Question and Answers:
What is the input/output Voltage for each UPS unit?
1.5 KVA = 120 VAC Single Phase Input/Output
2 KVA = 120 VAC Single Phase Input/Output 3 KVA = 120 VAC Single Phase Input/Output 6 KVA = 208 VAC Single Phase Input / 120/240 VAC Split Phase Output 10 KVA = 208 VAC Single Phase Input / 120/240 VAC Split Phase Output 15 KVA = 480 VAC Three Phase Input / 120/240 VAC Split Phase Output
What is the battery run time for each UPS unit? Minimum of 10 minutes.
Are the 15 kVA units single phase or 3 phase? Hardwired or plug in? 480 VAC Three Phase Input / 120/240 VAC Split Phase Output, hardwired.
Are the 10 kVA units single phase or 3 phase? Hardwired or plug in? 208 VAC Single Phase Input / 120/240 VAC Split Phase Output, Plug In, Are the 6 kVA units single phase or 3 phase? Hardwired or plug in? 208 VAC Single Phase Input / 120/240 VAC Split Phase Output, Plug In.
How long should the cords be? 6 feet.
How long should the 2/3 SOOW power cord be? 20 feet.
Is an external Power Conditioner needed? No.
Is economy mode operation needed on all UPS units? No.
Does the equipment need to be TAA Compliant? Yes
Are you allowing alternatives to Eaton/Powerware? Yes.
Do you need SNMP Network cards for all UPS? No.
For the 15 kVA units, will power distribution be off the unit itself or from a panel? From a Power Distribution Unit panel.
What type of outlets are needed for the 15 kVA unit PDUs – L-5/20, L-6/30, etc? Four 5-15/20R, One L5- 30R, One L6-20R, Four 6-15/20R, One L6/30R.
Is 15kVA needed because of capacity? Could two smaller units be used instead? Yes because of capacity. Two smaller units would not be acceptable.
Does the weight limit apply to the 15 kVA units as well? Yes, the weight limit applies to all of the units.
Is the total weight for the system, or, for each individual module? If we have a separate UPS, Battery and transformer can each weigh up to 375 lbs, or is the total for all three units together 375 lbs? Total weight limit is per system.
Is the weight limit due to a floor or ramp limit or to a rack limit? Due to lab bench specifications and employee safety.
“Dimensions – maximum dimensions for any one battery backup UPS unit is 13x36x26 inches (WxHxD).” Is this for each individual module of a modular system? Or is it for all modules together?
Dimensions are for all modules together.
Do all the unit need to be from the same manufacturer? Or can some be from one manufacturer and some from another? Different manufacturers ok.
What is the required delivery time after receipt of purchase order? Within 6 weeks after receipt of order.