D

A H

O

100% CD

3.27.19

N O

T

F

N

S T

R U

C T

I O

N

P

R E

L I M

I N

A R

Y

D

E S

I G

N

06.11.18 06:12 PM | G:\USDAAPHIS_PSD1\BIMCAD\Arch\A-101.dwg

A101

PACKAGE #1 AND #2 -

OVERALL PLANS

REPAIR ANY DAMAGE DONE TO SURROUNDING AREAS/CONSTRUCTION DURING

DEMOLITION.

B. ALL EXISTING CONDITIONS ARE NOT INDICATED ON THE DRAWINGS. CONTRACTOR

SHALL CAREFULLY EXAMINE THE EXISTING INSTALLATION AND ALL PROJECT

DRAWINGS TO BECOME FAMILIAR WITH THE SCOPE OF WORK.

C. CONTRACTOR SHALL PATCH AND REPAIR ANY DAMAGE OR PENETRATIONS AT ALL

ELEMENTS TO REMAIN (INCLUDING BUT NOT LIMITED TO WALLS, CEILINGS,

FLOORS, ETC.) CAUSED BY DEMOLITION ACTIVITIES OR REMOVAL OF ELECTRICAL,

MECHANICAL, AND ARCHITECTURAL ELEMENTS. REPLACE ITEMS NOT REPAIRABLE

TO ORIGINAL STATE. EXISTING FINISH MATERIALS, INCLUDING CEILINGS, TRIM,

ETC., SHALL BE PROTECTED AND RETAINED, UNLESS NOTED OTHERWISE.

D. PORTIONS OF THE BUILDING ARE TO REMAIN CONTINUOUSLY OCCUPIED

THROUGHOUT CONSTRUCTION. CONTRACTOR TO MAINTAIN CLEAR PATH OF

EGRESS THROUGHOUT CONSTRUCTION.

E. UNLESS NOTED OTHERWISE ALL DIMENSIONS ARE TO THE FACE OF STUD.

F. RE: A101 FOR OVERALL FLOOR PLANS.

SHEET NOTES:

FACE OF EXISTNG FINISH

1. NEW DOOR AND FRAME, COORDINATE WITH DOOR SCHEDULE AND ELECTRICAL

DRAWINGS FOR NEW ACCESS CONTROL TO BE DONE AT DOOR. PATCH, REPAIR

AND RE-FINISH WALL AS REQUIRED FOR ELECTRICAL WORK, RE: ELECTRICAL

DRAWINGS. FINISHES TO MATCH EXISTING FINISHES, VERIFY IN FIELD. RE: A-601

HEAD, JAMB DETAILS. THE SIZE OF THIS DOOR AND FRAME IS A CUSTOM SIZE,

REFERENCE A-601 FOR DOOR SCHEDULE AND NOTATIONS.

2. NEW FUSE STORAGE 'B1200 HAZMAT DRUM STORAGE LOCKER' OR EQUAL.

COORDINATE EXACT PLACEMENT ON SITE WITH GOVERNMENT OFFICIAL, RE:

MECHANICAL AND ELECTRICAL DRAWINGS FOR FURTHER ITEMS AND DETAILS.

3. RELOCATED EXISTING METAL CASEWORK.

4. NEW METAL WIRE SHELVING UNIT - (4) SHELVES HIGH - UNIT TO BE 48"X18"DX72"H.

5. RELOCATED EXISTING MIXER.

6. PAINT ALL WALLS WITHIN ROOM NOTED, PAINT WITH EPOXY HIGH PERFORMANCE

COATING, RE: SPECIFICATIONS. PROTECT EXISTING EQUIPMENT WHEN PAINTING,

MOVE FURNITURE AND EQUIPMENT AS NECESSARY TO ACCOMMODATE PAINT.

7. PAINT FLOOR WITHIN ROOM NOTED, PAINT WITH EPOXY HIGH PERFORMANCE

COATING, RE: SPECIFICATIONS.

8. NEW SINK, RE: PLUMBING DRAWINGS AND SPECIFICATIONS.

9. NEW EYEWASH, RE: PLUMBING DRAWINGS AND SPECIFICATIONS.

10. EXISTING FLOOR DRAIN TO REMAIN.

11. RELOCATED EXISTING STORAGE BINS, COORDINATE PLACEMENT WITH

GOVERNMENT REPRESENTATIVE ON SITE.

12. EXISTING SCALE AND ASSOCIATED ITEMS TO REMAIN IN PLACE.

STORAGE

ROOM

EXTERIOR

PAVEMENT/PARKING

GRAIN

ELEVATOR

MIXER

ROOM

CARTRIDGE

FUSE

STORAGE

INTERIOR ELEVATION NUMBER /

SHEET WHERE DRAWN

F.E.F. FACE OF EXISTNG FINISH

DIMENSION TO FACE OF

STUD OR EXISTING WALL

DOOR NUMBER (SEE SHEET A101)

PLAN LEGEND

DETAIL OR SECTION NUMBER

SHEET WHERE DRAWN

PLAN NOTE

ROOM NAME

WALL TYPE

WALL TYPE NOTE

X

X

X

A101

A801

A

B

C

D

101-1

A102

ENLARGED FLOOR PLAN CARTRIDGE ROOM

1/4"=1'-0"

A102

ENLARGED FLOOR PLAN PERSONNEL DOOR

1/4"=1'-0"

A102

ENLARGED FLOOR PLAN MIXER ROOM

1/4"=1'-0"

DRAWN BY |

REVISIONS

© | ALL RIGHTS RESERVED

w w w . c t a g r o u p . c o m

8 0 0 . 7 5 7 . 9 5 2 2

CHECKED BY |

U S

H

I S

P S

D

R

E N

O V

A T

I O

N S

P O

C A

T E

L L

O

I D

A H

O

100% CD

3.27.19

N O

T

F

N

S T

R U

C T

I O

N

P

R E

L I M

I N

A R

Y

D

E S

I G

N

06.11.18 06:12 PM | G:\USDAAPHIS_PSD1\BIMCAD\Arch\A-102.dwg

A102

PACKAGE #1 -

ENLARGED

PLANS

JC

SR

A102

ENLARGED FLOOR PLAN GAS CARTRIDGE FUSES

REPAIR ANY DAMAGE DONE TO SURROUNDING AREAS/CONSTRUCTION DURING

DEMOLITION.

B. ALL EXISTING CONDITIONS ARE NOT INDICATED ON THE DRAWINGS. CONTRACTOR

SHALL CAREFULLY EXAMINE THE EXISTING INSTALLATION AND ALL PROJECT

DRAWINGS TO BECOME FAMILIAR WITH THE SCOPE OF WORK.

C. CONTRACTOR SHALL PATCH AND REPAIR ANY DAMAGE OR PENETRATIONS AT ALL

ELEMENTS TO REMAIN (INCLUDING BUT NOT LIMITED TO WALLS, CEILINGS,

FLOORS, ETC.) CAUSED BY DEMOLITION ACTIVITIES OR REMOVAL OF ELECTRICAL,

MECHANICAL, AND ARCHITECTURAL ELEMENTS. REPLACE ITEMS NOT REPAIRABLE

TO ORIGINAL STATE. EXISTING FINISH MATERIALS, INCLUDING CEILINGS, TRIM,

ETC., SHALL BE PROTECTED AND RETAINED, UNLESS NOTED OTHERWISE. MATCH

EXISTING PAINT AND MATERIALS, VERIFY IN FIELD. CONFIRM AND CONSULT WITH

GOVERNMENT REPRESENTATIVE ON PATCH WORK PRIOR TO COMMENCING.

D. PORTIONS OF THE BUILDING ARE TO REMAIN CONTINUOUSLY OCCUPIED

THROUGHOUT CONSTRUCTION. CONTRACTOR TO MAINTAIN CLEAR PATH OF

EGRESS THROUGHOUT CONSTRUCTION.

E. UNLESS NOTED OTHERWISE ALL DIMENSIONS ARE TO THE FACE OF STUD.

F. RE: A101 FOR OVERALL FLOOR PLANS.

1. EXISTING ROOF ACCESS ROOFTOP ABOVE.

2. EXISTING SHINGLE ROOF TO REMAIN.

3. NEW OSHA COMPLIANT FALL PROTECTION RAILING AROUND PERIMETER OF

EXISTING ROOF WHERE SHOWN, RE: DETAILS ON A601. RAILING TO BE 'SAFETY

RAIL COMPANY: PERMANENT FACE MOUNT GUARDRAIL SYSTEM' OR EQUAL,

MOUNT/INSTALL PER MANUFACTURER RECOMMENDATIONS AND INSTRUCTIONS,

RE: A601 FOR DETAILS.

4. NEW STORAGE CABINET, CABINET TO BE ULINE 'H-1223' HEAVY DUTY STORAGE

CABINET OR EQUAL.

5. NEW MECHANICAL CONVECTION LABORATORY OVEN, RE: SPECIFICATIONS AND

MECHANICAL DRAWINGS.

6. NEW STAINLESS STEEL COUNTERTOP TO BE ULINE "INDUSTRIAL PACKING TABLE -

48 X 36", STAINLESS STEEL TOP 'H-3657-SS' " OR EQUAL.

7. RE: MECHANICAL AND ELECTRICAL DRAWINGS FOR FURTHER WORK TO OCCUR

WITHIN ROOM/AREA NOTED.

8. NEW LAB EQUIPMENT, RE: MECHANICAL DRAWINGS.

9. NEW SELF CONTAINED EYE WASH STATION, RE: PLUMBING DRAWINGS.

10. RE: MECHANICAL DRAWINGS AND DETAIL 3/A103 FOR INFILL DETAIL AT EXISTING

OPENING BEING UTILIZED FOR NEW LOUVER LOCATION AND TYPE. OPENING

OCCURS AT EXISTING EXTERIOR WALL BELOW ROOF LINE.

11. PAINT ALL WALLS WITHIN ROOM NOTED, PAINT WITH EPOXY HIGH PERFORMANCE

COATING, RE: SPECIFICATIONS. PROTECT EXISTING EQUIPMENT WHEN PAINTING,

MOVE FURNITURE AND EQUIPMENT AS NECESSARY TO ACCOMMODATE PAINT.

12. PAINT FLOOR WITHIN ROOM NOTED, PAINT WITH EPOXY HIGH PERFORMANCE

COATING, RE: SPECIFICATIONS.

13. ROUTE DUCTWORK TO FIT THROUGH RAILING OPENING, RE: MECHANICAL

DRAWINGS.

SHEET NOTES:

CYANIDE

ROOM

ROOF

ACCESS

(E) TABLE

(E) TABLE

(E) GRADER

(E) MIXER

(E) TABLE(E) STRG.(E) STRG.

(E) TABLE

(E) KILN

(E) STRG.

3'-0"

APPROX. 50'-4"

V.I.F. (VERIFY IN FIELD)

A P

P R

O X

V I F

A P

P R

O X

V I F

A601

A601

A601

GENERAL NOTES:

INTERIOR ELEVATION NUMBER /

SHEET WHERE DRAWN

F.E.F. FACE OF EXISTNG FINISH

DIMENSION TO FACE OF

STUD OR EXISTING WALL

DOOR NUMBER (SEE SHEET A101)

PLAN LEGEND

DETAIL OR SECTION NUMBER

SHEET WHERE DRAWN

PLAN NOTE

ROOM NAME

WALL TYPE

WALL TYPE NOTE

X

X

X

A101

101-1

A801

A

B

C

D

V I F

2" 'WALLGUARD CONCRETE FACED

INSULATED WALL PANEL' OR EQUAL

BACKER ROD AND SEALANT (ALL

SIDES)

INFILL CAVITY WITH BATT

INSULATION

TREATED WOOD BLOCKING AS NECESSARY

- VERIFY EXISTING WALL WIDTH IN FIELD

" GYPSUM WALL BOARD-MATCH PAINT

'PT1' PER SPECIFICATIONS, CREATE

FLUSH FINISH WITH EXISTING

ADJACENT WALL

*NOTE- REFERENCE MECHANICAL DRAWINGS - M-101 -

FOR AREAS WHERE NEW LOUVERS ARE TO OCCUR IN

THE EXTERIOR WALL - THIS DETAIL SHALL BE USED TO

INFILL THE WALL WHERE THE LOUVER DOES NOT INFILL

THE ENTIRETY OF THE EXISTING OPENING SIZE.

NEW MECHANICAL LOUVER,. RE:

MECHANICAL DRAWINGS AND

SPECIFICATIONS.

V.I.F.

VERIFY HEIGHT OF OPENING IN FIELD

A103

ENLARGED FLOOR PLAN CYANIDE ROOM

1/4"=1'-0"

A103

ENLARGED FLOOR PLAN CYANIDE ROOF TOP

1/4"=1'-0"

DRAWN BY |

REVISIONS

© | ALL RIGHTS RESERVED

w w w . c t a g r o u p . c o m

8 0 0 . 7 5 7 . 9 5 2 2

CHECKED BY |

U S

H

I S

P S

D

R

E N

O V

A T

I O

N S

P O

C A

T E

L L

O

I D

A H

O

100% CD

3.27.19

N O

T

F

N

S T

R U

C T

I O

N

P

R E

L I M

I N

A R

Y

D

E S

I G

N

06.11.18 06:12 PM | G:\USDAAPHIS_PSD1\BIMCAD\Arch\A-103.dwg

A103

PACKAGE #1

- ENLARGED

PLANS

JC

SR

A103

INFILL DETAIL AT EXTERIOR WALL OPENING

REPAIR ANY DAMAGE DONE TO SURROUNDING AREAS/CONSTRUCTION DURING

DEMOLITION.

B. ALL EXISTING CONDITIONS ARE NOT INDICATED ON THE DRAWINGS. CONTRACTOR

SHALL CAREFULLY EXAMINE THE EXISTING INSTALLATION AND ALL PROJECT

DRAWINGS TO BECOME FAMILIAR WITH THE SCOPE OF WORK.

C. CONTRACTOR SHALL PATCH AND REPAIR ANY DAMAGE OR PENETRATIONS AT ALL

ELEMENTS TO REMAIN (INCLUDING BUT NOT LIMITED TO WALLS, CEILINGS,

FLOORS, ETC.) CAUSED BY DEMOLITION ACTIVITIES OR REMOVAL OF ELECTRICAL,

MECHANICAL, AND ARCHITECTURAL ELEMENTS. REPLACE ITEMS NOT REPAIRABLE

TO ORIGINAL STATE. EXISTING FINISH MATERIALS, INCLUDING CEILINGS, TRIM,

ETC., SHALL BE PROTECTED AND RETAINED, UNLESS NOTED OTHERWISE. MATCH

EXISTING PAINT AND MATERIALS, VERIFY IN FIELD. CONFIRM AND CONSULT WITH

GOVERNMENT REPRESENTATIVE ON PATCH WORK PRIOR TO COMMENCING.

D. PORTIONS OF THE BUILDING ARE TO REMAIN CONTINUOUSLY OCCUPIED

THROUGHOUT CONSTRUCTION. CONTRACTOR TO MAINTAIN CLEAR PATH OF

EGRESS THROUGHOUT CONSTRUCTION.

E. UNLESS NOTED OTHERWISE ALL DIMENSIONS ARE TO THE FACE OF STUD.

F. RE: A101 FOR OVERALL FLOOR PLANS.

1. NEW OSHA COMPLIANT FALL PROTECTION RAILING AROUND PERIMETER OF

EXISTING MEZZANINE WHERE SHOWN. RAILING TO BE 'SAFETY RAIL COMPANY:

PERMANENT FLUSH MOUNT GUARDRAIL SYSTEM' OR EQUAL, MOUNT/INSTALL PER

MANUFACTURER RECOMMENDATIONS AND INSTRUCTIONS, MOUNT ON INSIDE

FACE OF CMU WALL.

2. EXISTING CMU BLOCK WALLS, FULLY GROUTED, TOP OF WALL IS APPROXIMATELY

14'-8" A.F.F. - VERIFY IN FIELD. RE: 4/A104 FOR EXISTING CONDITION IMAGES.

3. COORDINATE NEW RAILING WITH EXISTING MECHANICAL EQUIPEMENT AND

DUCTWORK ASSOCIATED WITH THE MECHANICAL MEZZANINE - VERIFY LOCATIONS

AND QUANTITY IN FIELD. RE: 4/A104 FOR EXISTING CONDITION IMAGES.

4. COORDINATE NEW RAILING WITH EXISTING AND NEW MECHANICAL EQUIPEMENT

AND DUCTWORK ASSOCIATED WITH THE MECHANICAL MEZZANINE - VERIFY

LOCATIONS AND QUANTITY IN FIELD. RE: MECHANICAL DRAWINGS. RE: 3/A104 FOR

EXISTING CONDITION IMAGES.

5. NEW OSHA COMPLIANT FALL PROTECTION RAILING AROUND PERIMETER OF

EXISTING MEZZANINE WHERE SHOWN. RAILING TO BE 'SAFETY RAIL COMPANY:

PERMANENT FACE MOUNT GUARDRAIL SYSTEM' OR EQUAL, MOUNT/INSTALL PER

MANUFACTURER RECOMMENDATIONS AND INSTRUCTIONS. COORDINATE

MOUNTING WITH EXISTING CONDUIT.

6. INSTALL SELF-CLOSING GATE FOR SQUARE OR ROUND POST MOUNT 23-29"

(SAFETY YELLOW) - GATE TO BE 'SAFETY RAIL COMPANY' OR EQUAL.

7. EXISTING FIXED LADDER MEZZANINE ACCESS - LADDER TO BE PROTECTED AND

MAINTAINED - PROVIDE GATE AT EXISTING LADDER.

8. NEW OSHA COMPLIANT FALL PROTECTION RAILING WHERE SHOWN ON SURFACE

OF MEZZANINE. RAILING TO BE 'SAFETY RAIL COMPANY: PERMANENT SURFACE

MOUNT GUARDRAIL SYSTEM' OR EQUAL, MOUNT/INSTALL PER MANUFACTURER

RECOMMENDATIONS AND INSTRUCTIONS. COORDINATE MOUNTING WITH

EXISTING CONDUIT.

SHEET NOTES:

MIXER

ROOM

STORAGE

ROOM

V I F

11'-8"

V.I.F.

V I F

NORTH

WAREHOUSE

1 6

19'-4"

9'-4"

28'-8"

A104

ENLARGED FLOOR PLAN MIXING ROOM MECHANICAL MEZZANINE

1/4"=1'-0"

A104

ENLARGED FLOOR PLAN NORTH WAREHOUSE MECHANICAL MEZZANINE

1/4"=1'-0"

DRAWN BY |

REVISIONS

© | ALL RIGHTS RESERVED

w w w . c t a g r o u p . c o m

8 0 0 . 7 5 7 . 9 5 2 2

CHECKED BY |

U S

H

I S

P S

D

R

E N

O V

A T

I O

N S

P O

C A

T E

L L

O

I D

A H

O

100% CD

3.27.19

N O

T

F

N

S T

R U

C T

I O

N

P

R E

L I M

I N

A R

Y

D

E S

I G

N

06.11.18 06:12 PM | G:\USDAAPHIS_PSD1\BIMCAD\Arch\A-104.dwg

A104

PACKAGE #1

- ENLARGED

PLANS

JC

SR

A104

EXISTING CONDITIONS OF MIXING ROOM MECHANICAL MEZZANINE

NOT TO SCALE

A104

EXISTING CONDITIONS OF NORTH WAREHOUSE MECHANICAL MEZZANINE

NOT TO SCALE

REPAIR ANY DAMAGE DONE TO SURROUNDING AREAS/CONSTRUCTION DURING

DEMOLITION.

B. ALL EXISTING CONDITIONS ARE NOT INDICATED ON THE DRAWINGS. CONTRACTOR

SHALL CAREFULLY EXAMINE THE EXISTING INSTALLATION AND ALL PROJECT

DRAWINGS TO BECOME FAMILIAR WITH THE SCOPE OF WORK.

C. CONTRACTOR SHALL PATCH AND REPAIR ANY DAMAGE OR PENETRATIONS AT ALL

ELEMENTS TO REMAIN (INCLUDING BUT NOT LIMITED TO WALLS, CEILINGS,

FLOORS, ETC.) CAUSED BY DEMOLITION ACTIVITIES OR REMOVAL OF ELECTRICAL,

MECHANICAL, AND ARCHITECTURAL ELEMENTS. REPLACE ITEMS NOT REPAIRABLE

TO ORIGINAL STATE. EXISTING FINISH MATERIALS, INCLUDING CEILINGS, TRIM,

ETC., SHALL BE PROTECTED AND RETAINED, UNLESS NOTED OTHERWISE.

D. PORTIONS OF THE BUILDING ARE TO REMAIN CONTINUOUSLY OCCUPIED

THROUGHOUT CONSTRUCTION. CONTRACTOR TO MAINTAIN CLEAR PATH OF

EGRESS THROUGHOUT CONSTRUCTION.

E. UNLESS NOTED OTHERWISE ALL DIMENSIONS ARE TO THE FACE OF STUD.

F. RE: A601 FOR DOOR TYPES, HARDWARE AND DETAILS.

G. RE: A801 FOR INTERIOR ELEVATIONS AND FIXTURE ACCESSIBILITY

REQUIREMENTS.

H. RE: A101 FOR OVERALL FLOOR PLANS.

1. RE: MECHANICAL AND ELECTRICAL DRAWINGS FOR WORK TO OCCUR IN THIS AREA.

2. SHOWER CONTROL WALL, RE: PLUMBING DRAWINGS.

3. SHOWER BENCH WALL, RE: SPECIFICATIONS. INSTALL BENCH PER MANUFACTURER

RECOMMENDATION.

4. WALL HUNG SINK AND ASSOCIATED MIRROR, RE: PLUMBING DRAWINGS AND A801.

5. TOILET PLUMBING FIXTURE, RE: PLUMBING DRAWINGS.

6. NEW BENCH RE: DETAILS ON A801.

7. EXISTING WALL MOUNTED COMMUNICATIONS EQUIPMENT ABOVE TO REMAIN, PROTECT ALL

ASSOCIATED ITEMS. DO NOT PAINT. VERIFY EXACT LOCATION IN FIELD.

8. RE-ROUTE EXISTING CONDUIT AS NECESSARY TO ACCOMMODATE NEW OPENING.

9. FACE OF GYPSUM CEILING, AND ASSOCIATED CEILING FRAMING TO BE 8'-0" ABOVE FINISH

FLOOR, PAINT PT1. RE: ELECTRICAL DRAWINGS FOR LIGHTING DETAILS.

10. FIBERGLASS SHOWER INSERT PER SPECIFICATIONS.

11. TILE TO CONCRETE FLOOR TRANSITION PER SPECIFICATIONS, RE: 4/A-111 FOR DETAILS.

12. MECHANICAL EQUIPMENT, RE: MECHANICAL DRAWINGS. RE: A601 FOR FURTHER DETAILS

13. NEW SLAB, S1, THROUGHOUT ENTIRETY OF AREA WHERE SLAB WAS REMOVED DURING

DEMOLITION. RE: DETAIL 4/A111. NEW SLAB TO RECEIVE TILE AND TILE COVE BASE

THROUGHOUT, INSTALL TILE PER MANUFACTURER INSTRUCTIONS AND RECOMMENDATIONS.

14. INSTALL ACCESSIBLE RESTROOM PANEL SIGNAGE PER DETAILS ON A801.

15. RE: MECHANICAL DRAWINGS FOR PIPING LOCATIONS. RE: A601 FOR THRU WALL

PENETRATION DETAILS.

16. NEW CONCRETE PAD FOR MECHANICAL EQUIPMENT. PAD TO BE SLAB TYPE 'S1'- NO VAPOR

BARRIER IS NEEDED AT THIS PAD LOCATION. REMOVE EXISTING ASPHALT AS NEEDED TO

ACCOMMODATE NEW PAD - PATCH EXISTING ASPHALT WHERE DAMAGE OCCURS.

17. FACE OF GYPSUM CEILING, AND ASSOCIATED CEILING FRAMING TO BE 9'-0" ABOVE FINISH

FLOOR, PAINT PT1. RE: ELECTRICAL DRAWINGS FOR LIGHTING DETAILS.

18. INSTALL STEEL FRAMING AROUND OPENING PER DETAILS ON A-601 - STEEL FRAMING TO BE

PAINTED TO MATCH DOOR FRAMES.

SHEET NOTES:

LOCKERS

STORAGE

5 5

B

B

B102

R.R.

B101

R.R.

1'-0"

MIN.

1'-0"

MIN.

4"

A801

A

B

C

D

A801

A

B

C

D

5'-9"5'-9"

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

R.R.

R.R.

CLO.

R S

R L

4'-0"

LOCKERS

STORAGE

B101

R.R.

B102

R.R.

A801

(1) LAYER

" TYPE 'X' EA. SIDE

4" METAL STUD AT 16" O.C.

FIBER GLASS BLANKET INSULATION, FILL STUD CAVITY.

NOTE: USE MOISTURE RESISTANT GYPSUM WALL

BOARD ON ALL WET WALL, RE: A801 AND

SPECIFICATIONS.

WALL TYPES:

(1) LAYER

" TYPE 'X' EA. SIDE

(2)STAGGERED 6" METAL STUDS AT 16" O.C.

FIBER GLASS BLANKET

INSULATION, FILL STUD CAVITY

NOTE: USE MOISTURE RESISTANT GYPSUM WALL

BOARD ON ALL WET WALLS, RE: A801 AND

SPECIFICATIONS.

VAPOR BARRIER

4" COMPACTED GRAVEL FILL

4" CONCRETE SLAB

w/#3 @ 16”OC EA WAY

1½” CLR FROM TOP OF SLAB

NOTES:

Concrete shall be f'c = 4,500psi ASTM C150 TYPE I/II, Fly Ash

ASTM C615 Class C or F, W/C +Fly Ash ratio = 0.45 max, ¾” max normal weight aggregate.

Rebar shall be ASTM A615, Grade 60.

S1

SLAB TYPES:

FF ELEV

#4 x 2'-6" DOWEL w/ 6" EMBED

SET IN EPOXY @ 16" OC

(N) CONC SLAB ON

GRADE, SEE SLAB

TYPE AND FLOOR

PLAN

(E) CONC SLAB ON GRADE

E Q

E Q

DEPRESSED SLAB - FINISH

FACE OF TILE TO MATCH

TOP OF EXISTING SLAB

TILE FLOOR FINISH, RE: PLANS

AND SPECIFICATIONS

INTERIOR ELEVATION NUMBER /

SHEET WHERE DRAWN

F.E.F. FACE OF EXISTNG FINISH

DIMENSION TO FACE OF

STUD OR EXISTING WALL

DOOR NUMBER (SEE SHEET A101)

PLAN LEGEND

DETAIL OR SECTION NUMBER

SHEET WHERE DRAWN

PLAN NOTE

ROOM NAME

WALL TYPE

WALL TYPE NOTE

X

X

X

A101

A801

A

B

C

D

101-1

A111

ENLARGED FLOOR PLAN BASEMENT RESTROOMS

1/4"=1'-0"

06.11.18 06:12 PM | G:\USDAAPHIS_PSD1\BIMCAD\Arch\A-111.dwg

A111

PACKAGE #2 -

ENLARGED

PLANS

JC

SR

A111

ENLARGED FLOOR PLAN OFFICES

1/4"=1'-0"

DRAWN BY |

REVISIONS

© | ALL RIGHTS RESERVED

w w w . c t a g r o u p . c o m

8 0 0 . 7 5 7 . 9 5 2 2

CHECKED BY |

U S

H

I S

P S

D

R

E N

O V

A T

I O

N S

P O

C A

T E

L L

O

I D

A H

O

100% CD

3.27.19

N O

T

F

N

S T

R U

C T

I O

N

P

R E

L I M

I N

A R

Y

D

E S

I G

N

A111

ENLARGED CEILING PLAN BASEMENT RESTROOMS

1/4"=1'-0"

A111

EXISTING SLAB TO NEW SLAB CONNECTION DETAIL

FINISH FLOOR

INSULATED HOLLOW

METAL DOOR TYPES

1 4

V I F

±2'-11

V.I.F.

A

8" 6"

3'-0"

HOLLOW

METAL DOOR TYPES

*FIELD VERIFY

DIMENSIONS OF

DOOR/FRAME TYPE

DOOR

NUMBER

ROOM NUMBER

B101-1

HARDWARE

GROUP

GLAZING

TYPE

B101

NOTES

1, 2

DOOR TYPE FRAME

TYPE

B

NA

1. PAINT DOOR AND FRAME, RE: SPECIFICATION.

2. DOOR TO RECEIVE KICK-PLATE AS APART OF THE HARDWARE SET PER

SPECIFICATIONS.

DOOR SCHEDULE NOTES

A. INSULATED FULLY TEMPERED.

GLAZING TYPES

NA = NOT APPLICABLE

DOOR SCHEDULE ABBREVIATIONS

B102-1 2B102 1, 22 B

NA

101-1 1101 1, 21 A

A

DOOR SCHEDULE

HARDWARE GROUPS:

GROUP 1 -

HINGE:

LOCKS:

CLOSER:

GASKETING:

THRESHOLD:

SWEEP:

SECURE CARD ACCESS J-BOX

FOR ELECTRIFIED DOOR HARDWARE FUNCTION

PER SPECIFICATIONS,

ENTRANCE LOCK WITH ELECTRIC STRIKE

PER SPECIFICATIONS.

PER SPECIFICATIONS.

PER SPECIFICATIONS.

PER SPECIFICATIONS.

GROUP 2 -

HINGES:

LOCK:

WALL STOP:

SILENCER:

PER SPECIFICATIONS,

PRIVACY FUNCTION.

PER SPECIFICATIONS.

PER SPECIFICATIONS.

FINISH FLOOR

METAL FRAME TYPES

INSULATED HOLLOW

METAL FRAME TYPES

2"

HOLLOW

2"

A601

A601

A601

A601

*FIELD VERIFY

DIMENSIONS OF

DOOR/FRAME TYPE

SEALANT PERIMETER

BOTH SIDES

INSULATED HOLLOW METAL FRAME,

RE: SCHEDULE, FRAME TO ALLOW

ELECTRICAL WIRING TO RUN

THROUGH FRAME, RE: ELECTRICAL

DRAWINGS

DOOR, RE: SCHEDULE

POSITION FRAME IN

SAME LOCATION AS

EXISTING, V.I.F.

EXISTING WALL

TO REMAIN

NEW PENETRATION

RE: MECHANICAL

DRAWINGS

RE: MECHANICAL DRAWINGS

FOR GOOSENECK

REQUIREMENTS AND LOCATION

6" MIN.

ROOF CEMENT

UNDER FLANGE

EXISTING ROOF

ASSEMBLY

SHINGLE -

LAP OVER METAL

FLANGE ASSOCIATED

WITH GOOSENECK

ROOF CEMENT

UNDER FLANGE

LAP METAL FLANGE

ASSOCIATED WITH GOOSNECK

OVER EXISTING SHINGLE

HEAD REINFORCEMENT

JAMB REINFORCEMENT (PLAN VIEW)

L3x3x

CONT ANGLE

EA SIDE OF HEAD

TYP EA SIDE

" CONT

CLOSURE PL

" CLOSURE PL w/

"Øx 4" HAS @ 6"

FROM BOT, THEN @ 32" OC.

* IF WALL IS HOLLOW PACK w/

NON-SHRINKING GROUT AND SET PL.

* IF WALL IS SOLID. PROVIDE

DRILLED HOLE & SET IN EPOXY.

L3x3x

CONT ANGLE

EA SIDE OF JAMB

INSTALLATION PROCEDURE:

1) SAWCUT HORIZONTAL SLOT INTO MASONRY ALONG NEW HEAD &

INSERT HEAD ANGLES.

2) REMOVE 2'-0" WIDE STRIP OF MASONRY AT EACH JAMB.

REMAINING CENTER SECTION OF MASONRY ACTS AS TEMPORARY

SHORING OF OPENING.

3) INSTALL JAMB REINFORCING ANGLES & CLOSURE PLATE. WELD

TOP OF JAMB ANGLE TO HEAD ANGLES.

4) REMOVE THE REMAINING CENTER SECTION OF (E) MASONRY & ADD

HEAD CLOSURE PLATE.

B

(E) MASONRY ON

CONCRETE WALL

NEW OPENING

(SEE ARCH)

A

3 SIDES

COPE HORIZ LEGS OF HEAD ANGLES &

EXTEND VERT LEG OVER JAMB ANGLES

(E) MASONRY

ON CONCRETE

WALL

3 - 12

TYP EA SIDE

3 - 12

A

B

(E) MASONRY ON

CONCRETE WALL

A601

NEW PENETRATION -

MAINTAIN 1/4" JOINT ALL

AROUND, PACK W/

GLASS FIBER OR OAKUM

AND SEAL W/ FIRE-

RESISTIVE SEALANT

PIPING OR CONDUIT

EXISTING WALL

EXTERIORINTERIOR

SEALANT AT PIPE PENETRATION DETAIL

1 1/2"=1'-0"

OSHA COMPLIANT -

FACE MOUNTED

RAILIING, TO BE

'SAFETY RAIL

COMPANY' OR EQUAL.

EXISTING GUTTER AND

ROOF EDGE AT LOW

SIDE OF EXISTING

ROOF - RAILING TO

NAVIGATE AROUND

GUTTER.

FACE MOUNTED

RAILING BEYOND

PARAPET BEYOND

TOP OF EXISTING ROOF

MOUNT TO EXISTING

EXTERIOR WALL PER

MANUFACTURER

RECOMMENDATIONS AND

INSTRUCTIONS.

POST TO BE AT 96"

O.C. MAXIMUM

OSHA COMPLIANT -

FACE MOUNTED

RAILIING, TO BE

'SAFETY RAIL

COMPANY' OR EQUAL.

EXISTING GUTTER AND

ROOF EDGE AT LOW

SIDE OF EXISTING

ROOF BEYOND -

RAILING TO NAVIGATE

AROUND GUTTER.

FACE MOUNTED

RAILING BEYOND

EXISTING PARAPET

TOP OF EXISTING ROOF

MOUNT TO EXISTING

EXTERIOR WALL PER

MANUFACTURER

RECOMMENDATIONS AND

INSTRUCTIONS.

POST TO BE AT 96"

O.C. MAXIMUM

SEALANT PERIMETER

BOTH SIDES

HOLLOW METAL FRAME, RE:

SCHEDULE

DOOR, RE: SCHEDULE

EXISTING WALL

TO REMAIN

RE: 3/A601 FOR REINFORCING OF NEW

OPENING DETAILS

DRAWN BY |

REVISIONS

© | ALL RIGHTS RESERVED

w w w . c t a g r o u p . c o m

8 0 0 . 7 5 7 . 9 5 2 2

CHECKED BY |

U S

H

I S

P S

D

R

E N

O V

A T

I O

N S

P O

C A

T E

L L

O

I D

A H

O

100% CD

3.27.19

N O

T

F

N

S T

R U

C T

I O

N

P

R E

L I M

I N

A R

Y

D

E S

I G

N

06.11.18 06:12 PM | G:\USDAAPHIS_PSD1\BIMCAD\Arch\A-601.dwg

A601

SCHEDULES

AND

DETAILS

JC

SR

A601

EXTERIOR HM DOOR HEAD/JAMB DETAIL

3"=1'-0"

A601

TYPICAL PIPE PENETRATION DETAIL

1-1/2"=1'-0"

A601

NEW OPENING IN EXISTING MASONRY

3/4"=1'-0"

A601

ROOF RAILING DETAIL I

3/4"=1'-0"

A601

ROOF RAILING DETAIL II

3/4"=1'-0"

A601

INTERIOR HM DOOR HEAD/JAMB DETAIL

3"=1'-0"

AutoCAD SHX Text B

REPAIR ANY DAMAGE DONE TO SURROUNDING AREAS/CONSTRUCTION DURING

DEMOLITION.

B. ALL EXISTING CONDITIONS ARE NOT INDICATED ON THE DRAWINGS. CONTRACTOR

SHALL CAREFULLY EXAMINE THE EXISTING INSTALLATION AND ALL PROJECT

DRAWINGS TO BECOME FAMILIAR WITH THE SCOPE OF WORK.

C. CONTRACTOR SHALL PATCH AND REPAIR ANY DAMAGE OR PENETRATIONS AT ALL

ELEMENTS TO REMAIN (INCLUDING BUT NOT LIMITED TO WALLS, CEILINGS,

FLOORS, ETC.) CAUSED BY DEMOLITION ACTIVITIES OR REMOVAL OF ELECTRICAL,

MECHANICAL, AND ARCHITECTURAL ELEMENTS. REPLACE ITEMS NOT REPAIRABLE

TO ORIGINAL STATE. EXISTING FINISH MATERIALS, INCLUDING CEILINGS, TRIM,

ETC., SHALL BE PROTECTED AND RETAINED, UNLESS NOTED OTHERWISE.

D. PORTIONS OF THE BUILDING ARE TO REMAIN CONTINUOUSLY OCCUPIED

THROUGHOUT CONSTRUCTION. CONTRACTOR TO MAINTAIN CLEAR PATH OF

EGRESS THROUGHOUT CONSTRUCTION.

E. UNLESS NOTED OTHERWISE ALL DIMENSIONS ARE TO THE FACE OF STUD.

F. COORDINATE ALL PLUMBING FIXTURES WITH PLUMBING DRAWINGS.

G. PROVIDE TREATED BLOCKING IN WALL FOR ALL MOUNTED FIXTURES AND

EQUIPMENT.

H. ALL DOORS SET WITH HINGE SIDE 4" FROM BACK OF DOOR FRAME TO FACE OF

ADJACENT WALL UNLESS DIMENSIONED OTHERWISE.

1. FRP, PLASTIC PANELING, UP TO 4'-6" A.F.F, RE: 4/A801 FOR DETAILS.

2. CLASS V SEMI-GLOSS PAINT TO CEILING, RE: SPECIFICATIONS.

3. COVED CERAMIC MOSAIC TILE BASE.

4. ADA ACCESSIBLE HEAVY DUTY HAT AND COAT HOOK, PROVIDE BLOCKING AS

NECESSARY.

5. EXISTING WALL MOUNTED COMMUNICATIONS EQUIPMENT ABOVE TO REMAIN,

PROTECT ALL ASSOCIATED ITEMS. DO NOT PAINT. VERIFY EXACT LOCATION IN FIELD.

6. WOOD BENCH, RE: 6/A801.

7. FIBERGLASS SHOWER INSERT PER SPECIFICATIONS.

8. HEAVY DUTY HAT AND COAT HOOK, PROVIDE BLOCKING AS NECESSARY.

SHEET NOTES:

GB GRAB BAR, RE: SPEC 102800. ALL GRAB BARS PER ANSI HANDICAP

ACCESSIBILITY STANDARDS. MOUNTING HEIGHT - 33" - 36" TO TOP A.F.F.

MU 24" x 36" MIRROR UNIT, RE: SPEC 102800. MOUNTING HEIGHT - 40" MAX TO BOT

MIRROR SURFACE.

PTD PAPER TOWEL DISPENSER, RE: SPEC 102800. MOUNTING HEIGHT - 40" MAX TO

BOT OF DISPENSER.

SD SOAP DISPENSER, RE: SPEC 102800. MOUNTING HEIGHT - 40" MAX TO BOT OF

DISPENSER.

TP TOILET PAPER DISPENSER, RE: SPEC 102800. MOUNTING HEIGHT - 15" MIN TO

OUTLET ABOVE FINISH FLOOR

VGB VERTICAL GRAB BAR, RE: SPEC 102800. INSTALL ALL GRAB BARS PER ANSI

HANDICAP ACCESSIBILITY STANDARDS. MOUNTING HEIGHT - 39" - 41" TO

BOTTOM A.F.F..

UG UNDER LAVATORY GAURD, RE: SPECIFICATIONS.

ENLARGED TOILET PLAN LEGEND:

TP

GB

SD

VGB

38"

18"

42"

GB

VGB

A B

C D

NORTH EAST

SOUTH WEST

MU1

UG

PTD

C

L

C

L

1'-0"1'-0"1'-0"

18"

42"

A

GB

VGB

TP

GB

SD

VGB

38"

B

C D

NORTH EAST

SOUTH WEST

MU1

UG

PTD

C

L

C

L

1'-0"1'-0" 2'-10"

DIM# MOUNTING HEIGHT

FIXTURE

GRAB BAR

URINAL

TOILET (ADA)

URINAL (ADA)

SINK (ADA)

TOILET

TOILET (ADA)

GRAB BAR (ADA)

TOILET PAPER HOLDER

GRAB BAR

GRAB BAR

GRAB BAR

MIRROR

TOILET PAPER HOLDER

TOILET PAPER HOLDER

SINK (ADA)

SINK (ADA)

A

B

C

C

D

E

F

G

G

H

J

K

L

M

N

O

P

18" VERTICAL GRAB BAR

18" VERTICAL GRAB BAR

Q

R

6" TO CENTER FROM ADJACENT WALL

18" TO CENTER FROM ADJACENT WALL

24" TO RIM ABOVE FINISH FLOOR

17" TO RIM ABOVE FINISH FLOOR

34" MAX TO SINK RIM ABOVE FINISH FLOOR

9" HIGH X 6" DEEP TOE CLEARANCE

27" MIN X 8" DEEP KNEE CLEARANCE

14" TO TOP OF SEAT

17" - 19" TOP OF SEAT

12" TO CENTER FROM ADJACENT WALL

7" - 9" TO CENTERLINE FROM TOILET

33" - 36" TO TOP A.F.F.

36" OUTSIDE TO OUTSIDE

42" OUTSIDE TO OUTSIDE

40" MAX TO BOT OF MIRROR SURFACE

19" MIN. TO CENTER ABOVE FINISH FLOOR

1…