12639519R0011-0003.pdf

PDF 2 MB Posted

Attached to
Safety & Health Upgrades, Pocatello Supply Depot
Solicitation number
12639519R0011
Issued by

About this file

Amendment to incorporate Addendum 1 to solicitation

View the file

Other files

File Type Posted
12639519R0011-0006.pdf PDF
12639519R0011-0005.pdf PDF
12639519R0011-0004.pdf PDF
Offeror_questions_and_responses_USDAPocatello_5_21_19.pdf PDF
Site_visit_attendees;_contact_list.docx DOCX document
12639519R0011-0002.pdf PDF
12639519R0011-0001.pdf PDF
Specifications.pdf PDF
USDA_Sustainable_Buildings_Implementation_Plan.doc DOC document
All_Green_Products.xls XLS spreadsheet
Drawings.pdf PDF
12639519R0011.pdf PDF
DOL_Wage_Determination_ID35.pdf PDF
Show all 13

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

(x)

12639519R0011 x x copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted ; or (c) By separate letter or telegram which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGEMENT TO BE RECEIVED AT

THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY RESULT IN REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted , such change may be made by telegram or letter, provided each telegram or letter makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.

x

APHIS-MN-126395

MINNEAPOLIS MN 55401

SUITE410

250 MARQUETTE AVE

USDA APHIS

05/21/20190003

13. THIS ITEM ONLY APPLIES TO MODIFICATION OF CONTRACTS/ORDERS. IT MODIFIES THE CONTRACT/ORDER NO. AS DESCRIBED IN ITEM 14.

12. ACCOUNTING AND APPROPRIATION DATA (If required) is not extended.is extended, Items 8 and 15, and returning

Offers must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended , by one of the following methods: (a) By completing

The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offers

11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS

FACILITY CODE CODE

10B. DATED (SEE ITEM 13)

10A. MODIFICATION OF CONTRACT/ORDER NO.

9B. DATED (SEE ITEM 11)

9A. AMENDMENT OF SOLICITATION NO.

CODE

8. NAME AND ADDRESS OF CONTRACTOR (No., street, county, State and ZIP Code)

7. ADMINISTERED BY (If other than Item 6)CODE 6. ISSUED BY

PAGE OF PAGES

4. REQUISITION/PURCHASE REQ. NO.3. EFFECTIVE DATE2. AMENDMENT/MODIFICATION NO. 5. PROJECT NO. (If applicable)

1. CONTRACT ID CODE

AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT

04/26/2019

CHECK ONE A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE CONTRACT

B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES (such as changes in paying office, C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:

D. OTHER (Specify type of modification and authority) appropriation date, etc.) SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(b).

E. IMPORTANT: Contractor is not, is required to sign this document and return __________________ copies to the issuing office.

ORDER NO. IN ITEM 10A.

14. DESCRIPTION OF AMENDMENT/MODIFICATION (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)

Tax ID Number: Not Available

DUNS Number: Not Available

This amendment is written to incorporate Addendum No. 1 (pages 2-5 of this amendment) into the solicitation.

16A. NAME AND TITLE OF CONTRACTING OFFICER (Type or print)15A. NAME AND TITLE OF SIGNER (Type or print)

15C. DATE SIGNED 16B. UNITED STATES OF AMERICA 15B. CONTRACTOR/OFFEROR 16C. DATE SIGNED

(Signature of person authorized to sign) (Signature of Contracting Officer)

JAMES G. ROLOFF

STANDARD FORM 30 (REV. 10-83)

Prescribed by GSA

FAR (48 CFR) 53.243

NSN 7540-01-152-8070

Previous edition unusable

Except as provided herein, all terms and conditions of the document referenced in Item 9 A or 10A, as heretofore changed, remains unchanged and in full force and effect .

05/21/2019

USDA_PSD1 Pocatello, ID

AD#1 - 1

http://www.ctagroup.com E-mail: info@ctagroup.com

ADDENDUM NO. 001

May 21st, 2019

To the plans and Specifications for: USDA Pocatello Supply Depot Renovations

Owner: United States Department of Agriculture

Architect: CTA Architects Engineers 800 Main St., Ste 800 Boise, Idaho 83702

NOTICE TO BIDDERS:

You are hereby notified of the following changes, deletions, corrections, additions, revisions, and/or modifications to the Plans and Specifications for the above-mentioned project, which are made a part thereof. You must acknowledge receipt of this Addendum to the Contractor on your Bid Proposal Form.

ATTACHMENTS:

Sheets: A-111, M-100 and M-104

DRAWINGS

Architectural

1. ADDED – A-111 – Sheet Notes 19, 20 and 21.

2. ADDED – 2/A-111 – Notes and locations for sheet notes 19 and 20.

3. ADDED – 3/A-111 – Notes and location for sheet notes 21.

Mechanical

1. REVISED - M100: Revise Bag In / Bag Out HEPA Filter Schedule to include all notes (1,2,3,4,5,6,7,8) instead of notes 1,2,3. Added note 6 to Exhaust Fan schedule.

2. REVISED – M104: Revised details 2/M104 to show ductwork sizes along with clarifying dampers needed.

3. ADDED – M100: general note 14: All equipment manufacturers are designated as “basis of design” unless indicated otherwise. Alternative manufacturers will be considered, but are subject to compliance with drawings and specifications.

END OF ADDENDUM NO. 001

Amendment 3, page 2; May 21, 2019

GENERAL NOTES:

A. MAINTAIN THE INTEGRITY OF ALL REMAINING BUILDING SYSTEMS AND RATINGS.

REPAIR ANY DAMAGE DONE TO SURROUNDING AREAS/CONSTRUCTION DURING

DEMOLITION.

B. ALL EXISTING CONDITIONS ARE NOT INDICATED ON THE DRAWINGS. CONTRACTOR

SHALL CAREFULLY EXAMINE THE EXISTING INSTALLATION AND ALL PROJECT

DRAWINGS TO BECOME FAMILIAR WITH THE SCOPE OF WORK.

C. CONTRACTOR SHALL PATCH AND REPAIR ANY DAMAGE OR PENETRATIONS AT ALL

ELEMENTS TO REMAIN (INCLUDING BUT NOT LIMITED TO WALLS, CEILINGS,

FLOORS, ETC.) CAUSED BY DEMOLITION ACTIVITIES OR REMOVAL OF ELECTRICAL,

MECHANICAL, AND ARCHITECTURAL ELEMENTS. REPLACE ITEMS NOT REPAIRABLE

TO ORIGINAL STATE. EXISTING FINISH MATERIALS, INCLUDING CEILINGS, TRIM,

ETC., SHALL BE PROTECTED AND RETAINED, UNLESS NOTED OTHERWISE.

D. PORTIONS OF THE BUILDING ARE TO REMAIN CONTINUOUSLY OCCUPIED

THROUGHOUT CONSTRUCTION. CONTRACTOR TO MAINTAIN CLEAR PATH OF

EGRESS THROUGHOUT CONSTRUCTION.

E. UNLESS NOTED OTHERWISE ALL DIMENSIONS ARE TO THE FACE OF STUD.

F. RE: A601 FOR DOOR TYPES, HARDWARE AND DETAILS.

G. RE: A801 FOR INTERIOR ELEVATIONS AND FIXTURE ACCESSIBILITY

REQUIREMENTS.

H. RE: A101 FOR OVERALL FLOOR PLANS.

1. RE: MECHANICAL AND ELECTRICAL DRAWINGS FOR WORK TO OCCUR IN THIS AREA.

2. SHOWER CONTROL WALL, RE: PLUMBING DRAWINGS.

3. SHOWER BENCH WALL, RE: SPECIFICATIONS. INSTALL BENCH PER MANUFACTURER

RECOMMENDATION.

4. WALL HUNG SINK AND ASSOCIATED MIRROR, RE: PLUMBING DRAWINGS AND A801.

5. TOILET PLUMBING FIXTURE, RE: PLUMBING DRAWINGS.

6. NEW BENCH RE: DETAILS ON A801.

7. EXISTING WALL MOUNTED COMMUNICATIONS EQUIPMENT ABOVE TO REMAIN, PROTECT ALL

ASSOCIATED ITEMS. DO NOT PAINT. VERIFY EXACT LOCATION IN FIELD.

8. RE-ROUTE EXISTING CONDUIT AS NECESSARY TO ACCOMMODATE NEW OPENING.

9. FACE OF GYPSUM CEILING, AND ASSOCIATED CEILING FRAMING TO BE 8'-0" ABOVE FINISH

FLOOR, PAINT PT1. RE: ELECTRICAL DRAWINGS FOR LIGHTING DETAILS.

10. FIBERGLASS SHOWER INSERT PER SPECIFICATIONS.

11. TILE TO CONCRETE FLOOR TRANSITION PER SPECIFICATIONS, RE: 4/A-111 FOR DETAILS.

12. MECHANICAL EQUIPMENT, RE: MECHANICAL DRAWINGS. RE: A601 FOR FURTHER DETAILS

13. NEW SLAB, S1, THROUGHOUT ENTIRETY OF AREA WHERE SLAB WAS REMOVED DURING

DEMOLITION. RE: DETAIL 4/A111. NEW SLAB TO RECEIVE TILE AND TILE COVE BASE

THROUGHOUT, INSTALL TILE PER MANUFACTURER INSTRUCTIONS AND RECOMMENDATIONS.

14. INSTALL ACCESSIBLE RESTROOM PANEL SIGNAGE PER DETAILS ON A801.

15. RE: MECHANICAL DRAWINGS FOR PIPING LOCATIONS. RE: A601 FOR THRU WALL

PENETRATION DETAILS.

16. NEW CONCRETE PAD FOR MECHANICAL EQUIPMENT. PAD TO BE SLAB TYPE 'S1'- NO VAPOR

BARRIER IS NEEDED AT THIS PAD LOCATION. REMOVE EXISTING ASPHALT AS NEEDED TO

ACCOMMODATE NEW PAD - PATCH EXISTING ASPHALT WHERE DAMAGE OCCURS.

17. FACE OF GYPSUM CEILING, AND ASSOCIATED CEILING FRAMING TO BE 9'-0" ABOVE FINISH

FLOOR, PAINT PT1. RE: ELECTRICAL DRAWINGS FOR LIGHTING DETAILS.

18. INSTALL STEEL FRAMING AROUND OPENING PER DETAILS ON A-601 - STEEL FRAMING TO BE

PAINTED TO MATCH DOOR FRAMES.

19. FURR OUT WALLS NOTED WITH

" HAT CHANNELS AND

" MOISTURE RESISTANT GYPSUM

WALL BOARD. USE HAT CHANNELS TO CREATE FLUSH WALL PLANE AND UNIFORMITY. FURR

OUT TO OCCUR FROM FLOOR TO 6" INCHES ABOVE CEILING. FRAME AROUND WHERE

EXISTING WINDOWS OCCUR.

20. FURR OUT EXISTING WALL SO FINISH FACE OF GYPSUM ALIGNS WITH EXISTING FACE OF THE

CONCRETE COLUMN. FURR OUT WITH METAL STUDS AND

" MOISTURE RESISTANT GYPSUM

WALLBOARD.

21. PROVIDE ACCESS PANEL IN GYPSUM CEILING. PROVIDE FLUSH ACCESS DOOR WITH

EXPOSED FLANGES AND CONCEALED HINGE - SIZE AS REQUIRED FOR

MECHANICAL/PLUMBING ACCESS. UNCOATED 16 GAGE STEEL SHEET DOOR FACTORY

PRIMED. LATCH AND LOCK TO BE CAM LATCH, SCREWDRIVER OPERATED.

SHEET NOTES:

LOCKERS

STORAGE

5 5

B

B

B102

R.R.

B101

R.R.

1'-0"

MIN.

1'-0"

MIN.

4"

A801

A

B

C

D

A801

A

B

C

D

5'-9"5'-9"

1919 1919

3'-11"

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

R.R.

R.R.

CLO.

R S

R L

4'-0"

LOCKERS

STORAGE

B101

R.R.

B102

R.R.

A801

(1) LAYER

" TYPE 'X' EA. SIDE

4" METAL STUD AT 16" O.C.

FIBER GLASS BLANKET INSULATION, FILL STUD CAVITY.

NOTE: USE MOISTURE RESISTANT GYPSUM WALL

BOARD ON ALL WET WALL, RE: A801 AND

SPECIFICATIONS.

WALL TYPES:

(1) LAYER

" TYPE 'X' EA. SIDE

(2)STAGGERED 6" METAL STUDS AT 16" O.C.

FIBER GLASS BLANKET

INSULATION, FILL STUD CAVITY

NOTE: USE MOISTURE RESISTANT GYPSUM WALL

BOARD ON ALL WET WALLS, RE: A801 AND

SPECIFICATIONS.

VAPOR BARRIER

4" COMPACTED GRAVEL FILL

4" CONCRETE SLAB

w/#3 @ 16”OC EA WAY

1½” CLR FROM TOP OF SLAB

NOTES:

Concrete shall be f'c = 4,500psi ASTM C150 TYPE I/II, Fly Ash

ASTM C615 Class C or F, W/C +Fly Ash ratio = 0.45 max, ¾” max normal weight aggregate.

Rebar shall be ASTM A615, Grade 60.

S1

SLAB TYPES:

FF ELEV

#4 x 2'-6" DOWEL w/ 6" EMBED

SET IN EPOXY @ 16" OC

(N) CONC SLAB ON

GRADE, SEE SLAB

TYPE AND FLOOR

PLAN

(E) CONC SLAB ON GRADE

E Q

E Q

DEPRESSED SLAB - FINISH

FACE OF TILE TO MATCH

TOP OF EXISTING SLAB

TILE FLOOR FINISH, RE: PLANS

AND SPECIFICATIONS

INTERIOR ELEVATION NUMBER /

SHEET WHERE DRAWN

F.E.F. FACE OF EXISTNG FINISH

DIMENSION TO FACE OF

STUD OR EXISTING WALL

DOOR NUMBER (SEE SHEET A101)

PLAN LEGEND

DETAIL OR SECTION NUMBER

SHEET WHERE DRAWN

PLAN NOTE

ROOM NAME

WALL TYPE

WALL TYPE NOTE

X

X

X

A101

A801

A

B

C

D

101-1

A111

ENLARGED FLOOR PLAN BASEMENT RESTROOMS

1/4"=1'-0"

06.11.18 06:12 PM | G:\USDAAPHIS_PSD1\BIMCAD\Arch\A-111.dwg

A111

PACKAGE #2 -

ENLARGED

PLANS

BID ADDENDUM 001 - 5.20.19

JC

SR

A111

ENLARGED FLOOR PLAN OFFICES

1/4"=1'-0"

DRAWN BY |

REVISIONS

© | ALL RIGHTS RESERVED

w w w . c t a g r o u p . c o m

8 0 0 . 7 5 7 . 9 5 2 2

CHECKED BY |

U S

D A

P H

I S

P S

D

R

E N

O V

A T

I O

N S

P O

C A

T E

L L

O

I D

A H

O

100% CD

3.27.19

N O

T

F

O R

C

N

S T

R U

C T

I O

N

P

R E

L I M

I N

A R

Y

D

E S

I G

N

A111

ENLARGED CEILING PLAN BASEMENT RESTROOMS

1/4"=1'-0"

A111

EXISTING SLAB TO NEW SLAB CONNECTION DETAIL

1/4"=1'-0"

Amendment 3, page 3; May 21, 2019

MECHANICAL LEGEND

CONDENSATE DRAIN

HOT WATER

COLD WATER

HARD COLD WATER

REFRIGERANT LIQUID/SUCTION LINES

GATE VALVE

BALL VALVE

BUTTERFLY VALVE

GLOBE VALVE

TRIPLE DUTY VALVE

SWING CHECK VALVE

STRAINER

FLEX CONNECTOR

HOSE END DRAIN VALVE

PRESSURE REDUCING VA.

SAFETY RELIEF VALVE

UNION

MOTORIZED T.C. VA/2-WAY

MOTORIZED T.C. VA/3-WAY

ECCENTRIC PLUG BALANCING VALVE

VALVE IN RISER

TEE UP

TEE DOWN

ELBOW UP

ELBOW DOWN

PIPE SIZE CHANGE

MANUAL FLOW BALANCING VALVE

(CIRCUIT SETTER)

AUTOMATIC FLOW BALANCING VALVE

DIAL THERMOMETER

PRESSURE GAUGE W/ SNUBBER

P

T

A

M

RLS

HARD

CW

HW

CD ELECTRIC THERMOSTAT

ELECTRIC THERMOSTAT W/GUARD

ACOUSTICALLY LINED SHEET

METAL DUCT

MANUAL BALANCING DAMPER

FLEX CONNECTOR

ACCESS DOORS

TURNING VANE ELL

45° LOW-LOSS TAKE-OFF FITTING W/

DAMPER & FLEX DUCT

45° LOW-LOSS TAKE-OFF FITTING W/

DAMPER & RIGID ROUND DUCT

90° TEE TAKE-OFF FITTING

CONICAL 90° TEE TAKE-OFF FITTING

45° TEE TAKE-OFF FIITTING

45°-90° TEE TAKE-OFF FITTING

SUPPLY AIR DUCT (SINGLE LINE)

RETURN AIR DUCT (SINGLE LINE)

EXHAUST AIR DUCT (SINGLE LINE)

DIFFUSER, REGISTER, OR GRILLE THROW

PATTERN SHOWN ON DWGS.

CONNECT NEW WORK TO EXISTING

SD-1 (PLAN CODE)

8x8 (NECK SIZE)

200 (CFM)

AD

AD

T

T

SA

RA

EA

SYMBOL DESCRIPTION SYMBOL DESCRIPTION

HVAC ABBREVIATIONS

AFF ABOVE FINISHED FLOOR

ACFM ACTUAL CFM

AHU AIR HANDLING UNIT

ANSI AMERICAN NATIONAL STANDARDS INSTITUTE

AMP AMPERE (AMP,AMPS)

APD AIR PRESSURE DROP

APPROX APPROXIMATE

BHP BRAKE HORSEPOWER, BOILER HORSEPOWER

BTU BRITISH THERMAL UNIT

MBH BTU PER HOUR (THOUSAND)

CU FT CUBIC FEET

CU IN CUBIC INCH

CFM CUBIC FEET PER MINUTE

SCFM CFM, STANDARD CONDITIONS

DB DECIBEL

DIA, Ø DIAMETER

ID DIAMETER, INSIDE

OD DIAMETER, OUTSIDE

DBT DRY-BULB TEMPERATURE

EAT ENTERING AIR TEMPERATURE

E.C. ELECTRICAL CONTRACTOR

EDR EQUIVALENT DIRECT RADIATION

EXP EXPANSION

EWT ENTERING WATER TEMPERATURE

F FAHRENHEIT

FPM FEET PER MINUTE

FPS FEET PER SECOND

FT FOOT OR FEET

HZ FREQUENCY

GA GAGE OR GAUGE

GAL GALLONS

G.C. GENERAL CONTRACTOR

GPH GALLONS PER HOUR

GPM GALLONS PER MINUTE

GPD GALLONS PER DAY

HD HEAD

HGT HEIGHT

HP HORSEPOWER

RH HUMIDITY, RELATIVE

KW KILOWATT

KWH KILOWATT HOUR

LAT LEAVING AIR TEMPERATURE

LWT LEAVING WATER TEMPERATURE

LF LINEAR FEET

MAX MAXIMUM

M.C. MECHANICAL CONTRACTOR

MIN MINIMUM

N O NORMALLY OPEN

N C NORMALLY CLOSED

N/A NOT APPLICABLE

NIC NOT IN CONTRACT

NTS NOT TO SCALE

NO NUMBER

OBD OPPOSED BLADE DAMPER

OA OUTSIDE AIR

% PERCENT

PH PHASE(ELECTRICAL)

LBS POUNDS

PSI POUNDS PER SQUARE INCH

PSIA PSI ABSOLUTE

PD PRESSURE DROP OR DIFFERENCE

PSIG PSI GAUGE

R/O RUN OUT

RH RELATIVE HUMIDITY

RA RETURN AIR

RPM REVOLUTIONS PER MINUTE

SH SENSIBLE HEAT

SPEC SPECIFICATION

SP VOL SPECIFIC VOLUME

STD STANDARD

SP STATIC PRESSURE

SUCT SUCTION

SA SUPPLY AIR

TEMP TEMPERATURE

TD TEMPERATURE DIFFERENCE

T STAT THERMOSTAT

TONS TONS OF REFRIGERATION

T.C. TEMPERATURE CONTROL

VAC VACUUM

VAV VARIABLE AIR VOLUME

VEL VELOCITY

V VOLT

VOL VOLUME

VFD VARIBLE FREQUENCY DRIVE

WPD WATER PRESSURE DROP

W/ WITH

EXISTING

(E)

1. THIS CONTRACTOR SHALL BE AWARE THAT THIS IS A REMODELING PROJECT AND AS SUCH, CERTAIN

ITEMS AND SIZES CANNOT BE FULLY ILLUSTRATED NOR EXPLAINED WITHOUT FIELD OBSERVATION.

THEREFORE, THIS CONTRACTOR IS ADVISED TO VISIT AND EXAMINE THE JOB SITE AND BUILDING IN

EVERY DETAIL AS PERTAINS TO THIS PROJECT AND MAKE ALLOWANCES IN HIS PROPOSAL FOR ALL

CONDITIONS THAT WILL AFFECT THE WORK INDICATED IN THE PROJECT SPECIFICATIONS AND

CONTRACT DRAWINGS.

2. ALL REMOVED ITEMS, EXCEPT THOSE NOTED TO BE REUSED OR TO REMAIN THE PROPERTY OF THE

OWNER, SHALL BECOME PROPERTY OF THE CONTRACTOR AND SHALL BE REMOVED FROM THE JOB

SITE. THE OWNER RESERVES THE RIGHT TO KEEP ANY REMOVED ITEMS EVEN THOUGH NOT NOTED ON

DRAWINGS.

3. WHERE EXISTING EQUIPMENT, DUCTS, PIPES ETC. ARE TO BE REMOVED, SUCH REMOVAL SHALL

INCLUDE ALL ANCHORS, BASES, HANGERS, ETC.

4. THIS CONTRACTOR MUST MEET WITH THE OWNER OR HIS REPRESENTATIVE AND DISCUSS THE

PROPOSED WORK SCHEDULE FOR REMOVAL, AND REMODELED WORK WITHIN CONTRACT DRAWINGS

PRIOR TO PERFORMING ANY WORK. THE CONTRACTOR SHALL INFORM THE OWNER OR HIS

REPRESENTATIVE, OF THE INTENT TO DO SO AT LEAST 48 HOURS BEFORE SUCH WORK BEGINS.

5. THIS CONTRACTOR SHALL PERFORM ALL CUTTING AND PATCHING REQUIRED.

6. HAZARDOUS MATERIALS, SUCH AS CYANIDE, STRYCHNINE, ZINC PHOSHPIDE, AND SODIUM NITRATE

MAY BE PRESENT IN DUCTWORK OR OTHER HVAC COMPONENTS. COMPLY WITH ALL OSHA SAFETY

STANDARDS FOR DEMOLITION, CONTAINMENT, AND DISPOSAL OF MATERIALS.

DEMO GENERAL NOTES:

GENERAL NOTES:

1. COORDINATE INSTALLATION OF DUCTWORK WITH STRUCTURAL

COMPONENTS AND OTHER SYSTEM INSTALLATIONS. GENERAL

CONTRACTOR TO SAW CUT AND CORE DRILL, PATCH AND REPAIR

SURFACES AS REQUIRED.

2. COORDINATE EXACT LOCATION OF DIFFUSERS AND GRILLES WITH

ARCHITECTURAL REFLECTED CEILING PLANS.

3. ALL DUCT DIMENSIONS SHOWN ARE INTERIOR DIMENSIONS.

4. COORDINATE LOCATION OF HVAC EQUIPMENT WITH ALL OTHER TRADES

TO MAINTAIN ACCESS AND SERVICE CLEARANCES.

5. PROVIDE ALL SEISMIC RESTRAINTS REQUIRED BY CODE, FOR ALL

EQUIPMENT, DUCT, PIPE, AND MATERIALS FURNISHED UNDER THIS

SECTION.

6. THE WORK INSTALLED UNDER THIS SECTION SHALL CONFORM TO ALL

APPLICABLE LOCAL CODES, REGULATIONS, AND STANDARDS.

7. THE DRAWINGS PROVIDED ARE SCHEMATIC IN NATURE. ABSOLUTE ACCURACY OF

THE DRAWINGS AND SPECIFICATIONS CAN NOT BE GUARANTEED. WHILE

REASONABLE EFFORT HAS BEEN MADE TO COORDINATE THE LOCATION OF

EQUIPMENT AND MATERIALS WITH THE STRUCTURE AND OTHER TRADES, IT IS

THE RESPONSIBILITY OF THE CONTRACTOR TO COORDINATE EXACT

REQUIREMENTS AND LOCATIONS AS GOVERNED BY ACTUAL JOB CONDITIONS.

8. INSULATE DUCTWORK PER INTERNATIONAL ENERGY CODE 2012.

9. FABRICATE AND INSTALL THE DUCT IN ACCORDANCE WITH SMACNA HVAC

DUCT CONSTRUCTION STANDARDS METAL AND FLEXIBLE.

10.PROVIDE ALL NECESSARY TRANSITIONS AND ADDITIONAL FITTINGS AS

REQUIRED TO CLEAR OBSTRUCTIONS, MAINTAIN CLEARANCES, AND

COORDINATE WITH OTHER TRADES AT NO EXTRA COST TO THE OWNER.

11.CONTRACTOR SHALL BE RESPONSIBLE FOR PROPER OPERATION OF ALL

SYSTEMS, MINOR SUBSYSTEMS, AND SERVICES PROVIDED UNDER THIS

DIVISION.

12.LOCATE ALL MANUAL BALANCE DAMPERS IN ACCESSIBLE AREAS EITHER

ABOVE ACOUSTICAL CEILING GRID OR IN ACCESSIBLE ATTIC AREA.

13. MOUNT THERMOSTATS AND HUMIDISTATS AT 54" A.F.F. UNLESS

OTHERWISE NOTED.

14. ALL EQUIPMENT MANUFACTURERS ARE DESIGNATED AS "BASIS OF

DESIGN" UNLESS INDICATED OTHERWISE. ALTERNATIVE MANUFACTURERS

WILL BE CONSIDERED, BUT ARE SUBJECT TO COMPLIANCE WITH

DRAWINGS AND SPECIFICATIONS.

MAKEUP AIR UNIT SCHEDULE

BASIS OF

DESIGN

MODEL TYPE

SUPPLY FAN HEATING SECTION EVAPORATIVE COOLING WEIGHT

NOTES

PLAN AREA POWER

MCA MOCP

CODE SERVED

(V/PH/HZ)

DESIGN ESP MOTOR FAN SPEED SYSTEM

FUEL

INPUT OUTPUT

MEDIA

EAT DB/WB

(F)

LAT

DB/WB (F)

UNIT

(CFM) (IN W.G.) (HP) (RPM)

TYPE

(MBH) (MBH) (LBS)

MAU-1 MIXING ROOM GREENHECK IGX-112-H22 INDOOR 230/3/60 23 35

5,000

1.5 5 1,725

INDIRECT GAS NG 488.8 391.1 CELDEK 95/62 64.9/64.9 2266

1,2,3,4,5,6,7,8,9,10,11

SCHEDULE NOTES:

1. EVAP COOLING AUTOMATIC DRAIN AND FILL WITH FREEZE PROTECTION. PROVIDE WATER AND DRAIN VALVES SHIPPED LOOSE. PROVIDE CELDEK EVAP COOLING MEDIA. COORDINATE WITH PLUMBING FOR WATER AND DRAIN CONNECTIONS.

2. UNIT IS SELECTED AT AN ELEVATION OF 4,500 FT ABOVE SEA LEVEL.

3. PROVIDE UNIT WITH ELECTRONIC MODULATION BURNER CONTROLS.

4. MOTORIZED INLET AIR DAMPER.

5. CONSTANT VOLUME FAN. INTERLOCK WITH EF-3.

6. PROVIDE WITH REMOTE CONTROL PANEL WITH TEMPERATURE CONTROL, FILTERS DIRTY, STARTERS.

7. PROVIDE UNIT WITH INLET AIR SENSOR

8. PROVIDE UNIT WITH FREEZE PROTECTION DRAIN CONTROL KIT FOR EVAPORATIVE COOLERS.

9. WINTER DESIGN CONDITIONS - 5F AND SUMMER DESIGN CONDITIONS - 91F DB / 63F WB.

10. PROVIDE MAU WITH DISCONNECT.

11. PROVIDE WITH FACTORY MOUNTED SKID AND INTERNALLY ISOLATED COMPONENTS.

VENTILATION HOOD SCHEDULE

PLAN

BASIS OF

DESIGN

MODEL NO. TYPE LENGTH

WIDTH HEIGHT

CFM

OUTLET OUTLET CONNECTED

MOUNTING NOTES:

CODE

(IN) (IN) SIZE (IN)

S.P. MAX. EXHAUST FAN

H-1 LABCONCO PROTECTOR PREMIER XL VENTILATION 96 in 32.0 59 1640 2 X 12Ø 0.3 EF-1 STAND 1

H-2 MONOXIVENT CUSTOM SLOTTED BENCH 72 in 6.0 70 5500 18Ø 0.6 EF-3 TOP OF COUNTER 2

SH-1 MONOXIVENT 15078-TT SNORKEL 7 ft - - 875 8Ø 1.2 EF-4 WALL MOUNT 3

SH-2 MONOXIVENT 15076-TT SNORKEL 7 ft - - 500 6Ø 1.9 EF-5 WALL MOUNT 3

SCHEDULE NOTES:

1. PROVIDE WITH TELESCOPING BASE STAND SET TO 34" IN HEIGHT, CATALOG NUMBER 3857300, STAINLESS STEEL WORK SURFACE, T8 LIGHT FIXTURE WITH INTEGRAL SWITCH.

2. PROVIDE WITH BLAST GATE AND WALL BRACKETS. SEE DETAIL 1/M104 FOR DETAILED DIMENSIONS AND REQUIREMENTS.

3. PROVIDE HOSE WITH LAMINATED PTFE HOSE WALL, GALVANIZED STEEL EXTERNAL HELIX, AND SERIES 15000-TT TUBE TYPE ARM WALL BRACKET.

DIFFUSER, REGISTER & GRILLE SCHEDULE

PLAN

BASIS OF

DESIGN

MODEL

FACE

NECK SIZE MATERIAL

COLOR/

MOUNTING NOTES

CODE SIZE FINISH

SD-1 TITUS 300RL 18"x6" - STEEL WHITE DUCT 1

SD-2 TITUS 300RL 10"x6" - STEEL WHITE DUCT 1

SCHEDULE NOTES:

1. PROVIDE DUCT MOUNTING HARDWARE

ROOFTOP UNIT SCHEDULE

BASIS OF DESIGN SIZE FLA

FAN SECTION HEATING SECTION DEHUMIDIFICATION SECTION FILTER SECTION WEIGHT

NOTES

PLAN AREA POWER

CODE SERVED

(V/PH/HZ)

TYPE

AIRFLOW MIN. OSA DESIGN ESP MOTOR FAN SPEED SYSTEM

FUEL

INPUT OUTPUT

DESSIANT

MODEL

DESSICANT CAPACITY

REACT. HEATER

QTY / MODEL

INPUT

TYPE NUMBER / SIZE

UNIT

(CFM) (CFM) (INCHES W.G.) (HP) (RPM)

TYPE

(MBH) (MBH)

TYPE

(LB/H) (MBH) (LBS)

RTU-1 CYANIDE ROOM MUNTERS ICA-0750-020-G 17 230/3/60 39.4 SWSI AIRFOIL

2,400 1,120

7.58 7.5 3,450

INDIRECT NG 200 160 ICA-750 TIGEL 73.3 2 / HPG-200 200.6 MERV 8

1 / 12x24, 1 / 24x24

1,2,3,4,5,6,7,8,9,10

CONDENSING UNIT / COOLING COILS

PLAN

CODE

BASIS OF DESIGN

PRE-COOLING POST-COOLING

REF. TYPE ROWS / FPI

FIN MATERIAL / TUBE

MATERIAL

CAPACITY CAPACITY POWER FLA MCA WEIGHT

(MBH) (MBH) (V/PH/HZ) (AMPS) (AMPS) (LBS)

CU-1 ICS 20ACCUD-460 98 110 230/3/60 103 125 3800 R404A 6 / 11 ALUMINUM / COPPER

PERFORMANCE

PLAN

WINTER DESIGN °F (DB) SUMMER DESIGN °F (DB / GR/LB) DEHUMIDIFICATION DESIGN °F (DB / GR/LB)

CODE EAT POST HEAT EAT PRECOOL DEHUMID POST COOL EAT PRECOOL DEHUMID POST COOL

RTU-1 -5 80.0 95 / 45.4 49 / 45.4 84 / 14.9 59 / 14.9 71 / 87.2 50 / 62.3 100 / 9.3 59 / 9.3

SCHEDULE NOTES:

1. UNITS SELECTED AT 4,500 FT ABOVE SEA LEVEL, 95°F DB / 62F WB SUMMER DESIGN TEMP, -5°F WINTER DESIGN TEMP, 72F DB / 59°F DEW POINT DESIGN DEHUMIDIFICATION CONDITIONS.

2. COORDINATE INSTALLATION WITH EXISTING STRUCTURE.

3. PROVIDE ALL SERVICE CLEARANCES REQUIRED.

4. UNIT IS A BUILT UP AIR HANDLER WITH PRE-COOL, DESSICANT, POST-COOL, AND HEATING SECTION. DESSICANT PORTION INCLUDES 652 CFM REACTIVATION FAN AND NATURAL GAS REACTIVATION HEAT.

5. PROVIDE WITH REMOTE MOUNTED SIEMENS S7-1200 CONTROLLER, KTP400, COLOR TOUCH HMI PACKAGE, FUSED DISCONNECT, FACTORY MOUNTED CONTROL ENCLOSURE, FILTER PRESSURE DIFFERENTIAL SWITCH.

6. CONFIGURE UNIT FOR END AIR DISCHARGE.

7. PROVIDE WITH MOTORIZED OUTSIDE AIR DAMPER AND ACTUATOR TO OPEN WHEN UNIT IS ENABLED.

8. PROVIDE RTU AND CU WITH ELECTRICAL DISCONNECT.

9. PROVIDE A 120V CONVENIENCE OUTLET WITH RTU-1.

10. PROVIDE UNITS WITH STRUCTURAL SKID TO BE MOUNTED TO EXISTING STRUCTURAL MEMBERS ON ROOF.

EMERGENCY EYEWASH SCHEDULE

PLAN FIXTURE

NOTES

CODE ITEM BASIS OF DESIGN MODEL TYPE FLOW RATE MATERIAL COLOR/FINISH

EEW-1 EMERGENCY EYE WASH HAWS 7500

WALL MOUNT, PORTABLE

0.4 GPM POLYETHYLENE GREEN 1

SCHEDULE NOTES:

1. PROVIDE WITH MODEL 9009 20 GALLON WASTE CONTAINER.

WALL LOUVER SCHEDULE

PLAN

BASIS OF DESIGN SERVICE

WIDTH x HEIGHT

CFM

MAX APD

MATERIAL NOTES

CODE

(IN) (IN W.C.)

LV-1 RUSKIN ELF375DX EF-5 18"x18" 500 0.1 EXTRUDED ALUMINUM 1, 2, 3

LV-2 RUSKIN ELF375DX FUSE STORAGE 36"x18" 345 0.1 EXTRUDED ALUMINUM 1, 2, 3

SCHEDULE NOTES

1. PROVIDE WITH BIRDSCREEN.

2. PROVIDE WITH GRAVITY BACKDRAFT DAMPER.

3. PROVIDE PAINT COLOR PALETTE WITH SUBMITTAL FOR ARCHITECT'S SELECTION.

BAG IN / BAG OUT HEPA FILTER SCHEDULE

PLAN CODE BASIS OF DESIGN SERVES CFM

INTAKE BOX SIZE

TYPE

FILTER SIZE PRESSURE DROP (IN W.C.)

WEIGHT

(LBS)

NOTES

WIDTH HEIGHT LENGTH WxHxTHICKNESS PRE-FILTER HEPA FILTER

FB-1

AAF | FLANDERS

BF1-1H2W EF-1 1640 31 30 37.5 MERV 8 / HEPA 24x24x2 / 24x24x12 0.5 1 510

1,2,3,4,5,6,7,8

FB-2

AAF | FLANDERS

BF1-1H2W EF-2 1715 31 30 37.5 MERV 8 / HEPA 24x24x2 / 24x24x12 0.5 1 510

1,2,3,4,5,6,7,8

SCHEDULE NOTES:

1. PROVIDE WITH BF1-1H2W-2GGF-304-D3 HOUSING SECTION, MOUNTING BASE, LIFTING LUG, AND GAGE PANEL FOR PRESSURE DROP ACROSS EACH FILTER.

2. PROVIDE FILTER BOX WITH LEFT SIDE DOOR ACCESS AND COORDINATE EXACT LOCATION AND CLEARANCES ON SITE.

3. FILTER BOX SHALL BE EQUIPPED WITH A FLUID SEAL FILTER CLAMING MECHANISM OPERATED BY A LOCKING HANDLE.

4. THE HOUSING SHALL BE EQUPPED WITH A BAG-OUT RING AROUND EACH FILTER ACCESS PORT.

5. THE HOUSING SHALL BE CONSTRUCTED OF T-304 11 AND 14 GAUGE STAINLESS STEEL SHEET METAL WITH CONTINUOUSLY WELDED RETAINING JOINTS.

6. WEATHER CAPS SHALL BE CONSTRUCTED FROM 14 GAUGE STAINLESS STEEL SHEET METAL AND INSTALLED TO PREVENT THE ACCUMULATION OF WATER AND DEBRIS.

7. THE FILTER SYSTEM SHALL BE TESTED IN ACCORDANCE WITH ANSI/ASME NQA-1.

8 THE OVERALL SYSTEM AND FILTER SEALING SURFACE SHALL BE LEAK TESTED BY THE "PRESSURE DECAY" METHOD IN ACCORDANCE WITH AG-1, 2012 MANDATORY APPENDIX TA-III, ARTICLE TAA-III-4200 AND HAVE A MAXIMUM LEAK RATE OF 0.0005 CFM PER CUBIC FOOR OF HOUSING FOR 15 MINUTES.

POWER VENTILATOR SCHEDULE

PLAN

CODE

TYPE LOCATION SERVES

BASIS OF DESIGN

DRIVE CFM

E.S.P. MOTOR POWER

WEIGHT(LBS)

NOTES:

MFGR MODEL

(IN)

HP

(V/PH/HZ)

EF-1 UTILITY ROOF CYANIDE VENT HOOD GREENHECK FJC-212-BI-X BELT

1,200

2.50 1 230/3/60 231 1,3,4,6

EF-2 UTILITY ROOF CYANIDE GRINDER/MIXER GREENHECK FJC-212-BI-X BELT

1,715

2.50 1 1/2 230/3/60 278 1,3,4,6

EF-3 UTILITY MIXING MIXING ROOM HOOD GREENHECK FJI-18-BI-X BELT

5,500

2.00 5 230/3/60 231 1,3,6

EF-4 UTILITY ROOF CARTRIDGE ROOM HOODS GREENHECK FJI-15-BI-X BELT

3,500

2.50 3 230/3/60 190 1,5,6

EF-5 INLINE WAREHOUSE LABEL MAKER GREENHECK SQ-80-7 DIRECT 500 1.90 3/4 230/3/60 88 1,2,6

EF-6 UTILITY ROOF CARTRIDGE ROOM HOODS GREENHECK FJC-312-BI BELT

1,500

2.00 1 230/3/60 176 1,5,6

SCHEDULE NOTES:

1. FAN SELECTIONS ARE AT 4,500 FT ABOVE SEA LEVEL.

2. PROVIDE WITH BACKDRAFT DAMPER IN DUCT.

3. PROVIDE AND MOUNT ON EXISTING CURB.

4. PROVIDE WITH HEPA FILTER.

5. MOUNT ON EXISTING STRUCTURE ABOVE CYANIDE ROOM.

6. DESIGN FANS TO MEET LOCAL CONDITIONS AND ALL CODE REQUIREMENTS.

VENTILATION HOOD SCHEDULE

PLAN

BASIS OF

DESIGN

MODEL NO. TYPE LENGTH

WIDTH HEIGHT

CFM

OUTLET OUTLET CONNECTED

MOUNTING NOTES:

CODE

(IN) (IN) SIZE (IN)

S.P. MAX. EXHAUST FAN

H-1 LABCONCO PROTECTOR PREMIER XL VENTILATION 96 in 32.0 59 1640 2 X 12Ø 0.3 EF-1 STAND 1

H-2 MONOXIVENT CUSTOM SLOTTED BENCH 72 in 6.0 70 5500 18Ø 0.6 EF-3 TOP OF COUNTER 2

SH-1 MONOXIVENT 15078-TT SNORKEL 7 ft - - 875 8Ø 1.2 EF-4 WALL MOUNT 3

SH-2 MONOXIVENT 15076-TT SNORKEL 7 ft - - 500 6Ø 1.9 EF-5 WALL MOUNT 3

SCHEDULE NOTES:

1. PROVIDE WITH TELESCOPING BASE STAND SET TO 34" IN HEIGHT, CATALOG NUMBER 3857300, STAINLESS STEEL WORK SURFACE, T8 LIGHT FIXTURE WITH INTEGRAL SWITCH.

2. PROVIDE WITH BLAST GATE AND WALL BRACKETS. SEE DETAIL 1/M104 FOR DETAILED DIMENSIONS AND REQUIREMENTS.

3. PROVIDE HOSE WITH LAMINATED PTFE HOSE WALL, GALVANIZED STEEL EXTERNAL HELIX, AND SERIES 15000-TT TUBE TYPE ARM WALL BRACKET.

DRAWN BY |

REVISIONS

© | ALL RIGHTS RESERVED

w w w . c t a g r o u p . c o m

8 0 0 . 7 5 7 . 9 5 2 2

CHECKED BY |

U S

H

I S

P S

D

R

E N

O V

A T

I O

N S

P O

C A

T E

L L O

I D

A H

O

100% CD

3.27.19

N O

T

F

N

S T

R U

C T

I O

N

P

R E

L I M

I N

A R

Y

D

E S

I G

N

06.22.18 09:33 AM | G:\USDAAPHIS_PSD1\BIMCAD\Mech\M100.dwg

M100

PACKAGE 1 HVAC

SCHEDULES

BID ADDENDUM 001 - 5.20.19

RR

TJ

Amendment 3, page 4; May 21, 2019

M104

MIXING ROOM HOOD DETAIL

SCALE: NTS

EXISTING

DUCTWORK UP

THROUGH ROOF

UTILITY SET FAN DETAIL

SCALE: NTS

M104

T

Y P

DUCT UP TO EF-3

45° TAPER ANGLE

6"

" SLOT

18"Ø

ROOFTOP UNIT

GAS PIPE ON ROOF

6" CAPPED DRIP LEG

REDUCING BUSHING

IF EQUIPMENT INLET

SIZE IS SMALLER

THAN GAS LINE

UNION

GAS STOP

FLOOR OR ROOF

M104

RTU/MAU GAS CONNECTION DETAIL

NOT TO SCALE

CYANIDE ROOM SEQUENCE OF OPERATION

THE CYANIDE ROOM INCLUDES A ROOFTOP DEHUMIDIFICATION UNIT (RTU-1), CONDENSING UNIT (CU-1), AND TWO EXHAUST FANS (EF-1, EF-2) SERVING THE LAB HOOD AND GRINDER/MIXER, RESPECTIVELY.

THESE SYSTEMS ARE DESIGNED TO BY CONSTANT VOLUME WITH NO AIR RECIRCULATION.

RTU-1 AND CU-1 CONTROLS SHALL BE PACKAGED WITH THE UNIT AND INCLUDE A GRAPHICAL

INTERFACE, LOCATED IN THE SPACE, FOR ADJUSTING SETPOINTS, VIEWING ALARMS, AND

SCHEDULING SYSTEM OPERATION.

FAN CONTROL:

THE SUPPLY FAN AND EXHAUST FANS SHALL OPERATE CONTINUOUSLY WHEN ENABLED. THE

EXHAUST FANS (EF-1, EF-2) SHALL BE INTERLOCKED WITH RTU-1 SUCH THAT BOTH EXHAUST FANS AND

RTU-1 SHALL RUN CONTINUOUSLY WHENEVER AN EXHAUST FAN IS ENABLED. EXHAUST FANS SHALL BE

ENABLED WITH A MANUAL SWITCH LOCATED NEAR THE CORRESPONDING HOOD. EXHAUST FANS AND

RTU-1 SHOULD OPERATE CONTINUOUSLY WHEN CYANIDE IS PRESENT IN THE SPACE.

OUTSIDE AIR DAMPER CONTROL:

THE OUTSIDE AIR DAMPER ON RTU-1 SHALL REMAIN 100% OPEN WHEN THE UNIT IS RUNNING AND

CLOSE COMPLETELY WHEN UNIT IS DISABLED.

DISCHARGE AIR CONTROL:

RTU-1 IS DESIGNED TO PROVIDE HEATING, COOLING, AND DEHUMIDIFICATION. WHEN THERE IS NO

CALL FOR HEATING OR COOLING FROM THE SPACE THERMOSTAT, DISCHARGE AIR TEMPERATURE

SHALL FLOAT. UPON A CALL FOR COOLING AT THE SPACE THERMOSTAT, THE DISCHARGE AIR

TEMPERATURE SHALL BE RESET TO MINIMUM. UPON A CALL FOR HEATING, THE DISCHARGE AIR

TEMPERATURE SHALL BE RESET TO MAXIMUM.

WHEN RTU-1 IS ENABLED, TEMPERATURE AND SPACE HUMIDITY SETPOINTS SHALL BE MAINTAINED AT

70F AND 20% RH RESPECTIVELY. SHOULD THE SPACE CONDITIONS RISE ABOVE SETPOINT

(ADJUSTABLE), THE DESSICANT WHEEL SHALL BE ACTIVATED AND MAINTAIN A MAXIMUM SUPPLY AIR

MOISTURE CONTENT OF 15 GRAINS OF MOISTURE PER POUND OF DRY AIR. SUPPLY AIR MOISTURE

CONTENT SHALL BE MODULATED WITH FACE AND BYPASS DAMPERS AROUND THE DESICCANT WHEEL, INTERNAL TO THE UNIT, USING MANUFACTURER'S CONTROL SEQUENCES.

SAFETIES AND ALARMS:

THE DIFFERENTIAL PRESSURE SENSOR ACROSS THE FILTER BANK SHALL SEND AN ALARM TO THE

CONTROL PANEL WHEN THE DIFFERENTIAL PRESSURE EXCEEDS 2 INCHES W.C. (ADJUSTABLE).

IF THE SPACE HUMIDITY SENSOR EXCEEDS 20% RELATIVE HUMIDITY, AN ALARM SHALL BE GENERATED

AT THE UNIT CONTROLLER.

IF THE SUPPLY AIR TEMPERATURE DROPS BELOW 40 DEGREES F, AN ALARM SHALL BE GENERATED AT

THE UNIT CONTROLLER.

MIXING ROOM SEQUENCE OF OPERATION

THE MIXING ROOM INCLUDES A BENCH STYLE HOOD WITH EXHAUST FAN (EF-3) AND A MAKEUP AIR

UNIT (MAU-1). CONTROLS SHALL BE PACKAGED WITH MAU-1 AND INCLUDE A USER INTERFACE FOR

ADJUSTING SETPOINTS, VIEWING ALARMS, AND SCHEDULING SYSTEM OPERATION.

FAN CONTROL:

THE MAKEUP AIR UNIT AND EXHAUST FAN SHALL OPERATE CONTINUOUSLY WHEN ENABLED. THE

EXHAUST FAN SHALL BE INTERLOCKED WITH MAU-1 SUCH THAT MAU-1 IS ENABLED WHEN THE HOOD IS

SWITCHED ON.

OUTSIDE AIR DAMPER CONTROL:

THE OUTSIDE AIR DAMPER ON MAU-1 SHALL REMAIN 100% OPEN WHEN THE UNIT IS RUNNING AND

CLOSE COMPLETELY WHEN UNIT IS DISABLED.

DISCHARGE AIR CONTROL:

MAU-1 IS DESIGNED TO PROVIDE HEATING AND COOLING. THE UNIT SHALL BE CONFIGURED TO

MAINTAIN 70F DISCHARGE AIR TEMPERATURE, BUT SHALL BE EQUIPPED WITH THE OPTIONAL ROOM

OVERRIDE FUNCTION. THE UNIT SHALL STAGE NATURAL GAS HEAT AND EVAPORATIVE COOLING

SECTIONS TO MAINTAIN SETPOINT.

EVAPORATIVE COOLING:

MAU-1 SHALL BE EQUIPPED WITH A DRAIN/FILL VALVE CONTROLLED AT THE UNIT LCD INTERFACE. THE

EVAPORATIVE COOLING SECTION SHOULD BE DRAINED PRIOR TO FREEZING OUTDOOR AIR

TEMPERATURES.

SAFETIES AND ALARMS:

THE DIFFERENTIAL PRESSURE SENSOR ACROSS THE FILTER BANK SHALL SEND AN ALARM TO THE

CONTROL INTERFACE LOCATED IN THE SPACE WHEN THE DIFFERENTIAL PRESSURE EXCEEDS 2

INCHES W.C. (ADJUSTABLE).

IF THE SUPPLY AIR TEMPERATURE DROPS BELOW 40 DEGREES F, AN ALARM SHALL BE GENERATED AT

THE UNIT CONTROLLER.

CARTRIDGE ROOM SEQUENCE OF OPERATION

THE CARTRIDGE ROOM CURRENTLY CONSISTS OF FOUR EXHAUST HOOD SYSTEMS: 2 SNORKEL

HOODS WITH FANS, 1 SLOTTED BENCH HOOD, AND 1 CANOPY HOOD. THE SLOTTED BENCH HOOD WILL

REMAIN, BUT ALL OTHERS WILL BE DEMOLISHED AND REPLACED WITH A SINGLE EXHAUST PLENUM

WITH FOUR SNORKEL HOODS. SNORKEL HOODS ARE INTENDED TO MAINTAIN A CONSTANT FLOW RATE

WHEN EF-4 IS OPERATING.

A SINGLE EXISTING ROOFTOP UNIT (RTU-2) SERVES THIS SPACE. THE CONTRACTOR IS RESPONSIBLE

FOR ALL NECESSARY ADJUSTMENTS TO RE-BALANCE AND INTERLOCK THE NEW EXHAUST FAN (EF-4)

AND EXISTING BENCH HOOD ((E)EF-2) WITH EXISTING ((E)RTU-2) SUCH THAT THE SPACE MAINTAINS

NEGATIVE PRESSURE WHEN EXHAUST HOODS ARE ON AND MAINTAINS SPACE AND DISCHARGE

TEMPERATURES AS ORIGINALLY DESIGNED.

AIRFLOW RATES:

(E)EF-2 (BENCH HOOD) - 1,500 CFM

EF-4 (NEW SNORKEL HOODS) - 3,500 CFM (700 CFM EACH)

(E)RTU-2 - 4,500 CFM

(E)RTU-2 SEQUENCE

(E)RTU-2 OUTDOOR AIR QUANTITIES ARE CONTROLLED BY MOTORIZED RETURN AIR AND MIXED AIR

DAMPERS. WHEN EXHAUST FANS ARE RUNNING, THE RETURN AIR DAMPER SHALL CLOSE AND THE

OUTDOOR AIR DAMPER SHALL OPEN TO PROVIDE 4,500 CFM OUTDOOR AIR. WHEN EXHAUST FANS ARE

OFF, THE OUTDOOR AIR DAMPER SHALL MODULATE TO MINIMUM POSITION, CORRESPONDING TO 250

CFM OUTDOOR AIR, AND THE RETURN AIR DAMPER MODULATE TO MAXIMUM OPEN POSITION.

EXHAUST FAN INTERLOCKS

EF-4 AND (E)EF-6 SHALL BE INTERLOCKED SUCH THAT BOTH FANS RUN SIMULTANEOUSLY WHEN

SWITCHED ON.

NOTES:

1. CONSTRUCT HOOD WITH 18 GAUGE WELDED GALVANNEALED SHEET METAL.

2. PROVIDE BLAST GATE FOR BALANCING AND WALL BRACKETS FOR MOUNTING.

M104

MIXING ROOM EXHAUST DETAIL

SCALE: NTS

DOWN TO H-2

EF-3MOTOR

SEE ARCHITECTURAL

PLANS FOR WALL

CONSTRUCTION AND

PATCHING

LOUVER

BIRD SCREEN

SEAL ALL

AROUND

DRILL 1/4" WEEP

HOLES 12" O.C. IN

BOTTOM BLADE

OF LOUVER

BOTTOM FLASHING TO

BE CONTINUOUS THRU

WALL WITH NO JOINTS

DUCT INSULATION

WHEN SPECIFIED

CAULK CONNECTION

WATER TIGHT

ALL AROUND

M104

LOUVER INSTALLATION DETAIL

SCALE: NTS

1/4" X 1/4" WIRE MESH

BIRD SCREEN

OUTLET AT

10'-0 ABOVE TOP

OF RTU-1 INTAKE.

HEPA

FILTER

BOX

EF-1,2MOTOR

SQUARE TO ROUND

TRANSITION

BUBBLE TIGHT 304

STAINLESS STEEL

DAMPER

BUBBLE TIGHT 304

STAINLESS STEEL

DAMPER

GUYWIRE &

TURNBUCKLES

MIN 4 EA @ 120°

H-2

FB-1,2

EXISTING CURB

EXHAUST FAN

TO OVERHANG

EXISTING

CURB NO

MORE THAN 6

INCHES.

EXISTING PLATFORM

NO LOSS STACK

x

DRAWN BY |

REVISIONS

© | ALL RIGHTS RESERVED

w w w . c t a g r o u p . c o m

8 0 0 . 7 5 7 . 9 5 2 2

CHECKED BY |

U S

H

I S

P S

D

R

E N

O V

A T

I O

N S

P O

C A

T E

L L

O

I D

A H

O

100% CD

3.27.19

N O

T

F

N

S T

R U

C T

I O

N

P

R E

L I M

I N

A R

Y

D

E S

I G

N

06.20.18 03:54 PM | G:\USDAAPHIS_PSD1\BIMCAD\Mech\M104.dwg

M104

PACKAGE #1

HVAC DETAILS

AND CONTROLS

BID ADDENDUM 001 - 5.20.19

RR

TJ

Amendment 3, page 5; May 21, 2019

Addendum No. 1_USDAPocatello_5_21_19.pdf
ADDENDUM NO.1_0
ATTACHMENTS:
DRAWINGS
1
A-111
M100 PACKAGE 1 HVAC SCHEDULES
M104 PACKAGE #1 HVAC DETAILS AND CONTROLS
M104-24x36
2019-05-21T11:48:25-0500
JAMES ROLOFF