12639519R0011-0003.pdf
PDF 2 MB Posted
- Attached to
- Safety & Health Upgrades, Pocatello Supply Depot
- Solicitation number
- 12639519R0011
About this file
Amendment to incorporate Addendum 1 to solicitation
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 12639519R0011-0006.pdf | ||
| 12639519R0011-0005.pdf | ||
| 12639519R0011-0004.pdf | ||
| Offeror_questions_and_responses_USDAPocatello_5_21_19.pdf | ||
| Site_visit_attendees;_contact_list.docx | DOCX document | |
| 12639519R0011-0002.pdf | ||
| 12639519R0011-0001.pdf | ||
| Specifications.pdf | ||
| USDA_Sustainable_Buildings_Implementation_Plan.doc | DOC document | |
| All_Green_Products.xls | XLS spreadsheet | |
| Drawings.pdf | ||
| 12639519R0011.pdf | ||
| DOL_Wage_Determination_ID35.pdf |
Show all 13
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
(x)
12639519R0011 x x copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted ; or (c) By separate letter or telegram which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGEMENT TO BE RECEIVED AT
THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY RESULT IN REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted , such change may be made by telegram or letter, provided each telegram or letter makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.
x
APHIS-MN-126395
MINNEAPOLIS MN 55401
SUITE410
250 MARQUETTE AVE
USDA APHIS
05/21/20190003
13. THIS ITEM ONLY APPLIES TO MODIFICATION OF CONTRACTS/ORDERS. IT MODIFIES THE CONTRACT/ORDER NO. AS DESCRIBED IN ITEM 14.
12. ACCOUNTING AND APPROPRIATION DATA (If required) is not extended.is extended, Items 8 and 15, and returning
Offers must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended , by one of the following methods: (a) By completing
The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offers
11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS
FACILITY CODE CODE
10B. DATED (SEE ITEM 13)
10A. MODIFICATION OF CONTRACT/ORDER NO.
9B. DATED (SEE ITEM 11)
9A. AMENDMENT OF SOLICITATION NO.
CODE
8. NAME AND ADDRESS OF CONTRACTOR (No., street, county, State and ZIP Code)
7. ADMINISTERED BY (If other than Item 6)CODE 6. ISSUED BY
PAGE OF PAGES
4. REQUISITION/PURCHASE REQ. NO.3. EFFECTIVE DATE2. AMENDMENT/MODIFICATION NO. 5. PROJECT NO. (If applicable)
1. CONTRACT ID CODE
AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT
04/26/2019
CHECK ONE A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE CONTRACT
B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES (such as changes in paying office, C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:
D. OTHER (Specify type of modification and authority) appropriation date, etc.) SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(b).
E. IMPORTANT: Contractor is not, is required to sign this document and return __________________ copies to the issuing office.
ORDER NO. IN ITEM 10A.
14. DESCRIPTION OF AMENDMENT/MODIFICATION (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)
Tax ID Number: Not Available
DUNS Number: Not Available
This amendment is written to incorporate Addendum No. 1 (pages 2-5 of this amendment) into the solicitation.
16A. NAME AND TITLE OF CONTRACTING OFFICER (Type or print)15A. NAME AND TITLE OF SIGNER (Type or print)
15C. DATE SIGNED 16B. UNITED STATES OF AMERICA 15B. CONTRACTOR/OFFEROR 16C. DATE SIGNED
(Signature of person authorized to sign) (Signature of Contracting Officer)
JAMES G. ROLOFF
STANDARD FORM 30 (REV. 10-83)
Prescribed by GSA
FAR (48 CFR) 53.243
NSN 7540-01-152-8070
Previous edition unusable
Except as provided herein, all terms and conditions of the document referenced in Item 9 A or 10A, as heretofore changed, remains unchanged and in full force and effect .
05/21/2019
USDA_PSD1 Pocatello, ID
AD#1 - 1
http://www.ctagroup.com E-mail: info@ctagroup.com
ADDENDUM NO. 001
May 21st, 2019
To the plans and Specifications for: USDA Pocatello Supply Depot Renovations
Owner: United States Department of Agriculture
Architect: CTA Architects Engineers 800 Main St., Ste 800 Boise, Idaho 83702
NOTICE TO BIDDERS:
You are hereby notified of the following changes, deletions, corrections, additions, revisions, and/or modifications to the Plans and Specifications for the above-mentioned project, which are made a part thereof. You must acknowledge receipt of this Addendum to the Contractor on your Bid Proposal Form.
ATTACHMENTS:
Sheets: A-111, M-100 and M-104
DRAWINGS
Architectural
1. ADDED – A-111 – Sheet Notes 19, 20 and 21.
2. ADDED – 2/A-111 – Notes and locations for sheet notes 19 and 20.
3. ADDED – 3/A-111 – Notes and location for sheet notes 21.
Mechanical
1. REVISED - M100: Revise Bag In / Bag Out HEPA Filter Schedule to include all notes (1,2,3,4,5,6,7,8) instead of notes 1,2,3. Added note 6 to Exhaust Fan schedule.
2. REVISED – M104: Revised details 2/M104 to show ductwork sizes along with clarifying dampers needed.
3. ADDED – M100: general note 14: All equipment manufacturers are designated as “basis of design” unless indicated otherwise. Alternative manufacturers will be considered, but are subject to compliance with drawings and specifications.
END OF ADDENDUM NO. 001
Amendment 3, page 2; May 21, 2019
GENERAL NOTES:
A. MAINTAIN THE INTEGRITY OF ALL REMAINING BUILDING SYSTEMS AND RATINGS.
REPAIR ANY DAMAGE DONE TO SURROUNDING AREAS/CONSTRUCTION DURING
DEMOLITION.
B. ALL EXISTING CONDITIONS ARE NOT INDICATED ON THE DRAWINGS. CONTRACTOR
SHALL CAREFULLY EXAMINE THE EXISTING INSTALLATION AND ALL PROJECT
DRAWINGS TO BECOME FAMILIAR WITH THE SCOPE OF WORK.
C. CONTRACTOR SHALL PATCH AND REPAIR ANY DAMAGE OR PENETRATIONS AT ALL
ELEMENTS TO REMAIN (INCLUDING BUT NOT LIMITED TO WALLS, CEILINGS,
FLOORS, ETC.) CAUSED BY DEMOLITION ACTIVITIES OR REMOVAL OF ELECTRICAL,
MECHANICAL, AND ARCHITECTURAL ELEMENTS. REPLACE ITEMS NOT REPAIRABLE
TO ORIGINAL STATE. EXISTING FINISH MATERIALS, INCLUDING CEILINGS, TRIM,
ETC., SHALL BE PROTECTED AND RETAINED, UNLESS NOTED OTHERWISE.
D. PORTIONS OF THE BUILDING ARE TO REMAIN CONTINUOUSLY OCCUPIED
THROUGHOUT CONSTRUCTION. CONTRACTOR TO MAINTAIN CLEAR PATH OF
EGRESS THROUGHOUT CONSTRUCTION.
E. UNLESS NOTED OTHERWISE ALL DIMENSIONS ARE TO THE FACE OF STUD.
F. RE: A601 FOR DOOR TYPES, HARDWARE AND DETAILS.
G. RE: A801 FOR INTERIOR ELEVATIONS AND FIXTURE ACCESSIBILITY
REQUIREMENTS.
H. RE: A101 FOR OVERALL FLOOR PLANS.
1. RE: MECHANICAL AND ELECTRICAL DRAWINGS FOR WORK TO OCCUR IN THIS AREA.
2. SHOWER CONTROL WALL, RE: PLUMBING DRAWINGS.
3. SHOWER BENCH WALL, RE: SPECIFICATIONS. INSTALL BENCH PER MANUFACTURER
RECOMMENDATION.
4. WALL HUNG SINK AND ASSOCIATED MIRROR, RE: PLUMBING DRAWINGS AND A801.
5. TOILET PLUMBING FIXTURE, RE: PLUMBING DRAWINGS.
6. NEW BENCH RE: DETAILS ON A801.
7. EXISTING WALL MOUNTED COMMUNICATIONS EQUIPMENT ABOVE TO REMAIN, PROTECT ALL
ASSOCIATED ITEMS. DO NOT PAINT. VERIFY EXACT LOCATION IN FIELD.
8. RE-ROUTE EXISTING CONDUIT AS NECESSARY TO ACCOMMODATE NEW OPENING.
9. FACE OF GYPSUM CEILING, AND ASSOCIATED CEILING FRAMING TO BE 8'-0" ABOVE FINISH
FLOOR, PAINT PT1. RE: ELECTRICAL DRAWINGS FOR LIGHTING DETAILS.
10. FIBERGLASS SHOWER INSERT PER SPECIFICATIONS.
11. TILE TO CONCRETE FLOOR TRANSITION PER SPECIFICATIONS, RE: 4/A-111 FOR DETAILS.
12. MECHANICAL EQUIPMENT, RE: MECHANICAL DRAWINGS. RE: A601 FOR FURTHER DETAILS
13. NEW SLAB, S1, THROUGHOUT ENTIRETY OF AREA WHERE SLAB WAS REMOVED DURING
DEMOLITION. RE: DETAIL 4/A111. NEW SLAB TO RECEIVE TILE AND TILE COVE BASE
THROUGHOUT, INSTALL TILE PER MANUFACTURER INSTRUCTIONS AND RECOMMENDATIONS.
14. INSTALL ACCESSIBLE RESTROOM PANEL SIGNAGE PER DETAILS ON A801.
15. RE: MECHANICAL DRAWINGS FOR PIPING LOCATIONS. RE: A601 FOR THRU WALL
PENETRATION DETAILS.
16. NEW CONCRETE PAD FOR MECHANICAL EQUIPMENT. PAD TO BE SLAB TYPE 'S1'- NO VAPOR
BARRIER IS NEEDED AT THIS PAD LOCATION. REMOVE EXISTING ASPHALT AS NEEDED TO
ACCOMMODATE NEW PAD - PATCH EXISTING ASPHALT WHERE DAMAGE OCCURS.
17. FACE OF GYPSUM CEILING, AND ASSOCIATED CEILING FRAMING TO BE 9'-0" ABOVE FINISH
FLOOR, PAINT PT1. RE: ELECTRICAL DRAWINGS FOR LIGHTING DETAILS.
18. INSTALL STEEL FRAMING AROUND OPENING PER DETAILS ON A-601 - STEEL FRAMING TO BE
PAINTED TO MATCH DOOR FRAMES.
19. FURR OUT WALLS NOTED WITH
" HAT CHANNELS AND
" MOISTURE RESISTANT GYPSUM
WALL BOARD. USE HAT CHANNELS TO CREATE FLUSH WALL PLANE AND UNIFORMITY. FURR
OUT TO OCCUR FROM FLOOR TO 6" INCHES ABOVE CEILING. FRAME AROUND WHERE
EXISTING WINDOWS OCCUR.
20. FURR OUT EXISTING WALL SO FINISH FACE OF GYPSUM ALIGNS WITH EXISTING FACE OF THE
CONCRETE COLUMN. FURR OUT WITH METAL STUDS AND
" MOISTURE RESISTANT GYPSUM
WALLBOARD.
21. PROVIDE ACCESS PANEL IN GYPSUM CEILING. PROVIDE FLUSH ACCESS DOOR WITH
EXPOSED FLANGES AND CONCEALED HINGE - SIZE AS REQUIRED FOR
MECHANICAL/PLUMBING ACCESS. UNCOATED 16 GAGE STEEL SHEET DOOR FACTORY
PRIMED. LATCH AND LOCK TO BE CAM LATCH, SCREWDRIVER OPERATED.
SHEET NOTES:
LOCKERS
STORAGE
5 5
B
B
B102
R.R.
B101
R.R.
1'-0"
MIN.
1'-0"
MIN.
4"
A801
A
B
C
D
A801
A
B
C
D
5'-9"5'-9"
1919 1919
3'-11"
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
R.R.
R.R.
CLO.
R S
R L
4'-0"
LOCKERS
STORAGE
B101
R.R.
B102
R.R.
A801
(1) LAYER
" TYPE 'X' EA. SIDE
4" METAL STUD AT 16" O.C.
FIBER GLASS BLANKET INSULATION, FILL STUD CAVITY.
NOTE: USE MOISTURE RESISTANT GYPSUM WALL
BOARD ON ALL WET WALL, RE: A801 AND
SPECIFICATIONS.
WALL TYPES:
(1) LAYER
" TYPE 'X' EA. SIDE
(2)STAGGERED 6" METAL STUDS AT 16" O.C.
FIBER GLASS BLANKET
INSULATION, FILL STUD CAVITY
NOTE: USE MOISTURE RESISTANT GYPSUM WALL
BOARD ON ALL WET WALLS, RE: A801 AND
SPECIFICATIONS.
VAPOR BARRIER
4" COMPACTED GRAVEL FILL
4" CONCRETE SLAB
w/#3 @ 16”OC EA WAY
1½” CLR FROM TOP OF SLAB
NOTES:
Concrete shall be f'c = 4,500psi ASTM C150 TYPE I/II, Fly Ash
ASTM C615 Class C or F, W/C +Fly Ash ratio = 0.45 max, ¾” max normal weight aggregate.
Rebar shall be ASTM A615, Grade 60.
S1
SLAB TYPES:
FF ELEV
#4 x 2'-6" DOWEL w/ 6" EMBED
SET IN EPOXY @ 16" OC
(N) CONC SLAB ON
GRADE, SEE SLAB
TYPE AND FLOOR
PLAN
(E) CONC SLAB ON GRADE
E Q
E Q
DEPRESSED SLAB - FINISH
FACE OF TILE TO MATCH
TOP OF EXISTING SLAB
TILE FLOOR FINISH, RE: PLANS
AND SPECIFICATIONS
INTERIOR ELEVATION NUMBER /
SHEET WHERE DRAWN
F.E.F. FACE OF EXISTNG FINISH
DIMENSION TO FACE OF
STUD OR EXISTING WALL
DOOR NUMBER (SEE SHEET A101)
PLAN LEGEND
DETAIL OR SECTION NUMBER
SHEET WHERE DRAWN
PLAN NOTE
ROOM NAME
WALL TYPE
WALL TYPE NOTE
X
X
X
A101
A801
A
B
C
D
101-1
A111
ENLARGED FLOOR PLAN BASEMENT RESTROOMS
1/4"=1'-0"
06.11.18 06:12 PM | G:\USDAAPHIS_PSD1\BIMCAD\Arch\A-111.dwg
A111
PACKAGE #2 -
ENLARGED
PLANS
BID ADDENDUM 001 - 5.20.19
JC
SR
A111
ENLARGED FLOOR PLAN OFFICES
1/4"=1'-0"
DRAWN BY |
REVISIONS
© | ALL RIGHTS RESERVED
w w w . c t a g r o u p . c o m
8 0 0 . 7 5 7 . 9 5 2 2
CHECKED BY |
U S
D A
P H
I S
P S
D
R
E N
O V
A T
I O
N S
P O
C A
T E
L L
O
I D
A H
O
100% CD
3.27.19
N O
T
F
O R
C
N
S T
R U
C T
I O
N
P
R E
L I M
I N
A R
Y
D
E S
I G
N
A111
ENLARGED CEILING PLAN BASEMENT RESTROOMS
1/4"=1'-0"
A111
EXISTING SLAB TO NEW SLAB CONNECTION DETAIL
1/4"=1'-0"
Amendment 3, page 3; May 21, 2019
MECHANICAL LEGEND
CONDENSATE DRAIN
HOT WATER
COLD WATER
HARD COLD WATER
REFRIGERANT LIQUID/SUCTION LINES
GATE VALVE
BALL VALVE
BUTTERFLY VALVE
GLOBE VALVE
TRIPLE DUTY VALVE
SWING CHECK VALVE
STRAINER
FLEX CONNECTOR
HOSE END DRAIN VALVE
PRESSURE REDUCING VA.
SAFETY RELIEF VALVE
UNION
MOTORIZED T.C. VA/2-WAY
MOTORIZED T.C. VA/3-WAY
ECCENTRIC PLUG BALANCING VALVE
VALVE IN RISER
TEE UP
TEE DOWN
ELBOW UP
ELBOW DOWN
PIPE SIZE CHANGE
MANUAL FLOW BALANCING VALVE
(CIRCUIT SETTER)
AUTOMATIC FLOW BALANCING VALVE
DIAL THERMOMETER
PRESSURE GAUGE W/ SNUBBER
P
T
A
M
RLS
HARD
CW
HW
CD ELECTRIC THERMOSTAT
ELECTRIC THERMOSTAT W/GUARD
ACOUSTICALLY LINED SHEET
METAL DUCT
MANUAL BALANCING DAMPER
FLEX CONNECTOR
ACCESS DOORS
TURNING VANE ELL
45° LOW-LOSS TAKE-OFF FITTING W/
DAMPER & FLEX DUCT
45° LOW-LOSS TAKE-OFF FITTING W/
DAMPER & RIGID ROUND DUCT
90° TEE TAKE-OFF FITTING
CONICAL 90° TEE TAKE-OFF FITTING
45° TEE TAKE-OFF FIITTING
45°-90° TEE TAKE-OFF FITTING
SUPPLY AIR DUCT (SINGLE LINE)
RETURN AIR DUCT (SINGLE LINE)
EXHAUST AIR DUCT (SINGLE LINE)
DIFFUSER, REGISTER, OR GRILLE THROW
PATTERN SHOWN ON DWGS.
CONNECT NEW WORK TO EXISTING
SD-1 (PLAN CODE)
8x8 (NECK SIZE)
200 (CFM)
AD
AD
T
T
SA
RA
EA
SYMBOL DESCRIPTION SYMBOL DESCRIPTION
HVAC ABBREVIATIONS
AFF ABOVE FINISHED FLOOR
ACFM ACTUAL CFM
AHU AIR HANDLING UNIT
ANSI AMERICAN NATIONAL STANDARDS INSTITUTE
AMP AMPERE (AMP,AMPS)
APD AIR PRESSURE DROP
APPROX APPROXIMATE
BHP BRAKE HORSEPOWER, BOILER HORSEPOWER
BTU BRITISH THERMAL UNIT
MBH BTU PER HOUR (THOUSAND)
CU FT CUBIC FEET
CU IN CUBIC INCH
CFM CUBIC FEET PER MINUTE
SCFM CFM, STANDARD CONDITIONS
DB DECIBEL
DIA, Ø DIAMETER
ID DIAMETER, INSIDE
OD DIAMETER, OUTSIDE
DBT DRY-BULB TEMPERATURE
EAT ENTERING AIR TEMPERATURE
E.C. ELECTRICAL CONTRACTOR
EDR EQUIVALENT DIRECT RADIATION
EXP EXPANSION
EWT ENTERING WATER TEMPERATURE
F FAHRENHEIT
FPM FEET PER MINUTE
FPS FEET PER SECOND
FT FOOT OR FEET
HZ FREQUENCY
GA GAGE OR GAUGE
GAL GALLONS
G.C. GENERAL CONTRACTOR
GPH GALLONS PER HOUR
GPM GALLONS PER MINUTE
GPD GALLONS PER DAY
HD HEAD
HGT HEIGHT
HP HORSEPOWER
RH HUMIDITY, RELATIVE
KW KILOWATT
KWH KILOWATT HOUR
LAT LEAVING AIR TEMPERATURE
LWT LEAVING WATER TEMPERATURE
LF LINEAR FEET
MAX MAXIMUM
M.C. MECHANICAL CONTRACTOR
MIN MINIMUM
N O NORMALLY OPEN
N C NORMALLY CLOSED
N/A NOT APPLICABLE
NIC NOT IN CONTRACT
NTS NOT TO SCALE
NO NUMBER
OBD OPPOSED BLADE DAMPER
OA OUTSIDE AIR
% PERCENT
PH PHASE(ELECTRICAL)
LBS POUNDS
PSI POUNDS PER SQUARE INCH
PSIA PSI ABSOLUTE
PD PRESSURE DROP OR DIFFERENCE
PSIG PSI GAUGE
R/O RUN OUT
RH RELATIVE HUMIDITY
RA RETURN AIR
RPM REVOLUTIONS PER MINUTE
SH SENSIBLE HEAT
SPEC SPECIFICATION
SP VOL SPECIFIC VOLUME
STD STANDARD
SP STATIC PRESSURE
SUCT SUCTION
SA SUPPLY AIR
TEMP TEMPERATURE
TD TEMPERATURE DIFFERENCE
T STAT THERMOSTAT
TONS TONS OF REFRIGERATION
T.C. TEMPERATURE CONTROL
VAC VACUUM
VAV VARIABLE AIR VOLUME
VEL VELOCITY
V VOLT
VOL VOLUME
VFD VARIBLE FREQUENCY DRIVE
WPD WATER PRESSURE DROP
W/ WITH
EXISTING
(E)
1. THIS CONTRACTOR SHALL BE AWARE THAT THIS IS A REMODELING PROJECT AND AS SUCH, CERTAIN
ITEMS AND SIZES CANNOT BE FULLY ILLUSTRATED NOR EXPLAINED WITHOUT FIELD OBSERVATION.
THEREFORE, THIS CONTRACTOR IS ADVISED TO VISIT AND EXAMINE THE JOB SITE AND BUILDING IN
EVERY DETAIL AS PERTAINS TO THIS PROJECT AND MAKE ALLOWANCES IN HIS PROPOSAL FOR ALL
CONDITIONS THAT WILL AFFECT THE WORK INDICATED IN THE PROJECT SPECIFICATIONS AND
CONTRACT DRAWINGS.
2. ALL REMOVED ITEMS, EXCEPT THOSE NOTED TO BE REUSED OR TO REMAIN THE PROPERTY OF THE
OWNER, SHALL BECOME PROPERTY OF THE CONTRACTOR AND SHALL BE REMOVED FROM THE JOB
SITE. THE OWNER RESERVES THE RIGHT TO KEEP ANY REMOVED ITEMS EVEN THOUGH NOT NOTED ON
DRAWINGS.
3. WHERE EXISTING EQUIPMENT, DUCTS, PIPES ETC. ARE TO BE REMOVED, SUCH REMOVAL SHALL
INCLUDE ALL ANCHORS, BASES, HANGERS, ETC.
4. THIS CONTRACTOR MUST MEET WITH THE OWNER OR HIS REPRESENTATIVE AND DISCUSS THE
PROPOSED WORK SCHEDULE FOR REMOVAL, AND REMODELED WORK WITHIN CONTRACT DRAWINGS
PRIOR TO PERFORMING ANY WORK. THE CONTRACTOR SHALL INFORM THE OWNER OR HIS
REPRESENTATIVE, OF THE INTENT TO DO SO AT LEAST 48 HOURS BEFORE SUCH WORK BEGINS.
5. THIS CONTRACTOR SHALL PERFORM ALL CUTTING AND PATCHING REQUIRED.
6. HAZARDOUS MATERIALS, SUCH AS CYANIDE, STRYCHNINE, ZINC PHOSHPIDE, AND SODIUM NITRATE
MAY BE PRESENT IN DUCTWORK OR OTHER HVAC COMPONENTS. COMPLY WITH ALL OSHA SAFETY
STANDARDS FOR DEMOLITION, CONTAINMENT, AND DISPOSAL OF MATERIALS.
DEMO GENERAL NOTES:
GENERAL NOTES:
1. COORDINATE INSTALLATION OF DUCTWORK WITH STRUCTURAL
COMPONENTS AND OTHER SYSTEM INSTALLATIONS. GENERAL
CONTRACTOR TO SAW CUT AND CORE DRILL, PATCH AND REPAIR
SURFACES AS REQUIRED.
2. COORDINATE EXACT LOCATION OF DIFFUSERS AND GRILLES WITH
ARCHITECTURAL REFLECTED CEILING PLANS.
3. ALL DUCT DIMENSIONS SHOWN ARE INTERIOR DIMENSIONS.
4. COORDINATE LOCATION OF HVAC EQUIPMENT WITH ALL OTHER TRADES
TO MAINTAIN ACCESS AND SERVICE CLEARANCES.
5. PROVIDE ALL SEISMIC RESTRAINTS REQUIRED BY CODE, FOR ALL
EQUIPMENT, DUCT, PIPE, AND MATERIALS FURNISHED UNDER THIS
SECTION.
6. THE WORK INSTALLED UNDER THIS SECTION SHALL CONFORM TO ALL
APPLICABLE LOCAL CODES, REGULATIONS, AND STANDARDS.
7. THE DRAWINGS PROVIDED ARE SCHEMATIC IN NATURE. ABSOLUTE ACCURACY OF
THE DRAWINGS AND SPECIFICATIONS CAN NOT BE GUARANTEED. WHILE
REASONABLE EFFORT HAS BEEN MADE TO COORDINATE THE LOCATION OF
EQUIPMENT AND MATERIALS WITH THE STRUCTURE AND OTHER TRADES, IT IS
THE RESPONSIBILITY OF THE CONTRACTOR TO COORDINATE EXACT
REQUIREMENTS AND LOCATIONS AS GOVERNED BY ACTUAL JOB CONDITIONS.
8. INSULATE DUCTWORK PER INTERNATIONAL ENERGY CODE 2012.
9. FABRICATE AND INSTALL THE DUCT IN ACCORDANCE WITH SMACNA HVAC
DUCT CONSTRUCTION STANDARDS METAL AND FLEXIBLE.
10.PROVIDE ALL NECESSARY TRANSITIONS AND ADDITIONAL FITTINGS AS
REQUIRED TO CLEAR OBSTRUCTIONS, MAINTAIN CLEARANCES, AND
COORDINATE WITH OTHER TRADES AT NO EXTRA COST TO THE OWNER.
11.CONTRACTOR SHALL BE RESPONSIBLE FOR PROPER OPERATION OF ALL
SYSTEMS, MINOR SUBSYSTEMS, AND SERVICES PROVIDED UNDER THIS
DIVISION.
12.LOCATE ALL MANUAL BALANCE DAMPERS IN ACCESSIBLE AREAS EITHER
ABOVE ACOUSTICAL CEILING GRID OR IN ACCESSIBLE ATTIC AREA.
13. MOUNT THERMOSTATS AND HUMIDISTATS AT 54" A.F.F. UNLESS
OTHERWISE NOTED.
14. ALL EQUIPMENT MANUFACTURERS ARE DESIGNATED AS "BASIS OF
DESIGN" UNLESS INDICATED OTHERWISE. ALTERNATIVE MANUFACTURERS
WILL BE CONSIDERED, BUT ARE SUBJECT TO COMPLIANCE WITH
DRAWINGS AND SPECIFICATIONS.
MAKEUP AIR UNIT SCHEDULE
BASIS OF
DESIGN
MODEL TYPE
SUPPLY FAN HEATING SECTION EVAPORATIVE COOLING WEIGHT
NOTES
PLAN AREA POWER
MCA MOCP
CODE SERVED
(V/PH/HZ)
DESIGN ESP MOTOR FAN SPEED SYSTEM
FUEL
INPUT OUTPUT
MEDIA
EAT DB/WB
(F)
LAT
DB/WB (F)
UNIT
(CFM) (IN W.G.) (HP) (RPM)
TYPE
(MBH) (MBH) (LBS)
MAU-1 MIXING ROOM GREENHECK IGX-112-H22 INDOOR 230/3/60 23 35
5,000
1.5 5 1,725
INDIRECT GAS NG 488.8 391.1 CELDEK 95/62 64.9/64.9 2266
1,2,3,4,5,6,7,8,9,10,11
SCHEDULE NOTES:
1. EVAP COOLING AUTOMATIC DRAIN AND FILL WITH FREEZE PROTECTION. PROVIDE WATER AND DRAIN VALVES SHIPPED LOOSE. PROVIDE CELDEK EVAP COOLING MEDIA. COORDINATE WITH PLUMBING FOR WATER AND DRAIN CONNECTIONS.
2. UNIT IS SELECTED AT AN ELEVATION OF 4,500 FT ABOVE SEA LEVEL.
3. PROVIDE UNIT WITH ELECTRONIC MODULATION BURNER CONTROLS.
4. MOTORIZED INLET AIR DAMPER.
5. CONSTANT VOLUME FAN. INTERLOCK WITH EF-3.
6. PROVIDE WITH REMOTE CONTROL PANEL WITH TEMPERATURE CONTROL, FILTERS DIRTY, STARTERS.
7. PROVIDE UNIT WITH INLET AIR SENSOR
8. PROVIDE UNIT WITH FREEZE PROTECTION DRAIN CONTROL KIT FOR EVAPORATIVE COOLERS.
9. WINTER DESIGN CONDITIONS - 5F AND SUMMER DESIGN CONDITIONS - 91F DB / 63F WB.
10. PROVIDE MAU WITH DISCONNECT.
11. PROVIDE WITH FACTORY MOUNTED SKID AND INTERNALLY ISOLATED COMPONENTS.
VENTILATION HOOD SCHEDULE
PLAN
BASIS OF
DESIGN
MODEL NO. TYPE LENGTH
WIDTH HEIGHT
CFM
OUTLET OUTLET CONNECTED
MOUNTING NOTES:
CODE
(IN) (IN) SIZE (IN)
S.P. MAX. EXHAUST FAN
H-1 LABCONCO PROTECTOR PREMIER XL VENTILATION 96 in 32.0 59 1640 2 X 12Ø 0.3 EF-1 STAND 1
H-2 MONOXIVENT CUSTOM SLOTTED BENCH 72 in 6.0 70 5500 18Ø 0.6 EF-3 TOP OF COUNTER 2
SH-1 MONOXIVENT 15078-TT SNORKEL 7 ft - - 875 8Ø 1.2 EF-4 WALL MOUNT 3
SH-2 MONOXIVENT 15076-TT SNORKEL 7 ft - - 500 6Ø 1.9 EF-5 WALL MOUNT 3
SCHEDULE NOTES:
1. PROVIDE WITH TELESCOPING BASE STAND SET TO 34" IN HEIGHT, CATALOG NUMBER 3857300, STAINLESS STEEL WORK SURFACE, T8 LIGHT FIXTURE WITH INTEGRAL SWITCH.
2. PROVIDE WITH BLAST GATE AND WALL BRACKETS. SEE DETAIL 1/M104 FOR DETAILED DIMENSIONS AND REQUIREMENTS.
3. PROVIDE HOSE WITH LAMINATED PTFE HOSE WALL, GALVANIZED STEEL EXTERNAL HELIX, AND SERIES 15000-TT TUBE TYPE ARM WALL BRACKET.
DIFFUSER, REGISTER & GRILLE SCHEDULE
PLAN
BASIS OF
DESIGN
MODEL
FACE
NECK SIZE MATERIAL
COLOR/
MOUNTING NOTES
CODE SIZE FINISH
SD-1 TITUS 300RL 18"x6" - STEEL WHITE DUCT 1
SD-2 TITUS 300RL 10"x6" - STEEL WHITE DUCT 1
SCHEDULE NOTES:
1. PROVIDE DUCT MOUNTING HARDWARE
ROOFTOP UNIT SCHEDULE
BASIS OF DESIGN SIZE FLA
FAN SECTION HEATING SECTION DEHUMIDIFICATION SECTION FILTER SECTION WEIGHT
NOTES
PLAN AREA POWER
CODE SERVED
(V/PH/HZ)
TYPE
AIRFLOW MIN. OSA DESIGN ESP MOTOR FAN SPEED SYSTEM
FUEL
INPUT OUTPUT
DESSIANT
MODEL
DESSICANT CAPACITY
REACT. HEATER
QTY / MODEL
INPUT
TYPE NUMBER / SIZE
UNIT
(CFM) (CFM) (INCHES W.G.) (HP) (RPM)
TYPE
(MBH) (MBH)
TYPE
(LB/H) (MBH) (LBS)
RTU-1 CYANIDE ROOM MUNTERS ICA-0750-020-G 17 230/3/60 39.4 SWSI AIRFOIL
2,400 1,120
7.58 7.5 3,450
INDIRECT NG 200 160 ICA-750 TIGEL 73.3 2 / HPG-200 200.6 MERV 8
1 / 12x24, 1 / 24x24
1,2,3,4,5,6,7,8,9,10
CONDENSING UNIT / COOLING COILS
PLAN
CODE
BASIS OF DESIGN
PRE-COOLING POST-COOLING
REF. TYPE ROWS / FPI
FIN MATERIAL / TUBE
MATERIAL
CAPACITY CAPACITY POWER FLA MCA WEIGHT
(MBH) (MBH) (V/PH/HZ) (AMPS) (AMPS) (LBS)
CU-1 ICS 20ACCUD-460 98 110 230/3/60 103 125 3800 R404A 6 / 11 ALUMINUM / COPPER
PERFORMANCE
PLAN
WINTER DESIGN °F (DB) SUMMER DESIGN °F (DB / GR/LB) DEHUMIDIFICATION DESIGN °F (DB / GR/LB)
CODE EAT POST HEAT EAT PRECOOL DEHUMID POST COOL EAT PRECOOL DEHUMID POST COOL
RTU-1 -5 80.0 95 / 45.4 49 / 45.4 84 / 14.9 59 / 14.9 71 / 87.2 50 / 62.3 100 / 9.3 59 / 9.3
SCHEDULE NOTES:
1. UNITS SELECTED AT 4,500 FT ABOVE SEA LEVEL, 95°F DB / 62F WB SUMMER DESIGN TEMP, -5°F WINTER DESIGN TEMP, 72F DB / 59°F DEW POINT DESIGN DEHUMIDIFICATION CONDITIONS.
2. COORDINATE INSTALLATION WITH EXISTING STRUCTURE.
3. PROVIDE ALL SERVICE CLEARANCES REQUIRED.
4. UNIT IS A BUILT UP AIR HANDLER WITH PRE-COOL, DESSICANT, POST-COOL, AND HEATING SECTION. DESSICANT PORTION INCLUDES 652 CFM REACTIVATION FAN AND NATURAL GAS REACTIVATION HEAT.
5. PROVIDE WITH REMOTE MOUNTED SIEMENS S7-1200 CONTROLLER, KTP400, COLOR TOUCH HMI PACKAGE, FUSED DISCONNECT, FACTORY MOUNTED CONTROL ENCLOSURE, FILTER PRESSURE DIFFERENTIAL SWITCH.
6. CONFIGURE UNIT FOR END AIR DISCHARGE.
7. PROVIDE WITH MOTORIZED OUTSIDE AIR DAMPER AND ACTUATOR TO OPEN WHEN UNIT IS ENABLED.
8. PROVIDE RTU AND CU WITH ELECTRICAL DISCONNECT.
9. PROVIDE A 120V CONVENIENCE OUTLET WITH RTU-1.
10. PROVIDE UNITS WITH STRUCTURAL SKID TO BE MOUNTED TO EXISTING STRUCTURAL MEMBERS ON ROOF.
EMERGENCY EYEWASH SCHEDULE
PLAN FIXTURE
NOTES
CODE ITEM BASIS OF DESIGN MODEL TYPE FLOW RATE MATERIAL COLOR/FINISH
EEW-1 EMERGENCY EYE WASH HAWS 7500
WALL MOUNT, PORTABLE
0.4 GPM POLYETHYLENE GREEN 1
SCHEDULE NOTES:
1. PROVIDE WITH MODEL 9009 20 GALLON WASTE CONTAINER.
WALL LOUVER SCHEDULE
PLAN
BASIS OF DESIGN SERVICE
WIDTH x HEIGHT
CFM
MAX APD
MATERIAL NOTES
CODE
(IN) (IN W.C.)
LV-1 RUSKIN ELF375DX EF-5 18"x18" 500 0.1 EXTRUDED ALUMINUM 1, 2, 3
LV-2 RUSKIN ELF375DX FUSE STORAGE 36"x18" 345 0.1 EXTRUDED ALUMINUM 1, 2, 3
SCHEDULE NOTES
1. PROVIDE WITH BIRDSCREEN.
2. PROVIDE WITH GRAVITY BACKDRAFT DAMPER.
3. PROVIDE PAINT COLOR PALETTE WITH SUBMITTAL FOR ARCHITECT'S SELECTION.
BAG IN / BAG OUT HEPA FILTER SCHEDULE
PLAN CODE BASIS OF DESIGN SERVES CFM
INTAKE BOX SIZE
TYPE
FILTER SIZE PRESSURE DROP (IN W.C.)
WEIGHT
(LBS)
NOTES
WIDTH HEIGHT LENGTH WxHxTHICKNESS PRE-FILTER HEPA FILTER
FB-1
AAF | FLANDERS
BF1-1H2W EF-1 1640 31 30 37.5 MERV 8 / HEPA 24x24x2 / 24x24x12 0.5 1 510
1,2,3,4,5,6,7,8
FB-2
AAF | FLANDERS
BF1-1H2W EF-2 1715 31 30 37.5 MERV 8 / HEPA 24x24x2 / 24x24x12 0.5 1 510
1,2,3,4,5,6,7,8
SCHEDULE NOTES:
1. PROVIDE WITH BF1-1H2W-2GGF-304-D3 HOUSING SECTION, MOUNTING BASE, LIFTING LUG, AND GAGE PANEL FOR PRESSURE DROP ACROSS EACH FILTER.
2. PROVIDE FILTER BOX WITH LEFT SIDE DOOR ACCESS AND COORDINATE EXACT LOCATION AND CLEARANCES ON SITE.
3. FILTER BOX SHALL BE EQUIPPED WITH A FLUID SEAL FILTER CLAMING MECHANISM OPERATED BY A LOCKING HANDLE.
4. THE HOUSING SHALL BE EQUPPED WITH A BAG-OUT RING AROUND EACH FILTER ACCESS PORT.
5. THE HOUSING SHALL BE CONSTRUCTED OF T-304 11 AND 14 GAUGE STAINLESS STEEL SHEET METAL WITH CONTINUOUSLY WELDED RETAINING JOINTS.
6. WEATHER CAPS SHALL BE CONSTRUCTED FROM 14 GAUGE STAINLESS STEEL SHEET METAL AND INSTALLED TO PREVENT THE ACCUMULATION OF WATER AND DEBRIS.
7. THE FILTER SYSTEM SHALL BE TESTED IN ACCORDANCE WITH ANSI/ASME NQA-1.
8 THE OVERALL SYSTEM AND FILTER SEALING SURFACE SHALL BE LEAK TESTED BY THE "PRESSURE DECAY" METHOD IN ACCORDANCE WITH AG-1, 2012 MANDATORY APPENDIX TA-III, ARTICLE TAA-III-4200 AND HAVE A MAXIMUM LEAK RATE OF 0.0005 CFM PER CUBIC FOOR OF HOUSING FOR 15 MINUTES.
POWER VENTILATOR SCHEDULE
PLAN
CODE
TYPE LOCATION SERVES
BASIS OF DESIGN
DRIVE CFM
E.S.P. MOTOR POWER
WEIGHT(LBS)
NOTES:
MFGR MODEL
(IN)
HP
(V/PH/HZ)
EF-1 UTILITY ROOF CYANIDE VENT HOOD GREENHECK FJC-212-BI-X BELT
1,200
2.50 1 230/3/60 231 1,3,4,6
EF-2 UTILITY ROOF CYANIDE GRINDER/MIXER GREENHECK FJC-212-BI-X BELT
1,715
2.50 1 1/2 230/3/60 278 1,3,4,6
EF-3 UTILITY MIXING MIXING ROOM HOOD GREENHECK FJI-18-BI-X BELT
5,500
2.00 5 230/3/60 231 1,3,6
EF-4 UTILITY ROOF CARTRIDGE ROOM HOODS GREENHECK FJI-15-BI-X BELT
3,500
2.50 3 230/3/60 190 1,5,6
EF-5 INLINE WAREHOUSE LABEL MAKER GREENHECK SQ-80-7 DIRECT 500 1.90 3/4 230/3/60 88 1,2,6
EF-6 UTILITY ROOF CARTRIDGE ROOM HOODS GREENHECK FJC-312-BI BELT
1,500
2.00 1 230/3/60 176 1,5,6
SCHEDULE NOTES:
1. FAN SELECTIONS ARE AT 4,500 FT ABOVE SEA LEVEL.
2. PROVIDE WITH BACKDRAFT DAMPER IN DUCT.
3. PROVIDE AND MOUNT ON EXISTING CURB.
4. PROVIDE WITH HEPA FILTER.
5. MOUNT ON EXISTING STRUCTURE ABOVE CYANIDE ROOM.
6. DESIGN FANS TO MEET LOCAL CONDITIONS AND ALL CODE REQUIREMENTS.
VENTILATION HOOD SCHEDULE
PLAN
BASIS OF
DESIGN
MODEL NO. TYPE LENGTH
WIDTH HEIGHT
CFM
OUTLET OUTLET CONNECTED
MOUNTING NOTES:
CODE
(IN) (IN) SIZE (IN)
S.P. MAX. EXHAUST FAN
H-1 LABCONCO PROTECTOR PREMIER XL VENTILATION 96 in 32.0 59 1640 2 X 12Ø 0.3 EF-1 STAND 1
H-2 MONOXIVENT CUSTOM SLOTTED BENCH 72 in 6.0 70 5500 18Ø 0.6 EF-3 TOP OF COUNTER 2
SH-1 MONOXIVENT 15078-TT SNORKEL 7 ft - - 875 8Ø 1.2 EF-4 WALL MOUNT 3
SH-2 MONOXIVENT 15076-TT SNORKEL 7 ft - - 500 6Ø 1.9 EF-5 WALL MOUNT 3
SCHEDULE NOTES:
1. PROVIDE WITH TELESCOPING BASE STAND SET TO 34" IN HEIGHT, CATALOG NUMBER 3857300, STAINLESS STEEL WORK SURFACE, T8 LIGHT FIXTURE WITH INTEGRAL SWITCH.
2. PROVIDE WITH BLAST GATE AND WALL BRACKETS. SEE DETAIL 1/M104 FOR DETAILED DIMENSIONS AND REQUIREMENTS.
3. PROVIDE HOSE WITH LAMINATED PTFE HOSE WALL, GALVANIZED STEEL EXTERNAL HELIX, AND SERIES 15000-TT TUBE TYPE ARM WALL BRACKET.
DRAWN BY |
REVISIONS
© | ALL RIGHTS RESERVED
w w w . c t a g r o u p . c o m
8 0 0 . 7 5 7 . 9 5 2 2
CHECKED BY |
U S
H
I S
P S
D
R
E N
O V
A T
I O
N S
P O
C A
T E
L L O
I D
A H
O
100% CD
3.27.19
N O
T
F
N
S T
R U
C T
I O
N
P
R E
L I M
I N
A R
Y
D
E S
I G
N
06.22.18 09:33 AM | G:\USDAAPHIS_PSD1\BIMCAD\Mech\M100.dwg
M100
PACKAGE 1 HVAC
SCHEDULES
BID ADDENDUM 001 - 5.20.19
RR
TJ
Amendment 3, page 4; May 21, 2019
M104
MIXING ROOM HOOD DETAIL
SCALE: NTS
EXISTING
DUCTWORK UP
THROUGH ROOF
UTILITY SET FAN DETAIL
SCALE: NTS
M104
T
Y P
DUCT UP TO EF-3
45° TAPER ANGLE
6"
" SLOT
18"Ø
ROOFTOP UNIT
GAS PIPE ON ROOF
6" CAPPED DRIP LEG
REDUCING BUSHING
IF EQUIPMENT INLET
SIZE IS SMALLER
THAN GAS LINE
UNION
GAS STOP
FLOOR OR ROOF
M104
RTU/MAU GAS CONNECTION DETAIL
NOT TO SCALE
CYANIDE ROOM SEQUENCE OF OPERATION
THE CYANIDE ROOM INCLUDES A ROOFTOP DEHUMIDIFICATION UNIT (RTU-1), CONDENSING UNIT (CU-1), AND TWO EXHAUST FANS (EF-1, EF-2) SERVING THE LAB HOOD AND GRINDER/MIXER, RESPECTIVELY.
THESE SYSTEMS ARE DESIGNED TO BY CONSTANT VOLUME WITH NO AIR RECIRCULATION.
RTU-1 AND CU-1 CONTROLS SHALL BE PACKAGED WITH THE UNIT AND INCLUDE A GRAPHICAL
INTERFACE, LOCATED IN THE SPACE, FOR ADJUSTING SETPOINTS, VIEWING ALARMS, AND
SCHEDULING SYSTEM OPERATION.
FAN CONTROL:
THE SUPPLY FAN AND EXHAUST FANS SHALL OPERATE CONTINUOUSLY WHEN ENABLED. THE
EXHAUST FANS (EF-1, EF-2) SHALL BE INTERLOCKED WITH RTU-1 SUCH THAT BOTH EXHAUST FANS AND
RTU-1 SHALL RUN CONTINUOUSLY WHENEVER AN EXHAUST FAN IS ENABLED. EXHAUST FANS SHALL BE
ENABLED WITH A MANUAL SWITCH LOCATED NEAR THE CORRESPONDING HOOD. EXHAUST FANS AND
RTU-1 SHOULD OPERATE CONTINUOUSLY WHEN CYANIDE IS PRESENT IN THE SPACE.
OUTSIDE AIR DAMPER CONTROL:
THE OUTSIDE AIR DAMPER ON RTU-1 SHALL REMAIN 100% OPEN WHEN THE UNIT IS RUNNING AND
CLOSE COMPLETELY WHEN UNIT IS DISABLED.
DISCHARGE AIR CONTROL:
RTU-1 IS DESIGNED TO PROVIDE HEATING, COOLING, AND DEHUMIDIFICATION. WHEN THERE IS NO
CALL FOR HEATING OR COOLING FROM THE SPACE THERMOSTAT, DISCHARGE AIR TEMPERATURE
SHALL FLOAT. UPON A CALL FOR COOLING AT THE SPACE THERMOSTAT, THE DISCHARGE AIR
TEMPERATURE SHALL BE RESET TO MINIMUM. UPON A CALL FOR HEATING, THE DISCHARGE AIR
TEMPERATURE SHALL BE RESET TO MAXIMUM.
WHEN RTU-1 IS ENABLED, TEMPERATURE AND SPACE HUMIDITY SETPOINTS SHALL BE MAINTAINED AT
70F AND 20% RH RESPECTIVELY. SHOULD THE SPACE CONDITIONS RISE ABOVE SETPOINT
(ADJUSTABLE), THE DESSICANT WHEEL SHALL BE ACTIVATED AND MAINTAIN A MAXIMUM SUPPLY AIR
MOISTURE CONTENT OF 15 GRAINS OF MOISTURE PER POUND OF DRY AIR. SUPPLY AIR MOISTURE
CONTENT SHALL BE MODULATED WITH FACE AND BYPASS DAMPERS AROUND THE DESICCANT WHEEL, INTERNAL TO THE UNIT, USING MANUFACTURER'S CONTROL SEQUENCES.
SAFETIES AND ALARMS:
THE DIFFERENTIAL PRESSURE SENSOR ACROSS THE FILTER BANK SHALL SEND AN ALARM TO THE
CONTROL PANEL WHEN THE DIFFERENTIAL PRESSURE EXCEEDS 2 INCHES W.C. (ADJUSTABLE).
IF THE SPACE HUMIDITY SENSOR EXCEEDS 20% RELATIVE HUMIDITY, AN ALARM SHALL BE GENERATED
AT THE UNIT CONTROLLER.
IF THE SUPPLY AIR TEMPERATURE DROPS BELOW 40 DEGREES F, AN ALARM SHALL BE GENERATED AT
THE UNIT CONTROLLER.
MIXING ROOM SEQUENCE OF OPERATION
THE MIXING ROOM INCLUDES A BENCH STYLE HOOD WITH EXHAUST FAN (EF-3) AND A MAKEUP AIR
UNIT (MAU-1). CONTROLS SHALL BE PACKAGED WITH MAU-1 AND INCLUDE A USER INTERFACE FOR
ADJUSTING SETPOINTS, VIEWING ALARMS, AND SCHEDULING SYSTEM OPERATION.
FAN CONTROL:
THE MAKEUP AIR UNIT AND EXHAUST FAN SHALL OPERATE CONTINUOUSLY WHEN ENABLED. THE
EXHAUST FAN SHALL BE INTERLOCKED WITH MAU-1 SUCH THAT MAU-1 IS ENABLED WHEN THE HOOD IS
SWITCHED ON.
OUTSIDE AIR DAMPER CONTROL:
THE OUTSIDE AIR DAMPER ON MAU-1 SHALL REMAIN 100% OPEN WHEN THE UNIT IS RUNNING AND
CLOSE COMPLETELY WHEN UNIT IS DISABLED.
DISCHARGE AIR CONTROL:
MAU-1 IS DESIGNED TO PROVIDE HEATING AND COOLING. THE UNIT SHALL BE CONFIGURED TO
MAINTAIN 70F DISCHARGE AIR TEMPERATURE, BUT SHALL BE EQUIPPED WITH THE OPTIONAL ROOM
OVERRIDE FUNCTION. THE UNIT SHALL STAGE NATURAL GAS HEAT AND EVAPORATIVE COOLING
SECTIONS TO MAINTAIN SETPOINT.
EVAPORATIVE COOLING:
MAU-1 SHALL BE EQUIPPED WITH A DRAIN/FILL VALVE CONTROLLED AT THE UNIT LCD INTERFACE. THE
EVAPORATIVE COOLING SECTION SHOULD BE DRAINED PRIOR TO FREEZING OUTDOOR AIR
TEMPERATURES.
SAFETIES AND ALARMS:
THE DIFFERENTIAL PRESSURE SENSOR ACROSS THE FILTER BANK SHALL SEND AN ALARM TO THE
CONTROL INTERFACE LOCATED IN THE SPACE WHEN THE DIFFERENTIAL PRESSURE EXCEEDS 2
INCHES W.C. (ADJUSTABLE).
IF THE SUPPLY AIR TEMPERATURE DROPS BELOW 40 DEGREES F, AN ALARM SHALL BE GENERATED AT
THE UNIT CONTROLLER.
CARTRIDGE ROOM SEQUENCE OF OPERATION
THE CARTRIDGE ROOM CURRENTLY CONSISTS OF FOUR EXHAUST HOOD SYSTEMS: 2 SNORKEL
HOODS WITH FANS, 1 SLOTTED BENCH HOOD, AND 1 CANOPY HOOD. THE SLOTTED BENCH HOOD WILL
REMAIN, BUT ALL OTHERS WILL BE DEMOLISHED AND REPLACED WITH A SINGLE EXHAUST PLENUM
WITH FOUR SNORKEL HOODS. SNORKEL HOODS ARE INTENDED TO MAINTAIN A CONSTANT FLOW RATE
WHEN EF-4 IS OPERATING.
A SINGLE EXISTING ROOFTOP UNIT (RTU-2) SERVES THIS SPACE. THE CONTRACTOR IS RESPONSIBLE
FOR ALL NECESSARY ADJUSTMENTS TO RE-BALANCE AND INTERLOCK THE NEW EXHAUST FAN (EF-4)
AND EXISTING BENCH HOOD ((E)EF-2) WITH EXISTING ((E)RTU-2) SUCH THAT THE SPACE MAINTAINS
NEGATIVE PRESSURE WHEN EXHAUST HOODS ARE ON AND MAINTAINS SPACE AND DISCHARGE
TEMPERATURES AS ORIGINALLY DESIGNED.
AIRFLOW RATES:
(E)EF-2 (BENCH HOOD) - 1,500 CFM
EF-4 (NEW SNORKEL HOODS) - 3,500 CFM (700 CFM EACH)
(E)RTU-2 - 4,500 CFM
(E)RTU-2 SEQUENCE
(E)RTU-2 OUTDOOR AIR QUANTITIES ARE CONTROLLED BY MOTORIZED RETURN AIR AND MIXED AIR
DAMPERS. WHEN EXHAUST FANS ARE RUNNING, THE RETURN AIR DAMPER SHALL CLOSE AND THE
OUTDOOR AIR DAMPER SHALL OPEN TO PROVIDE 4,500 CFM OUTDOOR AIR. WHEN EXHAUST FANS ARE
OFF, THE OUTDOOR AIR DAMPER SHALL MODULATE TO MINIMUM POSITION, CORRESPONDING TO 250
CFM OUTDOOR AIR, AND THE RETURN AIR DAMPER MODULATE TO MAXIMUM OPEN POSITION.
EXHAUST FAN INTERLOCKS
EF-4 AND (E)EF-6 SHALL BE INTERLOCKED SUCH THAT BOTH FANS RUN SIMULTANEOUSLY WHEN
SWITCHED ON.
NOTES:
1. CONSTRUCT HOOD WITH 18 GAUGE WELDED GALVANNEALED SHEET METAL.
2. PROVIDE BLAST GATE FOR BALANCING AND WALL BRACKETS FOR MOUNTING.
M104
MIXING ROOM EXHAUST DETAIL
SCALE: NTS
DOWN TO H-2
EF-3MOTOR
SEE ARCHITECTURAL
PLANS FOR WALL
CONSTRUCTION AND
PATCHING
LOUVER
BIRD SCREEN
SEAL ALL
AROUND
DRILL 1/4" WEEP
HOLES 12" O.C. IN
BOTTOM BLADE
OF LOUVER
BOTTOM FLASHING TO
BE CONTINUOUS THRU
WALL WITH NO JOINTS
DUCT INSULATION
WHEN SPECIFIED
CAULK CONNECTION
WATER TIGHT
ALL AROUND
M104
LOUVER INSTALLATION DETAIL
SCALE: NTS
1/4" X 1/4" WIRE MESH
BIRD SCREEN
OUTLET AT
10'-0 ABOVE TOP
OF RTU-1 INTAKE.
HEPA
FILTER
BOX
EF-1,2MOTOR
SQUARE TO ROUND
TRANSITION
BUBBLE TIGHT 304
STAINLESS STEEL
DAMPER
BUBBLE TIGHT 304
STAINLESS STEEL
DAMPER
GUYWIRE &
TURNBUCKLES
MIN 4 EA @ 120°
H-2
FB-1,2
EXISTING CURB
EXHAUST FAN
TO OVERHANG
EXISTING
CURB NO
MORE THAN 6
INCHES.
EXISTING PLATFORM
NO LOSS STACK
x
DRAWN BY |
REVISIONS
© | ALL RIGHTS RESERVED
w w w . c t a g r o u p . c o m
8 0 0 . 7 5 7 . 9 5 2 2
CHECKED BY |
U S
H
I S
P S
D
R
E N
O V
A T
I O
N S
P O
C A
T E
L L
O
I D
A H
O
100% CD
3.27.19
N O
T
F
N
S T
R U
C T
I O
N
P
R E
L I M
I N
A R
Y
D
E S
I G
N
06.20.18 03:54 PM | G:\USDAAPHIS_PSD1\BIMCAD\Mech\M104.dwg
M104
PACKAGE #1
HVAC DETAILS
AND CONTROLS
BID ADDENDUM 001 - 5.20.19
RR
TJ
Amendment 3, page 5; May 21, 2019
| Addendum No. 1_USDAPocatello_5_21_19.pdf |
| ADDENDUM NO.1_0 |
| ATTACHMENTS: |
| DRAWINGS |
| 1 |
| A-111 |
| M100 PACKAGE 1 HVAC SCHEDULES |
| M104 PACKAGE #1 HVAC DETAILS AND CONTROLS |
| M104-24x36 |